(E) DINING AREA (NOT A PART)
(E) KITCHEN AREA
(E) KITCHEN AREA
(E) ELECTRICAL ROOM
(E) STORAGE
(E) MEN'S (E) WOMEN'S
SERVICE AREA
SERVICE AREA
OMAKAZECHARCOAL GRILL
(E) ALL-GENDERRESTROOMWET AREA
SITE PLAN / VICINITY
MAP / SHEET INDEX /
PROJECT INFO
A-0
ADDRESS: 1108 S BALDWIN AVE., B7, ARCADIA, CA 91007
APN:5778-007-029
SCOPE OF WORKS: TENANT IMPROVEMENT FOR A JAPANESE RESTAURANT
- NEW SERVICE AREA
- NEW KITCHEN AREA WITH COOKING EQUIPMENT
- NEW EXHAUST TYPE I HOODS AND MAKE UP AIR
TOTAL AREA: 1,192 SF
TYPE OF OCCUPANCY: A-2
TYPE OF CONSTRUCTION: V-B (FIRE SPRINKLERED)
BUILDING STOREY: 2 (PROJECT LOCATE AT 1ST FLOOR)
DEFERRED PLAN CHECK SUBMITTALS & PERMITS:
- EXTERIOR SIGNAGE
- FIRE ALARM, FIRE SPRINKLER
HVAC WILL NOT BE ALTERED; ACCESSIBLE RESTROOMS WILL NOT BE ALTERED
4SHEET INDEX
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
- 2022 CBC, CPC, CMC, CEC & CFC
- 2022 CALIFORNIA ENERGY EFFICIENCY CODE
- 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSC)
- CITY MUNICIPAL CODE
APPLICABLE CODES 3
DESIGNER: CDA + PDG
17528 E ROWLAND ST
CITY OF INDUSTRY, CA 91748
TEL: (626) 590-2368
CONTACT PERSON: RICK WANG
PROJECT CONTACTS 2
SITE PLAN 8
N
VICINITY MAP 1
N
A-0 TITLE SHEET (SITE PLAN / VICINITY MAP / PROJECT CONTACTS)
A-1 EQUIPMENT PLAN & SCHEDULE / FINISH SCHEDULE
A-1.1 KEY PLAN
A-1.2 CALGREEN BUILDING MANDATORY
A-1.3 CALGREEN BUILDING MANDATORY
A-1.4 CALGREEN BUILDING MANDATORY
A-2 ACCESSIBILITY NOTES & DETAILS
E-1 ELECTRICAL PLAN & PANEL SCHEDULE
E-2 LIGHTING & REFLECTED CEILING PLAN
E-3 LIGHTING TITLE-24
P-1 GAS, HOT/COLD WATER
P-2 SEWER PLAN
M-1 HVAC PLAN
M-2 MECHANICAL PLAN
M-3 MECHANICAL DETAILS
M-4 DUCT WRAP DETAILS
M-5 DUCT WRAP DETAILS
EN-1 NON RESIDENTIAL T-24 SHEET
EN-2 NON RESIDENTIAL T-24 SHEET
6PROJECT SUMMARY
PROJECT
H.C. PATH OF
TRAVEL
PUBLIC SIDEWALK PROJECT
A-2
5
1.IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE AS-BUILT CONDITIONS.
THE GENERAL CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH EXISTING
CONDITIONS AND ADVISE THE OWNER AND ARCHITECT IN WRITING OF ANY
SITUATION THAT WOULD NOT ALLOW HIM TO PROCEED ON THE BASIS OF THESE
DOCUMENTS.
2.GENERAL CONTRACTOR TO NOTIFY THE ARCHITECT FOR ANY DISCREPANCIES
FOUND ON THE CONSTRUCTION DOCUMENTS PRIOR TO PROCEEDING. LARGE
SCALE DRAWINGS PRECEDENT TO SMALLER SCALE DRAWINGS.
3.THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND
PERFORM ALL SELECTIVE REMOVAL WORK REQUIRED FOR THIS CONTRACT.
4.THE ARCHITECT'S SELECTION OF MATERIAL AND DETAILS DOES NOT RELIEVE THE
CONTRACTOR OF VERIFYING WITH THEIR SUPPLIER THAT PROPOSED MATERIALS
ARE PROPER FOR THE INTENDED APPLICATION AND USE.
5.REFER TO M.E.P. DRAWINGS FOR LAYOUT, SIZE, CIRCUITING AND GENERAL
LOCATIONS OF MECHANICAL, ELECTRICAL AND PLUMBING ITEMS. REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF MECHANICAL, ELECTRICAL,
AND PLUMBING ITEMS.
6.ALL DIMENSIONS SHALL BE VERIFIED IN FIELD BEFORE PROCEEDING WITH WORK.
ARCHITECT SHALL BE NOTIFIED OF ANY MODIFICATIONS.
7.ALL DIMENSIONS ARE TO EXT. FACE OF FINISH GYPSUM BOARD UNLESS NOTED
OTHERWISE.
8.DOOR DESIGNATIONS IDENTIFY EACH DOOR BY NUMBER ASSOCIATED WITH THE
ROOM NUMBER THE DOOR SWINGS INTO. WHEN THE ROOM NUMBER DOES NOT
EXIST THE DOOR IS IDENTIFIED BY THE ROOM NUMBER OF CLOSEST ROOM.
9.WORK WHICH CREATES EXCESSIVE NOISE OR DISRUPTION TO TENANT SHALL BE
PERFORMED DURING NON-BUSINESS HOURS ONLY. CONTRACTOR TO
COORDINATE WITH BUILDING MANAGEMENT.
10.MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND FIRE LIFE SAFETY
DRAWINGS SHALL BE SUBMITTED FOR PLAN CHECK AS A SEPARATE PACKAGES
AND PERMITS SHALL BE OBTAINED, AS REQUIRED, BY THE CONTRACTOR.
11.ALL SPRINKLERS (ALL TYPES), SECURITY CAMERAS, SPEALERS ETC. SHALL BE
CENTERED WITHIN CEILING TILE UNLESS OTHERWISE NOTED.
12.LOCATIONS OF SPRINKLER ARE SHOWN FOR ARCHITECTURAL DESIGN INTENT
PLACEMENT. SPACING MUST ALSO SATISFY ALL CODES AND THE MORE
STRINGENT DIMENSIONS SHALL APPLY. CONTRACTOR SHOULD COORDINATE WITH
ARCHITECT IF SPRINKLER SPACING REQUIREMENT IS DIFFERENT FROM
REFLECTED CEILING PLANS.
13.CARPET OR CARPET TILE SHALL BE SECURELY ATTACHED; HAVE A FIRM CUSHION,
PAD OR BACKING OR NO CUSHION OR PAD, AND HAVE A LEVEL LOOP, TEXTURED
LOOP, LEVEL CUT PILE, OR LEVEL CUT/UNCUT PILE TEXTURE. THE MAXIMUM PILE
HEIGHT SHALL BE 1/2". EXPOSED EDGES OF CARPET SHALL BE FASTENED TO
FLOOR SURFACES AND HAVE TRIM ALONG THE ENTIRE LENGTH OF THE EXPOSED
EDGE.
14.GFRG ACCESS PANELS TO BE PROVIDED IN ALL HARD LID CEILINGS FOR FIRE
DAMPER, MECHANICAL EQUIPMENT, ABOVE CEILING REQUIRED PER CODE.
COORDINATE LOCATION OF THE ACCESS PANELS WITH ARCHITECT IF NOT SHOWN
ON THE DRAWINGS.
15.MISCELLANEOUS METAL SHOWN ON DRAWINGS ARE FOR DESIGN GUIDE ONLY.
GENERAL CONTRACTOR IS RESPONSIBLE FOR THE STRUCTURAL CALCULATION
AND INTEGRITY OF MISCELLANEOUS METALS.
16.MILLWORK DRAWINGS ARE FOR DESIGN INTENT ONLY. GENERAL CONTRACTOR IS
RESPONSIBLE FOR THE SUPPORT SYSTEM DESIGN AND STRUCTURAL INTEGRITY.
17.WHERE WORK INCLUDED IN THE WORK IS PHYSICALLY CONNECTED TO, IN
CONTACT WITH, OR APPLIED TO EXISTING BASE BUILDING CONSTRUCTION
(INCLUDING AT CORES AND EXTERIOR WALLS, FLOORS AND CEILINGS), THE
RESULTING ASSEMBLIES ARE TO MAINTAIN THE STRUCTURAL FIRE-RESISTIVE AND
WATERPROOFER'S INTEGRITY OF THE EXISTING BUILDING CONSTRUCTION. THERE
SHOULD BE NO MECHANICAL CONNECTION OF ANY INTERIOR CONSTRUCTION OR
FINISHES TO THE BASE BUILDING EXTERIOR CURTAIN WALL.
18.A RATED SEPARATION SHALL BE PROVIDED BETWEEN THE AREA OF WORK AND
ANY OCCUPIED AREA OF THE BUILDING.
GENERAL NOTES:
SERVICE AREA
SERVICE AREA
OMAKAZECHARCOAL GRILL
(E) ALL-GENDER
RESTROOMWET AREA
(E) LOBBY
(156 SF.)
(NOT A PART)
(E) DINING AREA (NOT A PART)
EQUIPMENT PLAN
& SCHEDULE /
FINISH SCHEDULE
A-16
7
MATERIALS NOTES:
CEILING PANEL -- The following ceiling panels are approved.
U.S. Gypsum #3270 Vinyl Rock
1) Walls and ceilings in all areas except dining area shall be durable, smooth, nonabsorbent, and easily washable with a light colored (light colored is defined as
having a light reflectance value of 70% or greater) finish.
2) All counter surfaces including underside shall be durable, smooth, nonabsorbent, easily washable finish (may require stainless steel or high pressure laminate).
3) Tiles in restrooms, service area and kitchen shall be durable, smooth, nonabsorbent, easily washable finish.
4) Flooring under equipment and at the base coves shall be completely smooth. Floor surfaces which contain slip-resistant agents shall be restricted to traffic areas
only.
5) All equipment shall be either easily movable (ie., on casters), on min. 6 inch rounded metal legs, or sealed to min. 4 inch solid masonry island with min. three-eighths
inch coved radius.
6) Concrete floor must use top-set type ceramic coved base.
7) Water resistant walls (ie. FRP, stainless steel, tiles) are required behind all sinks and dishwashers. Material to be min. 4 ft. high for LA County, min. 8 ft. high for other
counties. All restroom walls to have moisture resistant gypsum board backing.
8) A min. 50-foot candles of light measured 30" A.F.F. in prep areas; a min. 20-foot candles of light in sake bar, handwashing areas, utensil washing area, & restrooms;
a min. 10-foot candles of light in storage, janitorial area & walk-in cooler.
FINISH SCHEDULE NOTES:
FLOOR COVERING -- The following are approved.
Tiles -- American Olean; Dal Tiles or equivalent.
Topset Ceramic Coved Base -- B&W Tile Co. #S-3619T; OTW Inc. #S-3619T
Concrete Sealer -- Ameritone #7101, Aque Mix Choice 15 or equivalent.
FINISH SCHEDULE
DOOR SCHEDULE
NO.SIZE TYPE FINISH HRWR.REMARKTHK.MATERIAL
A 3'-0"X7'-0"SWINGING PAINT PUSH-PULL1-3/4"
B
Note 1,2,3,4,5ALUM. W/
GLASS
NOTE:
1) Existing
2) Manually operated edge- or surface-mounted flush bolts and surface bolts are prohibited.
3) Glazed panels at locations within 18" above walking surface subject to human impact shall be
of tempered glass.
4) Self-closing, tight-fitting door assembly.
5)a. Interior hinged doors and gates: 5lbs max
b. Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12
degrees from the latch is 5 seconds minimum. (CBC 11B-404.2.8.1)
1-3/4"SWINGING3'-0"X7'-0"Note 1,2,4,5
C
PAINT LEVER
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
D
9SERVICE COUNTER SECTION
N
EQUIPMENT SCHEDULE 8 1FULL-HEIGHT PARTITION WALL
2FULL-HEIGHT PARTITION WALL
COVE BASE DETAIL
4TOPSET COVE
3
BASE DETAIL
--5
■
■
■
■
■
■■
■
■
■
E
PAINT LEVER1-3/4"WOODSWINGING3'-0"X6'-8"Note 1,2,4,5
METAL
1
--
10
--
10
--
A
B
C
C
PAINT LEVER1-3/4"WOODSWINGING3'-0"X6'-8"Note 2,4,5
or adjacent to all disabled accessible building
Post International Symbol of Accessibility on
entrance.
H.C. SIGN
TACTILE
"EXIT" SIGN
EXIT........
48"x48" CLEAR
60"x60" CLEAR
60"x60" CLEAR
48"x48" CLEAR
FLOOR PLAN10
1
--
2
--
A-2
4
E
PAINT SLIDING1-3/4"WOODPOCKET3'-0"X6'-8"Note 2,5
SERVICE COUNTER ELEVATION 11
11--
D
D
SERVICE AREA
SERVICE AREA
OMAKAZECHARCOAL GRILL
(E) ALL-GENDER
RESTROOMWET AREA
(E) LOBBY
(156 SF.)
(NOT A PART)
(E) DINING AREA (NOT A PART)
(E) KITCHEN AREA
(E) KITCHEN AREA
(E) ELECTRICAL ROOM
(E) STORAGE
(E) MEN'S (E) WOMEN'S
KEY PLAN
A-1.1
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
1
N
KEY PLAN
EGRESS CALCULATION
TOTAL OCCUPANTS x 0.3" PER OCC. = 106 x 0.3 = MIN. 32" REQ'D (180" PROVIDED)
MIN. EGRESS WIDTH:A
OCC. LOAD OF 106 = MIN. 2 EXITS REQ'D (5 EXITS PROVIDED)
MIN. EXITS REQUIRED FOR DINING RM.:
"A-2" OCCUPANCY (WITH FIRE SPRINKLER): MAX. 250' REQ'D (117' PROVIDED)
MAX. TRAVEL DISTANCE:
MIN. SEPARATION OF 2 REQ'D EXITS = 50% OF 111' = MIN. 56' REQ'D (95' PROVIDED)
B
C
(1,192 SF.)
EXISTING LOBBY AREA:
WAITING AREA = 156 S.F./15 PERSONS PER S.F.= 11 PERSONS
TOTAL 11 PERSONS
EXISTING RESTAURANT AREA:
CUSTOMER AREA = 810 S.F./15 PERSONS PER S.F.= 54 PERSONS
KITCHEN & SERVICE AREA = 947 S.F./ 200 PERSONS PER S.F.= 5 PERSONS
TOTAL 59 PERSONS
NEW PROJECT RESTAURANT AREA:
CUSTOMER AREA = 474 S.F./15 PERSONS PER S.F.= 32 PERSONS
KITCHEN & SERVICE AREA = 718 S.F./ 200 PERSONS PER S.F.= 4 PERSONS
TOTAL 36 PERSONS
SUB TOTAL 106 PERSONS
OCCUPANT CALCULATION
SUMMARY OF ACCESSIBILITY UPGRADES 2
PATH OF TRAVEL NOTES:
NO ABRUPT CHANGES IN ELEVATION ALONG THE PATH OF TRAVEL SHOWN. THE
SLOPE AND CROSS-SLOPE ALONG THE PATH OF TRAVEL SHALL NOT EXCEED 5% AND
2% RESPECTIVELY. INSPECTOR TO VERIFY
JANITORIAL SINK DETAIL 3
CALGREEN BUILDING
MANDATORY
A-1.2
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
CALGREEN BUILDING
MANDATORY
A-1.3
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
CALGREEN BUILDING
MANDATORY
A-1.4
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
ACCESSIBILITY NOTES & DETAILS
Fig. 8
Fig.7GRAB BAR DETAIL
Fig. 6
TRAFFIC ENFORCEMENT OFFICER
PARKED IN THE SPACE (CENTEREDWHEN A VEHICLE IS PROPERLY
RECOMMENDED)
AT ENTRANCE TO STALL
EMBLEM MUST BE LOCATED INSTALL SO THAT IS VISIBLE BY A
C
A
B
Fig. 5ACCESSIBLE PARKING STALL
1. EACH SPACE FOR THE DISABLED IS REQUIRED TO BE IDENTIFIED BY A PERMANENT ,
REFLECTORIZED SIGN WITH THE INTERNATIONAL SYMBOL OF ACCESSIBLITY.
2. THE SURFACE OF EACH SPACE FOR THE DISABLED IS REQUIRED TO HAVE A 3 FOOT SQUARE
INTERNATIONAL SYMBOL OF ACCESSIBILITY ATENELED IN BLUE PAINT.
3. AT THE ENTRANCE TO OFFSTREET PARKING FACUTIES. A CONSPICUOUS SIGN AT LEAST 17" BY
22" IS REQUIRED. FOR SIGN INFORMATION.
ACCESSIBLE RESTROOM DETAILS
1. 1-1/4" TO 1-1/2" ROUND STEEL BARS WITH
1-1/2" CLEARANCE (FOR TANK TYPE TOILETS.
SOAP DISPENSER.
TOILET PAPER HOLDER.
(TILE, CEMENT, MARLITE ETC).
PAPER TOWEL DISPENSER.
36" ABOVE FLOOR MAY BE ALLOWED IF TANK
2. PROVIDE SOLID BACKING FOR MOUNTING
3. NO ROTATION PERMITTED IF FITTINGS USED.
TOILET SEAT COVER DISPENSER.
SMOOTH, HARD, NONABSORBENT SURFACE
OF BARS.
MIRROR
OBSTRUCTS PLACEMENT OF BARS).
GRAB BAR:
UNDER LAVATORY.
1. NO SHARP OR ABRASIVE SURFACES
2. LEVER FAUCET CONTROLS OPERABLE.
3. HOT WATER SUPPLY AND DRAIN PIPING INSULATED.
1. FLUSH CONTROL HANDLE ON WIDE SIDE WITH
3 LBS. MAXIMUM OPERATING FORCE.
WATER CLOSET:
LAVATORY:
WITH ONE HAND AND 5 LBS. MAXIMUM FORCE.
TOILET
A
E
D
F J
C
G
H J
1 LAVATORY2
SHALL COMPLY WITH LABC 6.302.4
TOILET ROOM VIEW SCREEN
Fig. 4
DRAWN BY JIMMY ZHANG (6
2
6
)
5
7
0
-
9
9
7
8
DESIGN FOR RESTAURANT PLU
S
,
I
N
C
.
Fig. 1
ACCESSORIES IN SANITARY FACILITIES
SIGNAGE
CORRIDORS AND AISLES
SANITARY FACILITY FIXTURES AND ACCESSORIES
MULTIPLE ACCOMMODATION SANITARY FACILITIES
LAVATORIES
ACCESSORIES IN SANITARY FACILITIES
Fig. 9TRUNCATED DOME
If a walk crosses or adjoins a vehicular way, and the walking
surfaces are not separated by curbs, railings or other elements
between the pedestrian areas and vehicular areas, the
boundary between the areas shall be defined by a continuous
detectable warning (per 11B-705.1) which is 36" wide.
Food Service Lines/Aisles
Fig. 2appropriate signage.
SITE ACCESSIBLE ROUTE OF TRAVEL
At least one accessible route within the boundary of the
state is provided to an accessible building entrance from:
Public transportation stops
Accessible parking spaces
Accessible passenger loading zones
Public streets and sidewalks
At every primary public entrance and at every major
junction along or leading to an accessible route of travel,
there shall be a sign displaying the international symbol of
comply with the requirements:
accessibility. Signs shall indicate the direction to
accessible building entrances and facilities and shall
Accessible entrances and routes of travel have
Entrance signage
11B-703.7.2.1
11B-206.2.1
Counters
60"
ACCESSORIES IN SANITARY FACILITIES
Fig. 3
DOORS
ENTRANCES AND EXITS
WALKS & SIDEWALKS
PARKING SIGNAGE
2--
1--
(E) ALL-GENDER
RESTROOM
H.
F.
G.
E.
D.
recommended).11118B.4.thru B.6 52.4.
If medicine cabinets are provided, at least one has a
usable shelf no higher than 44" above floor.4.23.9
Operable parts (including coin slots) of all fixtures or
accessories are located a maximum of 40" above floor
(i.e., soap dispensers, towels toilet seat covers, auto-
dryers, sanitary napkin dispensers, waste receptacles,
Controls and operating mechanisms are operable with
one hand and do not require tight grasping, pinching,
The force required to activate controls is 5 lb. max.
Coat hooks and shelving are located within
appropriate reach ranges (48" max. above floor
6.or twisting of the wrist.
27.6.1117B.4 4.
1115B.etc.).9.2
1117B.4
4
Fig.9174.23.
27.4.4
4" WIDE PAINTED
PARK'G STRIPES:
2-COATS OF BLUE
AT DISABLED STALLS
OCCUPANT IN WHITE
ON BLUE BACKGROUND
SHALL BE 36" WIDE TYP.
DISABLED STALL
SIGN TYP.
PRECAST CONC.
WHEEL STOP
NO PARKING
2%
S
L
O
P
E
M
A
X
.
STRIPES AT 36" O.C.
"NO PARKING" LETTERS
12" HI. MIN.
CURB FACE
6B
--
1:12 MAX SLOPE DN
1/4" DEEP GROOVES
3/4"Ø O.C.
(12" WIDTH MIN.)
EXISTING BUILDING
1:12 MAX SLOPE DN
ACCESSIBILITY
NOTES & DETAILS
A-2
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
ELECTRICAL PLAN
&
PANEL SCHEDULE
E-1ELECTRICAL LEGEND 2
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
1PANEL SCHEDULE
3MANDATORY MEASURES
ELECTRICAL NOTES 4
N
6ELECTRICAL PLAN
SERVICE AREA
SERVICE AREA
OMAKAZECHARCOAL GRILL
(E) ALL-GENDER
RESTROOM
WET AREA
EXIT SIGN W/ EMERGENCY
LIGHTING
THE EMERGENCY POWER SYSTEM SHALL
PROVIDE POWER FOR A DURATION OF NOT
LESS THAN 90 MINUTES AND SHALL
CONSIST OF STORAGE BATTERIES, UNIT
EQUIPMENT OR AN ON-SITE GENERATOR.
THE INSTALLATION OF THE EMERGENCY
POWER SYSTEM SHALL BE IN ACCORDANCE
WITH SECTION 2702
EMERGENCY LIGHTING FACILITIES SHALL BE
ARRANGED TO PROVIDE INITIAL
ILLUMINATION THAT IS AT LEAST AN
AVERAGE OF 1 FOOTCANDLE MEASURED
ALONG THE PATH OF EGRESS AT FLOOR
LEVEL. ILLUMINATION LEVELS SHALL BE
PERMITTED TO DECLINE TO 0.6
FOOTCANDLE AVERAGE AND A MINIMUM AT
ANY POINT OF 0.06 FOOTCANDLE AT THE
END OF THE EMERGENCY LIGHTING TIME
DURATION. A MAXIMUM-TO-MINIMUM
ILLUMINATION UNIFORMITY RATIO OF 40
TO 1 SHALL NOT BE EXCEEDED.
( CBC 1008)
LIGHTING SHUT-OFF DIAGRAM 3
KEY NOTES:
REFLECTED CEILING AND
LIGHTING PLAN
E-2
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
1
KEY NOTES:
LIGHTING SHUT-OFF DIAGRAM 2LIGHTING INSTALLATION
6REFLECTED CEILING AND LIGHTING PLAN
2MANDATORY MEASURES
N
SEISMIC DESIGN CATEGORY "D":
(CBC 803.9, ASCE 7-16 SEC. 13.5.6 AND
CISCA 3-4)
- HEAVY-DUTY GRID SYSTEM
- MIN. 2" WALL MOLDING
- ATTACHED GRID ON 2 ADJACENT WALLS
- 3/4" CLR. AT PERIMETER ON
UNATTACHED WALLS.
MAX. LENGTHS FOR VERTICAL STRUT:
EMT CONDUIT
1/2" EMT CONDUIT- UP TO 3'-11"
3/4" EMT CONDUIT- UP TO 6'-4"
1" EMT CONDUIT- UP TO 9'-9"
METAL STUD
250S137-33 UP TO 6'-10"
250S137-43 UP TO 8'-10"
400S137-43 UP TO 10'-10"
SUSPENDED CEILING DETAIL 4
EF #1
EF #2
EF #3
MA #1
MA #2 MA #3
TC
ENERGY CALCULATION
E-3
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
PLUMBING PLAN
P-1TRAP PRIMER DETAIL
PIPE MATERIAL SCHEDULE 3
6PLUMBING FIXTURE SCHEDULE 4
5VENT DETAIL
NOTE:
2
1
3
2GAS LINE SIZING CALCULATION
HOT & COLD WATER PLAN 7
N
1WATER HEATER
G (E) GAS METER
w
(E) WATER METER
1
1-1/4" S.O.V.
(277 CF/H)
1" S.O.V.
(192 CF/H)
2
3
4
4
3/
4
"
G
1-1/4" G
1" G
1-1/2" G1-1/4" G
3/4" G(E) WATER SUPPLY
(E) 1/2" CW
(E
)
1
/
2
"
C
W
(E
)
1
/
2
"
H
W
3/
4
"
C
W
3/
4
"
H
W
1/2" HW 1/2" CW
1/2" CW
1/2" CW
1/2" HW
1/2" HW1/
2
"
H
W
1/2" CW
1/
2
"
C
W
1/
2
"
H
W
1/
2
"
C
W
SEWER PLAN
P-2PIPE MATERIAL SCHEDULE 3
DRAINAGE PLAN
N
SLAP REPAIR
5
1
GAS ISOMETRIC 4
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
(E) 3" S
(E) 3" FCO.
3" FCO.
2" S
1-1/2" S
3" GS
3" FCO.
3"
G
S
3" FCO.
1-1/2" S
3" GS
3" GS
EXISTING MAIN SEWER
1-1/2" S
3"
S
1-1/2" S
(E) 3"VTR.
2"
G
S
2" GS
6PLUMBING FIXTURE SCHEDULE
7PLUMBING FIXTURE SCHEDULE
3"S
(N) 3"VTR.
3" S
3"
S
3" WCO.
3" GS
ENERGY COMPLIANCE
(PLUMBING)
EN-1
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
BK
64
6
A
r
m
i
t
o
s
P
l
a
c
e
D
i
a
m
o
n
d
B
a
r
,
C
A
9
1
7
6
5
T
:
9
0
9
.
5
6
9
.
2
5
8
6
E
m
a
i
l
:
b
k
e
n
g
i
n
e
e
r
s
8
8
@
g
m
a
i
l
.
c
o
m
C
O
N
S
U
L
T
I
N
G
E
N
G
I
N
E
E
R
S
I
N
C
12/28/23
M 22176
ENERGY COMPLIANCE
(HOOD)
EN-2
R e v i s i o n s :
P l a n C h e c k N o. :
D r a w n B y :
C h e c k e d B y :
P h a s e :
D a t e :
C D A P r o j e c t N o.
D r a w i n g T i t l e :
S t a m p :
C l i e n t :
P r o j e c t :
D r a w i n g No. :
SUSHI KISEN
1108 S BALDWIN AVE., B7
ARCADIA, CA 91007
--
2334
PLAN CHECK
CDA
PDG
+
TUSTIN OFFICE
150 EL CAMINO REAL. #112
TUSTIN, CA 92780
PHONE: 714 832 5100
INDUSTRY OFFICE
17528 E. ROWLAND ST,
CITY OF INDUSTRY, CA 91748
PHONE: 626 913 8101
BK
64
6
A
r
m
i
t
o
s
P
l
a
c
e
D
i
a
m
o
n
d
B
a
r
,
C
A
9
1
7
6
5
T
:
9
0
9
.
5
6
9
.
2
5
8
6
E
m
a
i
l
:
b
k
e
n
g
i
n
e
e
r
s
8
8
@
g
m
a
i
l
.
c
o
m
C
O
N
S
U
L
T
I
N
G
E
N
G
I
N
E
E
R
S
I
N
C
KRISHNA KUMAR
BK CONSULTING ENGINEERS INC
646 ARMITOS PLACE
DIAMOND BAR, CA 91765
KRISHNA KUMAR
BK CONSULTING ENGINEERS INC
646 ARMITOS PLACE
DIAMOND BAR, CA 91765
12/28/23
M 22176
909 569 2586
12/28/23
909 569 2586