LIGHTING CONTROL ACCEPTANCE DOCUMENT
Automatic Shut-off Controls: Automatic Time Switch Control and Occupant Sensor
Intent: Lights are turned off or set to a lower level when not needed per Section 110.9(a) & 130.1(c).
A. Construction Inspection
Fill out Section A to cover spaces 1 through 3 that are functionally tested under Section B.
Instruments needed to perform tests include, but are not limited to: hand-held amperage meter, power meter, or light meter
1:Automatic Time Switch Controls Construction Inspection—confirm for all listed in Section B
a. All automatic time switch controls are programmed for(check all):
F Weekdays F Weekend F Holidays
b. Document for the owner automatic time switch programming (check all):
F Weekday settings F Weekend settings F Holidays settings F Set-up settings
F Preference program setting F Verify the correct time and date is properly set in the time switch
r Verify the battery is installed and energized P Override time limit is no more than 2 hours
F Occupant Sensors and Automatic Time Switch Controls have been certified to the Energy Commission in accordance with
the applicable provision in Section 110.9 of the Standards, and model numbers for all such controls are listed on the Commission
database as Certified Appliance and Control Devices
2.Occupancy Sensor Construction Inspection—confirm for all listed in Section B
r Occupancy sensors are not located within 4 feet of any HVAC diffuser
F Ultrasonic occupancy sensors do not emit audible sound 5 feet from source
California Advanced Lighting TP Controls Training Program 1 r 1
-avec a IC ICA a r,Ur AL(.t r I AMPLEIlrvrc�n-�uv�-n
.ighting Control
roject Name:Warehouse 'Enforcement Agency:CITY OF ARCADIA 'Permit Number.COMM-18-0937
roject Addr ss:11700 Goldring Rd. 'City:Arcadia 'Zip Code:91006
B. Functional Testing of Lighting Controls
For every space in the building, conduct functional tests 1 through 5 below if applicable. If there are several geometrically similar spaces
that use the same lighting controls, test only one space and list in the cells below which "untested spaces" are represented by that
tested space. EXCEPTION: For buildings with up to seven (7) occupancy sensors, all occupancy sensors shall be tested. (NA7.6.2.3)
Representative Spaces Selected
Tested space/room name: Lab
Space Type (office, corridor, etc) Labratory
Untested areas/rooms Office 1, 2, Men's Restroom, Women's Restroom, Hall, Reception
Confirm compliance for all control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1:Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch
b. Verify the switch only operates lighting in the ceiling-height partitioned area in
which the switch is located.
Step 2:Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1.
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours(unless serving public areas and override switch is captive key
type).
Step 3:
System returned to initial operating conditions
2. Occupancy Sensors
Step 1:Simulate an unoccupied condition
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation.
Step 2:Simulate an occupied condition
r
a. Status indicator or annunciator operates correctly
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on Iw
manually
�e>L Oma`GCalifornia Advanced lighting
/ TP Controls'tanning Program mt,: r 1
,{.K l LC U..A l r.ur Al.L.r.r IVl.L' IIIVKt./1-L 11-VL-H
.fighting Control
roject Name:Warehouse IlEnforcement Agency:CITY OF ARCADIA (Penult Number.COMM-I8-0937
roject Address:11700 Goldring Rd. City:Arcadia pip Codc:91006
Step 3:
• r
System returned to initial operating conditions
3. Partial Off Occupancy Sensor
Step 1:Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an p.
unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack.
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power,or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60%of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method.
Light level may be used as a proxy for lighting power when measurements are taken
Step 2:Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition
4. Partial On Occupancy Sensors
Step 1.-Simulate an occupied condition.Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to r.
70% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights.
Step 2.Simulate an unoccupied condition
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation.
CALGTP CalifomiaAdvancedUghting
L Controls Training Program m,: - �r,
-LK l It ILA r L'U1 At,t.Gr 1 AIVt.L' Ilnnt,H-Lr rrrL-H
aghting Control
roject Name:Warehouse Enforcement Agency:CITY OF ARCADIA Permit Number:COMM-18-0937
rojcct Address:11700 Goldring Rd. pity:Arcadia 'Zip Code:91006
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
'250 ft , to Qualify for a Power Adjustment Factor (PAF)
Step 0: First,complete Functional Test 2(above)for each controlled zone.
'Step 1:Verify area served and compare actual PAF with claimed PAF.Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c).
e. Sensors shall not trigger in response to movement in adjacent walkways or f"
workspaces
f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)'
and all answers are Yes.
CAGTP California Advanced lightingControls Training Program
-LK I Ir ILA Ir.yr AI.I,GI'I AMA, IIIVKLH-LII-uL-H
lighting Control
roject Name:Warehouse 'Enforcement Agency:CITY OF ARCADIA ('Permit Number:COMM-I8-0937
reject Address:117000oIdring Rd. City:Arcadia ''Zip Code:91006
- C. Testing Results
1. Automatic Time Switch Controls(all answers must be Yes). r
2. Occupancy Sensor(On Off Control) (all answers must be Yes). F
3. Partial Off Occupancy Sensor(all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2.
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF (all answers must be Yes). Also must
pass Test 2.
Representative Spaces Selected
Tested space/room name: Office 6
Space Type (office, corridor, etc) Office
Untested areas/rooms Men's Restroom, Women's Restroom, Office 7, 8, 9, 10, 11, Lobby
Confirm compliance for all control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1: Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch F
b. Verify the switch only operates lighting in the ceiling-height partitioned area in
which the switch is located.
Step 2:Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1.
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
r
type).
Step 3:
F
System returned to initial operating conditions
2. Occupancy Sensors
Step 1:Simulate an unoccupied condition
1 1
Com_ T P California Advanced Lighting
Controls Training Program rt: ; c ,r t
-LKl It MAI G UP AIA.L'r I AMA&
r''-M-LI i-u-n
.ighting Control
roject Name:Warehouse 'Enforcement Agency:CITY OF ARCADIA I Permit Number COMM-18.0937
inject Address:11700 Goldring Rd. 'City:Arcadia ''Zip Code:91006
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes ' I
from start of an unoccupied condition per Standard Section 110.9(b)
b. The occupant sensor does not trigger a false 'on' from movement in an area F
adjacent to the controlled space or from HVAC operation.
Step 2:Simulate an occupied condition
F
a. Status indicator or annunciator operates correctly
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on F
manually
Step 3:
R
System returned to initial operating conditions
3. Partial Off Occupancy Sensor
Step 1:Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an r
unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in r
the aisle or stack.
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60%of installed lighting power for corridors and stairwells in which
the installed lighting power is 80%or less of the value allowed under the Area
Category Method. r
Light level may be used as a proxy for lighting power when measurements are taken
Step 2:Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled r
areas, Immediately upon an occupied condition
4. Partial On Occupancy Sensors
Step 1.-Simulate an occupied condition.Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to r
70% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100%of the lighting power, and manually r
deactivate all of the lights.
r% A Q P. --r-r-% California Advanced Liahtina
,r,K I It 11.-A I VP ALLF.r r AtvLG IIrvK.,H-L uvc-n
.fighting Control
reject Name:Warehouse (Enforcement Agency:CITY OF ARCADIA (Permit Number.COMM-180937
rojoct Address:11700 Goldring Rd. (City:Arcadia (Zip Code:91006
Step 2.Simulate an unoccupied condition
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
r
adjacent to the controlled space or from HVAC operation.
CAL TP California Advanced Lighting
Controls Training Program rt : -, ..c 1
.L'Klll'i.Al E ur At t.GriANI.E 111dKl,A-L11-VL-/\
ighting Control
roject Name:Warehouse I Enforcement Agency:CITY OF ARCADIA 'Permit Number.COMM-I 8-0937
roject Address:11700 Goldring Rd. [City:Arcadia Zip Codc:91006
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 ft , to Qualify for a Power Adjustment Factor (PAF)
Step 0: First,complete Functional Test 2(above)for each controlled zone.
Step 1:Verify area served and compare actual PAF with claimed PAF.Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c).
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces
f. All steps are conducted in Functional Test 2 'Occupancy Sensor(On Off Control)'
and all answers are Yes.
CALTP California AdTraining anced ProgramLightin
-LK 111.11-A IL Ur AlA,Lr I AAUP. bpatuA- 'rot-rt
.ighting Control
roject Name:Warehouse !Enforcement Agency:CITY OF ARCADIA IPennit Number.COMM-18-0937
roject Address:11700 Goldring Rd. IICity:Arcadia 'Zip Code:91006
• C. Testing Results
1. Automatic Time Switch Controls (all answers must be Yes). F
2. Occupancy Sensor(On Off Control) (all answers must be Yes). F
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
•
4. Partial On Occupant Sensor for PAF (all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF(all answers must be Yes). Also must
pass Test 2.
Representative Spaces Selected
Tested space/room name: Lounge
Space Type (office, corridor, etc) Open Office
Untested areas/rooms Conference, Office 3, 4, 5, Stair, Conference 2
Confirm compliance for all control system types (1-5) present in each space:
1. Automatic Time Switch Controls
Step 1:Simulate occupied condition
a. All lights can be turned on and off by their respective area control switch F
b. Verify the switch only operates lighting in the ceiling-height partitioned area in
which the switch is located.
Step 2:Simulate unoccupied condition
a. All lighting, including emergency and egress lighting, turns off. Exempt lighting may
remain on per Section 130.1(c)1 and 130.1(a)1.
b. Manual override switch controls only the lights in the selected ceiling height
partitioned space where the override switch is located and the lights remain on no
longer than 2 hours (unless serving public areas and override switch is captive key
type).
R
Step 3:
System returned to initial operating conditions F
2. Occupancy Sensors
Step 1:Simulate an unoccupied condition
l t
CAL TP California Advanced Lighting
Controls Training Program
ml.: n..e t
,r et i it rt,A tI G Or At,c.rA t A1Yt,C
.fighting Control
roject Name:Warehouse 'Enforcement Agency:CITY OF ARCADIA 'Permit Number COMM-18-0937
roject Address:11700 Goldring Rd. ''City:Arcadia 'Zip Code:91006
a. Lights controlled by occupancy sensors turn off within a maximum of 20 minutes I F
from start of an unoccupied condition per Standard Section 110.9(b)
•
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation.
Step 2:Simulate an occupied condition
F
a. Status indicator or annunciator operates correctly
b. Lights controlled by occupancy sensors turn on immediately upon an occupied
condition OR sensor indicates space is 'occupied' and lights may be turned on Fl
manually
Step 3:
13
System returned to initial operating conditions
3. Partial Off Occupancy Sensor
Step 1:Simulate an unoccupied condition
a. Lights go to partial off state within a maximum of 20 minutes from start of an
unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation. For library book stacks or
warehouse aisle, activity beyond the stack or aisle shall not activate the lighting in
the aisle or stack.
c. In the partial off state, lighting shall consume no more than 50% of installed lighting
power, or:
No more than 60% of installed lighting power for metal halide or high pressure
sodium lighting in warehouses.
No more than 60%of installed lighting power for corridors and stairwells in which
the installed lighting power is 80% or less of the value allowed under the Area
Category Method. �—
Light level may be used as a proxy for lighting power when measurements are taken
Step 2:Simulate an occupied condition
The occupant sensing controls shall turn lights fully ON in each separately controlled
areas, Immediately upon an occupied condition
4. Partial On Occupancy Sensors
Step 1.-Simulate an occupied condition.Verify partial on operation.
a. Immediately upon an occupied condition, the first stage activates between 50 to
r
70% of the lighting automatically.
b. After the first stage occurs, manual switches allow an occupant to activate the
alternate set of lights, activate 100% of the lighting power, and manually
deactivate all of the lights.
A J rettfn me A.t..e..ne.t I t,.Mtnn
,@.K 1 It It,A I r.yr ALA-CA'I AAUP, 14)L-H.
.fighting Contml
rojext Name:Warehouse Enforcement Agency:CITY OF ARCADIA (Permit Number.COMM-IR-0937
mjcxt Address:11700 Goldring Rd. (City:Arcadia (Zip Codc:91006
Step 2.Simulate an unoccupied condition
a. Both stages (automatic on and manual on) lights turn off within a maximum of 20
minutes from start of an unoccupied condition per Standard Section 110.9(a)
b. The occupant sensor does not trigger a false 'on' from movement in an area
adjacent to the controlled space or from HVAC operation.
CCS.. TP CaControlslifornia AdvancedTrainingProgram Lighting
. K11r11,AIL VN Al-ILLY 1AM1l,L� rtt,n-L11-VL-n
Lighting Control
roject Name:Warehouse „Enforcement Agency:CITY OF ARCADIA Permit Number.COMM-18-0937
roject Address:11700 Goldring Rd. (City:Arcadia IIZap Code:91006
5. Additional test for Occupancy Sensors Serving Small Zones in Office Spaces Larger than
250 fti", to Qualify for a Power Adjustment Factor (PAF)
Step 0: First,complete Functional Test 2(above)for each controlled zone.
'Step 1:Verify area served and compare actual PAF with claimed PAF.Refer to Functional Test 2.
a. Area served by controlled lighting ft2
b. Enter PAF corresponding to controlled area from line (a) above (<125 ft2 for
PAF=0.4, 126-250 ft2 for PAF=0.3, 251-500 ft2 for PAF=0.2).
c. Enter PAF claimed for occupant sensor control in this space from the Certificate of
Compliance.
d. The PAF corresponding to the controlled area (line b), is greater than or equal to
the PAF claimed in the compliance documentation (line c).
e. Sensors shall not trigger in response to movement in adjacent walkways or
workspaces
f. All steps are conducted in Functional Test 2 'Occupancy Sensor (On Off Control)'
and all answers are Yes.
CA GTP California Advanced UgMing
Controls Training Program -t : . . ,'
,GK I IF K.A I G UI AI,I,Lrr I AfdLIt I'rvKLA-L1DUL—A
.ighting Control
roject Name:Warehouse I Enforcement Agency:CITY OF ARCADIA (Permit Number.COMM-I8-0937
roject Address:11700 Goldring Rd. ilCity:Arcadia Zip Code:91006
• C. Testing Results
▪ 1. Automatic Time Switch Controls (all answers must be Yes). F
2. Occupancy Sensor(On Off Control) (all answers must be Yes).
3. Partial Off Occupancy Sensor (all answers must be Yes). For warehouses, library
book stacks, corridors, stairwells in nonresidential buildings must also be
accompanied by passing Test 1 or Test 2. r
4. Partial On Occupant Sensor for PAF(all answers must be Yes). r
5. Occupant Sensor serving small zones for PAF(all answers must be Yes). Also must
pass Test 2.
D. Evaluation :
r PASS: All applicable Construction Inspection responses are complete and all applicable
Equipment Testing Requirements responses are positive.
CAL TP California Advanced Lighting
Controls Training Program
I i 1 ..r 1
.GK I ICIt.A I C or ALt,Gr I ANt,L� r.,t-VL-A
*hung Control
roject Name:Warehouse [Enforcement Agency:CITY OF ARCADIA I Permit Number:COMM-18.0937
roject Address:11700 Goldring Rd. 'City:Arcadia I Zip Cale:91006
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Acceptance documentation is accurate and complete.
Documentation Author Company Name
Name Gary Logan Perception.Industries, Inc.
, Address City Long Beach
6285 E. Spring St.Suite 591
Zip Code Phone
90808 (562)858-1595
CEA/ATT Certification Author Signature
Identification (if TC-A813685
applicable)
.....".V.----
7
, ....______ _
Date of Signature:
04/22/2021
FIELD TECHNICIAN'S DECLARATION STATEMENT
I certify the following under penalty of perjury,under the laws of the State of California:
1.The information provided on this Certificate of Acceptance is true and correct.
2. I am the person who performed the acceptance verification reported on this Certificate of Acceptance(Field Technician).
3. The construction or installation identified on this Certificate of Acceptance complies with the applicable acceptance requirements indicated In the plans and
specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA7.
4. I have confirmed that the Certificate(s)of Installation for the construction or installation identified on this Certificate of Acceptance has been completed and
signed by the responsible builder/installer and has been posted or made available with the building permits) issued for the building.
Field Technician Name Company Name
Gary Logan Perception Industries, Inc.
Address: City Long Beach
6285 E. Spring St. Suite 591
Zip Code Phone
90808 (562)858-1595
ATT Certification Position with Company Vice President
Identification TC-A813685 (Title)
Field Technician Signature
6;i'"...----.211'
2 /)...."
Date of Signature: 04/22/2021
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this
Certificate of Acceptance.
2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design,construction
or installation of features, materials, components,or manufactured devices for the scope of work identified on this Certificate of Acceptance and attest to the
declarations in this statement(responsible acceptance person).
3. The information provided on this Certificate of Acceptance substantiates that the construction or installation identified on this Certificate of Acceptance complies
with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency,and conforms to the applicable acceptance
requirements and procedures specified in Reference Nonresidential Appendix NA7.
1. I have confirmed that the Certificate(s)of Installation for the construction or installation Identified on this Certificate of Acceptance has been completed and Is
posted or made available with the building permit(s)issued for the building.
5. I will ensure that a completed,signed copy of this Certificate of Acceptance shall be posted,or made available with the building permit(s)issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is
required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Acceptance Company Name Perception Industries, Inc.
Person Name Gary Logan
Address: City Long Beach
6285 E. Spring St. Suite 591
Zip Code Phone
90808 (562)858-1595
CSLB License 10 7642 Position with Company Vice President
............> ::::::
(Title)
Res onsible Accepta n Sign..
Date of Signature: 04/22/2021
L �� T n CaliforniaAdvancedLighting
r Controls Training Program •tti.:,.•............ 1 A ..r 1
.___._ ICAC L G UV.1lA.Bi t Ar .tt r pry KI-A-LII-VL-A
.fighting Control
roject Name:Warehouse I Enforcement Agency:CITY OF ARCADIA Permit Number.COMM-I8-0937
roject Address:11700 Goldring Rd. 'City:Arcadia 'IZip Code:91006
I
C,Aj_ TP CControlsalifornia AdvancedTrainingProgram Lighting
tut I It11.-A I r.yr AI,I,Gr t Atvt,G IIINK.,,,-Lt 1-v.3-.1
.utomatic Daylighting Control
rojeci Name:Warehouse l Enforcement Agency:CITY OF ARCADIA Permit Number:COMM-I8-0937
rojmt Address:11700 Goldring Rd. 'City:Arcadia Zip Code:91006
AUTOMATIC DAYLIGHTING CONTROL ACCEPTANCE DOCUMENT
Enforcement Agency Use: Checked by/Date
Check boxes for all pages of this NRCA-LTI-03-A completed and included in this submittal
1&2• NRCA-LTI-03-A Page Construction Inspection. This page required for all submittals.
• 3&q• NRCA-LTI 03 A Page Continuous dimming control functional performance test—watt-meter or amp-meter measurement
• NRCA-LTI-03-A Page
5&6 Stepped Switching/Stepped Dimming functional performance test—watt-meter or amp-meter measurement
!] \3CA-LTI-03-A Page Continuous dimming control functional performance test—light meter power measurement,and default look-up
7&8 table of fraction of rated power versus fraction of rated light output.
• NRCA-LTI-03-A Page
• 9&10 Stepped Switching/Stepped Dimming functional performance test—based or light outpjt
1. NA7.6.1.1 Construction Inspection:
1. Drawing of Daylit Zone(s) must be shown on plans or attached to this compliance document. By checking this
box, technician certifies that plans have been attached to this webform
F
Document Name and Page #'s E-5, E-6
Add Control Systems below. If sampling method is used in accordance with NA7.6.1.2. If adding, attach a page with names of other controls in sample(only fo
buildings with > 5 daylight control systems, sample group glazing same orientation)
Office 11
Office 11
• Plans Page Number E-6
Check if Tested Control is Representative of Sample r
2. System Information
Zone Type: Skylit(Sky), Primary Sidelit(PS),or Secondary Sidelit(SS)
Control Type: Continuous Dimming with more than 10 light levels(C), Stepped Dimming (SD), Switching (SW)
Design Footcandles: (Enter footcandle(fc) value or"U" if unknown):
3. Sensors and Controls
Control Loop Type: Open Loop(OL), Closed Loop(CL)
Sensor Location: Outside (0), Inside Skylight(TS), Near Windows facing out (NW), In Controlled Zone(CZ)
Sensor Location is Appropriate to Control Loop Type: (Yes/No) If control loop type is Open Loop(OL): Enter yes(Y) If location
Outside(0), Inside Skylight(IS),or Near Windows facing out(NW); otherwise, enter no(N).If Control loop type is Closed Loop
(CL): Enter yes(Y) if location = In Controlled Zone(CZ); otherwise, enter no(N).
Control Adjustments are in Appropriate Location (Yes/No): Yes, If Readily Accessible or Yes if in Ceiling less than or equal to 11 ft, Yes
CAL&TP California Advanced Lighting
Controls Training Program
-LK I)lr)I.A!E Ur AI.t.BYIAIrt.E IWKLA-LI1 tri-M
.utomatic Daylighting Control
reject Name:Warehouse llEnforcement Agency:CITY OF ARCADIA IIPem t Number.COMM-I8-0937
reject Address:11700 CroMring Rd. lICity:Arcadia kip Code:91006
No for all other.
4. Has Documentation Been Provided by the Installer:
Installation Manuals and Calibration Instructions Provided to Building Owner: (Yes/No) Yes
Location of Light Sensor on Plans: (Yes/No) es
Location of Light Sensor on Plans: (Page Number)
5. Separate Controls of Luminaires in Daylit Zones:
Are luminaires controlled by automatic daylighting controls only in daylit zones: (Yes/No) Yes
Separately circuited for daylit zones by windows and daylit zones under Skylights: (Yes/No) Yes
6. Daylighting Control Device Certification
Daylighting control has been certified in accordance with§110.9: (Yes/No)
Construction Inspection PASS/FAIL. If all responses on Construction Inspection pages 1 &2 are complete and all Yes/No questions
have a Yes response, the tests PASS; If any responses on this page are incomplete OR there are any No responses, the tests FAIL
PASS/FAIL Evaluation(check one):
11. PASS: If all responses on Construction Inspection pages 1 &2 are complete and all Yes/No questions have a Yes(Y)response, the
tests PASS
r FAIL: Any applicable Construction Inspection responses are incomplete OR there is one or more negative(N-no) responses in any applicable
Functional Performance Testing Requirements section. System does not pass and is NOT eligible for Certificate of Occupancy according to Section 10-
103(a)3B. Fix problem(s)and retest until the system(s) passes all portions of this test before retesting and resubmitting NRCA-LTI-03-A with PASSED
test to the enforcement agency. Describe below the failure mode and corrective action needed.
( A `\ TP California Advanced Lighting
Controls Training Program
..EK l It'ILA I t.V t AIA.-EX I A Nt.1c 0.N KLH-L I r-vi-H
,utomatic Daylighting Control
roject Name:Warehouse Enforcement Agency:CITY OF ARCADIA 'Permit Number:COMM-I8-0937
roject Addrecs:11700 Goldring Rd. City:Arcadia Zip Code:91006
2. NA7.6.1.2.1 Functional Performance Testing - Continuous Dimming Systems:
Power estimation using light meter measurement
Complete all tests on page 7&8(No Daylight Test, Full Daylight Test,and Partial Daylight Test) and fill out Pass/Fail section on Page 8.
Office 11
System Information
a. Control Loop Type: Open Loop or Closed Loop?(0 or C) 0
. Indicate if Mandatory control- M (required for skylit zone or primary sidelit zone with installed general lighting power > 120 W); rn
for Control Credit-CC; or Voluntary not for credit-V(M,CC,V)
c. If automatic daylighting controls are mandatory,are all general lighting luminaires in daylit zones controlled by automatic Yes
daylight controls?(Yes/No)
tl. General lighting design footcandles. (Enter footcandle(FC)value,or"U" if unknown.)
e. Power estimation method. (see line q) Default ratio of power to light(Dfc), cut-sheet ratio of power to light (CSfc) If CSF
attach cut-sheet. Enter Dfc or CSfc
Step 1: Identify Reference Location
(location where minimum daylight illuminance is measured in zone served by the controlled lighting.)
f. Method Used: Illuminance or Distance?(I or D) I
Override daylight control system and drive electric lights to highest light level for the following:
g. Highest light level fc -enter measured controlled electric lighting footcandles (fc)
h. Indicate whether this is Full Output(FO),or Task Tuned (Lumen Maintenance) (TT)
Step 2: No Daylight Test controls enabled & daylight less than 1 fc at reference location
i. Method Used: Night time manual measurement (Night), Night Time Illuminance Logging (Log), Cover Fenestration(CF),Cover COL;'
Open Loop Photosensor(COLP)
j. Reference Illuminance(footcandles)as measured at Reference Location(see Step 1). Enter footcandles 68
k. Enter Y if either of the following statements are true: If line h = FO; [Reference Illuminance(line j))/[Full Output fc(line g)] > Yes
70%?or[Reference Illuminance(line j)]/ [design footcandles (line d)] > 80%? (Yes/No)
Step 3: Full Daylight Test conducted when daylight > 150% of reference illuminance (line j)
I. Daylight illuminance(light level with electric lighting turned off) measured at Reference Location (fc) 78
m. Daylight illuminance(line I)greater than Reference Illuminance (line j)?(Yes/No) Yes
Fill out lines p through t only if electric lighting is turned down or off.
n.Total (daylight+ electric light) illuminance measured at the Reference Location (fc).
o. Electric lighting illuminance at the Reference Location(fc) [(line n)- (line W. 20
. Electric lighting illuminance(line o)divided by Highest Light Level fc(line g). Enter%. 22.222222222222;.
q. Dimmed luminaire fraction of rated power.Attach manufacturer's cut-sheet or use default graph of rated power to light output. 2
,el applicable control system on cut-sheet or graph. Enter fraction of rated power in %.
r. System Power Reduction = [1-line q] 68
s. Is System Power Reduction(line.r) > 65%when line h = FO, or > 56%when line h =TT(Yes/No). Yes
t. With uncontrolled lights also on, no lamps dimmed outside of daylit zone by control (Yes/No). Yes
u. Dimmed lamps have stable output, no perceptible flicker(Yes/No). Yes
CAL TP California Advanced Lighting
Controls Training Program
..EK I le ILA I it V 5 At-LEY I Alvis. ItiN I&H-L t ryr.I-„
,utormttic Daylighting Control
roject Name:Warehouse (Enforcement Agency:CITY OF ARCADIA Permit Number:COMM-I8-0937
roject Address:11700 Goldring Rd. 'City:Arcadia JZip Code:91006
v. Daylight Dimming plus OFF Controls PAF
(This portion of the full daylight test applies to lighting systems that are claiming a PAF for daylight dimming plus OFF controls.
- This portion of the full daylight test shall be conducted instead of steps I. thru u.)
Does the system automatically turn OFF the luminaires when full daylight is available?(Yes/No)
Step 4: Partial Daylight Test conducted when daylight between 60% and 95% of (line j).
Daylight illuminance(light level without electric light) measured at Reference Location (fc).
x. Daylight illuminance divided by the Reference Illuminance= (line w)/(line j). Enter%. 86.76470588235294
;. Is Ratio of Daylight illuminance to Ref. illuminance(line x) between 60%and 95%? (Yes/No). Yes
z.Total (daylight +electric light)illuminance measured at the Reference Location(fc).
aa. Total illuminance divided by the Reference Illuminance = (line z )/ (line j), Enter 0/0. 36.76470588235;96
bb. Is Total illuminance divided by the Reference illuminance(line aa)between 100% and 150%?(Yes/No). yes
PASS/FAIL Evaluation (check one):
PASS: All applicable Construction Inspection responses are complete and all applicable Functional Performance Testing Requirements responses are
positive (Y-yes)
FAIL: Any applicable Construction Inspection responses are incomplete OR there is one or more negative (N-no)responses in any applicable
Functional Performance Testing Requirements section. System does not pass and is NOT eligible for Certificate of Occupancy according to Section 10-
103(a)36. Fix problem(s)and retest until the system(s)passes all portions of this test before retesting and resubmitting NRCA-LTI-03-A with PASSED
test to the enforcement agency. Describe below the failure mode and corrective action needed.
Office 5
Office 5
Plans Page Number
Check if Tested Control is Representative of Sample
2. System Information
Zone Type: Skylit(Sky), Primary Sidelit(PS),or Secondary Sidelit(SS)
Control Type: Continuous Dimming with more than 10 light levels(C), Stepped Dimming(SD), Switching (SW)
Design Footcandles: (Enter footcandle (fc)value or"U"if unknown):
3. Sensors and Controls
Control Loop Type: Open Loop (OL), Closed Loop (CL)
Sensor Location: Outside(0), Inside Skylight(IS), Near Windows facing out(NW), In Controlled Zone(CZ) NW
Sensor Location is Appropriate to Control Loop Type: (Yes/No) If control loop type is Open Loop(OL): Enter yes(Y) if location = Yes
Outside(0), Inside Skylight(IS),or Near Windows facing out(NW); otherwise,enter no(N).If Control loop type is Closed Loop
(CL): Enter yes(Y)if location = In Controlled Zone(CZ); otherwise,enter no(N).
Control Adjustments are in Appropriate Location (Yes/No): Yes, If Readily Accessible or Yes if in Ceiling less than or equal to 11 ft, Yes
No for all other.
4. Has Documentation Been Provided by the Installer:
Installation Manuals and Calibration Instructions Provided to Building Owner: (Yes/No) Yes
CAL&TP California Advanced Lighting
TP Controls Training Program
art.:.. :.......... n ,.r t
,F.t<I II,ILA I t.yr At.Ltr I AIvLI IIiNki H-L11yV-H
,utomatic Daylighting Control
roject Name:Warehouse 'Enforcement Agency:CITY OF ARCADIA Permit Number:COMM-I8-0937
rojaa Address:11700 Goldring Rd. 'City:Arcadia Zip Calc:91096
Location of Light Sensor on Plans: (Yes/No) I Yes
Location of Light Sensor on Plans: (Page Number) E-6
5. Separate Controls of Luminaires in Daylit Zones:
Are luminaires controlled by automatic daylighting controls only in daylit zones: (Yes/No) Yes
Separately circuited for daylit zones by windows and daylit zones under skylights: (Yes/No) Yes
6. Daylighting Control Device Certification
Daylight:ng control has been certified in accordance with §110.9: (Yes/No) Yes
Construction Inspection PASS/FAIL. If all responses on Construction Inspection pages 1 &2 are complete and all Yes/No questions Pass
have a Yes response,the tests PASS; If any responses on this page are incomplete OR there are any No responses,the tests FAIL
PASS/FAIL Evaluation(check one):
a PASS: if all responses on Construction Inspection pages 1 &2 are complete and all Yes/No questions have a Yes(Y) response, the
tests PASS
r FAIL: Any applicable Construction Inspection responses are incomplete OR there is one or more negative(N- no) responses in any applicable
Functional Performance Testing Requirements section.System does not pass and is NOT eligible for Certificate of Occupancy according to Section 10-
103(a)3B. Fix problem(s)and retest until the system(s)passes all portions of this test before retesting and resubmitting NRCA-LTI-03-A with PASSED
test to the enforcement agency. Describe below the failure mode and corrective action needed.
CSL TP California Advanced Lighting
Controls Training Program
,rte I II'ILA I I Vr ALI..Lr I AIFLL I11 m-A-L.I I i 5
,ulomatie I}aylighling Control
roject Name:Warehouse Enforcement Agency:CITY OF ARCADIA I Permit Number:COMM-18-0937
roject Address:11700 Goldring Rd. [City:Arcadia Zip Code:91000
2. NA7.6.1.2.1 Functional Performance Testing - Continuous Dimming Systems:
Power estimation using light meter measurement
Complete all tests on page 7&8(No Daylight Test, Full Daylight Test,and Partial Daylight Test)and fill out Pass/Fail section on Page 8.
Office 5
System Information
a. Control Loop Type: Open Loop or Closed Loop?(0 or C) 0
b. Indicate if Mandatory control- M (required for skylit zone or primary sidelit zone with installed general lighting power> 120 W); M
for Control Credit-CC; or Voluntary not for credit-V(M,CC,V)
c. If automatic daylighting controls are mandatory,are all general lighting luminaires in daylit zones controlled by automatic Yes
daylight controls?(Yes/No)
d. General lighting design footcandles. (Enter footcandle(FC)value, or"U" if unknown.)
e. Power estimation method. (see line q) Default ratio of power to light(Dfc), cut-sheet ratio of power to light(CSfc) If CSFc --
attach
attach cut-sheet. Enter Dfc or CSfc
Step 1: Identify Reference Location
(location where minimum daylight illuminance is measured in zone served by the controlled lighting.)
f. Method Used: Illuminance or Distance? (I or 0)
Override daylight control system and drive electric lights to highest light level for the following:
Highest light level fc -enter measured controlled electric lighting footcandles(fc)
h. Indicate whether this is Full Output(FO), or Task Tuned (Lumen Maintenance) (TT)
Step 2: No Daylight Test controls enabled & daylight less than 1 fc at reference location
i. Method Used: Night time manual measurement(Night), Night Time Illuminance Logging (Log),Cover Fenestration (CF),Cover
Open Loop Photosensor(COLP)
i. Reference Illuminance (footcandles) as measured at Reference Location (see Step 1). Enter footcandles
k. Enter Y If either of the following statements are true: If line h = FO; [Reference Illuminance(line j)]/[Full Output fc(line g)] >
70%?or[Reference Illuminance(line j)]/ [design footcandles(line d)] > 80%? (Yes/No)
Step 3: Full Daylight Test conducted when daylight > 150% of reference illuminance (line j)
I. Daylight illuminance(light level with electric lighting turned off) measured at Reference Location(fc) 75
m. Daylight illuminance (line I) greater than Reference Illuminance(line j)?(Yes/No) Yes
Fill out lines p through t only if electric lighting is turned down or off.
n.Total (daylight + electric light) illuminance measured at the Reference Location (fc).
o. Electric lighting illuminance at the Reference Location(fc) [(line n)-(line I)]. ;9
n. Electric lighting illuminance(line o)divided by Highest Light Level fc(line g). Enter%. 1 1111111111 t i
q. Dimmed luminaire fraction of rated power.Attach manufacturer's cut-sheet or use default graph of rated power to light output.
Label applicable control system on cut-sheet or graph. Enter fraction of rated power in%.
r.System Power Reduction = [1 -line q)
s. Is System Power Reduction(line r) > 65%when line h = FO,or> 56%when line h=TT(Yes/No). Yes
t. With uncontrolled lights also on, no lamps dimmed outside of daylit zone by control (Yes/No).
u. Dimmed lamps have stable output, no perceptible flicker(Yes/No). Yes