HomeMy WebLinkAbout0496
."..~
.
t"LI_ ~
In ~
/~~~
,.
ORDIHAlrCE no. 496.
An OHDIiiJ\HCg OF TIlli CI'fY CO'JilCIL 0" ~!ill crfY OF j,RCiillIA hjjEUDIHG
SEC1'I0i,j 44 OF OH:)II'hdCE HO. 323, AIm AD7)I::G A ::lL' ~ECTION NO. 44.1 TO
SAID viLDIHJ.iJCE OJ.' SJi.ID cn'y.
Till:. CITY COlr..:C'::L W '1'1:E CITY 01' J.RCIIDIA J)8i>& 03DAIH AS FOLLO',;S:
SECTION 1. That Section 44 of Ordinance No. 323 of the City of
Arcadia, entitled "I~ Ordinance of the City Council of the City of
Arcadla relatine to fire protection and fire prevention, re8ulating the
burninG of brush, rubbish or other materials, for tho protection of fire
hose, fire apPsNltus and the water system of said City of Arcadia, pro-
hibi tins tbe tak:l.nc; of I'Jater ui thou.t permis sion of an authorized officer of
said City, establishing an int'\iners.tor d<.strict, creatin~ the office of
Chief of the Fire Department, establishinG a district north of Foothill
Boulevard as a fi~e hazard, providing for incinerators in.residential
districts, repealinG Ordinances lIos. 120, 154, 199 and all Ordinances in
conflict hereuith and providin[5 a penalty for the violation thereof.",
adopted Septer,lber 17, 1935, be and the same is. hereby arnEl'nded to read
as follows:
rsECT10,~ 44. PORT1I3LE OHSOLI,'lli BUGGY. It shall be unlawful for
any person to maintain or use, or cause or penlit to be maintained or used
any portable Gasoline filled tank or bUB3Y that has a capacity of more
than fifty (50) Gallons, or that is not constructed and approved as
provided in this :3ection. Eve.ry such portable fillinG tank or bU.";~y Sh1l11
, ..
be l',ounted upon all l.1etal \1heels equipped rrith rubber tires, and shall
be eq\upped vnth a pump fitted with hose att~chment not to exceed oi0ht
(8) feet in lenGth, with a :;round shutoff nozzle. The gasoline shall be
pumped directly into the reservoir or tank of the motor vehicle from such
porto.ble fillin ~ tank or bug::;y. Before any such portabl;:; fillin:; tank
or buSt3Y or any such pump is used, the same, and the desien and type
thereof, shall be approved by the Chief of the Fire Department.
SECTION 2. ~~at Ordinance No. 323 of said City be further amended
by addin:; thereto a new section to be known and numbered as Section
44.1, and to read as follows:
SEC'l'IOH 44.1. GASOLIl\'E S'rQli..,GE. It shall be unlawful for any person to
store or keep, or cause or permit to be stored or kept, or to deliver or
cause to be delivered for stora13e more than one (1) [\allon ,of ~asoline \7ith-
in o.ny public cara.;e, auto'lobile fillin::; sta'c.i.on, auto!'Jobile
-1-
Il\lf\rY"....
parking sto.tion,
dotd, 19?
,... ~-.
private rosidence.. court, apartment house or hotel, or \1ithin any
buildin~ or struc.;ure, or upon any premises, except such :;asoline as
may be contained In the tank of a motor lIlehlcle, except as hereinbefore
provided, or in the. follo\1in~ manner:
. (a.) All gasoline shall be stored in a tank or tanks outside
of any buildin3, 6nd every such tank or tanks shall be thoro~hly tested
for leaks and coated \"Ii th tar or other rust resistinG material before
being set in place. Before any such stora:;e tank is used, the sane shall
be approveu by the Chief of -the Fire Department. All such storage tanks
must be constructed of ~alvanized iron or steel and shall conform to
the following schedule,' to-I'T:1 t:
Minimum Tbickness of j,;etal
Cap~city in Gallons
1 to 1,100
1,101 to 2,500
2,501 to 4,000
4,001 to 10,500
10,501 to 12,500
12,501 to 15,000
15,001 to 17,500
l7,501 to 20,000
Galvanized Iron
Steel
12 gauge
12 gauge
7 :;au:;e
3/16
3/16
3/16
l/4
5/16
3/8
7/16
1/2
inch
inch
inch
inch
inch
inch
inch
inch.
(b) Every such stora~e tank shall be buried under Ground.
The top of each tar~ shall be at least four (4) feet belo~ the surface
of the zround and. e,t 10ast one (1) foot below the lowest floor level of
any buildin~ on the premises. The space ~bove the top of each such
tank shall be filled \"lith earth so as to be level with the surface of
tile surroundinJ ground.
( c) Ho such sto ra[!;e tank or piping shall be covered \7i th e:r th
or any other material until after the same shall have been inspected by
the Chief .of the Fire Department.
(d) Every p~p or device used for extracting 60.s01ine from
such stor8.3e tanks shall be set upon and firmly affixed to a solid foun-
dation subject to,the approval of the Chief of the Fire Department. It
shall be unla\"Tful to install or maintain any type of clear vision or
visible ;:;asoline pump or dispenser inside of any building.
(e) All pipe used shall be Julvanized iron. Every pipe
shall lead out of tee top of the tank with which it is connected, except
when connected \rlth a pressure tank. A vent pmpe from each such tank
-2-
.'DliXaI
d~ ~9?
_. .. ,~'"
..... ..---
shall extend up to the outside of the buildin~ to a point not less
than ei~hteen (18) inches above the roof, fire \/all, or any obstruction
on such builuin3, and in no case shall the Vent pipe pe less than
twelve (l2) feet in hei~ht, and such vent shall be provided I'uth a
standard. return ell and provided with a copper or brass Gauze not
coarser than thirty mesh. Such vent pipe shall be of not less than one
(1) inch inside diameter, and shall not extend into said storace tank
for a distance of :cnore than one (1) inch.
(f) Vfuere a series of tanks are installed which are
desi~ned and inten1ed to be used to store the same type of fuel, \ent
pipes may run into a main riser. Individual pipes shall be connected
hov/ever to the riSl3r not less than one (1) foot above the level of the
top of the hijhest tank or reservoir. Tho main vent pipe throush which
t\70 or more tanks are vented shall not be less than one and one-quarter
(li) inch in diame~er.
(g) A f~lling pipe shall be connected fdth each and every
such storaGe tank. Every such pipe shall extend up to the 3round level,
and shall be capped with a \7ater ti..:ht SCllew cap.
(h) Nothing in this section contained shall be deemed Or
construed to prohibit the storage of gasoline or other motor fuel
above c;round by any' person enBa~ed in the business of sellinc; or distrib-
uting gasoline or other motor fuel at I'Tholesale, provided, that all such
stor!l3e tanks shall be constructed of the materials and si1all conform to
the rules, regulations and requirements of the Board of Fire Underwriters
and the State Fire ~arshal; provided, that the code of the Board of
Fire Underwriters, and the rules, regulations and requirements of the
state Fire ~arshal stlall govern and control the installation and main-
tenance of all gasoline stora~e tanks not specifically covered by the
provisions of this Ordinance.
SECTION :S. PEHAL'l'Y FOR VIOLl,TIOIl OF THIS ORDIN.iII~CE. That
any person, firm or corporation violating any of the grovlsions of this
Ordinance shall be deemed guilty of a misdemeanor and upon conviction
thereof, shall be plmishable by a fine not exoeeding 0300.00 or by
imprisonment in the City Jail of said City of Arcadia or in the County
Jail of the County cf Los An3eles, s.tate of California, at
-3 - ..,OEXe,l)
the discretion
acL 19t
._' '.-..
-~
of the co~ittinBma3istrate, for a period not exceeding three months,
or by both such fine and imprisoIlI'lent.
SECT lOll 4. The City Clerk shall certify to the adoption of
this Ordinance and prior to the expiration of fifteen (15) days from
the passage thereof, shall cause the same, to be ,!ublished once in the
JU'cad.ia Tribune and Arcadia i:erTs, a nenspo.per of genera). circulation,
pUblished and circ:ulated in the City of Arcadia, and thirty (30) days
from and after thE' final passa[,\e thereof so.id Ordinance shall take
effect and be in f'0I'Ce.
I hereby certify that the foregoinG Ordinance ,"{as adopted
at a
regular
meetinG of the City Council of the City of
Arcadia, held on the uthday of November, 1942, by the affirmative vote
of at least three Council::::en, to-vTit:
AYES: Councilmen, Adcock, Jones, Leeper ,Nugent and Ormsby
NOES: None
ABSENT: None
.
~~~
City Cler
Sic;ned and approvej this uthday of November, 1942.
Ai,r1l:.,ST:
A>>.fi~ "~~
./ City Clerk.
~, ..4.(f)~
I,iayo
-4-
..'toE:f.SC
CAd. '/9rt