HomeMy WebLinkAbout1287
ORDINANCE NO. 1287
AN ORDINANCE OF THE CITY COUNCIL OF THE
CITY OF ARCADIA, CALIFORNIA, ADOPTING BY
REFERENCE THE "UNIFORM BUILDING CODE 1964
EDITION VOLUME I" AND "UNIFORM BUILDING
CODE 1964 EDITION VOLUME III, UNIFORM
BUILDING CODE STANDARDS" APPROVED BY THE
INTERNATIONAL CONFERENCE OF BUILDING
OFFICIALS LOCATED AT 50 SOUTH LOS ROBLES,
PASADENA, CALIFORNIA, AMENDING CHAPTER 1 .
OF ARTICLE VIII BY AMENDING SECTIONS 8110,'
8111, 8121.4, 8130, 8130.1, 8130.2, 8130.3,
8130.3.1, 8130.4, 8130.5, 8130.10, 8130.13,
8130.19 AND 8130.20 THEREOF AND ADDING NEW
SECTIONS 8130.3.2,8130.21, 8130.22, 8130.23,
8130.24, 8130.25 AND 8130.26 THERETO.
THE CITY COUNCIL OF THE CITY OF ARCADIA, CALIFORNIA, DOES
ORDAIN AS FOLLOWS:
SECTION 1. That Sections 8110, 8111, 8124.4, 8130, 8130.1
8130.2, 8130.3, 8130.3.1, 8130.4, 8130.5, 8130.10, 8130.13 and 8130.19
of the Arcadia Municipal Code are hereby amended to read respectively
as follows:
8110. UNIFORM BUILDING CODE ADOPTED. With the exception
of the deletions and amendments set forth more particularly herein-
after, there is hereby adopted by reference the following code for
the City, to wit: "Uniform Building Code 1964 Edition Volume I" with
appendices thereof, a code prescribing regulations governing the
erection, construction, enlargement, alteration, repair, moving, re-
moval, conversion, demolition, occupancy, equipment, use, height,
area and maintenance of buildings and structures, proposed and recom-
mended by the International Conference of Building Officials, 50 South
Los Robles, Pasadena, California, 91101, which foregoing code is
hereby designated as the "Primary Code" adopted by reference.
-1-
1287
d-l
%
8111. SECONDARY CODE ADOPTED. Volume III of the above adopted
Uniform Building Code, entitled "UNIFORM BUILDING CODE, 1964 EDITION,
VOLUME III, UNIFORM BUILDING CODE STANDARDS", a compilation of uniform
s~an~ards, proposed and recommended by the International Conference
of Building Officials, 50 South Los Robles, Pasadena, California,
91l91, which foregoing code is hereby designated as the "Secondary
Code", is hereby adopted by reference.
8121. 4. SAME. Whenever the term "Building Official" is
used, it shall mean the Superintendent of Building and Safety of the
City.
8130. AMENDMENTS, ADDITIONS AND DELETIONS. Said Uniform
Building Code is amended as provided in the following subsections.
8130.1. AMENDMENT. Section 201 of Chapter 2 of said Uni-
form Building Code as adopted by Part 1 of this Chapter is hereby
amended to read as follows:
Section 201. There is hereby established in the Department
of Public Works of the City the Division of Building and Safety which
shall be under the Jurisdiction of the Superintendent of Building and
Safety as designated by the appointing authority.
8130.2. AMENDMENT. Section 204 of Chapter 2 of said Uni-
form Building Code is hereby amended to read as follows:
Section 204. Upon written application of any person who
deems himself aggrieved by the decision of the Superintendent of
Building and Safety, relating to the use of any material or method
of construction not specifically prescribed by this code, and the use
of which has been denied by the Superintendent of Building and Safety
pursuant to the provisions of Section 105, the City Council shall at
its next regular meeting hear all persons and all evidence relating
thereto and shall upon the conclusion of said hearing render a final
and conclusive determination upon said application.
-2-
1287
d-l
8130.3. ADDITION. Chapter 2 of said Uniform Building Code
is hereby amended by adding thereto a new Section 204-A, the same to
read as follows:
Section 204-A. Upon written application by any interested
person, stating the variance requested and the reasons therefor, the
City Council, by motion or resolution passed or adopted by vote of at
least three members of the City Council entered upon the minutes, may
after receipt of the written recommendation of the City Engineer and
the Superintendent of Building and Safety of the City, grant a variance
from the requirements of anyone or more of the provisions of this
Chapter upon the terms and conditions specified in the written recom-
mendations of the City Engineer and the Superintendent of Building and
Safety. Upon receipt of such application, the City Clerk shall forth-
with refer the same to the City Engineer and to the Superintendent of
Building and Safety for investigation and written report by them to
the City Council within 15 days, and shall forthwith mail to the owners
of any real property which adjoins and is within 50 feet of the prop-
erty for which such variance application is made, notice that an appli-
cation for a variance of the provisions of this Chapter has been made
and stating the time and place of the hearing to be held upon such
application. Such hearing shall be held at the first regular meeting
of the City Council held 15 or more days after the filing of such appli-
cation, but such hearing may be continued from time to time for good
cause. Nothing herein contained shall preclude the holding of a special
meeting of the City Council at any time for the purpose of hearing and
passing upon such application, provided that at least three (3) days'
written notice shall have been given to the owners of any real property
which adjoins and is within 50 feet of the property for which variance
application is made. No notice shall be required when the applicant is
the owner of all real property which adjoins or is within 50 feet of
the real property for which such variance is requested and such fact
is disclosed in the application, or when all the owners of any real
-3-
1287
d-1
property which adjoins and is within 50 feet of the property for which
variance application is made waive notice by written waiver signed by
such party or parties and filed with the City Clerk, in either of which
events the City Council may hear and pass upon such application at any
time upon receipt of the written report of the City Engineer and the
Superintendent of Building and Safety.
8130.3.1. ADDITION. Section 301 of Chapter 3 of said Uni-
form Building Code is amended by adding thereto subsection (b)8 to
read as follows:
8. A statement of the names and addresses of all subcon-
tractors and material men who are to perform any work upon or supply
any materials to or for the improvement or structure for which a per-
mit is thus applied for. No final inspection or certificate of occu-
pancy shall be given or issued unless and until the general contractor
or owner shall, upon completion of the improvement or structure.for
which final inspection is sought or required, file in duplicate with
the Superintendent of Building and Safety a verified statement con-
taining the names and addresses of all subcontractors and material men,
other than those set forth in the original application, who shall have
performed work or furnished materials to or for the improvement of the
structure for which final inspection or certificate of occupancy is
sought or required.
8130.4. AMENDMENT. Section 302 (d) of Chapter 3 of said
Uniform Building Code is hereby amended to read as follows:
(d) Expiration. Every permit issued by the Superintendent
of Building and Safety under the provisions of this Code shall expire
by limitation and become null and void, if the building or work
authorized by such permit is not commenced within sixty (60) days
from the date of such permit, or if the building or work authorized
by such permit is suspended or abandoned at any time after the work
is commenced for a period of one hundred twenty (120) days. Every
permit issued shall expire one (1) year from date of issuance if the
-4-
1287
d-l
work permitted thereunder has not been completed. After expiration,
a new permit shall be obtained before any work is done, and the fee
therefor shall be the fee required for an original permit, determined
by the total valuation of the uncompleted portion of the work. If a
permit holder presents satisfactory evidence in writing that unusual
construction difficulties have prevented work being started within
the sixty (60) day period, or completed within one (1) year, the
Superintendent of Building and Safety may grant extensions of time
reasonably necessary by reason of said difficulties. No request of
such extension will be considered later than the thirtieth (30th) day
following the date on which said permit would otherwise expire.
8130.5. AMENDMENT. Section 303 of Chapter 3 of said Uni-
form Building Code is hereby amended to read as follows:
(a) Building Permit Fees. Before a building permit is
issued a permit fee therefor shall be paid to the City of Arcadia as
set forth in Table No.3-A. Where work for which a permit is required
by this code.is started or proceeded with prior to obtaining said
permit, the fees above specified shall be doubled, but. the payment of
such double fee shall not relieve any persons from fully complying
with the requirements of this code in the execution of the work nor
from any other penalties prescribed herein.
TABLE NO.3-A, BUILDING PERMIT FEES
TOTAL VALUATION
FEE
- -
Less than $20.00
$20.00, to and including $100.00
M. ore than 1100.00, to and including 1400.00
More than 400.00, to and including 700.00
More than 700.00, to and including 1,000.00
Each additional $1,000.00 or fraction, to and
including $25,000.00
Each additional $1,000.00 or fraction, to and
. including $50,000.00
Each additional $1,000.00 or fraction, to and
_ including $100,000.00
Each additional $1,000.00 or fraction, more
_ than $100,000.00
No Fee
$2.00
.3.00
5.00
6.00
3.00
2.50
1.50
1.00
-5-
1287
d-l
(b) Plan-checking Fees. Before,plans and specifications
are accepted for checking, a plan-checking fee in addition to the
building permit fee shall be paid to the City of Arcadia. The plan-
checking fee shall be one-half of the building permit fee.
(c) Refund of Fees. Where no work has been done under a
permit issued in accordance with the provisions of this Chapter, the
City Controller of the City, with the specific approval of the City
Manager of the City, may upon written request from the original permit
holder filed before the expiration of said permit, refund not more
than ninety percent (90%) of the permit fee, provided that no refund
shall be made by the City Controller until he has received a report
from the Superintendent of Building and Safety as. to the cost,of check-
ing plans, where applicable, and other work incidental to issuing said
~ - . . . ., ~. . , .. ~ . -. . . . - - . - .
permit. If the Superintendent of Building and Safety reports that
such costs exceed ten percent (10%) of the fee paid, the excess above
ten percent (10%) shall be deducted from the amount which might other-
wise be refunded by the City Controller.
8130.10. AMENI>>lENT. Section 2310 of said Uniform Building
Code is hereby amended to read as follows:
Section 2310. Retaining Walls shall be designed to resist
the lateral pressure of the retained 'material in accordance with
accepted engineering practice,' Walls retaining drained earth may be
designed for pressure equivalent to that exerted by a fluid weighing
not less t~an 30 P?unds per cubic foot and haying ~ depth equal to
that of the retained earth. ~ny.~u~charge shall be in additimto the
e9,u~~~~Elrlt ~lu~d. I?r:sst1r~.u _ ~e~ain.~n~ walls intended fo~ permanerl~l!
retaining earth cuts or fills adjacent to property lines or permanent
building shall be of concrete, masonry or steel.
-6-
1287
d-l
8130.13. AMENDMENT. The footnote to Table No. 5-C "Basic
Allowable Floor Area for Buildings One Story in Height" appearing on
page 50 of said Uniform Building Code, Edition 1964, Volume I, read-
ing as follows "For Buildings Located in Fire Zone No. 3 the Basic
Area May Be Increased 33 1/3 Percent", is hereby amended to read as
follows:
"For Buildings Located in Fire Zone No.3, the Basic Area
May Be Increased 33 1/3 Per Cent; For Buildings Not More Than One
Story in Height, Located in Fire Zone No. 1 and Zone C-M, used for
manufacturing and warehouse purposes, the basic area may be increased
33 1/3 Per Cent."
8130.19. ADDITION. Chapter 16 of Part 4 of said Uniform
Building Code is hereby amended by adding thereto a new Section 1605,
the same to read as follows:
Section 1605. General - Fire Zone No.4. Building or
structures hereafter erected, constructed, moved within or into Fire
Zone No. 4 shall, in addition to complying with the requirements of
this code for any building or structure in Fire Zone No.3, comply
.
with the following requirements of this Section.
1. Roof soffits (including eaves) in excess of twelve (12)
inches in width, open patios, carports, porches, unenclosed under-
floor areas, and all open structures, attached or detached, shall be
protected on the under side with materials as approved for one-hour
fire-resistive construction or shall be of incombustible material
throughout.
EXCEPTION: Eaves facing on a dedicated street need not be
protected.
2. Vents installed in areas required to be one-hour fire-
resistive construction or of incombustible material throughout, shall
be fusible link type vents.
3. Chimneys shall be equipped with approved spark arresters.
-7-
l287
d-l
SECTION 2. That Part 3 of Chapter 2 of Article VIII of the
. .- --
Arcadia Municipal Code is hereby amended by adding thereto n~~ Sec-
tions 8l30.3.2, 8130.21, 8130.22, 8130.23, 8130.24, 8130.25 and
. .".. .
8130.26, the same to read respectively as follows:
8130.3.2. AMENI>>lENT.Subsection (c) of Section 301 of
Chapter 3 of said Uniform Building Code is amended to read as follows:
(c) Plans and Specifications. With each application for
a building permit, and when required by the Superintendent of Building
and Safety for enforcement of any provision of this code, two (2)
sets of plans and specifications shall be submitted. Whether or not
a permit therefor is required by Chapter 6 of this Article, a complete
grading plan of the building site, showing the present grades of the
lot comprising the building site, the proposed finished grade of such
lot, and a method approved by the Superintendent of Building and
Safety for disposing of all surface water flowing upon or emanating
from such lot, shall likewise be submitted. The Superintendent of
Building and Safety may require all such plans and specifications to
be prepared and designed by an engineer or ,architect licensed by the
State to practice as such.
EXCEPTIONS: When authorized by the Superintendent of Build-
ing and Safety, plans and specifications need not be submitted for
the following:
1. One-story building of Type V conventional wood-stud
construction with an area not exceeding six hundred (600) square feet;
2. Group J, Division l, occupancies of Type V conventional
wood-stud construction.
3. Small and unimportant work.
8l30.2l. ADDITION. Section 2508 of said Uniform Building
Code is hereby amended by adding thereto a new paragraph 7 to read
as follows:
-8-
l287
d-l
7. Party walls and/or interior walls located between sep-
arate dwelling units not connected one with the other structurally,
shall have dead space between them packed with a fire resistive
material, or each wall may be of one (1) hour fire resistive con-
struction.
8130.22. ADDITION. Section 3312 of said Uniform Building
Code is hereby amended by adding thereto a new paragraph (d) to read
as follows:
(d) Emergency Lighting System. In additicn to the above,
all exit ways of Groups A, B, C, D, E, F and H occupancies shall be
illuminated by an approved emergency lighting system designed to
operate when other power sources are interrupted.
8130.23. AMENDMENT. Section 3805 of said Uniform Build-
ing Code is hereby amended to read as follows:
Section 3805. Every Group A and B Occupancy of any height,
and every Group C Occupancy two or more stories in height, and every
Group D, E, F, G, and H Occupancy three or more stories in height
and every Group E and F Occupancy over twenty thousand square feet
(20,000 sq. ft.) in area shall be equipped with one or more wet
standpipes extending from the cellar or basement into the topmost
story, provided that Group B buildings having no stage and having a
seating capacity of less than 500 need not be equipped with standpipes.
8130.24. AMENDMENT. Paragraphs (a), (b), (d), (e), (g),
and (j) of Section 3806 of said Uniform Building Code are hereby
amended to read as follows:
Section 3806. (a) Construction. Wet standpipes shall be
constructed as required for dry standpipes.
(b) Size. Wet standpipes shall have an internal diameter
sufficient to deliver 50 gallons of water per minute under 30 pounds
-9-
l287
d-l
per square inch pressure at the hose connection, based on the avail-
able water supply. Buildings of Groups A and B Occupancies shall
have wet standpipe systems capable of delivering the required quantity
and pressure from any two outlets simultaneously; for all other occu-
pancies only one outlet need be figured to be open at one time. In
no case shall the internal diameter of a wet standpipe be less than
two inches (2"), except when the standpipe is attached to an auto-
matic fire-extinguishing system as set forth in U.B.C. Standard
No. 38-1-64.
Any approved formula which determines pipe sizes on a pres-
sure drop basis may be used to determine pipe sizes for wet standpipe
systems. The Building Official may require delivery and pressure
tests on completed wet standpipe systems before approving such systems.
(d) Location. In Groups A and B Occupancies, outlets shall
be located as follows:
On each side of the stage, on each side of the rear of the
auditorium, and on each side of the rear of the balconies. Where
occupant loads are less than 500 the number of locations noted above
may be reduced upon the approval of the Building Official. In Groups
C, D, E, F, G, and H Occupancies the location of all wet standpipes
shall be approved by the Building Official.
(e) Outlets. All wet standpipes shall be equipped with
a one and one-half-inch (It") valve in each story, including the
basement or cellar of the building, and located not less than one
foot (1') nor more than six feet (6') above the floor.
(g) Water Supplies. All wet standpipes shall be connected
to a street water main not less than four inches (4") in diameter, or
when the water pressure is insufficient to maintain 30 pounds pressure
at the highest hose outlet such standpipe shall be connected to a
pressure tank, gravity tank, or fire pump. Such supply shall be
sufficient to furnish at least 30 pounds pressure at the topmost
standpipe outlet.
-10-
1287
d-1
When more than one wet standpipe is required in the building,
such standpipes shall be connected at their bases or at their tops
by pipes of equal size.
(j) Hose and Hose Reels. Each hose outlet of all wet stand-
pipes shall be supplied with a hose not less than one and one-half
inches (It'') in diameter. Such hose shall be equipped with a suit-
able brass or bronze nozzle and shall be not over seventy-five feet
(75') in length. An approved standard form of wall hose reel or rack
shall be provided for the hose and shall be located so as to make the
hose re~di1y accessible at all times and shall be recessed in the
walls or protected by suitable cabinets.
8130.25. ADDITION. Section 3309 of said Uniform Building
Code is hereby amended by adding thereto anew paragraph "h", to
read as follows:
(h) EXCEPTION: Smokeproof enclosures may incorporate
mechanically ventilated vestibules in lieu of openings directly to
outside air provided the following requirements are met:
1. Stair Tower.
a. Must be supplied with mechanically introduced air
by a separate duct system.
b. Must have mechanically exhausted air at top of
smoke tower.
c. Intake air must be introduced at one air change
every five (5) minutes.
d. Exhausted air must be adjusted to maintain a head
of .01 to .05 inches.
2. Vestibules.
1.1~
a. Must have supply air and exhaust air in separate
and independent duct systems.
b.
,
Must maintain a negative pressure by introducing
one and one-half (It) air changes per minute and exhausting three (3)
air changes per minute.
-11-
1287
d-1
c. Intake air must be located at or near floor level.
d. Intake air must be located at the ceiling line on
the wall, or in the ceiling.
e. Must have at least eighteen (18) inches wall space
above door openings.
3. Emergency Power.
a. All mechanical equipment and lighting for the stair
tower and vestibules to be provided with auxiliary power from a stand-
by motor generator or other similar source.
b. The stand-by generator shall be operated by a motor
which utilizes gasoline or diesel as its fuel, and shall contain suffi-
cient fuel in tanks to operate the generator for a minimum of two (2)
hours.
c. The generator shall be installed in a room sep-
arated from the rest of the building by one (1) hour fire resistive
occupancy separation.
4. Blowers and Fans.
a. Blowers and fans which do not run continuously
must be activated by heat and smoke detectors system of approved
design and materials.
b. A supervisory light and buzzer must be installed
in an approved location.
5. Doors.
a. Must be self-closing Class "B" fire doors.
8130.26. ADDITION. Said Uniform Building Code is hereby
amended by adding thereto a new Section 3002-A to read as follows:
Section 3002-A. In every building containing five (5) or
more stories at least one (1) elevator shall have at the ground floor,
adjacent to the elevator, a fire override switch.
-12-
1287
d-1
a~l. The fire switch shall be contained in an enclosed
box, with a glass front, locked, and with a name plate on the outside
,
reading "Elevator Switch. Fire Department Use Only".
a-2. The fire switch shall be connected with a separate
sourCe of power from a stand-by motor generator. This circuit must
follow a route that is safe from fire, and separated from all other
circuits in the building.
a-3. The stand-by generator shall be operated by a
motor which utilizes gasoline or diesel as its fuel, and shall contain
sufficient fuel in tanks to operate the generator for a minimum of
two (2) hours.
a-4. The Chief of the Fire Department, or his regu-
larly authorized deputy, shall make tests prior to acceptance of the
fire switch.
a-5. Copies of test to be conducted shall be supplied
to contractors by the Division of Building and Safety.
SECTION 3. Section 8130.20 of the Arcadia Municipal Code
is her.eby amended by amending Section 1311 of Chapter 13.1 of Part
III of the Uniform Building Code and by adding to Chapter 13.1 of
Part III of the Uniform Building Code a new Section 1311.1, the
same to read respectively as follows:
Sec. 1311. APARTMENT DEFINED. As used in this Chapter,
apartment house shall mean and include any building or portion thereof,
which is designed, built, rented, leased, let, or hired out to be occu-
pied, or which is occupied as the home or residence of two (2) or more
families living independently of each other and doing their own cook-
ing in the said building, and shall include flats and apartments.
-13-
1287
d-1
Sec. 1311.1. APPLICATION. Except where a more restrictive
provision in the Uniform Building Code, in the Arcadia Municipal Code,
or in any State law or regulation, is applicable, each provision of
this Chapter shall apply to all apartment houses as defined by the pre-
ceding Sec. 1311.
SECTION 4. The City Clerk shall certify to the adoption of
this ordinance.
I HEREBY CERTIFY that the foregoing ordinance was adopted
at a regular meeting of the City Council of the City of Arcadia held
on the 6th
day of July
, 1965, by the affirmative
vote of at least three Councilmen, to wit:
AYES: Councilmen Considine, Forman, Turner and Reibold
NOES: None
ABSENT: Councilman Balser
~~~
' i ty Clerk of the City of rcadia
SIGNED AND APPROVED this 6th
, 1965.
:--
~. ~
4~;~f;;~
i ty Clerk,
/, Y" ~',~'
,,' -- ...~-.:- ......."1
I"'", _,-' .'~, _ ,
,. . -' . ~ : ~ ~
'. ,
. ~ '
:.,,,
,-
(SEAL)
-14-
1287
d-1
TO:
PROM:
City Counoil
City Manager
City Attorney
JUne 9, 1965
Attacbed Ord1nance 1281 adopts bJ retel'!~~e t.be ,,~tOnD
Building Code 1964 BdiUon Vol\llle I and tbe Uzi1fonn Build1ng Code
1964 Edition Volume III, Unitonn Building Code standards,witb ame~-
ments and deletions recommended oJ the stat!. The Ordinance 111 to
be introduced only at the tortbl.'OIII1ng meeting acid a pUblic bearing
set tor tbe meet1ng ot July 6th, at the oonclusion ot 1Iblcb bearing
the Ordinance may be adopted. See memo re OrcUnanc8 1289 tor prO-
cedure on a4opUon ot Codell ~terence. ,
., .~,~~
JA}h Jts AMES A. HICKLIN
. c.' . .
,
It
,,>.
A,f,'
17-
,
'"
i4;,-
~~.
"'
1'!
4t-;1
..... " .:$,
':".r~'" r
/.
"
'1'~
or
'. ....
.,