HomeMy WebLinkAbout400 S Baldwin Ave - 2023 - T.I. FOR COSMETIC RETAIL STORE MAISON KOSE. WITH ELECTRICAL AND PLUMBING ONLYScale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A0.00
COVER SHEET
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
MAISON KOSE STORE TENANT IMPROVEMENT
PROJECT DESCRIPTION
PROJECT TYPE:
COMMERCIAL COSMETIC STORE TENANT IMPROVEMENT
CONSTRUCTION TYPE:
TYPE II B
1 HR. FULLY SPRINKLERED
ZONING:
COMMERCIAL
FIRE SPRINKLER:
EXISTING FIRE SPRINKLER
FIRE SPRINKLER AS DEFFERED SUBMITTAL
TOTAL FLOOR AREA:
1151 SF
OCCUPANCY TYPE:
M
EGRESS:
EXIT REQ.: 2
APPLICABLE CODES
2022 CALIFORNIA BUILDING CODE VOL 1 & 2
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA MECHANICAL CODE
2022CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING CODE
2022 T-24 ENERGY STANDARDS
ARCADIA MUNICIPAL CODE
OWNERS
JCOSME INTERNATIONAL INC.
A: 19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
T: (626) 233-5699
E: tonytiao@aol.com
DESIGNER
JONATHAN WANG
A: 12621 WASHINGTON PL, LOS ANGELES CA 90066
T: (626) 684-6651
E: jwang@jonathanwangdesign.com
MECHANICAL & ELECTRICAL & PLUMBING
INNODEZ DESIGN & ENGINEERING
A: 5777 WEST CENTURY BOULEVARD #1110, CA 90045
T: (424) 414-0997
E: moe@innodez.com
CONTACTS SHEET INDEX
ARCHITECTURAL
A0.00 COVER SHEET
A0.01 GENERAL NOTES
A0.02 GENERAL NOTES
A0.03 ACCESSIBILITY DETAILS
A0.04 GREEN BUILDING CODE REQUIREMENT
A0.05 PRODUCT SPEC SHEETS
A1.00 SITE PLAN
A1.01 DEMOLISH FLOOR PLAN & RCP
A1.02 PROPOSED FLOOR PLAN
A1.03 EGRESS PLAN
A1.04 PROPOSED REFLECTED CEILING PLAN
A2.01 STOREFRONT ELEVATIONS, SECTION AND DETAILS
A2.02 INTERIOR ELEVATIONS
A3.01 DETAILS
A3.02 DETAILS -ROLL DOWN GATE
STRUCTURAL
S1 FRAMING PLAN & DETAILS
S2 CEILING FRAMING PLAN & DETAILS
S3 WALL SHELF ANCHORAGE & DETAILS
MECHANICAL
M0.00 MECH GENERAL NOTES & SPECIFICATIONS
M0.01 MECH CODE CHECKING
M1.01 MECH LAYOUTS & EQUIPMENT SCHEDULE
M2.01 MECH GENERAL DETAILS
ELECTRICAL
E0.00 ELECTRICAL SPECIFICATIONS
E0.01 ELECTRICAL GENERAL NOTES
E1.00 LIGHTING LAYOUTS -MAIN FLOOR
E2.00 POWER LAYOUT MAIN FLOOR/ ROOF
E3.00 POWER LAYOUT MAIN FLOOR/ ROOF
PLUMBING
P0.00 PLUMBING GENERAL NOTES AND SPECIFICATIONS
P0.01 PLUMBING CODE CHECKING
P1.01 FIRST FLOOR WATER SUPPLY LAYOUT
P2.01 FIRST FLOOR SEWER LAYOUT
T24.01 T24.01
T24.02 T24.02
T24.03 T24.03
PROJECT
NORTH
TRUE
NORTH
COMMERCIAL SPACE DESIGN:
1. TENANT IMPROVEMENT OF CORE & SHELL TENANT SPACE INTO COSMETIC RETAIL STORE;
2. INSTALL & CONNECT NEW AIR DUCTS AND REGISTERS TO EXISTING HVAC UNIT;
3. TRENCH CONCRETE FLOOR & INSTALL UNDERGROUND ELECTRICAL CONDUITS;
4. INSTALL NEW FULL HEIGHT PARTITION WALL.
5. INSTALL NEW RECESSED CEILING LIGHT FIXTURES AND PENDANT TRACK LIGHTS;
6. INSTALL PRODUCT DISPLAY CABINETS WITH LED;
7. INSTALL SUSPEND AND WALL MOUNTED INTERIOR LED DECOR SIGNAGE;
8. INSTALL NEW TILE FLOORING;
9. INSTALL DRYWALL CEILING, WALL AND PAINT;
10. INSTALL TOP-ROLL DOWN SECURITY GRILLE;
WESTFIELD SANTA ANITA -SPACE K3 400 S. BALDWIN AVENUE, ARCADIA, CA91007
General Notes:
1.Landlord review is for design intent and compliance with Landlord’s Criteria only. Approval by Landlord or
Landlord’s agent shall not constitute or imply a representation or certification by Landlord that these drawings or
Tenant’s work is in compliance with insurance and indemnity requirements, or any laws, rules, regulations,
building codes, or ordinances, including but not limited to the American with Disabilities Act, and fire life safety.
Furthermore, Landlord assumes no responsibility for the engineering or safety of Tenant's design, nor is Landlord
responsible for any coordination between other trades and job conditions affected by tenant's work.
2.Landlord delivers the premises in AS-IS conditions. Tenant is responsible for all field verification and must
design and build to those specifications.
3.Tenant’s Architect to submit to city for permit approval, all plans must comply with local and state jurisdictions.
4.Tenant’s GC and Architect to follow Rules and Regulations and Westfield Design Criteria
5.Any changes of store design and construction after plan approval must be formally addressed with Westfield
and the City.
6.Tenant shall ensure that entire storefront is behind the lease line. Coordinate field conditions with Westfield on-
site TC/FM.
7.Any changes to store design and construction due to field conditions are the full responsibility and sole cost to
the Tenant.
8.Tenant’s GC must coordinate any work outside lease line with Westfield TC.
9.Any use of existing equipment or others to be brought up to code. Tenant is responsible for any required
upgrades.
10.Any imported items must comply with US local standard without impacting the schedule.
11.Tenant's barricade needs to be set up before construction start with mall required vendor. Please to ensure to
have the vendor to coordinate with the mall management for proper mall common area clearance. Graphic needs
to be approved by mall marketing Director.
12.Contractor must contact Facility Manager for a set of Rules and Regulations for each center. A pre-
construction meeting must be held with Facility Manager prior to starting any construction with an approved set of
plans from the city.
13.GC must scan or x-ray the slab prior to any trench or coring. Please check with the mall FM and send report to
FM/TC for review before any work.
14.Any mall tile to be purchased from mall Facility Manager
15.Tenant must survey the space before any design and construction.
16.GC to use mall required vendors (Barricade, FS, FA, Roofing...etc.) if applied. Contacts on Mall Construction
Manual.
17.We deliver the space as is pending Tenant's power and water usage. Any upgrade needed per code or design
will be at Tenant's responsibility.
18.No sturdor vent is allowed.
19.Crane lift needs to be approved by WF Risk Management. It will take about 2-4 weeks for review. GC must VIF
and send the Risk Management package at the beginning of construction.
20.Tenant must provide proper Tenant space main gas and/or water control valve per code at the mall common
area or through access panel and with mall name tag for way finding. TYP.
21.Any Tenant’s power is on mall house meter must have functional sub-meter for mall monthly reading. GC to
VIF and install one to match the existing one in the mall as needed in your space and coordinate with the mall FM
further as needed.
22.If is on Edison meter, Tenant must transfer account to their name, and coordinate with mall FM for temp power
as needed.
23.No items of significant weight to be supported by deck. Including ceiling framing, HVAC and it’s to span from
steel to steel. Tenant to check with the city on any specific requirements.
24.GC must provide labels (Space Name + WF Space # + Mailing Address #) to back door, power breaker/meter
at mall electrical room, any roof units, space water shut off valve...etc.
25.GC to hire mall required FS/FA vendors for design/permit and installation per your design.
26.All color and material selections must meet all code requirements for Flame Spread and Smoke Development
Factors.
27.Submit color and material sample board for review and approval. Submit samples for the forward selling areas
and storefront. It is important that storefront samples be part of this submittal.
28.Any existing system within Tenant's space that will be reused must be reconditioned to current LL's Standards
and Building Code at Tenants expense.
GENERAL NOTES
SCOPE OF WORK
OCCUPANCY
TYPE
STORAGE
MERCANTILE
OCCUPANCY ANALYSIS
AREA 185 SF
OCCUPANCY
LOAD FACTOR 300
OCCUPANCY 1
TOTAL OCCUPANCY = 15 OCCUPANCY
DEFERRED SUBMITTAL
FIRE SPRINKLER AS DEFERRED SUBMITTAL
STOREFRONT SIGNAGE UNDER SEPARATE PERMIT
RETAIL
MERCANTILE
832 SF
60
14
EXP. DATE: 09/30/2024
A101
2
2 2
2
1
A101
1
A101
A101
1
101
BUILDING SECTION
EXTERIOR ELEVATION
ROOM TAG
DOOR TAG
WINDOW TAG
Room Name
MATERIAL TAG
REVISION CLOUD & TAG1
1i WALL TAG
KEYNOTEXX
SPOT ELEVATION
INTERIOR ELEVATION
DETAIL CALLOUT
DETAIL REFERENCEA101
1
1 GRID LINE
LEVEL
0' -0"
CENTERLINE
PROPERTY LINE
PT-1
0' - 1 1/4"
DIMENSION
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
12" = 1'-0"
A0.01
GENERAL NOTES
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1. ALL WORK, CONSTRUCTION AND MATERIALS SHALL COMPLY WITH ALL PROVISIONS OF ALL GOVERNING NATIONAL, STATE AND LOCAL BUILDING CODES, AND
WITH OTHER RULES, REGULATIONS AND ORDINANCES GOVERNING THE PLACE OF BUILDING.
2. BUILDING CODE REQUIREMENTS TAKE PRECEDENCE OVER THE DRAWINGS AND IT SHALL BE THE RESPONSIBILITY OF ANYONE SUPPLYING LABOR OR
MATERIALS OR BOTH TO BRING TO THE ATTENTION OF THE ARCHITECT ANY DISCREPANCIES OR CONFLICT BETWEEN THE REQUIREMENTS OF CODE AND
THE DRAWINGS.
3. ASBESTOS: IF REMOVAL OF ANY FRIABLE ASBESTOS-CONTAINING MATERIALS IS REQUIRED, REMOVAL OF SUCH MATERIAL SHALL BE ACCOMPLISHED BY A
CONTRACTOR APPROVED AND LICENSED FOR SUCH WORK IN THE STATE OF CALIFORNIA. THE ARCHITECT/ ENGINEERS DO NOT TAKE ANY RESPONSIBILITY
FOR THE LOCATION, REMOVAL, OR DISPOSAL OF ANY ASBESTOS OR ASBESTOS-CONTAINING MATERIALS.
4. ALL WORK SHALL CONFORM TO TITLE 24, CALIFORNIA CODE OF REGULATIONS (C.C.R)
5. CONTRACTOR SHALL HAVE CURRENT WORKERS' COMPENSATION INSURANCE COVERAGE IN COMPLIANCE WITH SECTION 3800 OF THE CALIFORNIA LABOR
CODE, ON FILE WITH THE STATE CONTROL BOARD.
6. DRAWINGS --ALL DIMENSIONS SHALL BE VERIFIED AND REVIEWED BY THE CONTRACTOR. ANY DISCREPANCIES OR INFORMATION UNCLEAR TO THE
CONTRACTOR SHALL BE REVIEWED WITH THE ARCHITECT FOR DIRECTION. ANY ASSUMPTIONS MADE BY THE CONTRACTOR,WHICH CONFLICT WITH THE
WORK SHALL BE REPAIRED AND/OR REPLACED AT THE CONTRACTOR'S EXPENSE.
A. DIMENSION SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON THE DRAWINGS. DO NOT SCALE DRAWINGS. LARGE-SCALE DETAILS TAKE
PRECEDENCE OVER SMALL-SCALE DETAILS.
B. ALL DIMENSIONS ARE TO THE FACE OF FINISH SURFACE, UNLESS OTHERWISE NOTED. ALL WORK SHALL BE ERECTED PLUMB, LEVEL AND TRUE IN
ACCORDANCE WITH THE DETAILS.
C. DETAILS MARKED TYPICAL SHALL APPLY IN ALL CASES UNLESS SPECIFIED OTHERWISE.
7. CONTRACTORS SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES OR DEVIATIONS BETWEEN FIELD CONDITIONS AND PROPOSED SCOPE OF WORK
INDICATED ON DRAWINGS.
8. CONTRACTOR SHALL CHECK, REVIEW, AND VERIFY ALL FIELD MEASUREMENTS WITH PROPOSED SCOPE OF WORK AND EXPRESSED DIMENSIONS HEREIN.
CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIES, PRIOR TO STARTING OR CONTINUING ANY WORK.
9. THE CONTRACT ARCHITECTURAL AND STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATETHE
MEANS OR METHOD OF CONSTRUCTION. THE GENERAL CONTRACTOR AND HIS/HER SUBCONTRACTORS SHALL PROVIDE ALL MEASURES NECESSARY TO
PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO
CONSTRUCTION EQUIPMENT, ETC.. CONTRACTOR SHALL PROVIDE PLANS AND PERMITS FOR TEMPORARY SHORING OF EXCAVATIONS THAT REMOVE THE
LATERAL SUPPORT FROM A PUBLIC WAY OR AN EXISTING BUILDING OR STRUCTURE. OBSERVATION VISITS TO THE SITE BY THE ARCHITECT SHALLNOT
INCLUDE INSPECTION OF THE ABOVE ITEMS.
10. THE CONTRACTOR SHALL PURCHASE "ALL RISK" BUILDER'S RISK COVERAGE WITH A SUFFICIENT LIMIT TO PROTECT THE ACTUAL REPLACEMENT VALUE OF
THE WORK. THE ARCHITECT AND THE OWNER SHALL BE NAMED AS ADDITIONAL INSURED. SEE ARTICLE 11 OF AIA DOCUMENT A201 FOR FURTHER
INSURANCE INFORMATION.
11. THE CONTRACTOR'S CERTIFICATE OF INSURANCE SHALL BE PREPARED FOR THE OWNER'S RECORDS AND DELIVERED TO THE ARCHITECT PRIOR TO
CONSTRUCTION.
12. IN PREPARING A BID, THE CONTRACTOR SHALL HAVE VISITED THE SITE , CAREFULLY EXAMINED THE DRAWINGS AND THE METHODS OF REMOVAL AND
STORAGE OF MATERIALS, THE SEQUENCING OF OPERATION, AND THE PROBLEMS ATTENDANT THERETO. NO ALLOWANCE WILL BE MADE TO THE
CONTRACTOR FOR ANY ERROR THROUGH NEGLIGENCE IN OBSERVING THE SITE CONDITION.
13. CONTRACTOR SHALL INVESTIGATE AND BE PRESENT AT THE SITE DURING SITE CLEARING, EARTHWORK, EXCAVATIONS, ETC. IF ANY BELOW GRADE ITEMS
OR CONDITIONS ARE DISCOVERED WHICH CONFLICT WITH PROGRESS AND INTENT OF THE PROJECT, THE ARCHITECT SHALL BE NOTIFIED.
A. 13.1. ALL WORK LISTED, SHOWN OR IMPLIED ON ANY CONSTRUCTION DOCUMENT SHALL BE SUPPLIED AND INSTALLED BY THE CONTRACTOR EXCEPT
WHERE OTHERWISE NOTED.
14. CONTRACTOR SHALL COORDINATE ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL WORK FOR SIZE AND LOCATION OF WALL, FLOOR AND ROOF
OPENINGS, WALL OFFSETS, PROVISIONS FOR PRESENT AND FUTURE EQUIPMENT, ATTACHMENT AND MOUNTING OF FIXTURES, INSERTS OR OTHER
OPENINGS, AND OTHER DETAILS. SHOULD A COORDINATION ERROR OR OMISSION BE IDENTIFIED, THE CONTRACTOR SHALL NOTIFY THE ARCHITECTIN
WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION. THE ARCHITECT WILL ISSUE INSTRUCTIONS AS TO PROCEDURE.
15. THE CONTRACTOR SHALL NOT DEVIATE FROM STRUCTURAL DESIGN AS DOCUMENTED IN THE PLANS AND SPECIFICATIONS WITHOUT WRITTEN APPROVAL
OF THE STRUCTURAL ENGINEER AND BUILDING DEPARTMENT AUTHORITY.
16. PROVIDE TEMPORARY SANITARY FACILITIES FOR WORKMEN'S USE PER THE LOCAL BUILDING DEPARTMENT REGULATIONS.
17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED FLOORS OR ROOF. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER
SQUARE FOOT. CONTRACTOR SHALL PROVIDE ADEQUATE SHORING AND/OR BRACING WHERE STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH.
18. THE CONTRACTOR IS TO VENT EACH AREA FROM FUMES, DUST, ETC. DO NOT USE A/C SYSTEM AND OR FURNACES FAN SYSTEM DURING CONSTRUCTION.
COVER ALL VENTS AND REGISTERS TO PROTECT FROM DEBRIS. CAP ALL LINES TO ELIMINATE ALL GASES FROM ENTERING THE WORKSPACE AND LIVING
SPACE. FORCE FLUSH AND VACUUM HVAC SYSTEM UPON PROJECT COMPLETION, PRIOR TO THE RESTART OF THE SYSTEM.
19. THE CONTRACTOR SHALL CUT AND PATCH EXISTING WALLS, FLOORS, CEILING, ETC. AS REQUIRED TO COMPLETE THE WORK.
20. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL SITE WORK, CONSTRUCTIONS, PROPERTY, AND ANY PLANT MATERIAL. ANY ITEM TO REMAIN OR NOT IN
SCOPE OF PROJECT WHICH IS DAMAGED OR INJURED SHALL BE, AT THE CONTRACTOR'S COST TO HIMSELF, REPLACED, OR REPAIRED TO "AS IS"
CONDITIONS PRIOR TO CONSTRUCTION OR DEMOLITION. SUCH PATCHING OR REPAIR INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING:ANY BROKEN OR
DAMAGED UTILITIES , SPRINKLER PIPE, ELECTRICAL OR PHONE LINES. CONTRACTOR SHALL PATCH OR REPLACE ANY DAMAGED CONCRETE SIDE WALK.
21. CONTRACTOR SHALL KEEP PROJECT AND SITE AT ALL TIMES FREE FROM ACCUMULATION OF WASTE MATERIALS AND RUBBISH CAUSED BY CONTRACTOR,
PRIOR TO COMMENCING ANY WORK.
22. AT ALL TIMES THE BUILDING, WORK AREA AND SITE SHALL BE KEPT ORDERLY, CLEAN, AND FREE OF DEBRIS & DIRT. DEBRIS, WASTE, RUBBISH, AND DISUSED
IMPLEMENTS AND EQUIPMENT SHALL NOT ACCUMULATE OVER A 24 HOUR PERIOD, FLAMMABLE AND / OR TOXIC MATERIALS SHALL NOT BE STORED IN
PROJECT CONSTRUCTION STRUCTURES OR ADJACENT TO.
23. CONTRACTOR SHALL KEEP NOISE, DUST, DEBRIS, ETC. TO A MINIMUM STANDARD AS SET FORTH BY THE OWNER.
24. ALL MATERIAL STORED ON THE SITE SHALL BE STACKED NEATLY ON SKIDS, PLATFORMS OR BLOCKING "HIGH AND DRY" PROTECTED AS RECOMMENDED BY
THE MANUFACTURERS, FROM POTENTIAL DAMAGE AND DETERIORATION CAUSED BY THE ELEMENTS.
25. ALL EQUIPMENT, HARDWARE, AND OTHER ITEMS SHALL BE SUPPLIED AS SPECIFIED, UNLESS CHANGES ARE REVIEWED AND ACCEPTED BY BOTH THE
OWNER AND ARCHITECT. IF CHANGES ARE REQUIRED FOR ANY REASON TO COMPLY WITH THE DESIGN INTENT, CONTRACTOR SHALL NOTIFY ARCHITECT
IMMEDIATELY WITH RECOMMENDATION OF REMEDIAL COURSE OF ACTION.
26. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES PRIOR TO EXCAVATING FOR UTILITIES AND SHALL BE RESPONSIBLE FOR LOCATING ALL UNDERGROUND
CONSTRUCTION PRIOR TO EXCAVATION. CONTRACTOR SHALL NOTIFY OWNER AND ARCHITECT SHOULD A PROBLEMATIC CONDITION BE FOUND.
27. REGULATIONS, TAXES AND PERMITS --THE WHOLE OF THE WORK SHALL BE EXECUTED IN STRICT ACCORDANCE WITH THE REGULATIONS AND CODES OF
THE GOVERNMENTAL AGENCIES WHOSE JURISDICTION IS APPLICABLE. THE OWNER SHALL PAY FOR PLAN CHECKING AND BUILDING PERMITS. EACH SUB-
CONTRACTOR SHALL SATISFY LOCAL PERMIT, LICENSE, INSURANCE AND SAFETY REQUIREMENTS AND SHALL BE RESPONSIBLE FOR THE JOB INSPECTIONS
PERTAINING TO HIS/HER TRADE. ALL APPLICABLE SALES TAXES SHALL BE INCLUDED IN THE CONTRACT. SUB-CONTRACTORS SHALL OBTAIN AND PAY FOR
ALL PERMITS PERTAINING TO HIS/HER TRADE.
28. SUBMITTALS --CONTRACTOR SHALL SUBMIT THREE (3) COPIES OF SHOP DRAWINGS, CALCULATIONS OF FABRICATED PRODUCTS, AND FIVE (5) COPIES OF
MANUFACTURER'S CATALOG SHEETS, BROCHURES, COLOR SAMPLES, INSTALLATION INSTRUCTIONS, ETC. ON ACCEPTANCE. THE ARCHITECT'S APPROVAL
OF SUBMITTALS AND SHOP DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR
SPECIFICATIONS UNLESS HE/SHE HAS, IN WRITING, CALLED THE ARCHITECT'S ATTENTION TO SUCH DEVIATIONS AT THE TIME OF SUBMISSIONS;NOR SHALL
THE CONTRACTOR BE RELIEVED FROM RESPONSIBILITY FOR ERRORS OF ANY SORT IN THE SHOP DRAWINGS. ARCHITECT REQUIRES 72 HOURS FOR REVIEW
OF ALL SUBMITTALS.
29. MATERIALS --SUPPLY NEW, PURELY UNADULTERATED, FIRST LINE QUALITY MANUFACTURED MATERIALS SHIPPED TO THE JOB SITE IN ORIGINAL
CONTAINERS WITH THE MANUFACTURER'S LABEL SHOWING EXACT TYPE, SIZE, GRADE, WEIGHT, AND USE. STORE IN MANNER CONSISTENT WITH
MANUFACTURER'S RECOMMENDATIONS.
30. WORKMANSHIP --SHALL BE OF THE HIGHEST QUALITY AND DONE BY SKILLED EMPLOYEES IN THE PRACTICE OF THEIR TRADE. THE GENERAL CONTRACTOR
SHALL SUPERVISE AND DIRECT THE WORK USING HIS/HER BEST SKILL AND ATTENTION. THE GENERAL CONTRACTOR WILL BE SOLELY RESPONSIBLE FOR
ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES AND SHALL BE RESPONSIBLE TO COORDINATE ALL PORTIONS OF THE
WORK UNDER THIS CONTRACT.
31. RESPONSIBILITY OF SUBCONTRACTORS
A. EACH SUBCONTRACTOR SHALL AT ALL TIMES BE FULLY AWARE OF THE JOB PROGRESS TO ALLOW HIMSELF/HERSELF AMPLE LEAD TIME TO COMMENCE
EACH PHASE OF HIS/HER WORK.
B. SUBCONTRACTORS SHALL THOROUGHLY INSPECT ADJACENT WORK THAT MAY IMPACT INSTALLATION OF THEIR TRADE AND NOTIFY GENERAL
CONTRACTOR, IN WRITING, OF ANY IRREGULARITIES. COMMENCING WORK CONSTITUTES ACCEPTANCE OF CONDITIONS AND THEREFORE
RESPONSIBILITY FOR AND RECTIFICATION OF ANY RESULTING, UNSATISFACTORY WORK.
C. MATERIALS AND THE WORK OF OTHERS SHALL BE INSPECTED BY EACH TRADE PRIOR TO THE COMMENCEMENT OF HIS/HER PARTICULAR PHASE OF
CONSTRUCTION. DAMAGE NOTED DURING SAID INSPECTION SHALL BE REPORTED, IN WRITING, TO THE GENERAL CONTRACTOR. IF DAMAGE HAS NOT
BEEN REPORTED AS HEREIN DESCRIBED, THE SUBCONTRACTOR(S) WORKING ON THE JOB OR THOSE WHO JUST COMPLETED THEIR WORK SHALL BE
HELD RESPONSIBLE.
D. WITHOUT REPEATING IT IN EVERY SECTION OF THESE SPECIFICATIONS, IT SHALL BE CLEARLY UNDERSTOOD THAT EACH SUBCONTRACTOR SHALL
UNEQUIVOCALLY GUARANTEE, FOR A MINIMUM OF ONE YEAR AFTER NOTICE OF COMPLETION, UNLESS OTHERWISE NOTED, THAT IS/HER WORK BE FREE
FROM DEFECTS OF WORKMANSHIP AND MATERIALS.
E. ALL WORK WHICH, IN THE OPINION OF THE GENERAL CONTRACTOR, FAILS TO MEET THE STANDARD AS HEREIN DESCRIBED, SHALL BE REPLACED BY THE
SUBCONTRACTOR AT THE SUBCONTRACTOR'S SOLE EXPENSE INCLUDING THE WORK OF OTHERS DAMAGED BY INITIAL FAILURE OR CORRECTIVE
REPAIRS. THE INABILITY OF THE GENERAL CONTRACTOR, OR HIS/HER REPRESENTATIVE, TO NOTICE OMITTED OR FAULTY MATERIALS OR WORKMANSHIP
DURING CONSTRUCTION SHALL NOT CONSTITUTE A RELEASE FROM THESE REQUIREMENTS OF SUBCONTRACTOR. IF WORK IS CONSIDERED TO BE
SUBSTANDARD, THE WORK SHALL BE TESTED AS IS STANDARD TO THAT INDUSTRY. IF THE WORK FAILS TO MEET THE TESTING STANDARDS THE
SUBCONTRACTOR SHALL PAY FOR THE TESTING AND REPLACEMENT OF THE WORK. IF THE WORK PASSES THE TEST THE OWNER PAYS FOR THE TEST
AND REPAIR OF SAID WORK.
F. EACH SUBCONTRACTOR SHALL MAINTAIN ADEQUATE PROTECTION OF ALL HIS/HER WORK FROM DAMAGE AND SHALL PROTECT THE OWNER'S AND
OTHER TRADES' WORK AND PROPERTY FROM DAMAGE OR INJURY WHILE FULFILLING HIS/HER CONTRACT. ALL MATERIALS, WORK IN PLACE, FINISHES,
PAVING, AND SIDEWALKS AND EXISTING UTILITIES SHALL BE INCLUDED IN THE REQUIREMENT.
G. STRUCTURE AND CONTENTS SHALL BE PROTECTED FROM THE INCLEMENCY OF WEATHER DURING THE TERM OF THE WORK.
H. IN THE EVENT OTHER TRADES DAMAGE SUBCONTRACTORS' WORK, IT WILL BE THE SUBCONTRACTORS OBLIGATION TO RESOLVE THE COST OF REPAIRS
OF SAID DAMAGE WITH RESPONSIBLE SUB-CONTRACTORS. THE GENERAL CONTRACTOR SHALL HAVE THE POWER OF FINAL ARBITRATION IN THESE
MATTERS.
I. COOPERATION --EACH TRADE SHALL COOPERATE FULLY, BOTH WITH THE GENERAL CONTRACTOR'S SUPERINTENDENT AND OTHER TRADES, AND
CONSULT WITH OTHER TRADES (IN WRITING IF NEED BE), IN ORDER TO "CAN OUT", ALLOW PASSAGE, PROVIDE PROTECTION OR DO WORK NECESSARY
TO ALLOW OTHERS TO FOLLOW IN AN ORDERLY, PROFESSIONAL MANNER.
J. UNCRATING --ALL MATERIALS AND APPLIANCES SHALL BE UNCRATED BY SUBCONTRACTOR RESPONSIBLE FOR INSTALLATION, UNLESS OTHERWISE
SPECIFIED IN THE CONTRACT.
32. WORK, AUTHORIZATION AND PAYMENTS --ALL WORK DONE OR MATERIAL USED SHALL BE COVERED BY A CONTRACT,CONTRACT CHANGE ORDER,
PURCHASE ORDER, OR WORK ORDER. NO INVOICE WILL BE PROCESSED UNLESS IT LISTS THE CONTRACT, PURCHASE ORDER, WORK ORDER OR CHANGE
ORDER NUMBER.
33. PAYMENTS TO THE CONTRACTOR --RELEASES OF LIEN OR PARTIAL RELEASES TO THE AMOUNTS PAID TO SUBCONTRACTOR AS WELL AS THE GENERAL
CONTRACTOR'S RELEASES SHALL ACCOMPANY EACH CERTIFICATE FOR PAYMENT ACCORDING TO CURRENT LIEN LAW REGULATIONS.
34. CLEAN UP --THE CONTRACTOR SHALL CLEAN AND REMOVE FROM THE SITE ANY DEBRIS AND UNUSED MATERIALS. UNUSED MATERIALS, EQUIPMENT,
SCAFFOLDING AND DEBRIS SHALL BE REMOVED FROM THE SITE AT COMPLETION. FINAL CLEANING SHALL INCLUDE, REMOVAL OF ALL GREASE, DUST,
STAINS, LABELS, FINGERPRINTS, PAINT SPOTS FROM SITE AND EXPOSED INTERIOR AND EXTERIOR FINISH SURFACES; POLISH SURFACES SO DESIGNATED TO
SHINE FINISH; AND REPAIR, PATCH OR TOUCH UP OR REPLACE MARRED SURFACES TO SPECIFIED FINISH, OR TO MATCH ADJACENT SURFACES.
35. OCCUPANCY --THE OWNER RESERVES THE RIGHT TO OCCUPY THE PREMISES AT ANY TIME BEFORE COMPLETION. SUCH OCCUPANCY SHALL NOT
CONSTITUTE FINAL ACCEPTANCE OF ALL OR ANY PART OF THE WORK INCLUDED IN THE CONTRACT.
36. WARRANTEE --IT SHALL BE UNDERSTOOD, UNLESS OTHERWISE STATED, THAT ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD
OF ONE YEAR. COMMENCING UPON THE ACCEPTANCE OF THE COMPLETION OF THE PROJECT BY THE OWNER.
37. THE CONTRACTOR IS TO SIGN IN THE SPACE PROVIDED TO ACKNOWLEDGE THAT HE HAS READ THESE GENERAL AND SUPPLEMENTAL NOTES AND AGREES
WITH THEIR TERMS AND CONTENT. BY ENTERING INTO AN AGREEMENT WITH THE OWNER TO PERFORM THE WORK DESCRIBED IN THESE CONTRACT
DOCUMENTS, THE SUCCESSFUL BIDDER/CONTRACTOR HEREBY AGREES WITH THE PROVISIONS OF AIA DOCUMENT A201, GENERAL CONDITIONS OF THE
CONTRACT FOR CONSTRUCTION, 1987 EDITION.
38. CONTRACTOR TO INCORPORATE ALL RECOMMENDATIONS PER THE GEOLOGIC AND SOILS ENGINEERING EXPLORATION REPORT. REPORT SHALL BE
CONSIDERED PART OF THE CONSTRUCTION DOCUMENTS.
39. GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION WILL BE THOSE AGREED UPON BY AND BETWEEN THE OWNER AND THE CONTRACTOR.
HOWEVER, FOR THE PURPOSE OF COMPILING THESE SPECIFICATIONS, IT HAS BEEN ASSUMED THAT THE GENERAL CONDITIONS WILL BE THOSE CONTAINED
IN THE AIA DOCUMENT A201, A COPY OF WHICH IS ON FILE AT THE OFFICE OF THE ARCHITECT.
40. SHOULD ERRORS, OMISSIONS, OR DISCREPANCIES APPEAR IN THE DRAWINGS OR SPECIFICATION, OR IN THE WORK DONE BY OTHERS AFFECTING THIS
WORK, THE ARCHITECT SHALL BE NOTIFIED AT ONCE AND WILL ISSUE INSTRUCTIONS AS TO PROCEDURE.
41. BUILDING CODE REQUIREMENTS TAKE PRECEDENCE OVER THE DRAWINGS AND IT SHALL BE THE RESPONSIBILITY OF ANYONE SUPPLYING LABOR OR
MATERIALS OR BOTH TO BRING TO THE ATTENTION OF THE ARCHITECT ANY DISCREPANCIES OR CONFLICT BETWEEN THE REQUIREMENTS OF CODE AND
THE DRAWINGS. SHOULD THE CONTRACTOR PERFORM ANY WORK CONTRARY TO SUCH LAWS, OR REGULATIONS, HE/SHE SHALL BEAR ALL COSTS OF
REMOVAL AND CORRECTION.
42. THE CONTRACTOR SHALL REVIEW ALL DOCUMENTS RELATED TO THIS PROJECT FOR ERRORS, OMISSIONS, AND DISCREPANCIES PRIOR TO THE STARTOF
CONSTRUCTION. THE CONTRACTOR SHALL ARRANGE A PRE-CONSTRUCTION MEETING TO REVIEW ERRORS, OMISSIONS AND DISCREPANCIES PRIOR TO THE
PERFORMANCE OF ANY WORK.
43. THE CONTRACTOR SHALL PROVIDE THE OWNER A LIST OF THE HEATING, COOLING, WATER HEATING, AND WARRANTIES MANUAL AND LIGHTING SYSTEMS
AND CONSERVATION OR SOLAR DEVICES INSTALLED IN THE BUILDING AND INSTRUCTIONS ON HOW TO USE THEM EFFICIENTLY.
44. AFTER INSTALLING INSULATION, THE INSTALLER SHALL POST IN A CONSPICUOUS LOCATION IN THE BUILDING A CERTIFICATE SIGNED BY THE INSTALLER AND
THE BUILDER STATING THAT THE INSTALLATION CONFORMS WITH THE REQUIREMENTS OF TITLE 24, PART 2, CHAPTER 2-53, AND THAT THE MATERIALS
INSTALLED CONFORM WITH THE REQUIREMENTS OF TITLE 20, CHAPTER 2. THE CERTIFICATE SHALL STATE THE MANUFACTURER'S NAME AND MATERIAL
IDENTIFICATION, THE INSTALLED R-VALUE, AND WEIGHT PER SQUARE FOOT.
45. THE CONTRACTOR SHALL PROVIDE A FIRE PROTECTION SYSTEM DURING CONSTRUCTION AND MAINTAIN INSURANCE AND ADHERE TO REQUIREMENTS OF
LOCAL FIRE DEPARTMENT, PRIOR TO COMMENCING ANY CONSTRUCTION.
46. THE CONTRACTOR SHALL PROTECT TREES AND SHRUBS AS INDICATED TO REMAIN BY PROVIDING A FENCE AROUND THE TREE OR SHRUB OF SUFFICIENT
DISTANCE AWAY AND OF SUFFICIENT HEIGHT SO THAT TREES AND SHRUBS SHALL NOT BE DAMAGED IN ANY WAY. CONTRACTOR SHALL BE RESPONSIBLE
FOR ANY DAMAGE, WHICH MAY OCCUR.
47. CONTRACTOR SHALL PROVIDE PLANS FOR THE TEMPORARY SHORING AND SUPPORT OF PUBLIC WAYS OR EXISTING BUILDINGS THAT MAY BE AFFECTED BY
EXCAVATIONS NECESSITATED BY THE NEW CONSTRUCTION. EXCAVATION ADJACENT TO A PUBLIC WAY REQUIRES PUBLIC WORKS APPROVAL PRIOR TO
ISSUANCE OF BUILDING PERMITS.
48. THERE SHALL BE NO TRENCHES OR EXCAVATIONS FIVE FEET OR MORE IN DEPTH INTO WHICH A PERSON IS REQUIRED TO DESCEND OR THE CONTRACTOR
MUST OBTAIN A NECESSARY PERMIT FROM THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL SAFETY PRIOR TO THE ISSUANCE OF A BUILDINGOR
GRADING PERMIT.
49. GLASS DOORS, ADJACENT PANELS AND ALL GLAZED OPENING WITHIN 18" OF ADJACENT FLOOR SHALL BE OF TEMPERED GLASS. WHEN ENLARGING
EXISTING OPENING FOR A NEW WINDOW OR DOOR PROVIDE A NEW LINTEL IF REQUIRED.
50. OPEN EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, BETWEEN WALL AND FOUNDATION, BETWEEN WALL AND ROOF, BETWEEN WALL PANES,
AND PENETRATIONS THROUGH ENVELOPE SHALL BE SEALED, CAULKED, OR WEATHER-STRIPPED TO LIMIT AIR INFILTRATION OR WATER LEAKAGE. DOORS
AND WINDOW SHALL BE FULLY WEATHER STRIPPED. CONTRACTOR TO DESIGN AND SPECIFY ALL FLASHING AS REQUIRED TO PREVENT WATER
PENETRATION FROM THE EXTERIOR TO THE INTERIOR.
51. CONTRACTOR SHALL ISOLATE DISSIMILAR METALS TO PREVENT GALVANIC REACTIONS.
52. ROOFING CONTRACTOR IS RESPONSIBLE FOR INSURING THAT FLASHING AND WEATHER PROOFING ARE WATERTIGHT.
53. ALL PLUMBING, MECHANICAL SYSTEMS, DRAINAGE, SEWAGE SYSTEMS ARE TO BE DESIGNED AND SPECIFIED BY A LICENSED CONTRACTOR AND SHALL
CONFORM TO ALL LOCAL PREVAILING CODES.
54. ARCHITECT SHALL BE NOTIFIED OF DIMENSIONAL DISCREPANCIES AT THRESHOLD.
55. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY BLOCKING, BACKING, FRAMING, HANGERS OR OTHER SUPPORT FOR ALL FIXTURES, EQUIPMENT.
56. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY BLOCKING TO INSURE PROPER ATTACHMENT OF GYPSUM BOARD, CABINETRY, BASEBOARD, TRIM,
FASCIA, ETC.
57. ALL FINISH GRADES AND FLATWORK SHALL SLOPE AWAY FROM THE BUILDING.
58. 58. ANY SUBSTITUTIONS SHALL BE REVIEWED AND ACCEPTED BY OWNER AND ARCHITECT. PRIOR TO COMMENCING INSTALLATION, ANY ADDITIONAL COSTS
INCURRED BY THE CONTRACTOR DUE TO HIS/HER FAILURE TO OBTAIN REQUIRED ACCEPTANCE SHALL NOT BE REMEDIED BY THE OWNER OR AFFECT THE
CONTRACT PRICE.
59. ALL DOORLOCK SETS, CATCHES, BUMPERS, CABINET PULLS, MAIL-BOXES, BATHROOM ACCESSORIES ARE TO BE SPECIFIED BY ARCHITECT (SEE FINISH,
PLUMBING AND DOOR HARDWARE SCHEDULES) AND OR OWNER.
60. SET AND SECURE ALL CABINETRY, PLUMB AND SQUARE, COUNTER SINK ALL FASTENERS, COUNTERTOPS TO BE GLUED AND SCREWED SECURELY IN PLACE,
ADJUST ALL DOORS.
61. PROVIDE ALL INSULATION AS NOTED BETWEEN FRAMING; STAPLE TO STUDS, MAINTAIN 1 1/2" (MIN) AIRSPACE IN ALL ROOF CAVITIES.
62. PACK AND SEAL ALL CRACKS AROUND WINDOW, DOORS, AND OTHER PENETRATIONS WITH INSULATION. FILL ALL VOIDS,SEAL ALL JOINTS.
63. SEAL ALL VAPOR BARRIER JOINTS, EDGES, PENETRATIONS AND PUNCTURES WITH VAPOR BARRIER TAPE TO FORM A CONTINUOUS VAPOR BARRIER, 6 MIL.
(MINIMUM).
64. ALL PENETRATIONS THROUGH NOTED FIRE BARRIERS, WALLS, ETC. SHALL BE SEATED BY APPROVED FIRE BARRIER SEALANT, CAULKS, TAPES, AS
SPECIFIED.
65. PRIOR TO PAINTING , ALL SURFACES TO BE SANDED SMOOTH, ALL NAILS SET AND PUTTIED.
66. WHERE NEW ROOFING MATERIALS, MEMBRANES AND ROOF DECKS ARE EXPOSED TO WEAR AND POSSIBLE DAMAGE DURING CONSTRUCTION THE
CONTRACTOR SHALL PROVIDE PROTECTION, ADDITIONAL WATER-PROOFING, FLASHING, CAULKING, OR COVERING TO AVOID PRESENT OR FUTURE WATER
INFILTRATION. ALL PENETRATIONS SHALL BE PROPERLY AND COMPLETELY SEALED. DEBRIS AND LOOSE MATERIALS SHALL BE REGULARLY ELIMINATED
FROM ANY ROOFING OR DECKING INSTALLATION.
REFER TO GREEN BUILDING PLAN CHECK GENERAL NOTES SHEET A0.01 FOR NOTES 67 -88.
89. AN APPROVED SEISMIC GAS SHUTOFF VALVE WILL BE INSTALLED ON THE FUEL GAS LINE ON THE DOWN STREAM SIDE OF THE UTILITY METER ANDBE
RIGIDLY CONNECTED TO THE EXTERIOR OF THE BUILDING OR STRUCTURE CONTAINING THE FUEL GAS PIPING. (PER ORDINANCE 170,158) (SEPARATE
PLUMBING PERMIT IS REQUIRED)
90. PROVIDE 70 INCH HIGH NON ABSORBENT WALL ADJACENT TO SHOWER AND APPROVED SHATTER RESISTANT MATERIALS FOR SHOWER ENCLOSURE. (R308)
91. UNIT SKYLIGHTS SHALL BE LABELED BY A LA CITY APPROVED LABELING AGENCY. SUCH LABEL SHALL STATE THE APPROVED LABELING AGENCY NAME,
PRODUCT DESIGNATION AND PERFORMANCE GRADE RATING (RESEARCH REPORT NOT REQUIRED). (R308.6.9)
92. THE CONSTRUCTION SHALL NOT RESTRICT A FIVE-FOOT CLEAR AND UNOBSTRUCTED ACCESS TO ANY WATER OR POWER DISTRIBUTION FACILITIES (POWER
POLES, PULL-BOXES, TRANSFORMERS, VAULTS, PUMPS, VALVES, METERS, APPURTENANCES, ETC.) OR TO THE LOCATION OF THE HOOK-UP. THE
CONSTRUCTION SHALL NOT BE WITHIN TEN FEET OF ANY POWER LINES-WHETHER OR NOT THE LINES ARE LOCATED ON THE PROPERTY. FAILURE TO
COMPLY MAY CAUSE CONSTRUCTION DELAYS AND/OR ADDITIONAL EXPENSES.
93. PROVIDE DAMP-PROOFING FOR ALL WALLS BELOW GRADE THAT ENCLOSE USABLE SPACE." 91.1402.4
94. WATER HEATER MUST BE STRAPPED TO WALL. SEC. 507.3, UPC
95. SMOKE DETECTORS SHALL BE PROVIDED AS FOLLOWS:
A. IN NEW CONSTRUCTION SMOKE DETECTORS SHALL RECEIVE THEIR PRIMARY POWER SOURCE FROM THE BUILDING WIRING AND SHALL BE EQUIPPED
WITH BATTERY BACK UP AND LOW BATTERY SIGNAL.
B. SMOKE DETECTORS SHALL BE LOCATED IN EACH SLEEPING ROOM & HALLWAY OR AREA GIVING ACCESS TO A SLEEPING ROOM, AND ON EACH ACCESS
TO A SLEEPING ROOM, AND ON EACH STORY AND BASEMENT FOR DWELLINGS WITH MORE THAN ONE STORY.
96. PROVIDE AN APPROVED SPARK ARRESTER FOR THE CHIMNEY OF A FIRE PLACE, STOVE, OR BARBECUE. L.A.M.C. 57.20.25
97. PROVIDE ULTA-FLUSH WATER CLOSETS FOR ALL NEW COSTRUCTION. EXISTING SHOWER HEADS AND TOILETS MUST BE ADAPTED FOR LOW WATER
CONSUMPTION
VICINITY MAP ABBREVIATIONS
SYMBOLS
A.C.AIR CONDITIONING
ADJ.ADJACENT
ADDT'L ADDITIONAL
A.F.F.ABOVE FINISH FLOOR
A.H.AIR HANDLER
ALT.ALTERNATING
ALUM.ALUMINUM
BD.BOARD
BLD'G BUILDING
BLK'G BLOCKING
CALCS.CALCULATIONS
CL.CENTERLINE
CLG.CEILING
CONC.CONCRETE
CONT.CONTINUOUS
CORR.CORRUGATED
CNTR.CENTER
DET.DETAIL
DIA.DIAMETER
DIM.DIMENSION
DWGS.DRAWINGS
(E)EXISTING
EA.EACH
ELEC.ELECTRICAL
EQ.EQUAL
EXIST.EXISTING
EXPAND.EXPANDED
EXT.EXTERIOR
F.C.FINISH CEILING
F.F.FINISH FLOOR
FLR.FLOOR
F.S.FINISH SURFACE
GA.GAUGE
GALV.GALVANIZED
G.L.GRID LINE
GYP. BD.GYPSUM BOARD
HT.HEIGHT
H.V.A.C.HEATING /
VENTILATION / AIR
CONDITIONING
INT.INTERIOR
MAX.MAXIMUM
M.B.MACHINE BOLT
MECH.MECHANICAL
MIN.MINIMUM
MTL.METAL
(N)NEW
N/A NOT APPLICABLE
N.I.C.NOT IN CONTRACT
N.T.S NOT TO SCALE.
O.C.ON CENTER
PNT.PAINT
P.T.PRESSURE
TREATED
REF.REFERENCE
REQ'D REQUIRED
RM.ROOM
S.S.STAINLESS STEEL
SIM.SIMILAR
STL.STEAL
STLS.STAINLESS
STRUCT.STRUCTURE(AL)
STOR.STORAGE
SUSP.SUSPENDED
T.B.D.TO BE
DETERMINED
THK.THICK
T.O.W.TOP OF WALL
TYP.TYPICAL
U.N.O.UNLESS NOTED
OTHERWISE
V.I.F.VERIFY IN FIELD
V.S.VENT SHAFT
W/WITH
W.C.WATER CLOSET
WD.WOOD
W.H.WATER HEATER
W.P.WATERPROOFING
MEMBRANE
EXP. DATE: 09/30/2024
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A0.02
GENERAL NOTES
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
EXP. DATE: 09/30/2024
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A0.03
ACCESSIBILITY DETAILS
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
EXP. DATE: 09/30/2024
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A0.04
GREEN BUILDING CODE
REQUIREMENT
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
EXP. DATE: 09/30/2024
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A0.05
PRODUCT SPEC SHEET
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
www.dynamicclosures.com
Commercial
Roll Up Doors
If you want a motorized operator, or have limited space at the
sides of the opening for storing the door curtain, choose on
overhead rolling closure. Ouroverhead rolling grilles have a just as
much selection of materials, patterns, and finishes and colors as
our side folding models.
With a compactroll and minimalhead plate requirements,this security enclosureallows for avery polished appearance.
This line can have motorized or manual operation, and there are dozens of options for materials, patterns, finishes, and
colors.
This is a great door for securing retail spaces,
pharmacies,“store within a store”spaces,
and counters like airport kiosks. The curtain
arrives already wrapped on the barrel, and it’s
ready to just lift into place for your
contractors. The roll itselfis also much lighter
than others, making for easier handling.
Lift Ready
Labyrinth
Lift Ready
Portcullis
Lift Ready
Pristine
Lift Ready
Ventana
Lift Ready
Vortex
Curtain and Barrel Pre-wrapped
Drop-In Ready endplates
Manual Operation
Standard Cylinder Locking Bottom Bar
Clear Anodized Finish
Features:
Crank, Hoist, Electric Motor Operation
Hood and Fascia (with color options)
In Stock Finish - Clear and Black anodized
Custom Anodized - Bronze, Light Bronze, Champagne Anodized
Custom RAL - RAL Powder Coat Finish (Excluding SL Paravent)
Options
Aluminum Angles Clear Anodized (FOW "E" or "Z")
Steel Tubes Prime Painted with Mounting Saddle
Battery Back Up
Maintain a fully operational Access Control System
during power outages and brownouts
Mounting Type
Lift Ready Rolling Doors
Product
Specifications
If you have tight deadlines, a small installation budget, or a lot of doors to install, the Lift Ready Roll Up Security
Door is a great solution.It’s available for spaces up to 24’ wide by 12’ tall. Larger dimensions can be created for
custom doors.
The Lift Ready header plate is more compact (only 15” [381] square) thanwith other doors of the same size for acleaner visual look.
Lift ReadyPortcullis Lift ReadyPristine Lift ReadyVentana
Series Model Description Max Height Max Width Panel Width Curtain Weight
Lift Ready Labyrinth Open Air Grille 150 [3810] 288 [7315] 1.75 [44] 0.786 lb/ft² [4 kg/m²]
Lift Ready Portcullis Open Air Grille
Perforated Aluminum
150 [3810] 288 [7315] 1.75 [44]
150 [3810] 288 [7315] 3.75 [95]
0.786 lb/ft² [4 kg/m²]
Lift Ready Pristine Solid & Polycarbonate 150 [3810] 288 [7315] 3 [76]1.1 lb/ft² [5 kg/m²]
Lift Ready Ventana 1.125 lb/ft² [5 kg/m²]
Lift Ready Vortex Solid Aluminum 150 [3810] 288 [7315] 2.375 [60] 1.63 lb/ft² [8 kg/m²]
Lift ReadyPortcullis Lift ReadyVentana
www.dynamicclosures.com
Lotos Color Tuning LED Recessed Kit (6-Pack)
By WAC Lighting
Call Us (877) 875-3619
Lotos Color Tuning LED Recessed Kit (6-Pack)
By WAC Lighting
Product Options
Size: 4 Inch
Details
Switchable color temp from 2700K, 3000K, 3500K, 4000K &
5000K
Easily installed as either a remodel or new construction with an
optional frame-in kit sold separately
Translucent acrylic diffuser
Dimensions
4 Inch Option Transformer: Length 4.6", Width 4.6",
Height 1.25"
4 Inch Option Trim: Height 1", Diameter 4.75", Cutout
4.25"
Lighting
4 Inch
Lamp Type LED Built-in
Total Lumens 725
Total Watts 8.00
Volts 120 /277 Volt
Average
Lifespan (Hours)
50,000
CRI 90
Equivalent
Halogen, CFL or
LED Bulb Can
Be Used
No
Additional Details
Product URL:
https://www.lumens.com/lotos-color-tuning-led-recesse
d-kit-6-pack-by-wac-lighting-WAC2319660.html
Rating: ETL Listed Wet
Notes:
Prepared
by:
Prepared for:
Project:
Room:
Placement:
Approval:
ITEM#: WAC2319660
1 20
L-01
Summit ACLED 15W Beamshift Line Voltage
Head
By WAC Lighting Call Us (877) 875-3619
Summit ACLED 15W Beamshift Line Voltage Head
By WAC Lighting
Product Options
Finish: White,
Option: Cylinder Head,
Light Option: L-Track
Details
Driverless LED technology
Compact design
Easy change of beam angles in field
Performs better than a halogen 50W MR16
High quality consistent beam pattern
1 additional lens accessory can be used
90° vertical aiming & 360° horizontal
LED rated for 50,000 hours
Easy change of lenses or accessories
Dims with a electronic low voltage (ELV) dimmer 100% to 10%
600 lumens when using the spot lens configuration
Material: Diecast Aluminum
Installation Type: Track
ETL Listed
Warranty: 5 years
Made In China
Dimensions
Cylinder Head Option Head: Width 3.75", Height
6.13", Depth 2.63", Diameter 2.63"
Lighting
L-Track
Lamp Type LED Built-in
Total Lumens 750
Total Watts 15.00
Volts 120
Color Temp 3000 (Soft White)
CRI 90
Equivalent
Halogen, CFL or
LED Bulb Can
Be Used
No
Additional Details
Product URL:
https://www.lumens.com/summit-acled-15w-beamshift-
line-voltage-head-by-wac-lighting-WAC517125.html
Rating: ETL Listed
Notes:
Prepared
by:
Jonathan
Wang
12621
Washington
Pl
202
Los
Angeles,
CA 90066
(626)
684-6651
Prepared for:
Project:MAISON
KOSE
Room:
Placement:TRACK
LIGHT
Approval:
ITEM#: WAC517125
L-02
Page 1 of 3
10715 Springdale Ave, Suite 4, Santa Fe Springs, CA 90670
Tel: 888.287.9228 | Fax: 888.258.9183 | support@alphalite.com | alphalite.com
Project Name
catalog No.
tyPe
Note
Date
LED UtiLity Wrap LUminairE
DEscription
spEciFication FEatUrEs
The Alphalite LBW Series Utility Wrap Luminaire provides high light levels for commercial, industrial, retail and residential applications. Fixtures can be used in storage/utility ares, coves, display cases, shops, task and general area lighting. Low profile design offers easy handling and storage.
appLicationVersatile solution for general illumination from surface-mounted fixture. Ideal for corridors, hallways, stairwells, closets, storage rooms, and spaces that demand energy demand reduction and high quality light.
ElectricalLuminaire utilizes long life, high efficacy LEDs and a highly efficient, reliable LED driver. 120V-277V input voltage for increased versatility. 0-10V continuous dimming comes standard. Ideal when used in conjunction with controls and sensors. Comes equipped with quick disconnect for compliance with US code.
opticsThe LBW’s LED light engine and integrated optics delivers enhanced light quality and distribution. Precision-formed diffuser and reflector are designed LED light consistently, reducing glare and pixelation.
Certifications / Regulatory UL/cUL listed. All components used have UL approval. UL Class 2. Power supply: SCP, OTP, OVP protection, FCC Part 15 Class B, UL8750 Class 2. DLC Premium listed.
Warranty7-year limited warranty. See complete warranty terms for details.
Benefits- Lower installation costs and reduced maintenance costs- Attractive ROI and lower energy costs- Ideal for use with sensors and advanced controls- High quality light for a more productive space- Convenient access to replaceable, standard components reduces life cycle costs
ConstructionReflector utilizes highly reflective powder coat finish. Diffuser requires no additional frame or fastener for easy installation. Tool-less removal of diffuser allows access to LED array. LED module and driver are replaceable. LED module and driver are replaceable. Housing and optics maintain damp location rating with all internal components.
FinishHighly reflective finish. Baked white paint, applied after fabrication.
Quick Ship Product
LBW series
leD Utility Wrap luminaire
LBW-4L(40S)/835
LBW-4L(40S)/840
orDEring inFormation
Sample Number: LBW-4L(40S)/840
LBW
series
LBW - LED Utility
Wrap Luminaire
Form Factor
2 - 2’
4 - 4’
cri
8 - 83+ CRI
Dimming
(Blank) - 0-10V Continuous
Dimming
cct
35 - 3500K
40 - 4000K
50 - 5000K
Emergency Backup
EM700 - 700lm
EM1400 - 1400lm
EM2000 - 2000lm
Controls
mms - Integrated step dimming microwave
motion sensor with sync function
os - Integrated step dimming PIR occupancy
sensor
DL - Integrated daylight harvesting
smc - Smart Control System
Input Voltage
(Blank) - 120V-277V
Lumen Package
VL - Very Low Wattage
L - Low Wattage
*See energy data for details
L 8 40
Options
(Blank)(Blank)4
L-03
EXP. DATE: 09/30/2024
LOCATION OF SPACE K3
DISTANCE BETWEEN K3 STOREFRONT EXIT
DOORWAY TO MALL EXIT: 764 FEET
DISTANCE BETWEEN K3 REAR EXIT
DOORWAY TO MALL EXIT: 892 FEET
SPACE K3
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
12" = 1'-0"
A1.00
SITE PLAN
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
CONTRACT ALERT:
CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND NOTIFY DESIGNER OF ANY DISCREPANCIES.
A PLUS/MINUS DIMENSION IS INDICATED WHEREVER A PARTICULAR DISTANCE IS NOT CRITICAL.
1. APPROVED BUILDING ADDRESS NUMBERS SHALL BE PROVED AND MAINTAINED SO AS TO BE
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET FRONTING THE PROPERTY. THE NUMBERS SHALL
CONTRAST WITH THEIR BACKGROUND, BE ARABIC NUMERALS OR ALPHABET LETTERS, AND BE A
MINIMUM OF 8 INCHES HIGH WITH A MINIMUM STROKE WIDTH OF 5 INCH. CVIFD STANDARD #122 AND
CFC CHAPTER 5, SECTION 505.1.
2. CURTAINS, DRAPES AND OTHER DECORATIVE MATERIALS SUSPENDED FROM THE WALLS OR
CEILINGS SHALL MEET THE FLAME SPREAD PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 IN
ACCORDANCE WITH SECTION 806.2 OR BE NONCOMBUSTIBLE. CBC CHAPTER 8. SECTION 806.1.
3. EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD
OF THE ROOM OR SPACE POSTED IN A CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE OF AN APPROVED LEGIBLE
PERMANENT DESIGN AND SHALL BE MAINTAINED BY THE OWNER OR AUTHORIZED AGENT. CBC
CHAPTER 10, SECTION 10043.
4. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE SUFICIENT FOR THE OCUPANT LOAD
THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES. THE HEIGHT DOORS
SHALL NOT BE LESS THAN 80 INCHES. CBC CHAPTER 10, SECTION 1008.1.
5. WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER ENCLOSED AND UNENCLOSED
STAIRWAYS SHALL BE PROTECTED BY 1-HOUR FIRE RESISTANCE RATED CONSTRUCTION. CBC
CHAPTER 10, SECTION 1009.6.3.
6. EACH DOOR IN A MEANS OF EGRESS FROM A GROUP A ASSEMBLY AREA SHALL NOT BE PROVIDED
WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE. CBC CHAPTER
10, SECTION 1008.110.
7. ALWAYS REFER TO THE GENERAL NOTES, SPECIFICATIONS, KEYNOTES, AND REFERENCES AND
RELATED PLANS, SECTIONS, ELEVATIONS AND DETAILS.
8. BUILDING LOCATION: BLDG. LOCATION IS TO BE SET BY THE DATUM POINT SHOWN ON THIS PLAN.
IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL DIMENSIONS AND LOCATIONS FOR
COMPLANCE WITH THESE PLANS AND CITY, COUNTY, STATE ORDINANCES. CONTRACTOR IS TO
NOTIFY ARCHITECT/DESIGNER IMMEDIATELY OF AND DISCREPANCIES O CONDITIONS NOT
CONSISTENT WITH THESE PLANS.
9. BLDG CONFIGURATION: CONTRACTOR IS TO NOTIFY DESIGNER PRIOR TO ANY WORK IF THE WORK
DONE BY THE OWNER DOES NOT MATCH WHAT IS SHOWN ON THESE PLANS, THEREBY CHANGING
THE STRUCTURAL AND OR AESTHETIC ELEMENTS OF THIS BUILDING.
10. DIMENSIONS: FLOOR PLAN DIMENSIONS SHALL TAKE PRECEDENCE OVER STRUCTURAL PLAN
DIMENSIONS. ANY MISSING AND/OR CONFLICTING DIMENSIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE DESIGNER IMMEDIATELY FOR RESOLUTION.
11. DIMENSIONS: EXT. FACE OF FINISH,CENTERLINE OF STUDS OR POSTS UNLESS NOTIFIED
OTHERWISE (U.N.O). FACE OF STUDS = FO.S. CONSISTENT WITH THESE PLANS.
12. FLOW LINES: ALL WATER (FROM RAN, HOSES, ETC) IS TO FLOW AWAY FROM THE BULDING
PERIMETER AT 2% SLOPE MIN. FOR A DISTANCE OF AT LEAST 5 FT.
13. BUILDING LOCATION: SEE SITE PLAN FOR LOCATION OF BUILDING ON SITE.
14. DATUM ELEVATION: +0'-0" SET FROM FINISHED FLOOR HEIGHT OF EXISTING HOUSE
GENERAL NOTES
EXP. DATE: 09/30/2024
28' - 10 1/4"
3' - 0"6"2' - 6"
10
'
-
1
0
1
/
4
"
1'
-
0
"
10
"
13
'
-
2
"
3'
-
1
3
/
4
"
18
'
-
1
1
3
/
4
"
5'
-
7
1
/
2
"
1'
-
4
"
7' - 1 1/2"6' - 9"10' - 4"
38' - 3"
12' - 5 1/2"1' - 1"3' - 5"
6'
-
0
"
10
'
-
1
0
1
/
4
"
13
'
-
4
1
/
4
"
REMOVE (E) WALLS
REMOVE (E) STOREFRONT
LEASE LINE
CLOSURE LINE
POP OUT
LEASE LINE
MALL
(E) ELECTRICAL PANELS
TO REMAIN
(E) STOCKROOM
(E) SALES AREA
(E) WALLS TO REMAIN
(E) COLUMN TO REMAIN (E) COLUMN TO REMAIN
(E) WATER HEATER TO REMAIN
REMOVE (E) WALLS
REMOVE (E) CASH COUNTER
(E) ELEVATOR
N.I.C
(E) FLOOR OUTLET TO REMAIN
REMOVE (E) FINISH
FLOORING & BASE
(E) FINISH FLOORING
& BASE TO REMAIN
(E) FINISH FLOORING &
BASE TO REMAIN
F E
5
4
(E) RESTROOM TO BE
UPGRADED TO ADA RESTROOM
(E) LANDLORD
NEUTRAL PIER (TYP.
OF 2)
(E) TRANSFORMER
(E) WATER COOLER
TO REMAIN
6'
-
5
"
LA
HA
T
6' - 3"
6' - 7 1/4"
3' - 4 1/2"3' - 0"
(E) RESTROOM
(E) WALLS TO REMAINREMOVE (E) ACT CEILING
@11'-10" AFF
(E) ELEVATOR
N.I.C
REMOVE (E) STOREFRONT
LEASE LINE
CLOSURE LINE
POP OUT
LEASE LINE
F E
5
4
REMOVE (E) CON-TECH
LIGHTING,TYP. OF 12
REMOVE (E) 2X2 RECESSED
LIGHT, TYP. OF 10
REMOVE (E) CON-TECH
LIGHTING,TYP. OF 15.
REMOVE (E) CON-TECH
LIGHTING, TYP. OF 3
(E) RETRUN TO
BE RELOCATED
(E) SUPPLY TO BE RELOCATED,
TYP. OF 5
REMOVE (E) ACT CEILING
@10'-9" AFF
GYPSUM BD. CEILING TO
REMAIN, @10'-0" AFF
REMOVE (E) CON-
TECH
LIGHTING,TYP. OF 4
S
R
S
E
E
(E) GYPSUM BD. CEILING
TO REMAIN, @11'-8" AFF
F(E) GYPSUM BD. CEILING
TO REMAIN, @8'-1/2" AFF
(E) FAN TO REMAIN
(E) SPRINKLER HEAD TO REMAIN
(E) RESTROOM
(E) STOCKROOM
(E) SALES AREA
REMOVE (E) WALL
(E) WALL MOUNTED
EXIT SIGN TO REMAIN
REMOVE (E) FLUORESCENT
LIGHT, TYP. OF 6
(E) FLUORESCENT
LIGHT TO REMAIN,
TYP. OF 6
REMOVE (E) LIGHT, TYP. OF 4
(E) EXIT SIGN TO BE
RELOCATED,TYP. OF 2
(E) EMERGENCY LIGHT TO
BE RELOCATED
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T
(E) WALLS TO REMAIN
(N) INTERIOR NON BEARING WALL
(E) WALLS TO BE DEMOLISHED
(E) FLOOR TILES TO BE
DEMOLISHED
(E) FLOOR TILES TO REMAIN
(E) ELEMENT TO BE DEMOLISHED
LEGEND
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A1.01
DEMOLISH FLOOR PLAN
& RCP
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
GENERAL
ALWAYS REFER TO THE GENERAL NOTES, SPECIFICATIONS, KEYNOTES AND REFERENCED AND
RELATED PLANS, SECTIONS, ELEVATIONS AND DETAILS.
1 BUILDING LOCATION: BLDG. LOCATION IS TO BE SET BY THE DATUM POINT SHOWN ON THIS
PLAN. IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY ALL DIMENSIONS AND LOCATIONS
FOR COMPLIANCE WITH THESE PLANS AND CITY, COUNTY, STATE ORDINANOES, CONTPACTOR S
TO NOTFY DESIGNER IMMEDIATELY OF AND DISCREPANCES OR CONDITIONS NOT CONSISTENT
WITH THESE PLANS.
2 BLDG CONFGURATION: CONTRACTOR IS TO NOTFY DESIGNER PRIOR TO ANY WORK IF THE
WORK DONE BY THE OWNER DOES NOT MATCH WHAT IS SHOWN ON THESE PLANS, THEREBY
CHANGING THE STRUCTURAL AND OR AESTHETIC ELEMENTS OF THIS BUILDING.
3. DIMENSIONS: FLOOR PLAN DIMENSIONS SHALL TAKE PRECEDENCE OVER STRUCTURAL PLAN
DIMENSIONS: ANY MISSING AND/OR CONFLICTING DIMENSIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE DESIGNER IMMEDATELY FOR RESOLUTION.
4. DIMENSIONS; EXT. FACE OF FINISH, CENTERLINE OF STUDS OR POSTS UNLESS NOTIFIED
OTHERWISE (UN.O). FACE OF STUDS = F.O.S. CONSISTENT WITH THESE PLANS.
5. FLOW LINES: ALL WATER (FROM RAIN, HOSES, ETC) IS TO FLOW AWAY FROM THE BUILDING
PERIMETER AT 2% SLOPE MIN. FOR A DISTANCE OF AT LEAST 5 FT.
6. BUILDING LOCATION: SEE SITE PLAN FOR LOCATION OF BUILDING ON SITE
7. DATUM ELEVATION: +0-0" SET FROM FINISHED FLOOR HEIGHT OF EXISTING HOUSE
GENERAL NOTES
SLAB REPAIR DETAIL
1/4" = 1'-0"1 DEMO FLOOR PLAN
1/4" = 1'-0"2 DEMO RCP
EXP. DATE: 09/30/2024
IM
C
U
B
E
I
M
C
U
B
E
PLEASE SEE PRODUCT SPECIFICATION
PL
E
A
S
E
S
E
E
P
R
O
D
U
C
T
S
P
E
C
I
F
I
C
A
T
I
O
N
TYPE A2TYPE A1
3' - 0"
TYPE A3A4
6'
-
8
"
3' - 0"
6'
-
8
"
(E) ELEVATOR
N.I.C
LEASE LINE
CLOSURE LINE
POP OUT
LEASE LINE
(E) STOCKROOM
WALL SHELF
WALL SHELF
PO
S
C
O
U
N
T
E
R
@
3
4
"
A
F
F
HIGH COUNTER
DISPLAY TABLE-B
DISPLAY TABLE-B
DISPLAY TABLE-A
(N) ADA
RESTROOM(E) RESTROOM EQUIPMENT
3' - 0"
C7
C2
C1
C2
C4
C5
5
4
2' - 6"
3'
-
1
3
/
4
"
1' - 8"
3' - 3"
TESTER TABLE
3'
-
7
3
/
4
"
F E
(N) FULL-HEIGHT WALL
(N) FULL-HEIGHT WALL
(N) PARTITION (N) PARTITION(N) FULL-HEIGHT WALL
28' - 10 1/4"
1' - 8"1' - 9"
1' - 2"
3' - 3 1/2"
3' - 3 1/2"
12' - 0"
SIGN ABOVE
(N) DRYWALL WITH PAINT
(N) ROLL UP GRILLE,
SEE DETAIL ON A2.01,
AND PRODUCT SPEC
ON A0.05
C3
3' - 5"
5'
-
7
"
(E) FLOOR FINISH TO BE
REFURBISH AS NECESSARY
(N) 24X24 CERAMIC
TILE FLOORING, FINISH
(N) 8X8 CERAMIC TILE
FLOORING, FINISH
A3 (E) SALES AREA
8' - 9 3/4"
6'
-
5
"
5'
-
6
"
A4
SI
G
N
(E) LANDLORD
NEUTRAL PIER (TYP.
OF 2)
(N) PARTITION(E) DEMISING WALL
(E) DEMISING WALL
(E) CORRIDOR
(E) DEMISING WALL
7'
-
1
1
/
4
"
7'
-
1
1
/
4
"
1' - 2"
29
'
-
6
1
/
2
"
1' - 0"
11
'
-
1
1
"
1
A2.01
____
2
A2.02
____
1
A2.02
____
3
A2.02
____
6' - 6 1/4"24' - 11"
A1
(E) WATER HEATER
(E) WATER COOLER
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T3' - 4 1/2"3' - 0"
A2
3'
-
0
"
1' - 6"
6' - 9"
7' - 9"
1' - 0"
1' - 0"
A1.05
3
4 6
5
18' - 8 1/4"4' - 11"
1' - 10"21' - 9 1/4"4' - 11"
4'
-
3
"
3'
-
8
"
4'
-
5
"
4'
-
5
"
TESTER TABLE
C3
3'
-
1
"
HIGH COUNTER
C4
8' - 0"
C6
3'
-
1
1
"
3'
-
1
1
"
2'
-
8
"
5' - 4"
3' - 4 1/4"
2' - 11"
3' - 6"
5'
-
9
"
6'
-
3
1
/
2
"
6'
-
3
1
/
2
"
6'
-
9
1
/
2
"
4'
-
3
3
/
4
"
1'
-
6
"
8"
1' - 6"
(E) WALLS TO REMAIN
(N) INTERIOR NON BEARING WALL
(E) WALLS TO BE DEMOLISHED
ADA
30" X 48" ACCESSIBLE FLOOR
CLEARANCE
5'-0" WIDE ACCESSIBLE
TURNING RADIUS CLEARANCE
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A1.02
PROPOSED FLOOR PLAN
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1.INTERIOR HINGED DOORS AND GATES: 51LB MAXIMUM;
2.SLIDING OR FOLDING DOORS: 5LB MAXIMUM;
3.REQUIRED FIRE DOORS: THE MINIMUM OPENING FORCE
ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVY, NOT TO
EXCEED 15LB;
4.DOOR CLOSERS AND GATE CLOSERS SHALL BE ADJUSTED
SO THAT FROM AN OPEN POSITION OF 90 DEGREES, THE
TIME REQUIRED TO MOVE THE DOOR TO A POSITION OF 12
DEGREES FROM THE LATCH IS 5 SECONDS MINMUM. CBC
11B-404.2.8.1;
5. EGRESS DOOR HARDWARE SHALL BE ALWAYS OPERABLE
IN DIRECTION OF EGRESS
MARK TYPE WIDTH HEIGHT THICKNESS
A1 SECURITY GRILLE, ROLL DOWN, AUTOMATIC 24' -0"12' -0"2"
QUANTITY
1
A2 INTERIOR EXIT DOOR, 1 HR FIRE RATED
W/ PANIC HARDWARE & PUSH BAR 3' -0"6' -8"1 3/4"1
A3 EXISTING EXIT DOOR,SWING, FIRE RATED
W/ EXISTING PANIC HARDWARE & PUSH BAR
3' -0"6' -8"1
STATUS
NEW
NEW
EXISTING
DOOR SCHEDULE RETAIL SHELVING CABINET SCHEDULE
MATERIAL
ALUMINUM
STEEL
1/4" = 1'-0"
DOOR LEGEND
1 3/4"
NOTES:
HOLLOW METAL
1/4" = 1'-0"1 PROPOSED FLOOR PLAN
MARK NAME WIDTH DEPTH HEIGHT
C1 DISPLAY TABLE-A 5' -7"3' -5"
QUANTITY
1
C2 DISPLAY TABLE-B 3' -3 1/2"2' -1 1/2"2
C3 TESTER TABLE 8' -0"4' -5"2
C4
C5
HIGH COUNTER 6' -9 1/2"2' -11"2
C6
POS COUNTER 4' -3 1/2"1' -8"1
WALL SHELF 18' -4"1' -7 1/2"1
3' -11"
2' -7 1/2"
2' -10"
2' -11"
2' -10"
10' -0"
LEGEND
A4 INTERIOR BATHROOM DOOR, SWING, W/LEVER 3' -0"6' -8"1 3/4"1EXISTINGSOLID CORE
C7 WALL SHELF 21' -5"1' -7 1/2"110' -0"
EXP. DATE: 09/30/2024
(E) ELEVATOR
N.I.C
(E) STOCKROOM
(E) RESTROOM
3' - 0"
(N) SALES AREA
STORAGE
185 SF
1 OOC.
OCC. LOAD
REQ. DOOR WIDTH
(OCC. LOAD X 0.2)
PROVIDED DOOR WIDTH
1 OOC.
0.2 "
36 "
RETAIL
832 SF
14 OOC.
OCC. LOAD
REQ. DOOR WIDTH(OCC. LOAD X 0.2)
PROVIDED DOOR WIDTH
14 OOC.
2.8 "
36"
OCC. LOAD
REQ. DOOR WIDTH
(OCC. LOAD X 0.2)
PROVIDED DOOR WIDTH
1 OOC.
0.2 "
36 "
COMMON PATH OF TRAVEL
TO A POINT WHERE A CHOICE
OF TWO EXITS IS AVAILABLE =
26' - 0"
TENANT LINE
COMMON PATH OF TRAVEL
TO A POINT WHERE A CHOICE
OF TWO EXITS IS AVAILABLE =
30' - 2"
26' - 0"
17
'
-
0
"
2'
-
0
"
28' - 2"
12' - 11"
8'
-
3
"
COMMON PATH OF TRAVEL
TO A POINT WHERE A CHOICE
OF TWO EXITS IS AVAILABLE =
21' - 2"
1' - 0"
O N E -T H I R D D I A G O N A = 1 3' - 7 7/2 0 "
A R E A D I A G O N A L 4 0' - 1 0 1/1 6 "
O
N
E
-T
H
I
R
D
D
IA
G
O
N
A
L = 6' - 4 1
1/2
0"
A
R
E
A
D
I
A
G
O
N
A
L 1
9' - 1 2
1/3
2"
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A1.03
EGRESS PLAN
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
OCCUPANCY ANALYSIS (OCCUPANCY LOAD PER TABLE 1004.5)
OCCUPANCY TYPE AREA OCCUPANCY LOAD FACTOR OCCUPANCY
STORAGE MERCANTILE 185 SF 300 1
TOTAL BUILDING OCCUPANCY = 15 OCCUPANCY
1/4" = 1'-0"1 EGRESS PLAN
RETAIL MERCANTILE 832 SF 60 14
EXP. DATE: 09/30/2024
(E) GYPSUM BD. CEILING ,
@11'-8" AFF
F(E) GYPSUM BD.
CEILING, @8'-1/2" AFF
(E) FAN
(E) SPRINKLER HEAD
(E) STOCKROOM
(E) WALL
MOUNTED EXIT
SIGN
(E) ELEVATOR
N.I.C
F E
5
4
3' - 8 1/4"
3' - 0"3' - 0"3' - 0"3' - 0"3' - 0"3' - 0"4' - 3"4'
-
0
3
/
4
"
4'
-
0
3
/
4
"
3' - 0"3' - 0"3' - 0"3' - 0"3' - 0"4' - 3"
4'
-
1
"
4'
-
1
"
4'
-
1
"
4'
-
1
"
4'
-
1
"
1'
-
0
"
2'
-
0
"
18' - 2"
13
'
-
1
1
/
2
"
4'
-
1
1
"
4'
-
1
1
"
1'
-
6
"
8"
1'
-
3
"
3' - 6"
L-03
L-03
L-03
L-03L-03
L-03
L-01 L-01 L-01 L-01 L-01 L-01
L-01
L-01
L-01
L-01
L-01
L-01
L-01
L-01L-01L-01L-01L-01L-01L-01L-01
L-02 L-02
L-02
L-02L-02
L-02
L-02 L-02
L-02
L-02
L-02 L-02
1'
-
7
"
2'
-
0
"
10"
3' - 8 1/2"
3' - 0"
4' - 11"
5"
6"
3' - 0"
(N) GYPSUM BD. CEILING ,
@12'-0" AFF
46" MONITOR
46" MONITOR
(N) GYPSUM BD.
CEILING , @10'-0" AFF
SI
G
N
TENANT
LINES
R
S
E
E
POWER SUPPLY FROM FLOOR
POWER SUPPLY FROM WALL
L-02 SPOT LIGHT
L-01 RECESSED LIGHT
RCP LEGEND
SPRINKLER HEAD
EMERGENCY LIGHT
E
S
R
L-03 LINEAR LIGHT
HIGH LITES
ATLAS SOUND
RECEIVER
WALL MOUNTED EXIT SIGN
EXISTING RCP LEGEND
7'
-
7
1
/
2
"
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T
6"
6"
(N) ADA
RESTROOM
(N) SALES AREA
1' - 9"
1'
-
1
0
"
3'
-
6
"
8"
L-02 L-02
2' - 4"2' - 4"
8"
8"
2' - 3"2' - 9"
L-02 L-02
L-02
9' - 5"
8'
-
4
"
14' - 0"
7'
-
0
"
LIGHTING SPEC SHEET A0.05
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A1.04
PROPOSED REFLECTED
CEILING PLAN
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1/4" = 1'-0"1 PROPOSED RCP
EXP. DATE: 09/30/2024
IM
C
U
B
E
I
M
C
U
B
E
(N) 24 X 24 CERAMIC TILE W/
CERAMIC COVE BASE
(N) 8 X 8 CERAMIC TILE W/
CERAMIC COVE BASE
(E) CONCRETE FLOOR FINISH TO
BE REFURBISH AS NECESSARY
(E) ELEVATOR
N.I.C
(E) STOCKROOM
(N) ADA
RESTROOM
(N) SALES AREA
(N) 24 X 24 CERAMIC TILE W/
CERAMIC COVE BASE
SALES AREA
STOCKROOM
RESTROOM
AREA FLOORS BASES WALLS CEILINGS
ROOM FINISH SCHEDULE
NOTE:
WALL, FLOOR AND CEILING SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATION IN CBC T-803.11 AND CBC 303.1.1.
INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS SHALL COMPLY WITH CBC 804.2 THROUGH 804.4.1. DECORATIVE MATERIALS AND TRIM INSTALLED IN BUILDINGS
COVERED BY SFM SHALL COMPLY WITH THE PROVISION OF CBC 806.
NOTE:
ALL KITCHEN, WASHING, MOP, PREP, AND RESTROOM AREA, PROVIDE A 1'-0" CEMENT BOARD ON THE BOTTOM, & ABOVE 4'-0" DENS ARMO (MOLD RESISTANCE) AROUND THE WALL.
PROVIDE MER-KRETE HYDRO GUARD 2000 ON FLOOR & WALL BASE, MER KRETE HYDRO GUARD ONE 4'-0" H. ON WALL SEE SHEET A-X FOR DETAIL.
FINISHES IN ALL AREAS, OTHER THAN THE CUSTOMER WAITING OR DINING AREAS, MUST BE SMOOTH, NONABSORBENT, EASILY CLEANABLE, & DURABLE.
24
X
2
4
C
E
R
A
M
I
C
T
I
L
E
S
M
O
O
T
H
F
I
N
I
S
H
O
N
L
Y
SM
O
O
T
H
H
A
R
D
N
O
N
A
B
O
S
O
B
E
N
T
M
A
T
E
R
I
A
L
,
S
E
C
.
8
0
7
CO
V
E
B
A
S
E
Q
U
A
R
R
Y
T
I
L
E
S
W
/
M
I
N
.
3
/
8
"
R
A
D
I
U
S
&
MI
N
.
4
"
T
A
L
L
C
O
N
T
.
S
M
O
O
T
H
F
I
N
I
S
H
VI
N
Y
L
W
A
L
L
B
A
S
E
WA
S
H
A
B
L
E
F
R
P
P
A
N
E
L
F
I
N
I
S
H
CE
R
A
M
I
C
T
I
L
E
S
M
O
O
T
H
F
I
N
I
S
H
O
N
L
Y
SM
O
O
T
H
H
A
R
D
N
O
N
A
B
S
O
R
B
E
N
T
M
A
T
E
R
I
A
L
,
S
E
C
.
8
0
7
DR
Y
W
A
L
L
W
I
T
H
P
A
I
N
T
WA
S
H
A
B
L
E
D
R
Y
W
A
L
L
W
/
G
L
O
S
S
P
A
I
N
T
WA
S
H
A
B
L
E
2
X
4
A
C
O
U
S
T
I
C
C
E
I
L
I
N
G
T
I
L
E
S
EX
P
O
S
E
D
C
E
I
L
I
N
G
ST
A
I
N
L
E
S
S
S
T
E
E
L
ST
A
I
N
L
E
S
S
S
T
E
E
L
ST
A
I
N
L
E
S
S
S
T
E
E
L
CE
R
A
M
I
C
C
O
V
E
T
I
L
E
B
A
S
E
W
/
M
I
N
.
3
/
8
"
R
A
D
I
U
S
&
MI
N
.
4
"
T
A
L
L
C
O
N
T
.
S
M
O
O
T
H
F
I
N
I
S
H
ST
A
I
N
L
E
S
S
S
T
E
E
L
PO
L
I
S
H
E
D
C
O
N
C
R
E
T
E
F
L
O
O
R
W
I
T
H
A
P
P
R
O
V
E
D
SE
A
L
E
R
,
(
P
E
G
A
-
C
O
T
E
9
2
0
0
)
8
0
0
-
2
0
1
-
0
0
2
2
EP
O
X
Y
F
I
N
I
S
H
WA
S
H
A
B
L
E
G
L
O
S
S
P
A
I
N
T
O
V
E
R
D
R
Y
W
A
L
L
&
S
M
O
O
T
H
CE
R
A
M
I
C
T
I
L
E
S
F
I
N
I
S
H
O
N
L
O
W
E
R
H
A
L
F
O
F
W
A
L
L
8
X
8
C
E
R
A
M
I
C
T
I
L
E
S
M
O
O
T
H
F
I
N
I
S
H
O
N
L
Y
SM
O
O
T
H
H
A
R
D
N
O
N
A
B
O
S
O
B
E
N
T
M
A
T
E
R
I
A
L
,
S
E
C
.
8
0
7
1' - 5"
17
'
'
-
1
9
'
'
1'
-
6
"
4"
33
'
'
-
3
6
'
'
2' -
1
0
"
60'' MIN.
5' - 3 1/4"
34
'
'
M
A
X
.
2' -
9
1
/
2
"
40
'
'
M
A
X
.
3' -
3
1
/
2
"
17'' - 18''
1' - 5"
24'' MIN.
2' - 2"
4' -
0
"
7' - 7 1/4"
DRYWALL, PAINTED
WHITE IN SEMI-GLOSS
FINISH, TYP. BOD:
BENJAMIN MOORE SWISS
COFFEE OC-45
WHITE SUBWAY TILE IN
POLISHED FINISH, TYP. BOD:
DALTILE COLOR WHEEL
CLASSIC IN ARCTIC WHITE OR
EQUAL
MIN. 4'' TALL
CERAMIC TILE
COVE WALL BASE
34
'
'
M
A
X
.
2' -
9
1
/
2
"
40
'
'
M
A
X
.
3' -
3
1
/
2
"
4"
4' -
0
"
4' -
0
"
4"
7'' - 9''
8"
19
'
'
M
I
N
.
1' -
9
"
33
'
'
-
3
6
'
'
T
O
T
O
P
O
F
G
R
A
B
B
A
R
S
2'
-
9
"
40
'
'
M
A
X
.
3' -
3
1
/
2
"
33
'
'
-
3
6
'
'
2' -
1
0
"
12'' MAX.
11 1/2"
3' - 6'' MIN.
3' - 6"
6' - 5"
4' MIN.
4' - 3"
24'' MIN.
2' - 3 1/2"
4"
17
'
'
-
1
9
'
'
1'
-
6
"
4' -
0
"
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
As indicated
A1.05
FINISH PLAN &
SCHEDULE
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1/4" = 1'-0"1 FINISH PLAN
NOTE: ALL INTERIOR FINISH COMPLIANCE WITH 803.1 AND TABLE 803.13
FLAME SPREAD PROVISIONS.
1/2" = 1'-0"3 RESTROOM ELEVATION A
1/2" = 1'-0"4 RESTROOM ELEVATION B
1/2" = 1'-0"5 RESTROOM ELEVATION C
1/2" = 1'-0"6 RESTROOM ELEVATION D
EXP. DATE: 09/30/2024
I M CUBE I M CUBE
2' - 1 1/2"2' - 1 1/2"1' - 10"1' - 10"
12
'
-
0
"
10
'
-
0
"
13
'
-
1
1
"
27' - 8 1/2"
24' - 0 1/2"
2' -
0
"
7' - 1 1/4"5' - 7"7' - 1 1/4"
32' - 2 1/2"
13' - 1"
10"10"
5' - 5 3/4"1' - 10"2' - 3"5' - 5 3/4"1' - 10"2' - 3"
LEASE LINE
4 5
EXISTING LANDLORD
CONSTRUCTION TO REMAIN
UNALTERED(HATCHED AREA)
EXISTING LANDLORD
CONSTRUCTION TO REMAIN
UNALTERED(HATCHED AREA)
4' -
1
1
"
4' -
1
1
"
2' -
7
1
/
2
"
2' - 1 1/2"
2' -
1
0
"
LEASE LINECLOSURE LINE
POP OUT
LEASE LINE
DISPLAY TABLE-B
DISPLAY TABLE-B
DISPLAY TABLE-A
5
E
(N) PARTITION
1' -
2
"
OUTLINE OF
STOREFRONT BOX SIGN
(E) LANDLORD
NEUTRAL PIER (TYP.
OF 2)
(N) PARTITION
2' - 3"
1'
-
2
"
1
A2
.
0
1
_
_
_
_
4
46" MONITOR
46" MONITOR
(N) ROLL UP GRILLE, SEE
DOOR SCHEDULE ON A2.01
OUTLINE OF
BULKHEAD ABOVE
G.C. TO PROVIDE NEW MALL
TILE TO MATCH EXISTING
6 1
/
2
"
6 1
/
2
"
3' -
3
1
/
2
"
1' -
2
"
1' - 10"1' - 10"2' - 3"
4' -
1
1
"
4' -
1
1
"
32" MONITOR
6"
LEASE LINE
POP OUT
LEASE LINE
SALES AREA
MALL
SIGN
LED LIGHT
5/8" GYPSUM BD. FINISH
5/8" GYPSUM BD. FINISH
2" METAL STUDS
4" MTAL STUDS
5/8" GYPSUM BD. FINISH
STOREFRONT ROLL-UP GRILLE
EXISTING CONSTRUCTION BY
LANDLORD(HATCH AREA)
4" MTAL STUDS UP TO
STRUCTURE ABOVE
DISPLAY TABLE B
OUTLINE OF DOWNLIGHT
FIXTURE
2' -
7
1
/
2
"
3' - 3 1/2"
3' -
8
3
/
4
"
4' -
1
1
"
2' - 0 1/4"
2' -
4
1
/
2
"
1' - 2"
6 1/2"
6"
1' - 5 1/2"
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
As indicated
A2.01
STOREFRONT
ELEVATION SECTIONS
AND DETAILS
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1/2" = 1'-0"1 STOREFRONT ELEVATION
3/4" = 1'-0"3 STOREFRONT SECTION
1
'
-
0
"
2
PL
A
N
24'-0"
24'-0"
25'-3/4"
SECURITY DOOR ELEVATION PROVIDED FOR REFERENCE SEE
STRCT S-1 FOR ATTACHMENT AND A0.05 FOR DOOR SPEC
1/2" = 1'-0"1 STOREFRONT ELEVATION FLOOR PLAN/2
EXP. DATE: 09/30/2024
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
IM C U B E IM C U B E
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
13
'
-
1
1
"
46" MONITOR
3' - 5"
3' -
1
1
"
3' - 6"2' - 11"17' - 7 3/4"
16' - 1 3/4"
1' - 0"
(E) STOCKROOM
FE
1' -
8
"
10
'
-
0
"
6"6"
12
'
-
0
"
11
'
-
8
"
12
'
-
0
"
4"
1' - 2"
10
'
-
0
"
5' - 4"3' - 4 1/4"8' - 0"
3' - 1"
10"
29' - 6 1/2"
4 5
2' -
0
"
13
'
-
1
1
"
12
'
-
0
"
2' -
1
0
"
10
'
-
0
"
1' - 7 1/2"
4' - 3 3/4"6' - 9 1/2"6' - 9 1/2"1' - 7 1/2"5' - 9"
10"
10
'
-
0
"
10
'
-
0
"
2' -
0
"
8' - 5 3/4"
13
'
-
1
1
"
3' - 5"
3'
-
1
1
"
3' - 6"2' - 11"17' - 7 3/4"
16' - 1 3/4"
1' - 0"
(E) STOCKROOM
F E
1' -
8
"
10
'
-
0
"
6"6"
12
'
-
0
"
46" MONITOR10
'
-
0
"
5' - 4"3' - 4 1/4"8' - 0"
21' - 5"
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A2.02
INTERIOR ELEVATIONS
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1/4" = 1'-0"2 ELEVATION B
1/4" = 1'-0"1 ELEVATION C
1/4" = 1'-0"3 ELEVATION D
EXP. DATE: 09/30/2024
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No. Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
1/4" = 1'-0"
A3.01
DETAILS
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
1 Commercial Plan Corrections 10/20/2023
1
1
16 GA UNPUNCHED TRACT
(W/ 1.1/2" LEG) W/ #10
SCREWS EA STUD. SEE
CONNECTION SCHEDULE
IN DETAIL 1/-
#10 SCREW @ EACH
FLANGE T&B
CEILING JOIST
1"
1"
LOWER CEILING JOIST VERTICAL 362S162-33
MEMBER
362S162-33 MIN. @16" O.C.
TYP. (2) SHOT PINS @ 16"
O.C. SHOT PINS SHALL BE
HILTI X-U 0.157" DIA POWER
DRIVEN FASTENER PER
ICC ESR-2269 OR
APPROVED EQUAL. PIN
SHALL PENETRATE
CONCRETE EXACTLY 1".
PROVIDE PINS WITH 6" EOF
END OF TRACT
(E) CONC FLOOR
250T125-33 TRACK W/ (2) #8
SCREWS FR. TRACK TO STUDS
4.PARTIOTION WALL TO CEILING
TYP. DETAIL
METAL STUD, SEE STR. S-2 FORMOUNTING DETIAL
BOTTOM TRACK ANCHOR SEE DETAIL 1/A3.01
12
'
-
0
'
'
12
'
-
0
'
'
(E) CONC. DECK ABOVE, SEE STR.S-2 FOR MOUNTING DETIAL
1
METAL STUD, SEE STR. S-2 FORMOUNTING DETIAL
BOTTOM TRACK ANCHOR SEE DETAIL 1/A3.01
12
'
-
0
'
'
12
'
-
0
'
'
(E) CONC. DECK ABOVE, SEE STR.S-2 FOR MOUNTING DETIAL
16
'
-
0
'
'
V
.
I
.
F
1
11
'
-
8
'
'
12
'
-
0
'
'
12
'
-
0
'
'
EXP. DATE: 09/30/2024
1
(2) 0.157'' DIAMETER HILTI X-U SHOTPIN (LARR#25675)
(3)-#12 S.M.S
362S162-33 BRACE @48'' O.C.(ICC ESR-3064P
2
2 Commercial Plan Corrections 11/30/2023
362S162-33 BRACE @48'' O.C. (ICCESR-3064P)
362S162-33BRACE @48''O.C. (ICCESR-3064P)
2 11/30/2023
Scale
Drawing No.
Drawn By
Checked By
Project Title
Drawing Title
Date
Project
No.
North
DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL
CHECK AND VERIFY ALL DIMENSIONS AND REPORT ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE
WORK.
No.Revisions Date By
Stamp
Jonathan Wang Design Retains Design Copyright over
Design Drawings & Specifications.
DESIGNER
JONATHAN WANG DESIGN
12621 WASHINGTON PL.
LOS ANGELES, CA 90066
626.684.6651
STRUCTURAL
JUNFEI CHEN
DEYI CONSULTANTS, INC
2725 WHISPERING TRL. IRVINE, CA92602
T: (949) 656 -6134
E: JUNFEI.CHEN@DEYICONSULTANTS.COM
CLIENT
JCOSME INTERNATIONAL INC.
A:
E: TONYTIAO@AOL.COM
T: (626)233-5699
JWANG@JONATHANWANGDESIGN.COM
WWW.JONATHANWANGDESIGN.COM
The plans and specifications prepared by JONATHAN WANG DESIGN are protected from unauthorized
modification, reuse and/or release under California Business & Professions Code section 5536.4, Health & Safety
Code Section 19851(a), and Education Code Section 17316.
Copyright Notice
19224 E WALNUT DR, N, UNIT A.
CITY OF INDUSTRY, CA 91748
A3.02
DETAILS - ROLL DOWN
GATE
Project Number
Issue Date
Author
MAISON KOSE, SANTA
ANITA FASHION PARK
Checker
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
2 Commercial Plan Corrections 11/30/2023
2
EXP. DATE: 09/30/2024
PER S-1 DETAIL
BOTTOM OF STEEL TUBE
TO FLOOR PER S-1 DETAIL
ATTACH DOOR GUIDES TO
HSS PER MANUFACTURER
GUIDE SCREWS #10. FOLLOW
PRE-DRILLED HOLES
SPACING TO SECURE GUIDE.
NOTE: DOOR SHALL BE INSTALLED BY MANUFACTURER APPROVED VENDOR ONLY
P-1 W/
CBS
INDICATES VERTICAL POST.
INDICATES POST SIZE.
INDICATES POST HARDWARE AT BOTTOM OF POST. IF POST IS
SUPPORTED BY AN ELEVATED FLOOR, PROVIDE BLOCKING (EQUAL TO
THE POST ABOVE AND BELOW).
NOTES
1.THE GENERAL CONDITIONS, SPECIFICATIONS, STRUCTURAL DETAILS, AND THE FOLLOWING
APPLY TO THE WORK.
2.CONTRACTOR SHALL CHECK DIMENSIONS AGAINST THE ARCHITECTURAL PLAN AND NOTIFY
THE ARCHITECT AND ENGINEER OF ANY OMISSIONS AND/OR DISCREPENCIES BEFORE
STARTING WORK.
3.NON-BEARING INTERIOR WALL FRAMING SHALL BE IN ACCORDANCE WITH 3/S 3.00.
4.CONNECTION OF NON-BEARING INTERIOR WALLS TO SLAB ON GRADE SHALL BE IN
ACCORDANCE WITH 10/S 3.00.
5.CONNECTION OF NON-BEARING INTERIOR WALLS TO CONCRETE SLAB ABOVE SHALL BE IN
ACCORDANCE WITH 17/S 3.00.
6.TOP PLATE SPLICES SHALL BE IN ACCORDANCE WITH 21/S 3.00. BOTTOM PLATE SPLICES
SHALL BE IN ACCORDANCE WITH 19/S 3.00.
7.CONNECTIONS OF STUDS TO TRACK SHALL BE IN ACCORDANCE WITH 23/S 3.00.
LEGEND
S-1
PCC#1 11/06/2023
1/4 CONCRETE SLAB PER PLAN
3"
MI
N
1/2" STEEL PLATE A A (4) 1/2"Ø TITEN HD
1/4
1/4
COLUMN PER PLAN
A A
MI
N
1/2" STEEL PLATE (4) 1/2"Ø TITEN HD
3"
10"x10"x1/2"
SECTION A-A
PLATE
7"
TYP.
1.ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE
LATEST AISC SPECIFICATIONS AND THE CODE OF STANDARD PRACTICE. LICENSED
FABRICATORS SHALL BE APPROVED BY THE JURISDICTION.
2.ALL STEEL EXCEPT PIPE, TUBE & W ASTM A-36
PIPE ASTM A-53, TYPE E OR S, GRADE B
ROUND HSS ASTM A-500, GRADE C
RECTANGULAR HSS ASTM A-500, GRADE C
W-SHAPE ASTM A-992
3.BOLTS
·HIGH STRENGTH BOLTS ASTM F3125 GRADE A325
·ALL OTHER BOLTS ASTM A307 GRADE A
4. THREADED RODS
·HIGH STRENGTH RODS ASTM A193 GRADE B7 OR A449 OR F1554
·ALL OTHER RODS ASTM A36 OR ASTM F1554 GRADE 36
5.ANCHOR RODS
·HIGH STRENGTH ASTM A193 GRADE B7 OR ASTM A449 OR F1554
·ALL OTHER RODS ASTM A307 GRADE A OR ASTM F1554 GRADE 36
6.BOLT HOLES
·MINIMUM EDGE DISTANCE AISC TABLE J3.4
·MINIMUM SPACING 3 BOLT DIAMETER
·HIGH STRENGTH BOLTS FRICTION TYPE WITH CLASS A FAYING SURFACE
7.MINIMUM FILLET WELD AISC TABLE J2.4
8.ALL FIELD WELDING TO BE CONTINUOUSLY INSPECTED BY A SPECIAL INSPECTOR QUALIFIED IN
WELDING. FIELD WELDERS MUST BE APPROVED BY THE JURISDICTION.
9.ALL SHOP WELDS SHALL BE PERFORMED BY A LICENSED FABRICATOR'S SHOP APPROVED BY
THE JURISDICTION.
10.ALL UNEXPOSED STEEL STEEL STRUCTURES PAINTING COUNCIL
SPECIFICATION 1(5)687.
11.EXPOSED STEEL HOT-DIPPED GALVANIZED
12.EXPANSION ANCHORS KWIK BOLT TZ BY HILTI, ICC-ES ESR-1917
13.SCREW ANCHORS TITEN HD BY SIMPSON, ICC-ES ESR-2713
14.POWDER ACTUATED FASTENERS 0.145" DIAMETER PER ICC-ES ESR-2379
(COLA RR#25708 (HILTI OR APPROVED EQ)
0.157" DIAMETER PER ICC-ES ESR-2269
(COLA RR#25675) (HILTI OR APPROVED EQ)
15.ALL WALLS SHALL HAVE FASTENERS PLACED AT 6" FROM ENDS OF SILL PLATES. INSTALL PER
ICC REPORT REQUIREMENT AND MANUFACTURER'S RECOMMENDATIONS.
16.LIGHT GAGE COLD-FORMED STEEL MEMBERS SHALL CONFORM TO ASTM A1003, UNLESS
NOTED OTHERWISE.
17.ALL HIGH STRENGTH BOLTS SHALL BE BEARING TYPE (A32(5)N) WITH THREADS INCLUDED IN
SHEAR PLAN. WHERE INDICATED ON DRAWINGS, SLIP CRITICAL CONNECTION SHALL BE
FRICTION TYPE CONFORMING TO ASTM A325 (SC) WITH A CLASS A FAYING SURFACE. THERE
SHALL BE NO PAINT, OIL, LACQUER OR GALVANIZING ON THE CONTACT SURFACES. THE
INSTALLATION OF HIGH STRENGTH BOLTS SHALL BE IN CONFORMANCE WITH RCSC
SPECIFICATIONS.
18.ALL GROUT UNDER STEEL BEARING PLATES SHALL BE SOLID DRYPACK OR NON-SHRINK
GROUT. F'c = 4,000 PSI.
19.METAL FLOOR DECK:FLOOR: PLN (CATALOG VF(2) P. 90)
ROOF: PLN-24 (CATALOG VR1 - P. 29)
MFROM BY VERCO MANUFACTURING CO. (ASTM A-653, LARR #23789)
STRUCTURAL STEEL & METAL
STRUCTURAL STEEL WELDING
1.ALL WELDING FOR BUILDINGS SHALL BE IN STRICT CONFORMANCE WITH AWS D1.1-15 & AWS
D1.8-2016 FOR WELDS USED IN MEMBERS AND CONNECTIONS IN THE SEISMIC FORCE
RESISTING SYSTEM.
2.COMPLETE JOINT PENETRATION GROOVE WELDS SHALL HAVE A FILLER METAL WITH A NOTCH
TOUGHNESS OF 20 FOOT-POUNDS AVERAGE AT ZERO DEGREES FAHRENHEIT.
3.A WELDING PROCEDURE SPECIFICATION (W.P.S.) PER AWS D1.1 SHALL BE DEVELOPED BY THE
FABRICATOR/ERECTOR AND APPROVED BY THE ENGINEER OF RECORD OR HIS DESIGNEE.
THE WPS SHALL INCLUDE THE WELDING PARAMETERS RECOMMENDED BY THE ELECTRODE
MANUFACTURER.
4.TO ASSURE THE PROPER AMPERAGE AND VOLTAGE OF THE WELDING PROCESS, THE USE OF
A HAND HELD CALIBRATED AMP AND VOLT METER SHALL BE USED. THIS EQUIPMENT SHALL BE
USED BY THE FABRICATOR, ERECTOR AND THE INSPECTORS. AMPERAGE AND VOLTAGE
SHALL BE MEASURED NEAR THE ARC TRAVEL SPEED AND ELECTRODE STICK OUT SHALL BE
VERIFIED TO BE IN COMPLIANCE WITH THE APPROVED WPS.
5.FIELD WELDING TO BE DONE BY WELDERS CERTIFIED BY THE LADBS FOR STRUCTURAL STEEL.
FABRICATION PROCEDURES
1.FOR SHIELDED METAL ARC WELDING (SMAW), THE MAXIMUM PERMITTED ELECTRODE
DIAMETER SHALL BE PER AWS D1.1-15, SECTION 4.6.3(4). FOR FLUX CORED ARC WELDING
(FCAW), THE MAXIMUM PERMITTED ELECTRODE DIAMETER SHALL BE ACCORDING TO AWS
D1.1-15, SECTION 4.14.1.2.
2.WELDING SEQUENCE: BOTH FLANGES SHALL BE WELDED PRIOR TO ANY SUPPLEMENTAL
WELDING TO THE SHEAR TAB.
3.AFTER WELDING, THE BACKING BAR AND THE RUN-OFF TABS ARE TO BE REMOVED FROM THE
BOTTOM FLANGE. (NOTE, ONLY THE RUN-OFF TABS NEED TO BE REMOVED FROM THE TOP
FLANGE, NOT THE BACKING BAR). THE WELD ROOT SHALL BE INSPECTED AND TESTED PER
AWS REQUIREMENTS GIVEN IN SECTION 8. IF REJECTABLE INDICATIONS ARE FOUND, REMOVE
BY BACK GOUGING TO SOUND METAL. THE BACK GOUGED AREA SHALL BE WELDED AND IF
REINFORCING PLATES ARE NOT USED, THE WELD SHALL BE REINFORCED WITH A FILLET WELD.
THE SIZE OF THE REINFORCING FILLET WELD SHALL BE EQUAL TO 1/4 OF THE BEAM FLANGE
THICKNESS, BUT NOT LESS THAN 1/4" AND NOT IN EXCESS OF 3/8" PER AWS D1.1-15, NOTE J OF
FIGURE 2.4.
5/8" GYPSUM BD. FINISH
STOREFRONT ROLL-UP
GRILLE
EXISTING CONSTRUCTION
BYLANDLORD(HATCH AREA)
362S125-33MIN STUDS
@16" O.C. TYP
362S125-33MIN STUDS
@16" O.C. TYP
5' MAX
(4)#10 SMS, TYP
362S125-33 MIN
BRACE @ 48"O.C.
(2) SHOT PIN @ 12"
OC TO CONC. FLOOR
PER NOTE#1
NOTE#1: HILTI X-U 0.157"Ø POWER DRIVEN FASTENERS PER ICC ESR-2269 (COLA RR
#25675) OR APPROVED EQUAL. PINS SHALL PENETRATE CONCRETE MIN. 1". PROVIDE
PINS WITHIN 6" OF END OF TRACT.
5
4
F E
A3
A2
A4
HS
S
4
x
4
x
1
/
4
HS
S
4
x
4
x
1
/
4
NOTE:.
1.SPECIAL INSPECTION REQUIRED FOR POST INSTALLED ANCHORS.
4. FOR THE WELD OF THE BOTTOM BEAM FLANGE TO THE COLUMN FLANGE, FOLLOW
STEPS A THROUGH G BELOW:
A.THE ROOT PASS SHOULD NOT EXCEED 1/4” IN LAYER THICKNESS.
B.THE FIRST HALF LENGTH ROOT SHOULD BE MADE WITH ONE OF THE FOLLOWING
TECHNIQUES, AT THE OPTION OF THE CONTRACTOR:
·THE ROOT PASS MAY BE INITIATED NEAR THE CENTER OF THE JOINT. IF THIS
APPROACH IS USED, THE WELDER SHOULD EXTEND THE ELECTRODE THROUGH
THE WELD ACCESS HOLE, APPROXIMATELY 1" BEYOND THE OPPOSITE SIDE OF
THE GIRDER WEB. THIS IS TO ALLOW ADEQUATE ACCESS FOR CLEARING AND
INSPECTION OF THE INITIATION POINT OF THE WELD BEFORE THE SECOND
HALF-LENGTH OF THE ROOT PASS IS APPLIED. IT IS NOT DESIRABLE TO INITIATE
THE ARC IN THE EXACT CENTER OF THE GIRDER WIDTH SINCE THIS WILL LIMIT
ACCESS TO THE START OF THE WELD DURING POST-WELD OPERATIONS. AFTER
THE ARC IS INITIATED, TRAVEL SHOULD PROGRESS TOWARD THE END OF THE
JOINT (OUTBOARD BEAM FLANGE EDGE), AND THE WELD SHOULD BE
TERMINATED ON A WELD TAB/RUN OFF TAB. TABS SHALL EXTEND THE JOINT, NO
END DAMS.
·THE WELD MAY BE INITIATED ON THE WELD TAB, WITH TRAVEL PROGRESSING
TOWARD THE CENTER OF THE GIRDER FLANGE WIDTH. WHEN THIS APPROACH IS
USED, THE WELDER SHOULD STOP WELD APPROXIMATELY 1" BEFORE THE BEAM
WEB. IT IS NOT ADVISABLE TO LEAVE THE WELD CRATER DIRECTLY IN THE
CENTER OF THE BEAM FLANGE WIDTH SINCE THIS WILL HINDER POST-WELD
OPERATIONS.
C.THE HALF LENGTH ROOT PASS SHOULD BE THOROUGHLY SLAGGED AND CLEANED.
D.THE END OF THE HALF LENGTH ROOT PASS THAT IS NEAR THE CENTER OF THE BEAM
FLANGE SHOULD BE VISUALLY INSPECTED TO ENSURE FUSION, SOUNDNESS, FREEDOM
FROM SLAG INCLUSIONS, AND EXCESSIVE POROSITY.
E.THE RESULTING BEAD PROFILE SHOULD BE SUITABLE FOR OBTAINING FUSION BY THE
SUBSEQUENT PASS TO BE INITIATED ON THE OPPOSITE SIDE OF THE GIRDER WEB. IF THE
PROFILE IS NOT CONDUCIVE TO GOOD FUSION, THE START OF THE FIRST ROOT PASS
SHOULD BE GROUND GOUGED, CHIPPED OR OTHERWISE PREPARED TO ENSURE
ADEQUATE FUSION.
F.THE SECOND HALF OF THE WELD JOINT SHOULD HAVE THE ROOT PASS APPLIED BEFORE
ANY OTHER WELD PASSES ARE PERFORMED. THE ARC SHOULD BE INITIATED AT THE END
OF THE HALF LENGTH ROOT PASS THAT IS NEAR THE CENTER OF THE BEAM FLANGE, AND
TRAVEL SHOULD PROGRESS TO THE OUTBOARD END OF THE JOINT, TERMINATING ON THE
WELD TAB.
G.EACH WELD LAYER SHOULD BE COMPLETED ON BOTH SIDES OF THE JOINT BEFORE A
NEW LAYER IS DEPOSITED.
H.WELD TABS SHOULD BE REMOVED AND GROUND FLUSH TO THE BEAM FLANGE.
5.DEVIATION FROM THE PRECEDING PROCEDURES MAY BE MADE PROVIDING THE CONTRACTOR
SUBMITS IN WRITING AN ALTERNATE SEQUENCE THAT IS APPROVED BY THE ENGINEER PRIOR
TO FABRICATION OR REPAIR.
6.FOR ORDINARY MOMENT RESISTING FRAMES, OMRF, WITH FLEXIBLE DIAPHRAGMS, THE
BACKING BAR AND THE RUN-OFF TABS ARE NOT REQUIRED FROM THE BOTTOM FLANGE.
7.FIELD WELDING OF REINFORCING STEEL SHALL BE PERFORMED BY WELDERS SPECIFICALLY
CERTIFIED FOR REINFORCING STEEL. PRIOR TO WELDING, THE "CARBON EQUIVALENT" (CE)
OF STEEL SHALL BE DETERMINED. REINFORCING STEEL WHOSE "CE" CANNOT BE IDENTIFIED
OR WHOSE "CE" EXCEEDS 0.75% SHALL NOT BE WELDED. EXCEPT FOR REINFORCING STEEL
CONFORMING WITH ASTM A.706, REINFORCING STEEL SHALL BE PREHEATED AS SHOWN IN
TABLE 1.RGA 3-77. IN ADDITION, STEEL WITH "CE" BETWEEN 0.66% AND 0.75% SHALL BE
WELDED ONLY.
PCC#2 11/30/2023
2
EXP. DATE: 09/30/2024
S-1
SCALE: 1/4" = 1'-0"
20 10
7.LATERAL BRIDGING FOR STEEL STUDS IS REQUIRED WHEN WALL BOARD, INSTALLED PER
CBC (CHAPTER 25) DOES NOT CONTINUE FULL-HEIGHT ON BOTH SIDES. BRIDGING SHALL BE
INSTALLED PER MANUFACTURERS RECOMMENDATIONS UNLESS SPECIFICALLY SHOWN
OTHERWISE ON THESE PLANS.
8.ALL SCREWS SHALL BE INSTALLED IN ACCORDANCE WITH THE SCREW MANUFACTURER'S
RECOMMENDATIONS. ALL SCREWS SHALL PENETRATE AND PROTRUDE THROUGH THE
ATTACH MATERIALS A MINIMUM OF 3 FULL EXPOSED THREADS PER AISI STANDARD GENERAL
PROVISIONS D1.3.
9.ALL SCREWS MUST COMPLY WITH SAE STANDARD J78, STEEL SELF-DRILLING SELF-TAPPING
SCREWS, AND MUST HAVE A TYPE II COATING IN ACCORDANCE WITH ASTM B633,
ELECTRODEPOSITED COATINGS OF ZINC ON IRON AND STEEL.
10.ALL SHEET METAL SCREWS SHALL BE DARTS BRAND SELF DRILLING SELF TAPPING PER
ICC-ER 1408 (LARR 25904) PER PLAN OR APPROVED EQUAL BY ENGINEER.
11.MAXIMUM STUD DEPTH IS 8", UNLESS WEB BRACING IS SPECIFICALLY DESIGNED BY
ENGINEER.
12.AXIALLY LOADED STUDS SHALL HAVE FULL BEARING AGAINST INSIDE TRACK WEB PRIOR TO
STUD AND TRACK ATTACHMENT. SPLICES IN AXIALLY LOADED MEMBERS SHALL NOT BE
PERMITTED.
13.BUTT WELDS OR SPLICES SHALL BE USED AT ALL JOINTS IN TRACK. SPLICES IN AXIAL
LOADED STUDS OR BRACES ARE NOT PERMITTED. ALL WELDS SHALL BE PLUG, BUTT, OR
SEAM WELDS. WHERE STUDS ARE BURNED THROUGH BY WELDING, PROVIDE SUITABLE
STITCH PLATE OF THE SAME GAUGE.
14.WHERE HOLES ARE SPECIFICALLY PERMITTED ON THESE PLANS, HOLES SHALL BE NEATLY
DRILLED. TORCH CUTTING IS NOT PERMITTED.
15.TOP AND BOTTOM TRACKS SHALL BE OF EQUAL MATERIAL, THICKNESS AND WIDTH AS STUDS
AND SHALL BE UNPUNCHED. USE DEFLECTION RATED TRACK.
16.STUDS AT CABINETS AND SHELVES SHALL BE SPACED AT 50% OF STUD SPACEING SPECIFIED
PER SCHEDULE.
17.ALL SHEATHING AND WALL FINISHES MUST REMAIN ON STUDS UNLESS SPECIFICALLY
APPROVED BY ENGINEER IN WRITING.
18.UTILITY PUNCH HOLES IN STUDS SHALL BE LOCATED AWAY FROM CONNECTIONS.
19.TRACK SHALL BE UNPUNCHED WITH GAUGE TO MATCH STUD FRAMING WITH 1.1/2" FLANGE,
UNLESS OTHERWISE NOTED.
20.ALL STUDS FOR SUBMITTAL SHALL BE PUNCHED (i.e. WITH SPACING @ 24" OC) UNLESS
NOTED OTHERWISE.
21.WALL STUD BRIDGING SHALL BE INSTALLED IN A MANNER TO PROVIDE RESISTANCE TO BOTH
MINOR AXIS BENDING AND ROTATION. BRIDGING ROWS TO BE EQUALLY SPACED.
22.ALL BUILT-UP MEMBERS MUST BE FASTENED TOGETHER TO ACT AS ONE UNIT.
23.HOLES FOR 1/2" DIAMETER OR GREATER BOLTS, SHALL BE NO MORE THAN 1/16" LARGER
THAN THE BOLT DIAMETER PER AISI NAS E3A.
24.TEMPORARY BRACING REQUIREMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR
25.FOR LIGHT GA STEEL CONNECTIONS USE SIMPSON S/JCT (MAX FILL IN ALL HOLES INCLUDING
TRIANGLE HOLES) AT ALL SINGLE JOIST TO FLUSH BEAM CONNECTIONS.
26.STEEL BRACING (ALL STEEL SOLUTION) MUST BE PROVIDED ON WEBS OF ALL BEARING
STUDS PER THE GENERAL DETAILS. ALTERNATIVELY, BRACING MAY BE ACHEIVED AFTER
DRYWALL OR STUCCO IS DIRECTLY ATTACHED FULL HEIGHT TO BOTH SIDES OF THE STUD.
ATTACHMENT OF DRYWALL/STUCCO IS TO BE PER IBC CHAPTER 25, WITH MAXIMUM
CONNECTOR SPACING OF 7" OC ALONG EDGES AND 12" OC ALONG INTERMEDIATE STUDS.
NOTE: MATERIALS INSTALLED OVER RESILIENT CHANNELS OR SIMILAR IS NOT CONSIDERED
DIRECTLY ATTACHED.
27.CARRY ALL MULTIPLE STUDS OR POSTS FROM FLOOR ABOVE DOWN TO FLOOR OR BEAM
BELOW/ PROVIDE 4x SOLID BLOCKING AT FLOOR LEVEL TO TRANSFER LOAD FROM UPPER
POST TO LOWER POST.
28.ALL SCREWS TO HAVE 3/4" MIN EDGE DISTANCE, UNO
29.WELD STUDS ONLY AS INDICATED ON PLANS. WELDS SHALL COMPLY WITH ANSI/AWS D1.1,
D1.3 AND CBC 2204. WELDERS SHALL BE CERTIFIED AS REQUIRED BY THE BUILDING
OFFICIAL.
30.ALL FRAMING MEMBERS AND PREFABRICATED ASSEMBLIES SHALL BE INSTALLED TIGHT
AGAINST ABUTTING MEMBERS. ENDS SHALL BE CUT SQUARELY OR AT AN ANGLE TO ENSURE
A TIGHT FIT.
31.STUDS AT VENEER SHALL BE MIN 43 MIL. UNO ON PLANS.
30 15 5
SPECIFICATIONS
1.ALL LIGHT GAUGE STEEL FRAMING MEMBERS SHALL COMPLY WITH CBC 2022 AND AISI
STANDARDS:
STRUCTURAL MEMBERS AISI S240-15
NON-STRUCTURAL MEMBERS AISI S220-15
TRUSS DESIGN AISI S202-15
SEISMIC DESIGN AISI S400-15
2.ALL LIGHT GAUGE MEMBERS SHALL BE PRODUCTS MANUFACTURED BY THE MEMBERS OF THE
STEEL STUD MANUFACTURES ASSOCIATION, SSMA, COMPLYING WITH THE INTERNATIONAL
BUILDING CODE AND ICC-ES ESR-3064P.
3.ALL STUD/TRACK MATERIAL SHALL CONFORM TO THE FOLLOWING:
16 GAUGE AND HEAVIER - 50 KSI MIN YIELD, 65 KSI MIN TENSILE STRENGTH
PAINTED STEEL PER ASTM A570-GRADE 50
ASTM A607-GRADE 50
GALVANIZED STEEL PER ASTM A44(6)GRADE D
18 GAUGE AND LIGHTER - 33 KSI MIN YIELD, 45 KSI MIN TENSILE STRENGTH
PAINTED STEEL PER ASTM A570-GRADE 33
ASTM A611-GRADE C
GALVANIZED STEEL PER ASTM A44(6)GRADE A
4.ALL MISCELLANEOUS STEELS SHALL CONFORM TO THE FOLLOWING UNO:
20 TO 18 GAUGE 33 KSI MIN YIELD STRENGTH (45 KSI MIN TENSILE STRENGTH)
16 TO 10 GAUGE 50 KSI MIN YIELD STRENGTH (65 KSI MIN TENSILE STRENGTH)
3/16" AND HEAVIER ASTM A36
5.ALL WELDING SHALL BE PERFORMED BY CERTIFIED LIGHT GAUGE WELDERS, CERTIFIED FOR
ALL APPROPRIATE DIRECTIONS PER 2008 AWS D1.3. WELDING RODS SHALL CONFORM TO THE
FOLLOWING:
18 GA AND LIGHTER SHEET TO SHEET - E60XX
16 GA AND HEAVIER SHEET TO SHEET - E70XX OR E6013
LT.GPT STEEL TO STRUCTURAL STEEL. ASTM A36
6.ALL CALCULATED STUD PROPERTIES, PER AISI SPECIFICATION, ARE BASED ON THE
FOLLOWING THICKNESS TABLE:
23
--
5
23
--
3
4
2
5
11
1
2
3
4
5
SPAN
SPAN
BEARING/STRUCT WALL.
MTL. CEILING JOIST, SEE SCHEDULE
FOR JOIST SIZE.
OPT CEILING JOIST SUPPORTING LINE
PER DETAIL 23/-
LATERAL SUPPORT PER DETAIL 24/-,
LOCATION BY GC.
JOIST SPAN DETERMINED BY
DISTANCE BETWEEN TWO
CONSECUTIVE SUPPORTING POINTS.
NOTE:
1.PROVIDE LATERAL BRACING MEMBERS PER DETAIL 24/- @ 8' O.C. EACH WAY.
2.LATERAL BRACING IS NOT REQD IF CEILING JOISTS ARE SURROUNDED BY
SHEAR PANELS OR AREA OF CEILING IS LESS THAN 144 SQ FT & CEILING JOISTS
ARE ATTACHED TO WALLS WHICH ARE DIRECTLY ATTACHED TO STRUCT FLOOR.
3.SPECIAL INSPECTION REQUIRED FOR POST INSTALLED ANCHORS.
25
97
68
54
43
33
27
18
12
14
16
18
20
22
25
0.1017
0.0713
0.0566
0.0451
0.0346
0.0283
0.0188
MILS GAUGE (IN)
DESIGNATION THICKNESS DESIGN
THICKNESS
CEILING FRAMING PLAN 3
CONNECTION TO WALL
SPAN (FT)
SPACINGCEILING JOIST SIZE
CEILING JOIST SCHEDULE
DRYWALL
CEIL'G
7'-0"24" OC362S162-33 (3) #10 SCREWS
NOTE:
·DRYWALL CEILING COMPRISES OF (1) LAYER OF 1/2" DRYWALL.
·BRACING FOR CEILING JOIST IN FLEXURE IS NOT REQUIRED, UNO
·CEILING IS NOT ACCESSIBLE.
26
CEILING LATERAL BRACING
BOTTOM OF STRUCT
FLOOR ASSEMBLY
362S125-33 CUT FLANGE &
BEND WEB FOR ATTACHMENT
SEE PLAN FOR LOCATION,
INSTALL BRACE IN PAIR4
5
.
0
0
°
24
CONNECTORS:
FOR WOOD:(2) #10x2.1/2 WOOD SCREWS
(2" MIN PEN INTO JOIST)
FOR CONC:(2) 0.157Ø SHOT-IN ANCHORZ
W/ 3/4" MIN PENETRATION
FOR STEEL:(2) #8 TEK SCREWS
23
(3) #10 SCREWS
SUSPENDED CEILING FRAMING
HEADER
16 GA UNPUNCHED TRACT
(W/ 1.1/2" LEG) W/ #10
SCREWS EA STUD. SEE
CONNECTION SCHEDULE
IN DETAIL 3/-
STUD BRIDGING
LOCATE BRIDGING
WITHIN 12" BELOW
CEILING JOIST
#10 SCREW @ EACH
FLANGE T&B
CEILING JOIST
1"
1"
(2) 0.157Ø
SHOT-IN
ANCHOR @ 12"
OC W/ 1" MIN
PENETRATION
CONCRETE/
CMU WALL
#10 SCREW @
EACH FLANGE
T&B
CEILING JOIST
MTL STUD
1"
1"
METAL JOIST
TO CONC/CMU WALL
METAL JOIST
TO STUD WALL
25
3
3
3
2
2
2
2
1
1
1
1
1
(E)DRYWALL CEILING
2
PCC#1 11/06/2023
362S125-33 DIA. BRACE @ 8' OC EW
W/ (2) #10 SCREWS @ EA END & #10
SCREW @ EA CROSSING STUD.
BEND FLANGE/WEB FOR
ATTACHMENT
NOTE#1: HILTI X-U 0.157"Ø POWER DRIVEN FASTENERS
PER ICC ESR-2269 (COLA RR #25675) OR
APPROVED EQUAL. PINS SHALL PENETRATE
CONCRETE MIN. 1". PROVIDE PINS WITHIN 6"
OF END OF TRACT.
362S125-33 MIN.
STUDS @ 16" OC,
TYP 362T125-33 TRACK W/
(2) #8 SCREWS FR.
TRACK TO STUDS
362S162-33 @ 24"
OC W/ (2) #8 SMS
TO TRACK
(2) SHOT PIN @ 12" OC TO
CONC. FLOOR PER NOTE#1
PER SCHEDULEPER SCHEDULE
362T125-33 TRACK
W/ SCREWS @ TO
WALL PER 26/-
DRY WALL WHERE
OCCURS PER ARCH
(E) CONC. FRAMING
PCC#2 11/30/2023
2
EXP. DATE: 09/30/2024
S-
2030
1929
1828
27
1626
25
24
23
22
21
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
32inch
MONITOR
WALL SHELF ANCHORAGE
16
-
16
-
10
'
-
0
"
M
A
X
10
'
-
0
"
M
A
X
A A
10
'
M
A
X
SH
E
L
F
M
E
M
B
E
R
B
Y
O
T
H
E
R
S
CONC SLAB
312"
2"
MIN
2"
MIN
1"
T
Y
P
1/4" THICK BASE
PLATE W/ (4) 1/2" Ø
TITEN HD BOLTS W/
4" EMBED MIN
SECTION A-A
2"
BASE PLATE CONNECTION
SIMP. A35 TOP
& BOTT. OF
BLKG. TYP.
SHELF
MEMBER AND
CONNECTION
BY OTHERS
4X8 BLKG. WHERE
ANCHORS OCCURS
1/4" THK. PLATE W/
4-1/4"ØX3" LAG
SCREWS
1"
3"
1"
1"3"1"
A - A
A
A
4X8 BLKG. W/ SIMP.
A35 EA. SIDE TOP &
BOTT. TYP.
METAL STUD
L3"X3"X18GA X3"
W/(3)#10 EACH LEG
METAL STUD
ELEVATION
L3"X3"X18GA X3"
W/(3)#10 EACH LEG
BASE PLATE CONNECTION
18
-
18
-
18
-
18
-
18
-
16
-
18
-
NOTE:.
1.SPECIAL INSPECTION REQUIRED FOR POST INSTALLED ANCHORS.
3
PCC#1 11/06/2023
PCC#2 11/30/2023
EXP. DATE: 09/30/2024
FLEX. CONN.
MVD
AVD
BDD
MD
RISE OR DROP IN DIRECTION OF AIR FLOW
MANUAL VOLUME DAMPER
BACKDRAFT DAMPER
AUTOMATIC VOLUME DAMPER
SINGLE LINE DUCT WORK
FLEXIBLE DUCT
MODULATING DAMPER
EXHAUST DUCT, SECTION
FLEXIBLE CONNECTION
TURNING VANES
SPLITTER DAMPER
EXTRACTOR AT BRANCH DUCT
RETURN DUCT, SECTION
SUPPLY DUCT, SECTION
DUCT WORK (WIDTHxDEPTH)AxB
AxB
R. OR D.
AD
AFD
RR
SD
SWR
LD
SWE
ER
VAV
UC
DL
DUCT SMOKE DECTECTOR
SIDE WALL RETURN OR EXHAUST
UNDER CUT DOOR
LINEAR DIFFUSER
VARIABLE AIR VOLUME
SIDE WALL SUPPLY REGISTER
EXHAUST REGISTER
RETURN REGISTER
DOOR LOUVER
THERMOSTAT
SUPPLY DIFFUSER
AUTOMATIC FIRE DAMPER
ACCESS DOOR
U.C.
S
T
D.L.
DUCT TRANSITION, ROUND AND RECTANGULAR
LINED DUCT WORK (WIDTHxDEPTH DIMENSIONS ARE FOR I.D.)
T/B TO BELOW
F/B FROM BELOW
T/A TO ABOVE
F/A FROM ABOVE
PROVIDE EQUIPMENT INDICATED ON THE DRAWINGS, AND AS REQUIRED FOR
A COMPLETE FUNCTIONING SYSTEM.
DEFINITIONS:
FURNISH: TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR
INSTALLATION.
INSTALL: TO PLACE IN POSITION AND MAKE CONNECTIONS FOR SERVICE OR
USE.
PROVIDE: TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED
USE.
WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE
DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER
SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED
PROJECT. PROVIDE A SEPARATE LINE ITEM DEDUCT AMOUNT ON THE
PROPOSAL FORM TO DELETE WARRANTY SERVICE, AT THE OWNER'S OPTION.
PROVIDE OPERATION MANUALS, MAINTENANCE MANUALS AND SCHEMATICS
FOR ALL MECHANICAL EQUIPMENT INSTALLED.
COORDINATION: COORDINATE WITH THE WORK OF OTHER SECTIONS,
EQUIPMENT FURNISHED BY OTHERS, REQUIREMENTS OF THE OWNER, AND WITH
THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE PROJECT SITE.
ROOF PENETRATIONS SHALL COMPLY WITH "SMACNA" AND "NRCA"
STANDARDS, AND WITH THE REQUIREMENTS OF THE EXISTING ROOFING
WARRANTY, IF APPLICABLE. DO NOT PERFORM ROOFING PENETRATIONS IN A
MANNER WHICH WOULD VOID OR OTHERWISE LIMIT THE EXISTING ROOF
WARRANTY.
DUCT DIMENSIONS: UNLESS OTHERWISE NOTED, DUCT DIMENSIONS ON THE
DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
SHEET METAL DUCTWORK: PROVIDE SHEET METAL DUCTWORK FABRICATED
AND INSTALLED IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS,
FOR 1" W.G. PRESSURE CLASS, SEAL CLASS "A". SHEET METAL SHALL BE
GALVANIZED SHEET STEEL OF LOCK FORMING QUALITY, WITH G90 ZINC
COATING. SHEET STEEL SHALL COMPLY WITH ASTM A653 STANDARD
SPECIFICATION FOR STEEL SHEET METAL, ZINC COATED (GALVANIZED) OR
ZINC-IRON ALLOY-COATED (GALVANNEALED) BY THE HOT DIP PROCESS, AND
A924 STANDARD SPECIFICATION FOR GENERAL REQUIREMENTS FOR SHEET,
METALLIC-COATED BY THE HOT DIP PROCESS. ALL ANGLE IRON USED FOR
SUPPORT SHALL BE GALVANIZED. CONNECTIONS TO WALLS OR FLOOR SHALL
BE AIR TIGHT WITH ANGLE IRON AND CAULKING. SEAL ALL DUCT SEAMS,
TRANSVERSE AND LONGITUDINAL, AIR TIGHT. PROVIDE TURNING VANES AT
ALL 90º ELBOWS. TRAPEZE DUCT HANGERS: PROVIDE MINIMUM 1" X 2" X 1" X
18 GAUGE CHANNELS WITH MINIMUM 1" X 18 GAUGE STRAPS TO STRUCTURAL
SUPPORT.
ROUND SHEET METAL DUCT: PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK
(DUCT SIZES UP TO 10") GALVANIZED STEEL COMPLYING WITH SMACNA
STANDARDS. SPIRAL SEAM DUCTWORK SHALL HAVE SMACNA SEAM TYPE RL-1.
FIBER GLASS DUCT BOARD IS AN ACCEPTABLE ALTERNATIVE IF APPROVED BY
OWNER AND THE LOCAL BUILDING CODE OFFICIAL. PRODUCT AND
INSTALLATION MUST MEET NAIMA STANDARDS AND OTHER APPLICABLE
CODES AND REGULATIONS.
EXPOSED DUCTWORK: EXPOSED DUCTWORK SHALL BE CLEANED OF DEBRIS
AND OIL, THEN WIPED DOWN WITH VINEGAR OR OTHER SURFACE PREPARING
CHEMICAL TO PREPARE DUCT FOR PAINT.
DUCT SEALANT: PROVIDE POLYMERIC RUBBER TYPE SEALANT FOR USE ON
BOTH INTERIOR LOCATED DUCTWORK AND DUCTWORK EXPOSED TO
OUTDOOR CONDITIONS. SEALER SHALL HAVE HIGH BONDING STRENGTH FOR
SURE, FIRST TIME SEALING OF JOINTS IN LOW, MEDIUM, AND HIGH PRESSURE
DUCT SYSTEMS. SEALER SHALL BE HIGH IN SOLID CONTENT. PROVIDE A TWO
PART TAPE SEALING SYSTEM, CONSISTING OF WOVEN FIBER TAPE
IMPREGNATED WITH A GYPSUM MINERAL COMPOUND, AND A MODIFIED
ACRYLIC/SILICONE ACTIVATOR THAT REACTS EXOTHERMICALLY WITH THE
TAPE. TWO PART TAPE SEALING SYSTEM MUST BE RATED FOR BOTH INDOOR
AND OUTDOOR APPLICATION. TAPE SHALL NOT CONTAIN ASBESTOS.
DUCT INSULATION: MATERIAL FOR SUPPLY AND RETURN AIR DUCT ABOVE
CEILING INSIDE THE BUILDING SHALL HAVE THE EQUIVALENT THERMAL
RESISTANCE OF MINIMUM R-6. THE REQUIRED R VALUES ARE FOR INSTALLED
INSULATION WITH 25% COMPRESSION AT THE CORNERS. PROVIDE PINS AND
WASHERS IN ACCORDANCE WITH SMACNA REQUIREMENTS AND AS
REQUIRED TO PREVENT INSULATION FROM SAGGING. PROVIDE ADEQUATE
INSULATION AT THE SUPPLY AIR DIFFUSERS TO PREVENT CONDENSATION.
FLEXIBLE DUCT : UL #181 LISTED, CLASS 1, AND CONTAIN A 0.1 PERM RATED
POLYETHYLENE INNER LINER, WITH R-8 FIBERGLASS INSULATION. FLEXIBLE
DUCTS SHALL BE SECURED TO RIGID SHEET METAL COLLARS AND AIR
DIFFUSERS WITH NYLON TIES OR STAINLESS STEEL WORM GEAR STRAPS. SEAL
ALL CONNECTIONS AND JOINTS AIRTIGHT. SUPPORT FLEXIBLE DUCTS FROM
THE BUILDINGS STRUCTURE WITH MINIMUM 1" WIDE, 18 GAUGE, GALVANIZED
STEEL STRAP AT MAXIMUM 4'-0" CENTERS. PROVIDE 4" WIDE SHEET METAL
SADDLES AT EACH SUPPORT EACH STRAP. SAG OF FLEXIBLE DUCT BETWEEN
HANGERS SHALL NOT EXCEED 1/2" PER FOOT OF SUPPORT SPACING. RADIUS
FOR TURNS OF FLEXIBLE DUCTS SHALL BE A MINIMUM OF ONE DUCT DIAMETER.
FLEXIBLE DUCT RUNS SHALL NOT EXCEED 10'-0" IN LENGTH AND SHALL BE THE
SAME SIZE AS THE DIFFUSER NECK CONNECTION.
ROUND VOLUME DAMPERS: PROVIDE MINIMUM 20 GAUGE GALVANIZED STEEL
FRAME AND BLADES, MINIMUM 3/8" SQUARE STEEL AXLE, MOLDED SYNTHETIC
BEARINGS, WITH LOCKING POSITION REGULATOR. REGULATOR SHALL BE
POSITIONED WITH SHEET METAL BRACKET BEYOND DUCT COVERING. WHERE
POSITIONING REGULATOR IS NOT ACCESSIBLE, PROVIDE COUPLING AND
EXTENSION ROD WITH REGULATOR FOR CEILING OR WALL INSTALLATION, AS
REQUIRED.
RECTANGULAR VOLUME DAMPERS: PROVIDE MINIMUM 16 GAUGE
GALVANIZED STEEL CHANNEL FRAME, 16 GAUGE GALVANIZED STEEL BLADES,
MINIMUM ½" HEXAGONAL AXLE, BOLDED SYNTHETIC BEARINGS, WITH 3/8"
SQUARE PLATED STEEL CONTROL SHAFT. LINKAGES SHALL BE CONCEALED IN
THE FRAME. OPERATING SHAFT SHALL EXTEND BEYOND FRAME AND DUCT TO
A LOCKING QUADRANT WITH ADJUSTABLE LEVER. MAXIMUM BLADE WIDTH
SHALL NOT EXCEED 6".
DUCT TURNING VANES:
PROVIDE FABRICATED TURNING VANES AND VANE RUNNERS,
CONSTRUCTED IN ACCORDANCE WITH SMACNA "HVAC DUCT
CONSTRUCTION STANDARDS". PROVIDE TURNING VANES
CONSTRUCTED OF CURVED BLADES, SUPPORTED WITH BARS
PERPENDICULAR TO BLADES, AND SET INTO SIDE STRIPS SUITABLE FOR
MOUNTING IN DUCTWORK. FOLLOW SMACNA GUIDELINES FOR
SPACING SUPPORT, AND CONSTRUCTION. ALL BLADES SHALL BE
DOUBLE THICKNESS AIRFOIL TYPE. FLEXIBLE DUCT CONNECTORS:
PROVIDE U.L. LABELED 30 OUNCE NEOPRENE COATED FIBERGLASS
FABRIC DUCT CONNECTORS. DUCT ACCESS DOORS: PROVIDE
HINGED ACCESS DOORS IN DUCTWORK WHERE REQUIRED FOR
ACCESS TO EQUIPMENT. PROVIDE INSULATED ACCESS DOORS FOR
INSULATED DUCTWORK. CONSTRUCT OF SAME OR THICKER GAUGE
SHEET METAL AS DUCT IN WHICH IT IS INSTALLED. PROVIDE FLUSH
FRAMES FOR UN-INSULATED DUCTS, AND EXTENDED FRAMES FOR
EXTERNALLY INSULATED DUCTS. PROVIDE CONTINUOUS HINGE ON
ONE SIDE, WITH ONE HANDLE-TYPE LATCH FOR ACCESS DOORS 12"
HIGH AND SMALLER, AND TWO HANDLE-TYPE LATCHES FOR LARGER
ACCESS DOORS.
HVAC CONTROL SYSTEM:
PROVIDE ALL THE NECESSARY CONTROLS AND CONTROL WIRING IN
CONDUIT COMPATIBLE TO SYSTEMS SHOWN ON EQUIPMENT
SCHEDULE M2.0. PROGRAMMABLE THERMOSTAT FOR EACH SYSTEM
SHALL ENABLE THE SUPPLY FAN AND CYCLE THE COOLING AND
HEATING STAGES TO MAINTAIN SPACE SET-POINT. SUPPLY FAN RUNS
CONTINUOUSLY DURING THE OCCUPIED MODE. EACH THERMOSTAT
SHALL HAVE A DEAD BAND OF AT LEAST 5 DEGREES (ADJ) WITHIN
WHICH THE SUPPLY OF HEATING AND COOLING IS SHUT OFF, EACH
THERMOSTAT SHALL HAVE SETBACK AND SET-UP CAPABILITY DURING
THE UNOCCUPIED MODE. FOR SETBACK, THE HEATING SHALL RESTART
AND TEMPORARILY OPERATE ACCORDING TO A SET-POINT
ADJUSTABLE DOWN TO 55 DEGREES. FOR SET-UP, THE COOLING
SHALL RESTART AND TEMPORARILY OPERATE ACCORDING TO A
SET-POINT ADJUSTABLE UP TO 85 DEGREES OR TO PREVENT HIGH
SPACE HUMIDITY LEVELS. EACH SYSTEM SHALL BE PROVIDED WITH A
MOTORIZED OUTSIDE AIR DAMPER THAT WILL AUTOMATICALLY SHUT
WHEN THE SYSTEM OR SPACES SERVED ARE NOT IN USE. VENTILATION
OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY
CLOSING DURING PREOCCUPANCY BUILDING WARM-UP, COOL
DOWN, AND SETBACK, EXCEPT WHEN VENTILATION REDUCES
ENERGY COSTS (e.g., NIGHT PURGE) OR WHEN VENTILATION MUST BE
SUPPLIED TO MEET CODE REQUIREMENTS.
COMMISSIONING/VERIFICATION:
HVAC CONTROL SYSTEM SHALL BE TESTED TO ENSURE THAT CONTROL
ELEMENTS ARE CALIBRATED, ADJUSTED, AND IN PROPER WORKING
CONDITION, AND THAT THE SYSTEM MEETS THE DESIGN
REQUIREMENTS.
TEST AND BALANCE:
CONTRACT DIRECTLY A THIRD PARTY TO PROVIDE TEST AND
BALANCE OF THE HVAC SYSTEM. THE GENERAL CONTRACTOR IS
RESPONSIBLE FOR SCHEDULING. TEST AND ADJUST ALL MECHANICAL
SYSTEM AND EQUIPMENT TO ASSURE PROPER BALANCE AND
OPERATION. PERFORM TESTS IN ACCORDANCE WITH NEBB
PROCEDURAL STANDARDS-1999 OR AABC 2002, AND ASHRAE
STANDARD 111. ELIMINATE NOISE AND VIBRATION, AND ASSURE
PROPER FUNCTION OF CONTROLS. SUBMIT COMPLETED TEST AND
BALANCE REPORT TO OWNER'S REPRESENTATIVE. BALANCING
CONTRACTOR SHALL BE INDEPENDENT AND CERTIFIED WITH NEBB OR
AABC. BALANCE ALL SYSTEMS WITHIN 5% OF AIR FLOW INDICATED
ON DRAWINGS, AND REPORT ALL DISCREPANCIES TO THE HVAC
CONTRACTOR FOR CORRECTION. MARK FINAL BALANCE POSITIONS
ON DAMPERS WITH PERMANENT MARKER.
COMPLETION REQUIREMENTS:
THE CONTRACTOR SHALL PROVIDE, WITHIN 90 DAYS AFTER THE DATE
OF SYSTEM ACCEPTANCE, RECORD DRAWINGS AND AN OPERATING
AND MAINTENANCE MANUAL TO THE BUILDING OWNER OR THE
DESIGNATED REPRESENTATIVE OF THE OWNER. THE RECORD
DRAWING SHALL BE OF THE ACTUAL INSTALLATION AND INCLUDE AS
A MINIMUM THE LOCATION AND PERFORMANCE DATA ON EACH
PIECE OF EQUIPMENT, GENERAL CONFIGURATION OF DUCT AND
PIPE DISTRIBUTION SYSTEM INCLUDING SIZES, AND THE TERMINAL AIR
OR WATER DESIGN FLOW RATES. THE OPERATING AND
MAINTENANCE MANUALS SHALL BE IN ACCORDANCE WITH
INDUSTRY-ACCEPTED STANDARDS AND SHALL INCLUDE, AT A
MINIMUM, THE FOLLOWING:
(A) SUBMITTAL DATA STATING EQUIPMENT SIZE AND SELECTED
OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
MAINTENANCE
(B) OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
PIECE OF EQUIPMENT REQUIRING MAINTENANCE, EXCEPT
EQUIPMENT NOT FURNISHED AS PART OF THE PROJECT. REQUIRED
ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED
(C) NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY
(D) HVAC CONTROLS SYSTEMS MAINTENANCE AND CALIBRATION
INFORMATION, INCLUDING WIRING DIAGRAMS, SCHEMATICS, AND
CONTROL SYSTEM SEQUENCE DESCRIPTIONS. DESIRED OR
FIELD-DETERMINED SET-POINTS SHALL BE PERMANENTLY RECORDED
ON CONTROL DRAWINGS AT CONTROL DEVICES OR, FOR DIGITAL
CONTROL SYSTEMS, IN PROGRAMMING COMMENTS
(E) A COMPLETE NARRATIVE OF HOW EACH SYSTEM EACH SYSTEM IS
INTENDED TO OPERATE, INCLUDING SET-POINTS.
1.THE INTENT OF THESE PLANS AND SPECIFICATIONS IS TO INCLUDE ALL LABOR, EQUIPMENT,
MATERIALS, AND SERVICES NECESSARY TO FURNISH, INSTALL, TEST, AND ADJUST A
COMPLETE WORKABLE HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM AS
SHOWN, PRESCRIBED, OR REASONABLY IMPLIED BUT NOT LIMITED TO THAT EXPLICITLY
INDICATED IN THE CONTRACT DOCUMENTS, BUT NECESSARY FOR THE PROPER EXECUTION
AND COMPLETION OF THE INTENT THEREOF.
2.THE ENTIRE INSTALLATION SHALL CONFORM TO THE APPLICABLE CODES AND
REGULATIONS REQUIRED BY AUTHORITIES HAVING JURISDICTION. IN THE EVENT OF
CONFLICT BETWEEN SPECIFICATIONS, CODES, AND REGULATIONS, THE MORE RESTRICTIVE
SHALL APPLY.
3.DRAWINGS FOR HVAC WORK ARE DIAGRAMMATIC SHOWING THE GENERAL LOCATION,
TYPE, LAYOUT, AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR
EXACT MEASUREMENT, REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. PROVIDE
ALL DUCTWORK, MATERIALS, CONNECTIONS, ACCESSORIES, FITTINGS, OFFSETS,
TRANSITIONS, DAMPERS AS REQUIRED FOR A COMPLETE WORKABLE SYSTEM.
4.ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS AND APPROVED LISTING. ALL EQUIPMENT, PIPING AND SUPPORTS
SHALL BE RESTRAINED IN ACCORDANCE WITH THE LATEST EDITION OF THE "GUIDELINES
FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING PIPING SYSTEMS" BY
THE SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION
(SMACNA). ALL EQUIPMENT SHALL BE ANCHORED TO RESIST THE LATERAL FORCE
REQUIREMENTS OF CHAPTER 16 OF THE 2022 CALIFORNIA BUILDING CODE.
5.COORDINATE THE INSTALLATION OF THE HVAC SYSTEM WITH ALL OTHER TRADES PRIOR TO
FABRICATION OR INSTALLATION. COORDINATE THE LOCATIONS OF PENETRATIONS AND
FINAL LOCATION OF ALL EQUIPMENT WITH THE GENERAL CONTRACTOR. PROVIDE
EQUIPMENT WEIGHTS, EQUIPMENT DIMENSIONS, PLATFORM SIZES & LOCATIONS, CURB
SIZES & LOCATIONS, CONCRETE PAD SIZES AND LOCATIONS AS REQUIRED. COORDINATE
LOCATIONS OF GAS & CONDENSATE LINES WITH PLUMBING CONTRACTOR. COORDINATE
LOCATIONS OF POWER, DISCONNECTS, AND CONTROL CONDUIT WITH THE ELECTRICAL
CONTRACTOR. COORDINATE LOCATIONS OF ALL DIFFUSERS, REGISTERS, AND GRILLES
WITH ARCHITECTURAL PLANS, ELECTRICAL LIGHTING PLANS AND ARCHITECTURAL
ELEVATIONS.
6.DETAILS FOR EQUIPMENT PADS, PLATFORMS, AND FLASHINGS SHALL BE AS INDICATED BY
THE ARCHITECTURAL/STRUCTURAL/CIVIL DRAWINGS, UNLESS NOTED OTHERWISE.
7.ALL EQUIPMENT, DUCTS, PIPING, SUPPORTS, AND OTHER DEVICES OUTSIDE OF THE
BUILDING OR EXPOSED TO WEATHER, SHALL BE COMPLETELY WEATHER-PROOFED.
8.OUTSIDE AIR INTAKES SHALL BE AT LEAST 10 FT. AWAY OR 3 FT. BELOW ANY VENT OR
EXHAUST DISCHARGE.
9.ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. DUCTWORK SHALL BE CONSTRUCTED,
ERECTED, INSULATED AND TESTED IN ACCORDANCE CHAPTER 6 OF THE 2022 CALIFORNIA
MECHANICAL CODE.
10.ALL EXHAUST FANS SHALL BE EQUIPPED WITH A BACK DRAFT DAMPER.
11.DUCT AND AIR TRANSFER PENETRATIONS THRU BUILDING ASSEMBLIES REQUIRING
PROTECTION SHALL BE PROTECTED WITH FIRE DAMPERS, SMOKE DAMPERS, COMBINATION
SMOKE/FIRE DAMPERS AND CEILING RADIATION DAMPERS IN ACCORDANCE WITH
SECTION 607 OF THE CALIFORNIA MECHANICAL CODE. DUCTS NOT REQUIRING DAMPERS
SHALL COMPLY WITH SECTION 714 & 717 OF THE 2022 CALIFORNIA BUILDING CODE.
12.INSTALL SMOKED DETECTORS AND PROVIDE FOR SMOKE DETECTION AND AUTOMATIC
SHUT-OFF OF ALL AIR HANDLING EQUIPMENT IN ACCORDANCE WITH SECTION 606 OF THE
2022 CALIFORNIA MECHANICAL CODE.
13.UNLESS NOTED OTHERWISE, ALL LINE VOLTAGE WIRING, CONDUIT, FINAL CONNECTIONS,
DISCONNECTS, STARTERS, AND OVER CURRENT PROTECTION DEVICES SHALL BE
FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AS INDICATED ON THESE
MECHANICAL DRAWINGS AND/OR ELECTRICAL DRAWINGS AND/OR ELECTRICAL
SECTION OF THE SPECIFICATIONS.
14.INSTALL ALL LOW VOLTAGE HVAC CONTROL WIRE AND DEVICES PER PLAN. ALL WIRE
SHALL BE IN CONDUIT PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR
UNLESS NOTED OTHERWISE.
15.PROVIDE OWNER WITH THREE COPIES OF A CERTIFIED AIR BALANCE REPORT PREPARED IN
BY A THIRD PARTY CERTIFIED BY THE AABC OR NEBB. TEST, ADJUST AND BALANCE THE
HVAC SYSTEM IN ACCORDANCE WITH AABC OR NEBB PROCEDURES. PROVIDE
START-UP/TEST REPORTS FOR ALL AIR HANDLING EQUIPMENT, FANS, AND REFRIGERATION
EQUIPMENT. TEST AND VERIFY PROPER OPERATION OF ALL MAKE-UP AIR/EXHAUST AIR
INTERLOCK SYSTEMS AND THEIR SEQUENCES OF OPERATION. BALANCE ALL AIR FLOWS
WITHIN 5% OF DESIGN VALUES. PERMANENTLY MARK BALANCE POSITION OF ALL
REGULATING DEVICES.
16.PROVIDE OWNER WITH THREE SETS OF AS-BUILT PLANS AND OPERATIONS AND
MAINTENANCE MANUALS. CLEARLY IDENTIFY ALL EQUIPMENT WITH PERMANENT PLASTIC
OR METAL LABELS/TAGS (PEN MARKING NOT ACCEPTABLE).
17.PROVIDE ONE YEAR WARRANTY ON ALL LABOR, PARTS AND MATERIALS.
18.ANY CHANGE OR DEVIATION FROM THESE PLANS OR SPECIFICATIONS SHALL REQUIRE THE
WRITTEN APPROVAL OF THE ENGINEER PRIOR TO COMMENCEMENT OF SUCH WORK. 19.0
a)DUCTS FOR DEMAND CONTROLLED VENTILATION SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH THE FAN MANUFACTURER'S INSTALLATION INSTRUCTIONS, THE
PROVISIONS ASHRAE 62.2, TABLE 5.3, OR THE AIRFLOW SHALL BE MEASURED AS REQUIRED
BY AND IN COMPLIANCE WITH ASHRAE 62.2, 5.4.
1.ALL CONTRACTORS (GENERAL CONTRACTOR AND SUB-CONTRACTORS) BIDDING THIS
PROJECT ARE REQUIRED TO VISIT THE JOB SITE AND VERIFY THE EXISTING CONDITIONS PRIOR
TO SUBMITTING THEIR BID. CONTRACTORS ARE TO CAREFULLY REVIEW ALL CONSTRUCTION
DOCUMENTS AND NOTE ANY DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS
AND THE CONDITIONS OBSERVED AT THE JOB SITE PRIOR TO SUBMISSION OF ANY BID. THE
BUILDING OWNER REPRESNENTATIVE LISTED BELOW MAY BE CONTACTED FOR ACCESS TO
THE JOB SITE.
2.CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE LOCATION AND CONDITION OF ALL
POINTS OF CONNECTION, LOCATION AND CONDITION OF ALL BUILDING
(ROOF/FLOOR/CEILING) PENETRATIONS, LOCATION AND CONDITION OF ALL UTILITIES AND
BUILDING SYSTEMS INCLUDING, BUT NOT LIMITED TO, GAS, WATER, SEWER, VENT,
ELECTRICAL, BUILDING MECHANICAL SYSTEMS, DUCT CONNECTIONS, EXHAUST/OUTSIDE AIR
CONNECTIONS, SECURITY, FIRE ALARM, DATA, AND PHONE PRIOR TO SUBMISSION OF THEIR
BID.
3.ANY DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONS
OBSERVED SHALL BE BROUGHT TO THE ATTENTION, IN WRITING, TO THE ARCHITECT AND/OR
ENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION.
4.NO WORK SHALL BE DONE ON ANY PART OF THE BUILDING BEYOND THE POINT INDICATED IN
EACH SUCCESSIVE INSPECTION WITHOUT FIRST OBTAINING THE WRITTEN APPROVAL OF THE
CODE OFFICIAL. NO CONSTRUCTION SHALL BE CONCEALED WITHOUT BEING INSPECTED
AND APPROVED.
SHEET TAG TITLE SCALE
M 0.00 MECHANICAL GENERAL NOTES AND SPECIFICATIONS NTS
3/8" = 1'- 0"FIRST FLOOR - MECHANICAL LAYOUT
MECHANICAL GENERAL DETAILS
MECHANICAL LIST OF DRAWINGS (LoD):
M 1.01
M 2.01 NTS
MECHANICAL SPECIFICATIONS
HVAC GENERAL NOTES LEGEND
SPECIAL NOTICE TO CONTRACTORS
M 0.01 CALIFORNIA MECHANICAL CODE CHECKING NTS
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
M0.00
MECH GENERAL NOTES
AND SPECIFICATIONS
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
402.4 Outdoor Air Intake Protection. Required outdoor-
air intakes shall be covered with a screen having not less than
14 of an inch (6.4 mm) openings, and shall have not more than
12 of an inch (12.7 mm) openings.
402.4.1 Weather Protections. Outdoor air intakes that
are part of the mechanical ventilation system shall be
designed to manage rain entrainment, to prevent rain
intrusion, and manage water from snow in accordance
with ASHRAE 62.1.
402.5 Bathroom Exhaust Fans. [HCD 1 & HCD 2] Each
bathroom shall be mechanically ventilated in accordance with
Division 4.5 of the California Green Building Standards Code
(CALGreen).
407.2.2 Exhaust Outlets. Exhaust outlets shall be
located a minimum of 10 feet (3048 mm) above adjoining
grade and 10 feet (3048 mm) from doors, occupied areas,
and operable windows.
Exception: Airborne infection isolation rooms shall
comply with Section 414.1.
CALIFORNIA MECHANICAL CODE CHECKING:
PLEASE REFER TO TABLE 506.2(1) FOR MINIMUM S
HEET METAL THICKNESS FOR ROUND DUCTS
604.0 Insulation of Ducts.
604.1 General. Air ducts conveying air at temperatures
exceeding 140°F (60°C) shall be insulated to maintain an insu-
lation surface temperature of not more than 140°F (60°C). Fac-
tory-made air ducts and insulations intended for installation on
the exterior of ducts shall be legibly printed with the name of
the manufacturer, the thermal resistance (R) value at installed
thickness, flame-spread index, and smoke developed index of
the composite material. Internal duct liners and insulation shall
be installed in accordance with SMACNA HVAC Duct Con-
struction standards – Metal and Flexible. [OSHPD 1, 1R, 2,
3, 4 & 5] Cold air ducts shall be insulated wherever necessary
or to prevent condensation.
Exceptions:
(1)Factory-installed plenums, casings, or ductwork furnished
as part of HVAC equipment tested and rated in accor-
dance with approved energy efficiency standards.
(2)Ducts or plenums located in conditioned spaces where heat
gain or heat loss will not increase energy use.
(3)For runouts less than 10 feet (3048 mm) in length to air ter-
minals or air outlets, the rated R-value of insulation need
not exceed R-3.5.
(4)Backs of air outlets and outlet plenums exposed to uncon-
ditioned or indirectly conditioned spaces with face areas
exceeding 5 square feet (0.5m2) need not exceed R-2;
those 5 square feet (0.5m2) or smaller need to be insu-
lated.
(5)Ducts and plenums used exclusively for evaporative cool-
ing systems.
E 502.4 Ducts. Ducts shall be sized, installed, and tested in
accordance with Section E 502.4.1 though Section E 502.4.4.
E 502.4.1 Insulation and Ducts. Portions of the air
distribution system installed in or on buildings for heat-
ing and cooling shall be R-8. Where the mean outdoor
dew-point temperature in a month exceeds 60°F (16°C),
vapor retarders shall be installed on conditioned-air sup-
ply ducts. Vapor retarders shall have a water vapor per-
meance not exceeding 0.5 perm [2.87 E-11 kg/(Pa.s.m2)]
where tested in accordance with Procedure A in ASTM
E96.
Insulation shall not be required where the ducts are
within the conditioned space. [ASHRAE 90.2:6.4]
E 502.4.4 Duct Sizing. Duct systems shall be sized in
accordance with ACCA Manual D or other methods
approved by the Authority Having Jurisdiction with the
velocity in the main duct not exceed 1000 feet per
minute (ft/min) (5.08m/s) and the velocity in the sec-
ondary branch duct not to exceed 600 ft/min (3.048 m/s).
310.0 Condensate Wastes and Control.
310.1 Condensate Disposal. Condensate from air wash-
ers, air-cooling coils, condensing appliances, and the over-
flow from evaporative coolers and similar water-supplied
equipment or similar air-conditioning equipment shall be col-
ected and discharged to an approved plumbing fixture or dis-
posal area. Where discharged into the drain system,
equipment shall drain by means of an indirect waste pipe. The
Waste pipe shall have a slope of not less than 18 inch per foot
(10.4 mm/m) or 1 percent slope and shall be of approved cor-
rosion-resistant material not smaller than the outlet size in
accordance with Section 310.3 or Section 310.4 for air-cool-
ing coils or condensing appliances, respectively. Condensate
or wastewater shall not drain over a public way.
310.3 Condensate Waste Pipe Material and Sizing.
Condensate waste pipes from air-cooling coils shall be sized
in accordance with the equipment capacity as specified in
Table 310.3. The material of the piping shall comply with the pressure
and temperature rating of the appliance or equipment,
and shall be approved for use with the liquid being discharged.
EQUIPMENT CAPACITY IN
TONS OF REFRIGERATION
MINIMUM CONDENSATE
PIPE DIAMETER
(inches)
Up to 20 3 4
21 – 40 1
41 – 90 1 14
91 – 125 1 12
126 – 250 2
TABLE 310.3
MINIMUM CONDENSATE WASTE PIPE SIZE
For SI units: 1 ton of refrigeration = 3.52 kW, 1 inch = 25 mm
310.3.1 Cleanouts. Condensate drain lines shall be
configured or provided with a cleanout to permit the
clearing of blockages and for maintenance without
requiring the drain line to be cut.
310.5 Point of Discharge. Air conditioning condensate
waste pipes shall connect indirectly, except where permitted
in Section 310.6, to the drainage system through an air gap or
air break to trapped and vented receptors, dry wells, leach
pits, or the tailpiece of plumbing fixtures. A condensate drain
shall be trapped in accordance with the appliance manufac-
turer's instructions or as approved.
310.6 Condensate Waste From Air-Conditioning
Coils. Where the condensate waste from air-conditioning
coils discharges by direct connection to a lavatory tailpiece or
to an approved accessible inlet on a bathtub overflow, the con-
nection shall be located in the area controlled by the same
person controlling the air-conditioned space.
311.3 Prohibited Source. Outside or return air for a heating
or cooling air system shall not be taken from the following loca-
tions:
(1)Less than 10 feet (3048 mm) in distance from an appliance
vent outlet, a vent opening of a plumbing drainage system,
or the discharge outlet of an exhaust fan, unless the outlet
is 3 feet (914 mm) above the outside-air inlet.
(2)Less than 10 feet (3048 mm) above the surface of an abut
ting public way, sidewalk, street, alley, or driveway.
Mechanical draft
vent terminal
(see Section 802.8)
Mechanical draft
vent terminal
(see Section
802.8.1)
Direct vent terminal clearance
Minimum Clearance, C
Input (Btu/hr)Clearance (inches)
10 000 or less 6
10 001 to 50 000 9
Over 50 00012
(See Section 8.2.8.2)
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm,
1000 British thermal units per hour = 0.293 kW
Forced air inlet
Grade
3 ft. min.12 inch minimum
4 feet minimum
4 f
e
e
t
mi
n
i
m
u
m
12
i
n
c
h
m
i
n
i
m
u
m
12 i
n
c
h
m
i
n
i
m
u
m
C
Less
than 10 feet
FIGURE 802.8
EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEMS
[NFPA 54: FIGURE A.12.9]
701.10.1 Minimum Screen Mesh Size. Screens shall
be not less than 14 of an inch (6.4 mm) mesh. [NFPA
54:9.3.7.2]
DUCT SIZING, THICKNESS & INSULATION
CONDENSATE DRAIN:AIR INTAKE AND EXHAUST:
502.1 Exhaust Opening Protection. Exhaust openings ter-
minating to the outdoors shall be covered with a corrosion-
resistant screen having not less than 14 of an inch (6.4 mm)
openings, and shall have not more than 12 of an inch (12.7 mm)
openings.
Exception: Clothes dryers.
504.4 Clothes Dryers. A clothes dryer exhaust duct shall
not be connected to a vent connector, gas vent, chimney, and
shall not terminate into a crawl space, attic, or other concealed
space. Exhaust ducts shall not be assembled with screws or
other fastening means that extend into the duct and that are
capable of catching lint, and that reduce the efficiency of the
exhaust system.
504.4.1 Provisions for Makeup Air. Make up air shall
be provided in accordance with the following:
(1)Makeup air shall be provided for Type 1 clothes dry-
ers in accordance with the manufacturer's instruc-
tions. [NFPA 54: 10.4.3.1] Where a closet is designed
for the installation of a clothes dryer, an opening of
not less than 100 square inches (0.065 m2) for
makeup air shall be provided in the door or by other
approved means.
(2)Provision for makeup air shall be provided for Type
2 clothes dryers, with a free area of not less than 1
square inch (0.0006 m2) for each 1000 British ther-
mal units per hour (Btu/g)(0.293 kW) total input rat-
ing of the dryer(s) installed [NFPA 54:10.4.3.2].
504.4.3.1 Exhaust Ducts for Type 2 Clothes
Dryers. Exhaust ducts for Type 2 clothes dryers
shall comply with the following:
(1)Exhaust ducts for Type 2 clothes dryers shall
comply with Section 504.4. [NFPA 54:10.4.5.1]
(2)Exhaust ducts for Type 2 clothes dryers shall be
constructed of sheet metal or other noncom-
bustible material. Such ducts shall be equiva-
lent in strength and corrosion resistance to ducts
0.0195 of an inch (0.4953 mm) thick. [NFPA
54:10.4.5.2]
(3)Type 2 clothes dryers shall be equipped or
installed with lint-controling means. [NFPA
54:10.4.5.3]
(4)Exhaust ducts for Type 2 clothes dryers shall be
installed with a clearance of not less than 6
inches (152 mm) from adjacent combustible
material. Where exhaust ducts for Type 2
clothes dryers are installed with reduced clear-
ances, the adjacent combustible material shall
be protected in accordance with Table 303.10.1.
[NFPA 54:10.4.5.4]
(5)Where ducts pass through walls, floors, or par-
titions, the space around the duct shall be
sealed with noncombustible material. [NFPA
54:10.4.5.4]
504.4.2.1 Length Limitation
Unless otherwise permitted or required by the dryer
manufacturer's instructions and approved by the
Authority Having Jurisdiction, domestic dryer moisture
exhaust ducts shall not exceed a total combined
horizontal and vertical length of 14 feet (4267 mm),
including two 90 degree (1.57 rad) elbows. A length of
2 feet (610 mm) shall be deducted for each 90 degree
(1.57 rad) elbow in excess of two
GAS CLOTHES DRYER:
FACTORY-MADE AIR DUCTS
FACTORY-MADE AIR DUCTS SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL
181 AND INSTALLED IN ACCORDANCE WITH THE TERMS OF THEIR LISTING, THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND SMACNA HVAC DUCT
CONSTRUCTION STANDARDS-METAL AND FLEXIBLE.
FACTORY-MADE AIR DUCTS SHALL NOT BE USED FOR VERTICAL RISERS IN AIR-DUCT
SYSTEMS SERVING MORE THAN TWO STORIES AND SHALL NOT PENETRATE A
FIRE-RESISTANCE-RATED ASSEMBLY OR CONSTRUCTION.
FACTORY-MADE AIR DUCTS SHALL BE INSTALLED WITH NOT LESS THAN 4 INCHES (102
MM) OF SEPARATION FROM EARTH, EXCEPT WHERE INSTALLED AS A LINER INSIDE OF
CONCRETE, TILE, OR METAL PIPE AND SHALL BE PROTECTED FROM PHYSICAL DAMAGE.
THE TEMPERATURE OF THE AIR TO BE CONVEYED IN A DUCT SHALL NOT EXCEED 250°F
(121° C). FLEXIBLE AIR CONNECTORS SHALL NOT BE PERMITTED.
RECTANGULAR DUCTS
SUPPORTS FOR RECTANGULAR DUCTS SHALL BE
INSTALLED ON TWO OPPOSITE SIDES OF EACH DUCT AND
SHALL BE RIVETED, BOLTED, OR METAL SCREWED TO
EACH SIDE OF THE DUCT AT INTERVALS SPECIFIED.
METAL DUCTS
DUCTS SHALL BE SUPPORTED AT EACH CHANGE OF
DIRECTION AND IN ACCORDANCE WITH SMACNA HVAC
DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE.
RISER DUCTS SHALL BE HELD IN PLACE BY MEANS OF
METAL STRAPS OR ANGLES AND CHANNELS TO SECURE
THE RISER TO THE STRUCTURE.
METAL DUCTS SHALL BE INSTALLED WITH NOT LESS THAN
4 INCHES (102 MM) SEPARATION FROM EARTH. DUCTS
SHALL BE INSTALLED IN A BUILDING WITH CLEARANCES
THAT WILL RETAIN THE FULL THICKNESS OF
FIRE-PROOFING ON STRUCTURAL MEMBERS.
COMBUSTIBLES WITHIN DUCTS OR PLENUMS
MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
HAVE A FLAME SPREAD INDEX NOT TO EXCEED 25 AND A SMOKE-DEVELOPED INDEX NOT TO
EXCEED 50, WHERE TESTED AS A COMPOSITE PRODUCT IN ACCORDANCE WITH ASTM E84 OR
UL 723.
EXCEPTIONS:
1.RETURN-AIR AND OUTSIDE-AIR DUCTS, PLENUMS, OR CONCEALED SPACES THAT SERVE A
DWELLING UNIT.
2.AIR FILTERS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 311.2.
3.WATER EVAPORATION MEDIA IN AN EVAPORATIVE COOLER.
4.CHARCOAL FILTERS WHERE PROTECTED WITH AN APPROVED FIRE SUPPRESSION SYSTEM.
5.PRODUCTS LISTED AND LABELED FOR INSTALLATION WITHIN PLENUMS IN ACCORDANCE WITH
SECTION 602.2.1 THROUGH SECTION 602.2.3.
6.SMOKE DETECTORS.
7.DUCT INSULATION, COVERINGS, AND LININGS AND OTHER SUPPLEMENTARY MATERIALS
INSTALLED IN ACCORDANCE WITH SECTION 604.0.
8.MATERIALS IN A HAZARDOUS FABRICATION AREA INCLUDING THE AREAS ABOVE AND BELOW
THE FABRICATION AREA SHARING A COMMON AIR RECIRCULATION PATH WITH THE
FABRICATION AREA.
NOTES ON DUCTS MATERIAL & CONSTRUCTION:
FLEXIBLE AIR DUCTS
FLEXIBLE AIR DUCTS SHALL COMPLY WITH UL 181, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE.
FLEXIBLE AIR DUCT INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING:
1.DUCTS SHALL BE INSTALLED USING THE MINIMUM REQUIRED LENGTH TO MAKE THE CONNECTION.
2.HORIZONTAL DUCT RUNS SHALL BE SUPPORTED AT NOT MORE THAN 4 FEET (1219 MM) INTERVALS.
3.VERTICAL RISERS SHALL BE SUPPORTED AT NOT MORE THAN 6 FEET (1829 MM) INTERVALS.
4.SAG BETWEEN SUPPORT HANGERS SHALL NOT EXCEED 1/2 INCH (12.7 MM) PER FOOT (305 MM) OF SUPPORT SPACING.
5.SUPPORTS SHALL BE RIGID AND SHALL BE NOT LESS THAN 11/2 INCHES (38 MM) WIDE AT POINT OF CONTACT WITH THE DUCT SURFACE.
6.DUCT BENDS SHALL BE NOT LESS THAN ONE DUCT DIAMETER BEND RADIUS.
7.SCREWS SHALL NOT PENETRATE THE INNER LINER OF NON-METALLIC FLEXIBLE DUCTS UNLESS PERMITTED IN ACCORDANCE WITH THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
8.FITTINGS FOR ATTACHING NON-METALLIC DUCTS SHALL BE BEADED AND HAVE A COLLAR LENGTH OF NOT LESS THAN 2 INCHES (51 MM) FOR
ATTACHING THE DUCT.
EXCEPTION: A BEAD SHALL NOT BE REQUIRED WHERE METAL WORM-GEAR CLAMPS ARE USED OR WHERE ATTACHING METALLIC DUCTS USING SCREWS IN
ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
9.DUCT INNER LINER SHALL BE INSTALLED AT NOT LESS THAN 1 INCH (25.4 MM) ON THE COLLAR AND PAST THE BEAD PRIOR TO THE APPLICATION OF THE
TAPE AND MECHANICAL FASTENER. WHERE MASTIC IS USED INSTEAD OF TAPE, THE MASTIC SHALL BE APPLIED IN ACCORDANCE THE MASTIC
MANUFACTURER'S INSTRUCTIONS.
10.DUCT OUTER VAPOR BARRIERS SHALL BE SECURED USING TWO WRAPS OF APPROVED TAPE. A MECHANICAL FASTENER SHALL BE PERMITTED TO BE
USED IN PLACE OF, OR IN COMBINATION WITH, THE TAPE.
11.FLEXIBLE AIR DUCTS SHALL NOT PENETRATE A FIRE-RESISTANCE-RATED ASSEMBLY OR CONSTRUCTION.
12.THE TEMPERATURE OF THE AIR TO BE CONVEYED IN A FLEXIBLE AIR DUCT SHALL NOT EXCEED 250°F (121 °C).
13.FLEXIBLE AIR DUCTS SHALL BE SEALED IN ACCORDANCE WITH SECTION 603.10.
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
M0.01
MECHANICAL CODE
CHECKING.
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
GENERAL NOTES:
1.MECHANICAL CONTRACTOR TO COORDINATE ROUTING AND LOCATION OF
MECHANICAL COMPONENTS AND EQUIPMENT WITH ALL OTHER TRADES AND
EXISTING FIELD CONDITIONS PRIOR TO PERFORMING WORK.
2.CONTRACTOR TO CUT AND PATCH AS REQUIRED TO PERFORM THE WORK.
3.ACCESS DOORS ARE REQUIRED FOR ANY COMPONENT REQUIRING ACCESS
ABOVE HARD LID CEILINGS. COORDINATE SIZE, LOCATION AND FINISH WITH
ARCHITECT PRIOR TO PERFORMING WORK.
4.REFER TO THE DIAGRAMS THAT APPLY TO THIS SHEET WHICH PROVIDE
GENERAL GUIDANCE FOR INSTALLATION THOUGH NOT ALL COMPONENTS
AND ACCESSORIES MAY BE SHOWN.
5.PRIOR TO INSTALLATION, CONFIRM SPECIFIC LOCATION FOR ALL
THERMOSTATS / SENSORS WITH ARCHITECT. MOUNT AT 48" A.F.F. OR IN
ACCORDANCE WITH ADA REQUIREMENTS. PROVIDE LOCKING COVERS.
6.COORDINATE AND CONFIRM BORDER, FRAME, FINISH, AND LOCATION WITH
ARCHITECT PRIOR TO ORDERING.
7.ANY PENETRATIONS THROUGH WALL STUDS, FLOOR JOISTS, OR ROOF TO
BE IN ACCORDANCE WITH THE LATEST ADOPTED BUILDING CODE.
8.DUCT DIMENSIONS SHOWN ARE CLEAR INSIDE DIMENSIONS.
9.CONTRACTOR TO CONFIRM ADEQUATE RETURN AIR PATH BACK TO MAIN
AIR HANDLING UNIT.
IM
CUBE
IM
CUBE
(E) ELEVATOR
N.I.C
(E) STOCKROOM
WALL SHELF
WALL SHELF
PO
S
C
O
U
N
T
E
R
@
3
4
"
A
F
F
HIGH COUNTER
DISPLAY TABLE-B
DISPLAY TABLE-B
DISPLAY TABLE-A
(N) ADA
RESTROOM
(E) RESTROOM EQUIPMENT
C4
C5
5
4
TESTER TABLE
F E
(N) FULL-HEIGHT WALL
(E) SALES AREASI
G
N
(E) CORRIDOR
(E) WATER HEATER
(E) WATER COOLER
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T
TESTER TABLE
HIGH COUNTER
C4
THE WHOLE MECHANICAL SYSTEM (DUCTS,
DIFFUSERS, FANS AND AHU) IS EXISTING TO REMAIN
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
M1.01
MECH. LAYOUTS AND
EQUIPMENT SCHEDULE.
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
DUCT
SUPPLY
BUTTERFLY DAMPER
IN BRANCH DUCT
WRAP INSULATION
SUSPENDED CEILING
2" EXTERNAL
BAND SUPPORT
ROOF STRUCTURE
TIE OFF TO
METAL
EXTERNAL INSULATION
MAX. LENGTH 5'-0"
FLEX DUCT WITH MIN R-5
DIFFUSER W/ROUND
LAY-IN SUPPLY AIR
NECK & O.B.D.
8M) WITH EXTERNAL INSULATION
MAXIMUM 5' LENGTH
MEDIUM PRESSURE, ACOUSTICAL
INSULATION
FLEX DUCT (EQUAL TO FLEX MASTER
HIGH EFFICIENCY
SPIN-IN TAP
SUPPLY AIR DIFFUSER CONNECTION
30/12
18/12 12/12 30/12
18/12
% GAS SAFETY
TRANSITIONDIFFUSERTRANSITIONDIFFUSER
MAIN BRANCH TAKE-OFFS
SPLITTER DAMPER
30/12 18 12
16/12 20/12
30/12 18/12
20/1216/12
RISERS
36/24
RISE
36 24
24/36 DN D = DROP
R = RISE R
36/24
24/36 DN
36/24
SIDEWALL REGISTERS
36/12 24/12
GRILLE
SIDEWALLSIDEWALL GRILLE
24/12
AIR EXTRACTOR
36/12
DUCT CROSSOVERS
UNDERNEATH
THIS DUCT RUNTURNING VANES
ELBOW WITHTHIS DUCT RUNS
UNDERNEATH
SUB-BRANCH TAP AND TEE
18/12
12/8
30/1212/8
12/8
18/12
18/1230/12
EXTERIOR WALL CONSTRUCTION
WITH INSULATION
METAL OR WOOD STUDS
AIR FLOW REFRIGERANT LINES
PLASTIC WALL SLEEVE WITH
CHROME ESCUTCHEONCLEARANCE AROUND
MAINTAIN SERVICE
UNIT
CONDENSING UNIT
AIR COOLED
SIGHT GLASS
REFRIGERANT VALVE
FILTER DRYER
(TYPICAL)
NEOPRENE PAD
HOUSEKEEPING PAD
4" THICK CONCRETE
OUTSIDE AIR CONDITIONER
CEILING EXHAUST FAN DETAIL
IN-LINE FAN DETAIL
CEILING
EXHAUST
GRILLE
GASKETED
ACCESS
PANEL
FLEXIBLE CONNECTION
MOUNT FAN FROM
STRUCTURE ABOVE WITH
THREADED RODS. PROVIDE
NEOPRENE VIBRATION
ISOLATORS.
BACKDRAFT
DAMPER
FLEXIBLE
CONNECTION
RECTANGULAR OR
ROUND DUCTWORK
AS SPECIFIED ON
PLANS
ABOVE WITH THREADED RODS.
MOUNT FAN FROM STRUCTURE
PROVIDE NEOPRENE VIBRATION
ISOLATORS.
DUCTWORK
BACKDRAFT
DAMPER
MECHANICAL CONTRACTOR SHALL EXAMINE ALL OTHER
SPECIFICATIONS, DRAWINGS AND ALL FEATURES OF BUILDING
CONSTRUCTION WHICH MAY AFFECT HIS WORK AND SHALL B
GOVERNED BY THESE AND OTHER SPECIFICATIONS, INCLUDIN THE
GENERAL CONDITIONS AND PARTICULAR INSTRUCTIONS T ALL
BIDDER AND SUPPLIERS
ALL WORK SHALL BE EXECUTED AND INSPECTED IN STRICT
ACCORDANCE WITH ALL LOCAL CODES AND/OR STATE CODES,
LAWS, ORDINANCES, RULES AND REGULATIONS APPLICABLE TO
THIS PARTICULAR CLASS OF WORK, AND EACH CONTRACTOR
SHALL INCLUDE IN HIS PRICE ALL APPLICABLE SERVICE CHARGES,
FEES, PERMITS, TAXES, AND OTHER SIMILAR COSTS IN
CONNECTION THEREWITH
PRIOR TO FABRICATION OF DUCTWORK, THE MECHANICAL
CONTRACTOR SHALL EXAMINE AND VERIFY ALL CONDITIONS
ABOVE AND BELOW THE CEILING WHICH MAY INTERFERE WITH THE
DUCT SYSTEM AND NOTIFY THE ARCHITECT OF ANY CONFLICT
ENCOUNTERED CONTRACTOR SHALL PROVIDE ALL OFFSETS, ETC
WHICH MAY BE REQUIRED, WITHOUT ADDITIONAL COST TO THE
OWNER
ALL SHEET METAL DUCT CONSTRUCTION SHALL BE IN STRICT
ACCORDANCE WITH "SMACNA" LOW PRESSURE DUCT
CONSTRUCTION STANDARD
TURNING VANES SHALL BE INSTALLED IN ALL BENDS IN
RECTANGULAR DUCT EXCEEDING 30"
ALL DUCTS SHALL BE SUPPORTED WITH 1"WIDE, 16 GAUGE,
GALVANIZED STEEL BANDS
ALL RECTANGULAR DUCT SHALL BE INSULATED WITH A MIN OF
1"INTERNAL LINER, 2 LBS DENSITY R-60 ALL ROUND DUCTS AND
DIFFUSER TOPS SHALL HAVE A MIN 2" THICK OF FOIL BACKED
BLANKET TYPE INSULATION R=4-4 2, WITH ALL JOINTS BUTTED AND
TAPED
ALL DUCT DIMENSIONS SHOWN ON PLANS ARE INTERNAL
THE MECHANICAL CONTRACTOR SHALL COORDINATE THE
LOCATION OF SUPPLY AND RETURN AIR REGISTERS, DUCTS,
GRILLES AND DIFFUSERS WITH LIGHTING AND CEILING PATTERNS
PROVIDE LATERAL BRACING OF ALL DUCTS AND PIPES AS
REQUIRED BY CODE
INSULATE AND SEAL ALL DUCTWORK PER CHAPTER 10 OF THE
STATE MECHANICAL CODE (T-24, PART 4)
MOUNT ALL THERMOSTATS AT 48" ABOVE FINISHED FLOOR
ALL BRACING OF DUCTS AND PIPING SHALL BE INSTALLED IN
ACCORDANCE WITH SMACNA GUIDELINES
WHERE BRACING DETAILS ARE NOT SHOWN ON THE DRAWINGS
OR IN THE GUIDELINES, THE FIELD INSTALLATION SHALL BE SUBJECT
TO THE APPROVAL OF THE ARCHITECT AND THE MECHANICAL
ENGINEER
DUCT SMOKE DETECTOR SHALL BE INSTALLED BELOW THE ROOF
ALL MECHANICAL EQUIPMENT AND SYSTEMS INSTALLED AS PART
OF PROJECT SHALL COMPLY WITH ALL REQUIREMENTS OF THE
2013 CALIFORNIA MECHANICAL CODE AND THE 2013
CALIFORNIA BUILDINGCODE AND THE 2013 CALIFORNIA
BUILDING ENERGY EFFICIENCY STANDARDS
OUTSIDE AIR FOR A HEATING OR COOLING SYSTEM SHALL NOT BE
TAKEN FROM CLOSER THAN 10 FEET FROM AN APPLIANCE VENT
OUTLET, VENT OPENING OF A PLUMBING SYSTEM, OR THE
DISCHARGE OUTLET OF EXHAUST FAN, UNLESS THE OUTLET IS 3 FT
ABOVE THE OUTSIDE AIR INLET (CMC 314 3)
PROVIDE 120 VOLT ELECTRICAL OUTLETS WITHIN 25 FT OF ALL
MECH EQUIPT (CMC 309)
HEATING,VENTILATING,ANDAIR CONDITIONING SYSTEMS SHALL BE
BALANCED IN ACCORDANCE WITH ONE OF THE FOLLOWING
METHODS IN ACCORDANCE WITH CMC 317 1 REQUIREMENTS
AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE
ACCA MANUAL B
ASHRAE 111
NEBB PROCEDURAL STANDARDS FOR TESTING,ADJUSTING
ADJUSTING BALANCING OF ENVIRONMENTAL SYSTEMS
SMACNA HVAC TESTING,ADJUSTING,AND BALANCING
MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL BE NON
COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX NOT TO
EXCEED 25 AND A SMOKE DEVELOPED INDEX NOT TO EXCEED 50
WHERE TESTED AS A COMPOSITE PRODUCT IN ACCORDANCE
WITH ASTM E84 OR UL 723
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
M2.01
MECHANICAL GENERAL
DETAILS
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
INSTALLATION
RECEPTACLES
HEIGHTS:
h1: 18 in
h2: 42 in
h3: 48 in
h4: 60 in
h5: 84 in
h6: 94 in
1.ELECTRICAL GENERAL NOTES 2. ELECTRICAL POWER NOTES
3. NETWORK CABLING REQUIREMENTS
4. GENERAL FIRE ALARM NOTES
5.ELECTRICAL ABBREVIATIONS:
A.ALL REQUIRED DOCUMENTATION REGARDING THE DESIGN OF FIRE
DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS AND THE
PROCEDURES FOR MAINTENANCE, INSPECTION, AND TESTING OF
FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS SHALL BE
MAINTAINED AT AN APPROVED, SECURED LOCATION FOR THE LIFE
OF THE SYSTEM PER IFC 901.6.2.1.
B.THE FIRE ALARM CONTROL PANEL DISCONNECTING MEANS SHALL
HAVE A RED MARKING, SHALL ONLY BE ACCESSIBLE TO AUTHORIZED
PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT".
THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE
IDENTIFIED AT THE FIRE ALARM CONTROL UNIT PER NFPA 72
4.4.1.4.2.2 AND 4.4.1.4.2.3.
C.ROUTE ALL CONDUIT TIGHT TO DECK IN ACCORDANCE TO NEC
300.4(E)
D.FIRE ALARM SYSTEM SHALL BE INSTALLED PER CURRENT NFPA
STANDARDS.
E.ALL ELECTRICAL THAT MAY NEED TO BE MAINTAINED WHILE
ENERGIZED SHALL BE FIELD MARKED WITH ARC FLASH LABELING
AND BE FULLY VISIBLE TO QUALIFIED PERSONNEL PRIOR TO
EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF
EQUIPMENT.
F.SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH
THE MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKINGS
SHALL INCLUDE THE DATE THE FAULT CURRENT CALCULATIONS
WERE PERFORMED AND BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE ENVIRONMENT INVOLVED.
G.FIRE ALARM DEVICE LOCATIONS ARE SHOWN FOR REFERENCE ONLY.
THE ELECTRICAL CONTRACTOR SHALL INCLUDE A PRICE IN THE
ELECTRICAL BID FOR A LANDLORD APPROVED FIRE ALARM SYSTEM,
INCLUDING PLANS AND ALL ASSOCIATED DOCUMENTATION
REQUIRED. THESE PLANS SHALL BE SUBMITTED TO THE LOCAL
AUTHORITIES HAVING JURISDICTION BY A QUALIFIED AND LICENSED
DESIGN-BUILD FIRE ALARM CONTRACTOR FOR A COMPLETE AND
APPROVED FIRE ALARM SYSTEM. THE PLANS SHALL BE SIGNED AND
SEALED BY THEIR LOCAL DESIGN ENGINEER AND SUBMITTED FOR
PLAN REVIEW PRIOR TO RECEIVING SPECIFIC PERMITS FOR THIS
WORK. THE FIRE ALARM CONTRACTOR SHALL ALSO SUBMIT ALL
SHOP DRAWINGS, BATTERY CALCULATIONS, SPECIFICATION SHEETS,
ETC. AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION TO
THEIR LOCAL DESIGN ENGINEER FOR REVIEW AND APPROVAL.
H.COORDINATE WITH MECHANICAL INSTALLER TO PROVIDE AND
INSTALL CONDUIT AND JUNCTION BOXES FOR MECHANICAL
THERMOSTATS.
A.EACH CAT 5 CABLE RUN MUST BE KEPT TO A MAXIMUM OF 295 FEET
(90 METERS). INCLUDING PATCH CORDS, ENTIRE CHANNEL MAXIMUM
LENGTH NOT TO EXCEED 328 FEET (100 METERS).
B.MAINTAIN PAIR TWISTING AS CLOSE AS POSSIBLE TO FINAL
TERMINATION POINTS WITH MAXIMUM UNTWISTED SEGMENT OF 1/2".
C.WHERE NECESSARY, GRADUALLY BEND CABLE TO MAINTAIN THE
MINIMUM BEND RADIUS OF 4 TIMES THE CABLE DIAMETER (APPROX.
1").
D.USE LOW TO MODERATE PRESSURE TO DRESS CABLES NEATLY
WITH CABLE TIES.
E.USE LOW TO MODERATE FORCE WHEN PULLING CABLE. DO NOT
EXCEED MAXIMUM OF 25 POUNDS OF FORCE.
F.USE CABLE PULLING LUBRICANT FOR CABLE RUNS THAT MAY
EXCEED 25 POUNDS OF FORCE WHEN PULLING.
G.MAINTAIN 12" OF SEPARATION FROM POWER CABLES THAT MAY BE
SOURCES OF EMI (ELECTRICAL CABLES, TRANSFORMERS, LIGHT
FIXTURES, ETC.)
H.INSTALL PROPER CABLE SUPPORTS WITH MAXIMUM OF 5 FEET OF
SEPARATION.
I.LEAVE EXCESS WIRE COILED IN THE CEILING OR NEAREST
CONCEALED SPACE. MAINTAIN 5 FEET OF SLACK AT WORK OUTLET
AND 10 FEET OF SLACK AT PATCH PANEL END.
J.FURNISH AND INSTALL GROMMETS WHEN PASSING THROUGH METAL
STUDS AND OTHER POTENTIAL HAZARDS.
K.CONTRACTOR IS RESPONSIBLE FOR MEETING BOTH NATIONAL FIRE
AND BUILDING CODES AND ANY LOCAL AMENDMENTS BY THE
AUTHORITIES HAVING JURISDICTION AND MAINTAIN FIRESTOPS AT
ALL CABLES THAT PENETRATE FIREWALLS. PLENUM RATED CABLES
SHALL BE INSTALLED WHERE REQUIRED.
L.DO NOT SPLICE OR BRIDGE CABLE AT ANY POINT.
M.DO NOT INSTALL CABLE SUPPORTED FROM CEILING TILES.
N.DO NOT OVER TIGHTEN (25 POUNDS PER SQUARE INCH MAXIMUM)
WITH USING CABLE OR PLASTIC TIES.
O.DO NOT USE OIL OR OTHER LUBRICANT NOT SPECIFICALLY
DESIGNED FOR NETWORK CABLE PULLING.
P.DO NOT SUPPORT CABLES DIRECTLY FROM ELECTRICAL CONDUITS
OR FIXTURES
A.GC SHALL VERIFY ANY THIRD PARTY INSPECTIONS REQUIRED BY
LOCAL AUTHORITY HAVING JURISDICTION PRIOR TO BIDDING THIS
PROJECT.
B.ALL LOW VOLTAGE WIRING TO BE IN CONDUIT UNLESS APPROVED
OTHERWISE BY AUTHORITY HAVING JURISDICTION.
C.ALL EMERGENCY LIGHTS & EXIT SIGNS ARE TO BE CONNECTED TO
THE UNSWITCHED PORTION OF THE ADJACENT LIGHTING CIRCUIT. ALL
EMERGENCY FIXTURES TO REMAIN ACTIVE FOR 90 MINUTE MINIMUM.
D.ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT
SHALL BE LABELED AND LISTED BY A CERTIFIED TESTING
LABORATORY OR AGENCY.
E.ALL LIGHTING, DUCTWORK, SOFFITS, AND CEILING COMPONENT
HEIGHTS ARE TO BE COORDINATED WITH THE ARCHITECT.
F.ATTENTION LIGHTING SUPPLIER AND CONTRACTOR: ENSURE ALL
LIGHTING EXPOSED TO PLENUM IS PLENUM RATED.
G.COORDINATE THE MOUNTING OF ALL HIGH-BAY FIXTURES AND
CEILING FANS WITH ARCHITECT PRIOR TO INSTALLATION.
H.. VERIFY MOUNTING HEIGHTS OF ALL FIXTURES WITH ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN.
I.FIRE ALARM CONTRACTOR SHALL VERIFY ALL BUILDING AND FIRE
DEPARTMENT REQUIREMENTS REGARDING SHUT OFF OF ANY
NECESSARY COMPONENTS UPON ACTIVATION OF THE FIRE ALARM.
THIS INCLUDES, BUT IS NOT LIMITED TO:
a.AUDIO/MUSIC SYSTEM(S)
b.ROOFTOP UNITS
c.TANNING EQUIPMENT
d.EXERCISE FANS
J.PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE
PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, ISOLATED
GROUND CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE
SIZED PER NEC BASED ON THIN 600 VOLT COPPER SINGLE
CONDUCTORS, PLUS THE EQUIPMENT GROUNDING CONDUCTOR.
K.WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN
CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS.
L.CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
PANELBOARD IDENTIFICATION SCHEDULES.
M.BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS
NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH CIRCUITS
HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE SHALL BE USED
FOR THE FINAL CONNECTION (15 FOOT MAXIMUM).
N.WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND DERATE
CURRENT CARRYING CONDUCTORS PER NEC.
O.PROVIDE HANDLE TIES ON ALL MULTIWIRE BRANCH CIRCUITS TO
MEET NEC REQUIREMENTS.
P.SUPPORT FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE SHALL
BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE ONLY THE
TOP AND BOTTOM CHORDS FOR SUPPORTING THE ELECTRICAL
SYSTEM INSTALLATIONS. REFER TO STRUCTURAL PLANS.
Q.WHERE GROUPED CONDUITS ARE INSTALLED WITHIN THE JOIST
SPACE, COORDINATE WITH SPRINKLER CONTRACTOR PRIOR TO
INSTALLATION IN ORDER TO MAINTAIN REQUIRED CLEARANCES FROM
SPRINKLERS.
R.SEAL PENETRATIONS IN FIRE RATED WALLS PER NEC 300.21.
S.ELECTRICAL EQUIPMENT, FIXTURES, DEVICES, AND OTHER ITEMS
SHOWN IN THESE PLANS IN GREY HALFTONE ARE EITHER EXISTING TO
REMAIN OR PART OF LANDLORD SHELL PACKAGE.
T.PROVIDE ARC-FLASH COORDINATION STUDY PER NEC.
U.PROVIDE (1) 1/2" CONDUIT AND (1) 4" SQUARE BOX WITH SINGLE GANG
DEVICE RING FOR ALL THERMOSTAT LOCATIONS INDICATED ON
MECHANICAL DRAWINGS. ROUTE CONDUIT FROM BOX TO ACCESSIBLE
CEILING CAVITY. PROVIDE PLASTIC BUSHING ON EXPOSED CONDUIT
ENDS. PROVIDE PULL STRING IN ALL EMPTY CONDUIT SYSTEMS.
COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHTS WITH
MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
V.ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE LOW
VOLTAGE CONTRACTOR TO CLARIFY SCOPE OF WORK BEFORE BID OR
INSTALLATION
W.WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED
FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON
PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH
MASONRY:
a.SWITCHES 48" AFF
b.RECEPTACLES 18" AFF
c.VOICE/DATA 18" AFF
ABC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
CF CEILING FAN
CP CIRCULATING PUMP
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
EDF ELECTRIC DRINKING FOUNTAIN
EF EXHAUST FAN
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPT
GR GROUND
HC HVAC CONTRACTOR
JB JUNCTION BOX
PC PLUMBING CONTRACTOR
TTB TELEPHONE TERMINATION BOARD
UC UNDERCOUNTER
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VIF VERIFY IN FIELD
WH WATER HEATER
WP WEATHER PROOF DEVICE
WR WEATHER RESISTANT DEVICE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
A.THE INTENT OF THE FIRE ALARM SYSTEM DEVICES INDICATED ON
THIS DRAWING ARE FOR PERFORMANCE SPECIFICATIONS AND
LOCATIONS ONLY. THE SUCCESSFUL FIRE ALARM SYSTEM
CONTRACTOR SHALL PROVIDE COMPLETE PERMIT DRAWINGS,
INCLUDING WIRING MEANS AND METHODS, BATTERY
CALCULATIONS, DEVICE CUT SHEETS, ETC. FOR THE EQUIPMENT
THEY SHALL PROVIDE. PROVIDE 15% SPARE CAPACITY FOR NEW
SYSTEMS. COORDINATE FINAL REQUIREMENTS WITH ALL
AUTHORITIES HAVING JURISDICTION.
B.THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL LISTED
CENTRAL STATION.
C.FIRE ALARM CONTRACTOR SHALL SUBMIT FIRE ALARM
SUBMITTALS TO THE OWNER'S REPRESENTATIVE WITHIN 30 DAYS
AFTER CONTRACT IS AWARDED.
D.WALL MOUNTED DEVICES SHALL BE 80" AFF TO BOTTOM OF DEVICE
UNLESS NOTED OTHERWISE.
E.SURFACE MOUNTING OF FIRE ALARM CONDUIT IS NOT PERMITTED
IN FINISHED AREAS.
F.BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC SPRINKLER
SYSTEM.
G.REMOVE ALL EXISTING FIRE ALARM SYSTEMS FROM PREVIOUS
TENANTS PRIOR TO INSTALLING NEW EQUIPMENT.
H.ALL REQUIRED DOCUMENTATION REGARDING THE DESIGN OF FIRE
DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS AND THE
PROCEDURES FOR MAINTENANCE, INSPECTION, AND TESTING OF
FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS SHALL
BE MAINTAINED AT AN APPROVED, SECURED LOCATION FOR THE
LIFE OF THE SYSTEM PER IFC 901.6.2.1.
I.THE FIRE ALARM CONTROL PANEL DISCONNECTING MEANS SHALL
HAVE A RED MARKING, SHALL ONLY BE ACCESSIBLE TO
AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE
ALARM CIRCUIT". THE LOCATION OF THE CIRCUIT DISCONNECTING
MEANS SHALL BE IDENTIFIED AT THE FIRE ALARM CONTROL UNIT
PER NFPA 72 4.4.1.4.2.2 AND 4.4.1.4.2.3.
J.ROUTE ALL CONDUIT TIGHT TO DECK IN ACCORDANCE WITH NEC
300.4(E).
K.FIRE ALARM SYSTEMS SHALL BE INSTALLED PER CURRENT NFPA
STANDARDS.FIRE ALARM DEVICE LOCATIONS ARE SHOWN FOR
REFERENCE ONLY. THE ELECTRICAL CONTRACTOR SHALL INCLUDE
A PRICE IN THE ELECTRICAL BID FOR A LANDLORD APPROVED FIRE
ALARM SYSTEM, INCLUDING PLANS AND ALL ASSOCIATED
DOCUMENTATION REQUIRED. THESE PLANS SHALL BE SUBMITTED
TO THE LOCAL AUTHORITIES HAVING JURISDICTION BY A
QUALIFIED AND LICENSED DESIGN-BUILD FIRE ALARM
CONTRACTOR FOR A COMPLETE AND APPROVED FIRE ALARM
SYSTEM. THE PLANS SHALL BE SIGNED AND SEALED BY THEIR
LOCAL DESIGN ENGINEER AND SUBMITTED FOR PLAN REVIEW
PRIOR TO RECEIVING SPECIFIC PERMITS FOR THIS WORK. THE
FIRE ALARM CONTRACTOR SHALL ALSO SUBMIT ALL SHOP
DRAWINGS, BATTERY CALCULATIONS, SPECIFICATION SHEETS,
ETC. AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION TO
THEIR LOCAL DESIGN ENGINEER FOR REVIEW AND APPROVAL.
ELECTRICAL SPECIFICATIONS
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
SCOPE OF WORK:
ELECTRICAL
LIGHTING AND
POWER DESIGN
MAISON KOSE
E0.00
ELECTRICAL
SPECIFICATIONS
SCOPE OF WORK:
ALL MECHANICAL LOADS ARE REMAIN
EXISTING.
TI FOR THE LIGHTING AND POWER
1.DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK.
2.WHEREVER THE WORD "PROVIDE" IS USED, IT SHALL MEAN TO "PROVIDE AND INSTALL".
3.FINAL CONCECTIONS TO EQUIPMENT SHALL BE PER MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS AND INSTRUCTIONS. IT
SHALL BE
THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED.
4.IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO ESTABLISH A STANDARD OF QUALITY. THE ENGINEER RESERVES THE RIGHT
TO APPROVE METHODS AND MATERIALS NOT REFLECTED HEREIN.
5.CONTRACTOR SHALL REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER RELATED DRAWINGS PRIOR TO BID.
6.CONTRACTOR SHALL VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED IN THE CONTRACT DOCUMENTS.
CONTRACTOR
SHALL INCLUDE IN HIS BID, ANY COSTS REQUIRED TO MAKE HIS WORK MEET THE CONTRACT SCOPE UTILIZING EXISTING CONDITIONS.
7.WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
8.WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE AND NATIONAL CODES AND ORDINANCES.
9.PROVIDE PERMITS AND INSPECTIONS REQUIRED.
10.GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A
PERIOD
OF ONE YEAR AFTER OWNER'S ACCEPTANCE, DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
11.PROVIDE RECORD DRAWINGS TO ENGINEER. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS,
REROUTINGS, ETC.
12.VERIFY SPECIFIC LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
13.ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE
CORRECTIONS CECESSARY AT NO COST TO OWNER.
14.RECESSED LIGHT FIXTURES INSTALLED IN GYP. BOARD OR PLASTER CEILINGS SHALL HAVE PLASTER FRAMES INSTALLED PRIOR TO CEILING
MATERIAL.
15.RECESSED FIXTURES INSTALLED INDOORS SHALL BE THERMALLY PROTECTED.
16.SEE DIVISION 15 DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO AND CONCECT EQUIPMENT AS REQUIRED.
17.PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS.
18.ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY.
19.WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS
SHALL BE LISTED AS SUITABLE FOR 75 DEGREE C.
20.THE FOLLOWING CONDUCTOR SIZES SHALL BE UTILIZED FOR 20 AMP CIRCUITS PERTAINING TO DISTANCES (IN FEET) INDICATED:
120VOLT, 1PH CONDUCTOR 240 VOLT, (1PH)
0-64 #12AWG 0-129
65--106 #10AWG 130-212
107-160 #8AWG 213-321
NOTE: BASED ON 75°c COPPER CONDUCTORS INSTALLED IN EMT WITH 16AMP LOAD @ 85% P.F.
21.CONTRACTOR SHALL REVIEW ARCHITECTURAL, STRUCTURAL AND MECHANICAL DRAWINGS AND SHALL PROVIDE LIGHTS, SWITCHES,
RECEPTACLES,
EQUIPMENT CONCECTIONS, ETC., AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS, EVEN IF SUCH AREAS ARE NOT SHOWN ON
ELECTRICAL DRAWINGS. LAYOUTS, FIXTURE TYPES, QUANTITIES AND SPACING SHALL BE IN ACCORDANCE WITH SIMILAR AREAS ON THIS
PROJECT.
CONTRACTOR SHALL INCLUDE COSTS FOR THE ABOVE IN HIS BID. IN ADDITION, CONTRACTOR SHALL PROVIDE LAYOUT DRAWINGS FOR
WORK IN SUCH AREAS AND SUBMIT FOR APPROVAL PRIOR TO ROUGH-IN.
22.WIRE SHALL BE COPPER, 75 DEGREES C RATED FOR GENERAL USE, FOR WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL
BE
COPPER, MINIMUM 90 DEGREES C RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREES C AMBIENT. CONDUCTOR
AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS. 600 VOLT COMPACT ALUMINUM WIRE AND CABLE IN SIZES 1/0 AND
LARGER
MAY BE SUBSTITUTED FOR COPPER ON SERVICES AND FEEDERS IF AMPACITY IS EQUIVALENT TO OR GREATER
23.CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED
UNDER THIS SECTION OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.
24.CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO
SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT OR INSTALLATION METHODS.
25.ELECTRICAL SYSTEMS SHALL BE COMPLETE, OPERABLE AND READY FOR CONTINUOUS OPERATION AT COMPLETION OF PROJECT.
26.RECEPTACLES WHICH ARE SHOWN WALL MOUNTED ON THE ELECTRICAL DRAWINGS ON WALLS WHICH, ON THE ARCHITECTURAL DRAWINGS
AND ELEVATIONS ARE SHOWN AS GLASS OR PARTITIONS, SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES MOUNTED ADJACENT TO BAS OR
WALLS.
27.RECEPTACLES AT COUNTER SHALL BE MOUNTED WITH THEIR LONG AXIS HORIZONTAL AT +46" UNLESS NOTED.
28.FLUSH FLOOR RECEPTACLE OUTLETS SHALL BE WIREMOLD 862 SERIES. PROVIDE CARPET OR TILE FLANGE TO MATCH FLOOR FINISH.
29.THE COLOR OF THE DEVICES AND COVER PLATES SHALL BE AS DIRECTED BY ARCHITECT. IN DAMP OR WET LOCATIONS COVER PLATES
SHALL BE STAINLESS STEEL. IN DRY LOCATIONS COVER PLATES SHALL BE SMOOTH HIGH ABUSE NYLON OR EQUIVALENT. PROVIDE COVER
PLATES FOR SWITCHES, RECEPTACLES, TELEPHONE, TELEVISION, COMPUTER AND J-BOX OUTLETS AS REQUIRED.
30.ROMEX CABLE WITH A GROUNDING CONDUCTOR MAY BE USED WHERE PERMITTED BY BOTH THE N.E.C. AND LOCAL ORDINANCES.
31.DISCONCECT SWITCHES SHALL BE GENERAL DUTY TYPE. FUSIBLE SWITCHES SHALL ACCEPT CLASS 'R' FUSES ONLY AND REJECT ALL
OTHERS.
32.FINAL CONCECTIONS TO VIBRATING EQUIPMENT SHALL BE WITH FLEX (LIQUIDTIGHT FOR EXTERIOR APPLICATIONS) AND APPROVED
FITTINGS. DO NOT SECURE CONDUITS, DISCONCECTS OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT.
33.THE ENGINEER OF RECORD HAS PERFORMED SHORT CIRCUIT CALCULATIONS AND THE AIC RATINGS INDICATED FOR EACH DEVICE IS
ADEQUATE TO PROTECT THE EQUIPMENT AND THE ELECTRICAL SYSTEM.
NOTES:
1. FIXTURES SHALL HAVE APPROPRIATE U.L. LABEL (i.e., DAMP OR WET) AS REQUIRED BY CODES AND ORDINANCES.
2. FIXTURES SHALL INCLUDE ALL ACCESSORIES CECESSARY FOR INSTALLATION ACCORDING TO MANUFACTURER'S SHOP DRAWINGS AND AS REQUIRED BY
CODES AND LOCAL ORDINANCES.
3. PRIOR TO ORDERING ANY LIGHTING EQUIPMENT, THE CONTRACTOR SHALL COORDINATE ALL FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED
CEILING PLANS AND CEILING CAVITY
DEPTHS.
4. ALL LAMPS SHALL BE PROVIDED AND INSTALLED ACCORDING TO THE ATTACHED FIXTURE SCHEDULE AND SPECIFICATIONS ENSURE COMPATIBILITY
BETWEEN FIXTURE, LAMP(S) AND
BALLAST(S). (OSRAM SYLVANIA SERIES)
5. CONTRACTOR SHALL VERIFY FIXTURE VOLTAGES AND CEILING TRIM COMPATIBILITY PRIOR TO ORDERING FIXTURE.
6. PROVIDE APPROVED FIRE-RATED ENCLOSURES FOR ALL LIGHTING FIXTURES LOCATED IN FIRE-RATED CEILINGS.
7. LIGHTING FIXTURE CATALOG NUMBERS ARE SERIES TYPE ONLY. PROVIDE ALL CECESSARY HARDWARE AS REQUIRED BY THE SPECIFICATIONS, DRAWINGS,
AND PROJECT CONDITIONS FOR A COMPLETE
INSTALLATION.
8. ALL FIXTURES SHALL BE ORDERED WITH APPROPRIATE BALLAST(S) THAT HAVE U.L. AND CB, LABELS. ALL BALLASTS MUST CONFORM TO TITLE 24 AND/OR
IECC REQUIREMENTS FOR
PERFORMANCE. PROVIDE MULTIPLE BALLASTS FOR DUAL LEVEL SWITCHING AND WIRING (i.e. TANDEM) AS INDICATED ON THE PLANS.
9. UPON INITIAL ENERGIZING OF ALL NEW FLUORESCENT LAMPS, A CONTINUOUS PERIOD OF 30 HOURS SHALL OCCUR PRIOR TO DE-ENERGIZING OF LAMPS
FOR MANUFACTURER REQUIRED
10. ALL FLUORESCENT BALLASTS SHALL BE ELECTRONIC TYPE. PROVIDE END OF LIFE (EOL) SHUT-DOWN PROTECTION FOR COMPACT FLUORESCENT LAMPS.
11. ENSURE COMPATIBILITY OF ALL LIGHTING SYSTEM COMPONENTS, ESPECIALLY DIMMED SYSTEMS. FIXTURES, LAMPS, BALLAST(S), AND DIMMING
SYSTEMS/INDIVIDUAL CONTROLS MUST BE FACTORY CERTIFIED
COMPATIBLE FOR FULL RANGE OF DIMMING COMPATIBILITY.
12. PROVIDE CLEARANCES FROM COMBUSTIBLES, A MINIMUM OF 3/4" (OTHER THAN AT POINTS OF SUPPORT) AND 3" FROM INSULATION FOR RECESSED
LIGHTING FIXTURES WHICH ARE NON-IC
RATED.
13. PROVIDE A MINIMUM OF TWO (2) #12 SUPPORT WIRES ATTACHED TO BUILDING FRAME IN ADDITION TO T-BAR CLIPS FOR FLUORESCENT FIXTURES
RECESSED IN SUSPENDED T-BAR CEILING.
14. FIXTURES WITH EMERGENCY BATTERY BACKUP SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHING IN COMPLIANCE WITH CEC ARTICLE 700.
15. EMERGENCY LIGHTING UNITS SHALL BE EQUIPPED WITH FACTORY-INSTALLED INTEGRAL TEST SWITCHES.
16. PROVIDE DOOR-TO-FRAME AND LENS-TO-DOOR GASKETING, INVERTED LENS, AND FOOD SERVICE RATING FOR ALL FIXTURES LOCATED IN FOOD
SERVICE AREAS.
17. FLUORESCENT LUMINARIES THAT UTILIZE DOUBLE-ENDED LAMPS AND CONTAIN BALLAST(S) THAT CAN BE SERVICED IN PLACE, OR BALLASTED LUMINAIRES
THAT ARE SUPPLIED FROM
MULTI- WIRE BRANCH CIRCUITS AND CONTAIN BALLAST(S) THAT CAN BE SERVICED IN PLACE, SHALL HAVE DISCONCECTING MEANS EITHER INTERNAL OR
EXTERNAL TO EACH LUMINAIRE SO TO DISCONCECT
SIMULTANEOUSLY FROM THE SOURCE OF SUPPLY ALL CONDUCTORS OF THE BALLAST (INCLUDING THE GROUNDED CONDUCTOR IF ANY). IN
ACCORDANCE WITH CEC ARTICLE 410, THE LINE-SIDE TERMINALS OF
THE DISCONCECTING MEANS SHALL BE LOCATED SO AS TO BE ACCESSIBLE TO QUALIFIED PENSIONS BEFORE SERVICING OR MAINTAINING THE BALLAST.
18. ALL FLUORESCHENT LAMPS SHALL BE OF A LOW MERCURY DESIGN, HAVE A MINIMUM CRI RATING OF 85 AND 3500K COLOR TEMPERATURE UNLESS
NOTED OTHERWISE.
1.THE ENGINEER OF RECORD HAS PERFORMED VOLTAGE DROP CALCULATIONS AND ALL BRANCH CIRCUITS AND FEEDERS COMPLY WITH CEC
210-19(A) FPN NO4.
2.THE CONTRACTOR SHALL PROVIDE 120V CONCECTION TO NEAREST MAINTENANCE RECEPTACLE WHERE REQUIRED FOR CONDENSATE
PUMPS ASSOCIATED WITH FAN COIL UNITS. COORDINATE WITH MECHANICAL CONTRACTOR.
3.THE CONTRACTOR SHALL COORDINATE THE SPECIFIC LOCATION, MOUNTING HEIGHT, ROTATION, TYPE, COLOR, ETC. OF ALL DEVICES PRIOR
TO INSTALLATION.
4.CONCECTIONS TO HYDROMASSAGE BATHTUBS, JACCUZZI TUBS OR SIMILAR EQUIPMENT SHALL BE MADE IN ACCORDANCE WITH ARTICLE
680.70 OF THE CEC. PROVIDE BONDING AS REQUIRED BY ARTICLE 680.74 OF THE CEC.
5.ALL INDOOR FLUORESCENT FIXTURES THAT UTILIZE DOUBLE-ENDED LAMPS AND CONTAIN BALLAST(S) THAT CAN BE SERVICED IN PLACE OR
BALLASTED LUMINARIES THAT ARE SUPPLIED FROM MULTIWIRE BRANCH CIRCUITS AND CONTAIN BALLAST(S) THAT CAN BE SERVICED IN
PLACE SHALL COMPLY WITH 410.73 (G) OF THE CEC.
6.CEILING MOUNTED SMOKE AND CARBON MONOXIDE DETECTORS PER NFPA 72, SECTION R314 MUST COMPLY WITH U.L. 2075 AND SHALL BE
INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS.
7.ALL SMOKE DETECTORS AND COMBINATION SMOKE/CARBON MONOXIDE DETECTORS SHALL BE HARDWIRED ON SAME CIRCUIT AND HAVE A
BATTERY BACKUP SYSTEM.
8.WHEN MORE THAN EITHER ONE (1) SMOKE ALARM OR MORE THAN ONE (1) CARBON MONOXIDE ALARM IS REQUIRED TO BE INSTALLED WITHIN
AN INDIVIDUAL DWELLING UNIT, ALL ALARM DEVICES SHALL BE INTERCONCECTED IN SUCH A MANNER THAT THE ACTUATION OF ONE ALARM
WITH ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL UNIT. SMOKE AND CARBON MONOXIDE ALARMS SHALL BE INSTALLED IN THE
FOLLOWING LOCATIONS. (IRC SECTION R3143 AS AMENDED)
A.SMOKE ALARMS IN EACH SLEEPING ROOM.
B.SMOKE ALARMS OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS.
C.SMOKE ALARMS ON EACH ADDITIONAL STORY OF THE DWELLING INCLUDING BASEMENTS BUT NOT INCLUDING CRAWL SPACE
AND UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR
BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT
LOWER LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL..
D.CARBON MONOXIDE ALARMS OUTSIDE OF SLEEPING AREAS IN THE IMMEDIATE VICINITY OF THE BEDROOMS IN DWELLING
UNITS WITHIN WHICH FUEL-FIRED APPLIANCES ARE INSTALLED AND IN DWELLING UNITS THAT HAVE ATTACHED GARAGES.
E.CARBON MONOXIDE ALARMS WITHIN EACH BEDROOM WHICH CONTAINS A FUEL-FIRED APPLIANCE.
43. ALL BRANCH CIRCUITS THAT SUPPLY 125-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN
DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. CEC ARTICLE 210.12 (A).
44.ALL ATTIC ACCESSES SHALL BE PROVIDED WITH A SWITCHED LIGHT AND 120 VOLT GFI OUTLET AT OR NEAR THE FORCED AIR UNIT. LOCATE
LIGHT SWITCH AT THE ATTIC ACCESS OPENING.
ELECTRICAL GENERAL NOTES
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
E0.01
ELECTRICAL GENERAL
NOTES
L-01
L-01
L-01
L-01
L-02 L-02
L-02
L-02L-02
L-02
L-02 L-02
L-02
L-02
L-02 L-02
L-02 L-02
L-02 L-02
L-02
LIGHT SWITCH - WALL MOUNTED @ +48" AFF UNLESS NOTED
SUBSCRIPTS:
2 = 2-POLE SWITCH
3 = 3 WAY SWITCH
4 = 4 WAY SWITCH
DM = DIMMER SWITCH
K = KEY OPERATED SWITCH
MD = COMBINED WITH OCCUPANCY SENSOR
P = SWITCH WITH PILOT LIGHT
T = THERMAL OVERLOAD SWITCH
OS = OCCUPANCY SENSOR SWITCH
L-01 RECESSED LIGHT 10W
EXIT WALL MOUNTED EXIT SIGN
EMERGENCY BATTERY UNIT WITH EMERGENCY LIGHT HEADS
LIGHTING SYMBOLS
L-02 SPOT LIGHT 15W
L-03 LINEAR LIGHT 25W
OS
OS
DS
DS
D
D
D
D
a
a a a a a a a
b
b
b
b
b
b
b
b
b
b
c
c
c c c c c c
d
d
d
d
d
EXIT
DAY LIGHT SENSOR
OS
LED LIGHT STRIP 3W/FT
D
e e
D
L-03
L-03
L-03
L-03L-03
L-03
L-01 L-01 L-01 L-01 L-01 L-01
L-01
L-01
L-01
L-01
L-01
L-01
L-01
L-01L-01L-01L-01L-01L-01L-01L-01
d
L-02
L-02
L-02
E
E
F
L-02
L-
0
3
IM
CUBE
IM
CUBE
(E) ELEVATOR
N.I.C
LEASE LINE
CLOSURE LINE
POP OUT
LEASE LINE
(E) STOCKROOM
WALL SHELF
WALL SHELF
PO
S
C
O
U
N
T
E
R
@
3
4
"
A
F
F
HIGH COUNTER
DISPLAY TABLE-B
DISPLAY TABLE-B
DISPLAY TABLE-A
(N) ADA
RESTROOM(E) RESTROOM EQUIPMENT
C7
C2
C2
C4
C5
5
4
TESTER TABLE
F E
(N) PARTITION
SIGN ABOVE
(N) ROLL UP GRILLE,
SEE PRODUCT SPECS
ON A2.01
C3
(N) 24X24 CERAMIC
TILE FLOORING, FINISH
(N) 8X8 CERAMIC TILE
FLOORING, FINISH
A3 (E) SALES AREA
A4
SI
G
N
(E) LANDLORD
NEUTRAL PIER (TYP.
OF 2)
(N) PARTITION
(E) CORRIDOR
A1
(E) WATER HEATER
(E) WATER COOLER
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T
A2
TESTER TABLE
C3
HIGH COUNTER
C4
C6
GRILLE DOOR DEDICATED ELECTRICAL
b
b
b
bb
L-01L-01
L-01
d
d
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
E1.00
LIGHTING LAYOUT- MAIN
FLOOR
WALL MOUNTED SOCKET
FLOOR MOUNTED SOCKETGFCI/W.P
1 DISCONNECT FOR EXHAUST FAN
WH
AHU-01
2 DISCONNECT FOR WATER HEATER
3 DISCONNECT FOR OUTDOOR UNIT
4 DISCONNECT FOR AH UNIT
POWER LEGEND
DISCONNECT SWITCH
2
4
1
CU-013
IM
CUBE
IM
CUBE
(E) ELEVATOR
N.I.C
LEASE LINE
CLOSURE LINE
POP OUT
LEASE LINE
(E) STOCKROOM
WALL SHELF
WALL SHELF
PO
S
C
O
U
N
T
E
R
@
3
4
"
A
F
F
HIGH COUNTER
DISPLAY TABLE-B
DISPLAY TABLE-B
DISPLAY TABLE-A
(N) ADA
RESTROOM(E) RESTROOM EQUIPMENT
C7
C2
C2
C4
C5
5
4
TESTER TABLE
F E
(N) PARTITION
SIGN ABOVE
(N) ROLL UP GRILLE,
SEE PRODUCT SPECS
ON A2.01
C3
(N) 24X24 CERAMIC
TILE FLOORING, FINISH
(N) 8X8 CERAMIC TILE
FLOORING, FINISH
A3 (E) SALES AREA
A4
SI
G
N
(E) LANDLORD
NEUTRAL PIER (TYP.
OF 2)
(N) PARTITION
(E) CORRIDOR
A1
(E) WATER HEATER
(E) WATER COOLER
(E) ELECTRICAL PANELS
TO REMAIN
(E) TRANSFORMER
LA
HA
T
A2
TESTER TABLE
C3
HIGH COUNTER
C4
C6
GRILLE DOOR DEDICATED ELECTRICAL
AF
C
I
AF
C
I
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
E2.00
POWER LAYOUT MAIN
FLOOR
(E) FLOOR OUTLET
(E) FLOOR OUTLET
(N) OUTLET
AF
C
NOTE: ALL OUTLETS ARE NEW
OR REQUIRE RELOCATION
UNLESS OTHERWISE NOTED
NOTE: ALL DISCONNECT ARE EXISTING
POWER RISER DIAGRAM
SCALEE-1
2
SERVICE ENTRANCE
FROM UTILITY
240/120 V, 1Ø, 60Hz
MELECTRICAL METER
PANEL HA 3Ø
3X70A 480/277V (E)
30 KVA STEP DOWN TRANSFORMER
3X125A
(E) SUB-PANEL LA
3Ø
3X200A
MAIN: 200AT,225AF
NEMA 1
LOCATION: STOCK ROOM
Feeder Size: 4 - 3/0 AWG THHN,
1 - # 4 GND THHN IN
4" PVC
120/208V
277/480V
(E)
(E)
(E)
MAIN 400A 277/480V
70A 480/277V
(E)
Feeder Size: 4 - 8 AWG THHN,
1 - #8 GND THHN IN
4" PVC
(E)
(E)
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH
BALDWIN AVENUE
ARCADIA, CA 91007
E3.00
POWER LAYOUT MAIN
FLOOR/ ROOF
NOTE:
EC 220-4(a), 430-24, 430-25, 430-26, and Article 440 Motor-driven air-conditioning and refrigeration equipment is found in Article 440. 13 430.24 Several Motors or a
Motor(s) and Other Load(s) Conductors supplying several motors, or a motor(s) and other load(s), shall have an ampacity not less than the sum of each of the following:
125 percent of the full-load current rating of the highest rated motor, as determined by 430.6(A) Multiply the largest motor (one motor only) by 25% and add to load.
Largest motor = 9300*1.25= 11625. approximately 70% demand.
C
3. ANY DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONS OBSERVED SHALL
BE BROUGHT TO THE ATTENTION, IN WRITING, TO THE ARCHITECT AND/OR ENGINEER PRIOR TO
PROCEEDING WITH CONSTRUCTION.
2. CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE LOCATION AND CONDITION OF ALL POINTS OF
CONNECTION, LOCATION AND CONDITION OF ALL BUILDING (ROOF/FLOOR/CEILING) PENETRATIONS,
LOCATION AND CONDITION OF ALL UTILITIES AND BUILDING SYSTEMS INCLUDING, BUT NOT LIMITED TO
GAS, WATER, SEWER, VENT, ELECTRICAL, BUILDING MECHANICAL SYSTEMS, DUCT CONNECTIONS,
EXHAUST/OUTSIDE AIR CONNECTIONS, SECURITY, FIRE ALARM, DATA, AND PHONE PRIOR TO SUBMISSION
OF THEIR BID.
1. ALL CONTRACTORS (GENERAL CONTRACTOR AND SUB-CONTRACTORS) BIDDING THIS PROJECT ARE
REQUIRED TO VISIT THE JOB SITE AND VERIFY THE EXISTING CONDITIONS PRIOR TO SUBMITTING THEIR BID.
CONTRACTORS ARE TO CAREFULLY REVIEW ALL CONSTRUCTION DOCUMENTS AND NOTE ANY
DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONS OBSERVED AT THE
JOB SITE PRIOR TO SUBMISSION OF ANY BID. THE BUILDING OWNER REPRESENTATIVE LISTED BELOW MAY BE
CONTACTED FOR ACCESS TO THE JOB SITE.
S= %
SHEET
TYPICAL
SHT
TYP
VTR
SLOPE AT A PERCENTAGE
VENT THRU ROOF
ABOVEABV
BELOW
AFF
AP
BEL
BLDG
ACCESS PANEL
ABOVE FINISH FLOOR
BUILDING
CEILINGCLG
CONT
EL
FINISH
FLOOR
FIN
FL
ELEVATION
CONTINUATION
GRADEGR
NTS
OC
NOT TO SCALE
ON CENTER
DN
UP
-PLUMBING NOTE CALL-OUT
POC POINT OF CONNECTION
CV CHECK VALVE
SOV SHUT-OFF VALVE
TP TRAP PRIMER & TRAP PRIMER PIPING
FS FLOOR SINK
FD FLOOR DRAIN
G
CD
NEW GAS
NEW CONDENSATE DRAIN
CW
HW
NEW COLD WATER
NEW HOT WATER
DESCRIPTIONABBRV.
SS or W
V
COMPRESSED AIR
FCO
CA
WCO
NEW SEWER OR WASTE
WALL CLEANOUT
FLOOR CLEANOUT
PRV
T & P
PIPE UP
PIPE DOWN
BACKFLOW PREVENTER W SOV'S
CA
NEW VENT
PLUMBING / GENERAL NOTES
SHOWERS AND TUB-SHOWERS COMBINATIONS IN ALL BUILDINGS SHALL
BE PROVIDED WITH INDIVIDUAL CONTROL VALVES OF THE PRESSURE
BALANCE, THERMOSTATIC, OR COMBINATION OF BOTH THAT PROVIDE
SCALD AND THERMAL SHOCK PROTECTION. VALVES SHALL BE ADJUSTED
TO DELIVER A MAXIMUM MIXED WATER SETTING OF 120 DEGREES FAHRENHEIT.
THE WATER HEATER THERMOSTAT SHALL NOT BE CONSIDERED A SUITABLE
CONTROL FOR MEETING THIS PROVISION.
VERIFY AND WHERE WATER PRESSURE EXCEEDS 80 PSI AN APPROVED PRESSURE
REGULATOR PRECEDED BY AN ADEQUATE STRAINER SHALL BE INSTALLED
1-INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE WITH MINIMUM
3/4" DRAIN PIPE AND TERMINATE TO THE EXTERIOR OF THE BUILDING OVER
WINDOW, DOOR OR VISIBLE LOCATION. DISCHARGE FROM A RELIEF
VALVE INTO A WATER HEATER PAN SHALL BE PROHIBITED .
3- 2 GPM SHOWER FIXTURE, MAX.1.5 GPM BATHROOM FAUCET, MAX. 2 GPM
KITCHEN FAUCET, AND MAX 1.28 WATER CLOSET TO CONFORM TO CITY GREEN
REQUIREMENTS.
BATHROOMS: PROVIDE AN EXHAUST FAN (AT LEAST 50 CFM) DUCTED TO THE
OUTSIDE (MINIMUM 4" DIAMETER FLEX DUCT WITH A MAXIMUM LENGTH OF
70")WITH A MINIMUM VENTILATION RATE OF 100 CFM, IDENTIFY THE REQUIREMENT
FOR A BACK-DRAFT DAMPER ON THE DUCT, AN ENERGY STAR COMPLIANT
EXHAUST FAN THAT IS CONTROLLED BY A HUMIDITY SENSOR THAT IS CAPABLE OF
BEING ADJUSTED BETWEEN ≤ 50-PERCENT TO 80-PERCENT HUMIDITY; AND A
SEPARATE SWITCH FROM THE LIGHT UNLESS THE FAN IS ALLOWED TO OPERATE
WITH THE LIGHT SWITCHED OFF.
4-NOTE THAT ALL PLUMBING VENTS SHALL TERMINATE NOT LESS THAN 6"
ABOVE ROOF NOR LESS THAN 1' FROM ANY VERTICAL SURFACE. VENTS
SHALL TERMINATE NOT LESS THAN 10" FROM OR 3' ABOVE ANY WINDOW,
DOOR OPENING AIR INTAKE, OR VENT SHAFT NOR 3' FROM LOT LINE.
IF WATER PRESSURE EXCEEDS 80 PSI, AND EXPANSION TANK AND AN APPROVED
PRESSURE REGULATOR SHALL BE INSTALLED.
NON-REMOVABLE BACK FLOW PREVENTER OR BIBB-TYPE VACUUM
BREAKER WILL BE INSTALLED ON ALL EXTERIOR HOSE BIBS. HOT WATER
RE-CIRCULATING SYSTEM IS INSTALLED, THE ENTIRE LENGTH
OF HOT WATER PIPES SHALL BE INSULATED.
1-Projects which disturb less than one acre of soil shall manage storm water drainage during construction
by one of the following: A. Retention basins. B. Where storm water is conveyed to a public drainage
system, water shall be filtered by use of a barrier system, wattle or other approved method.
2-Site grading or drainage system will manage all surface water flows to keep water from entering
buildings (swales, water collection, French drains, etc.). CGC Section 4.106.3. Exception: Additions not
altering the drainage path.
4-Landscape irrigation water use shall have weather or soil based controllers. CGC Section 4.304.1.
5-The plans that a minimum of 65% of construction waste is to be recycled. CGC Section 4.408.1.
6-The contractor shall submit a Construction Waste Management Plan, per CGC Section 4.408.2.
7-The builder is to provide an operation manual (containing information for maintaining appliances, etc.)
for the owner at the time of final inspection. CGC Section 4.410.1.
THE WORK INCLUDES MODIFICATION TO THE EXISTING PLUMBING SYSTEM AND PROVIDING NEW
MATERIALS, FITTINGS AND ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING PLUMBING
SYSTEM. THE WORK ALSO INCLUDES ROUGH-IN AND FINAL CONNECTIONS TO FOOD SERVICE
EQUIPMENT AND BEVERAGE DISPENSING EQUIPMENT PROVIDED BY OTHERS. ALL WORK SHALL BE
IN ACCORDANCE WITH LOCAL CODES AND/OR ORDINANCES AND IS SUBJECT TO INSPECTION.
HOOK-UP CHARGES, PERMITS AND ALL OTHER EXPENSES RELATED TO A COMPLETE AND
FUNCTIONING PLUMBING SYSTEM ARE INCLUDED AS A PART OF THIS SECTION. WARRANTY:
PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND MATERIALS AS
REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE
COMPLETED PROJECT. PROVIDE A SEPARATE LINE ITEM DEDUCT AMOUNT ON THE PROPOSAL
FORM TO DELETE WARRANTY SERVICE, AT THE OWNER'S OPTION. THE INTENT OF THE DRAWINGS IS
TO INDICATE THE GENERAL EXTENT OF WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR
PLUMBING WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, FIXTURES AND
EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENTS. REFER
TO MANUFACTURER'S STANDARD ROUGH-IN DRAWINGS FOR PLUMBING FIXTURE INSTALLATION
REQUIREMENTS. COMPLY WITH ALL APPLICABLE ADA INSTALLATION REQUIREMENTS.
COORDINATE WITH THE WORK OF OTHER SECTIONS, EQUIPMENT FURNISHED BY OTHERS, AND
WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE PROJECT SITE.
PIPING SYSTEMS - GENERAL:
ALL PIPING SHALL BE RUN PARALLEL TO BUILDING LINES AND SUPPORTED AND ANCHORED AS
REQUIRED TO FACILITATE EXPANSION AND CONTRACTION. ALL PIPING SHALL BE CONCEALED
EXCEPT IN UNFINISHED SPACES. INSTALL AS REQUIRED TO MEET ALL CONSTRUCTION CONDITIONS
AND TO ALLOW FOR INSTALLATION OF OTHER WORK SUCH AS DUCTS AND ELECTRICAL CONDUIT.
AT ALL CONNECTIONS BETWEEN FERROUS PIPING AND NONFERROUS PIPING, PROVIDE AN
ISOLATING DIALECTIC UNION. ALL HANGERS SHALL BE COMPATIBLE WITH PIPING MATERIAL TO
PREVENT CORROSION. PROVIDE ALL FITTINGS, ACCESSORIES, OFFSETS, AND MATERIALS
NECESSARY TO FACILITATE THE PLUMBING SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN
AND THE EQUIPMENT INDICATED.
FIXTURES/EQUIPMENT FURNISHED BY OTHERS:
PLUMBING CONTRACTOR SHALL PROVIDE UTILITY CONNECTIONS REQUIRED SUCH AS WATER,
GAS, AIR, SUPPLIES, WASTE OUTLET, TRAPS, ETC. AT ALL PLUMBING TYPE FIXTURES OR EQUIPMENT
FURNISHED BY OWNER, GENERAL CONTRACTOR, FOOD SERVICE CONTRACTOR, EQUIPMENT
SUPPLIER, ETC. INCLUDED ARE STOP VALVES, ESCUTCHEONS, AND CHROME PLATED BRASS
TUBING WITH COMPRESSION FITTINGS.
SEWER AND WASTE PIPING:
PROVIDE ALL DRAINS AND SEWERS WITHIN THE SPACE WITH CONNECTION TO THE EXISTING
DRAINAGE SYSTEMS ON-SITE. SANITARY DRAINAGE PIPING ABOVE FLOOR SHALL BE CO-EXTRUDED
PVC DWV (SCHEDULE 40) PIPE, FITTINGS AND CONNECTIONS. SANITARY DRAINAGE PIPING
BELOW GRADE SHALL BE CO-EXTRUDED PVC DWV (SCHEDULE 40) PIPE WITH SOLVENT WELD
FITTINGS MAY BE USED (WHERE PERMITTED BY CODE/LOCAL AUTHORITIES). ALL DRAINAGE PIPING
SHALL BE UNIFORMLY PITCHED, 1/4" PER FOOT UNLESS OTHERWISE REQUIRED BY EXISTING
CONDITIONS, OR INDICATED ON THE DRAWINGS.
VENTS:
PROVIDE A COMPLETE SYSTEM OF STANDARD WEIGHT CAST IRON NO-HUB VENT RISERS WHERE
THE CEILING SPACE IS USED AS A RETURN AIR PLENUM OR USE CO-EXTRUDED PVC DWV
(SCHEDULE 40) PIPE (WHERE PERMITTED BY CODE/LOCAL AUTHORITIES) WHERE THERE IS A DUCTED
RETURN AIR SYSTEM. DO NOT USE PVC PIPE IN RETURN AIR PLENUM SPACES. THE VENT SYSTEM
SHALL BE CARRIED THROUGH THE ROOF WITH APPROPRIATE FLASHING.
CONDENSATE AND INDIRECT DRAIN PIPING:
PIPING ABOVE FLOOR SHALL BE CO-EXTRUDED PVC DWV (SCHEDULE 40) PIPE, FITTINGS AND
CONNECTIONS. PIPING BELOW GRADE SHALL BE CO-EXTRUDED PVC DWV(SCHEDULE 40) PIPE
WITH SOLVENT WELD FITTINGS.
CLEANOUTS:
PROVIDE CLEANOUTS AT THE END OF EACH HORIZONTAL RUN, AND AT THE BASE OF ALL
VERTICAL WASTE AND DRAIN PIPES. CLEANOUTS SHALL BE OF THE SAME SIZE AS THE PIPES THEY
SERVE, CONFORMING TO CODE REQUIREMENTS. PROVIDE SUITABLE WALL OR FLOOR
CLEANOUTS WITH ACCESSORIES TO OBSCURE FROM VIEW.
WATER DISTRIBUTION PIPING:
LAYOUT WATER PIPING SO THAT THE ENTIRE SYSTEM CAN BE DRAINED. HOT AND COLD WATER
PIPING SHALL BE 1/2" MIN. CPVC PIPE WITH SOLVENT FITTING. PROVIDE WATER HAMMER
ARRESTERS AT EACH FIXTURE OR GROUP OF FIXTURES AS REQUIRED. INSTALL CHROME PLATED
BRASS ESCUTCHEON PLATES AT ALL PENETRATIONS THROUGH FINISHED SURFACES (INCLUDING
CABINET INTERIORS).
PIPE INSULATION:
INSULATE (AS ALLOWED BY CODE) ALL LISTED SERVICE PIPING AS FOLLOWS. DOMESTIC
COLD/HOT WATER, HOT WATER RETURN, STORM WATER PIPING. PROVIDE 1" PREFORMED
FIBERGLASS, ASJ/SS-11, FLAME SPREAD 25, SMOKE DEVELOPED 50, ASTM C-547. FOR
CONDENSATE PIPING PROVIDE 1/2" THICK INSULATION OF SAME CHARACTERISTICS AS LISTED FOR
1" ABOVE. WHERE PERMITTED BY LOCAL CODES, PROVIDE 1/2" SELF-ADHESIVE UNICELLULAR
FOAM PIPE INSULATION WITH PRE-FORMED PVC FITTING COVERS - EQUAL TO SELF-ADHESIVE
ARMSTRONG 2000 WITH K FACTOR OF 0.27 AT 75 DEGREES MEAN TEMPERATURE. INSULATE ANY
EXPOSED CONDENSATE PIPING WITH WASTE TEMPERATURE BELOW 60 DEGREES F.
SHUT-OFF VALVES:
SHUTOFF VALVES, WITH UNIONS SHALL BE PROVIDED FOR SERVICE TO EACH PLUMBING FIXTURE,
FOOD SERVICE EQUIPMENT ITEM OR OTHER EQUIPMENT ITEM, TO FACILITATE ISOLATION FOR
REPAIR OR REPLACEMENT. VALVES SHALL BE EQUAL TO JENKINS #902-T BALL VALVE,
CHROME-FINISHED BRONZE, TEFLON SEATS AND PACKING, 400 LB. W.O.G., SOLDER END.
ACCESS PANELS:
ACCESS PANELS SHALL BE PROVIDED WHERE CONCEALED CONTROL DEVICES, VALVES, ETC. ARE
CONCEALED WITHIN WALLS. WHERE ACCESS FOR ADJUSTMENT AND MAINTENANCE IS POSSIBLE
THROUGH LAY-IN SUSPENDED CEILINGS, ACCESS PANELS ARE NOT REQUIRED.
PIPING SYSTEM:
PVC SCHEDULE 40, SCHEDULE 80 AND CPVC PIPE WITH SOLVENT FITTINGS SHALL BE USED WHERE
PERMITTED BY CODE/LOCAL AUTHORITIES.
INSTALLATION: THOROUGHLY CLEAN ITEMS BEFORE INSTALLATION. CAP PIPE OPENINGS TO
EXCLUDE DIRT UNTIL FIXTURES ARE INSTALLED AND FINAL CONNECTIONS HAVE BEEN MADE.
PROCEED AS RAPIDLY AS CONSTRUCTION WILL PERMIT. SET FIXTURES LEVEL AND IN PROPER
ALIGNMENT. INSTALL SUPPLIES IN PROPER ALIGNMENT WITH FIXTURES. INSTALL SILICONE SEALANT
BETWEEN FIXTURES AND ADJACENT MATERIAL, FOR SANITARY JOINT, AND OMIT ESCUTCHEONS.
REPAIR EXISTING PLUMBING SYSTEM COMPONENTS DAMAGED BY CONSTRUCTION OPERATIONS
AND RESTORE TO ORIGINAL CONDITIONS. TEST WATER SYSTEM UNDER 150 PSIG HYDROSTATIC
PRESSURE, FOR FOUR (4) HOURS MINIMUM. WHEN TESTING INDICATES MATERIALS OR
WORKMANSHIP IS DEFICIENT, REPLACE OR REPAIR AS REQUIRED, AND REPEAT TEST UNTIL
STANDARDS ARE ACHIEVED. ROOF PENETRATIONS SHALL COMPLY WITH "SMACNA" AND "NRCA"
STANDARDS, AND WITH THE REQUIREMENTS OF THE EXISTING ROOFING WARRANTY, IF
APPLICABLE. DO NOT PERFORM ROOFING PENETRATIONS IN A MANNER WHICH WOULD VOID
OR OTHERWISE LIMIT THE EXISTING ROOFING WARRANTY.
1.THE INTENT OF THESE PLANS AND SPECIFICATIONS IS TO INCLUDE ALL LABOR,
EQUIPMENT, MATERIALS, AND SERVICES NECESSARY TO FURNISH, INSTALL,
TEST, AND ADJUST A COMPLETE WORKABLE PLUMBING INSTALLATION AS
SHOWN, PRESCRIBED, OR REASONABLY IMPLIED BUT NOT LIMITED TO THAT
EXPLICITLY INDICATED IN THE CONTRACT DOCUMENTS, BUT NECESSARY FOR
THE PROPER EXECUTION AND COMPLETION OF THE INTENT THEREOF.
2.THE ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE
2022 CALIFORNIA PLUMBING CODE, 2022 CALIFORNIA BUILDING CODE, 2022
CALIFORNIA ENERGY CONSERVATION CODE AND ALL OTHER APPLICABLE
CODES AND REGULATIONS REQUIRED BY AUTHORITIES HAVING JURISDICTION.
IN THE EVENT OF CONFLICT BETWEEN SPECIFICATIONS, CODES, AND
REGULATIONS, THE MORE RESTRICTIVE SHALL APPLY.
3.COORDINATE ENTIRE INSTALLATION OF THE PLUMBING SYSTEM WITH THE
WORK OF OTHER TRADES PRIOR TO ANY FABRICATION OR INSTALLATION.
FIELD VERIFY ALL DIMENSIONS AND CONDITIONS. REPORT ANY
DISCREPANCIES, IN WRITING, TO THE ENGINEER PRIOR TO COMMENCEMENT
OF WORK.
4.CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS WITH ALL CHANGES
NOTED THEREON AT THE COMPLETION OF THE PROJECT IN ACCORDANCE
WITH THE SPECIFICATIONS. PROVIDE ONE YEAR WARRANTY ON ALL PARTS
AND LABOR.
6.THE DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW SCOPE.
CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES TO
PROVIDE THE BEST ARRANGEMENT OF ALL DUCT, PIPE, CONDUIT, ETC.
7.ALL CUTTING AND PATCHING OF THE EXISTING STRUCTURE SHALL BE
PROVIDED UNDER OTHER SECTIONS OF THE WORK. PROVIDE NECESSARY
REQUIREMENTS TO THE PROJECT SUPERINTENDENT.
8.ALL HOT WATER PIPING AND RE-CIRCULATION PIPING (EXCEPT RUNOUTS 12
FT. OR SHORTER TO INDIVIDUAL FIXTURES) SHALL BE INSULATED TO MEET THE
REQUIREMENTS OF THE 2022 CALIFORNIA ENERGY CONSERVATION CODE
9.CONDENSATE DRAINS SHALL BE PROVIDED FOR EACH AIR CONDITIONING
UNIT. HORIZONTAL CONDENSATE DRAINS ABOVE ANY CEILING SHALL BE
INSULATED WITH MIN. 3/8" THICK CLOSED CELL INSULATION.
10.PIPING:
A.WASTE, VENT, AND STORM DRAIN PIPING SHALL BE CO-EXTRUDED PVC
SCHEDULE 40) PIPE
B.WATER PIPE SHALL BE CPVC PIPE
C.CONDENSATE PIPING SHALL BE CO-EXTRUDED PVC (SCHEDULE 40) PIPE
D.INSIDE GAS PIPING SHALL BE BLACK IRON SCHEDULE 40 WITH MALLEABLE
IRON FITTINGS. OUTSIDE SHALL BE GALVANIZED IRON SCHEDULE 40 WITH
GALVANIZED FITTINGS. GAS LINE TO BE PAINTED GRAY IN COLOR. A 24
HOUR METERED GAS TEST SHALL BE REQUIRED.
E.ALL PIPING NOT ENCLOSED IN CONDITION SPACE OR AT EXTERIOR WALLS
SHALL BE INSULATED.
F.PIPING: PVC SCHEDULE 40, SCHEDULE 80 AND CPVC PIPING WITH SOLVENT
WELD FITTINGS SHALL BE USED WHERE PERMITTED BY CODE/LOCAL
AUTHORITIES
11.ALL VENTS OR EXHAUSTS SHALL BE AT LEAST 10 FT. AWAY OR 3 FT. ABOVE ANY
WINDOW, DOOR, OPENING, OR AIR INTAKE.
12.CLEANOUTS SHALL BE INSTALLED PER THE CALIFORNIA PLUMBING CODE.
13.PROVIDE WATER TIGHT FLASHINGS WHEREVER PIPES PASS THROUGH
EXTERIOR WALLS, ROOFS, OR FLOORS.
14.PROVIDE ISOLATION FOR ALL PIPES THAT COME IN CONTACT WITH THE
STRUCTURE.
15.LOCATION OF EXISTING UTILITIES AND POINTS OF CONNECTION ARE
APPROXIMATE. CONTRACTOR SHALL VERIFY EXACT LOCATIONS AND DEPTHS
OF EXISTING UTILITIES AND SERVICES PRIOR TO STARTING WORK OF THIS
SECTION. IF INDICATED POINTS OF CONNECTION CANNOT BE MADE TO
EXISTING UTILITIES AS FOUND, THE CONTRACTOR SHALL NOTIFY THE
ENGINEER PRIOR TO INSTALLING ANY WORK WHICH MAY BE AFFECTED.
16.VALVES SHALL BE NIBCO, JENKINS, HAMMOND, RED & WHITE OR APPROVED
EQUAL. SERVICE PRESSURE SHALL BE SUITABLE FOR SERVICE INTENDED. THE
MAIN WATER SHUT OF VALVE SHALL BE A FULL PORT BALL TYPE AND
APPROVED FOR SERVICE INTENDED.
17.CONTRACTOR SHALL PROVIDE ALL SHUT OFF VALVES AS NECESSARY TO
ISOLATE ANY EQUIPMENT, PLUMBING ITEMS, OR FIXTURES, THAT MAY NEED
SERVICING OR ARE SUBJECT TO FAILURE WHETHER OR NOT SUCH VALVES
ARE SHOWN ON THE DRAWINGS.
18.PROVIDE HANGERS AND SUPPORTS AS REQUIRED. PLUMBERS TAPE AND WIRE
ARE NOT ACCEPTABLE.
19.CONTRACTOR IS RESPONSIBLE FOR HIS OWN TRENCHING, BACKFILL, AND
COMPACTION OF TRENCHES NECESSARY TO COMPLETE HIS SCOPE OF
WORK. BACKFILLED TRENCHES SHALL BE RETURNED TO THEIR ORIGINAL
GRADE UNLESS NOTED OTHERWISE.
20.CONTRACTOR SHALL AFFIX A MAINTENANCE LABEL TO ALL EQUIPMENT
REQUIRING ROUTINE MAINTENANCE AND SHALL PROVIDE MAINTENANCE
AND OPERATIONAL MANUALS IN ACCORDANCE WITH THE SPECIFICATIONS.
21.ALL EQUIPMENT THAT REQUIRES KEYS OR SPECIAL TOOLS TO OPERATE SHALL
SUPPLY THE OWNER WITH TWO OF ANY SUCH KEYS OR TOOLS FOR EACH
PIECE OF EQUIPMENT THAT REQUIRE THE SAME.
25.ANY CHANGE OR DEVIATION FROM THESE PLANS OR SPECIFICATIONS SHALL
REQUIRE THE APPROVAL, IN WRITING, OF THE ENGINEER PRIOR TO
COMMENCEMENT OF SUCH WORK.
26.ALL PLUMBING, ELECTRICAL, AND GAS LINES SHALL BE CONCEALED WITHIN
THE THE BUILDING STRUCTURE TO AS GREAT EXTENT AS POSSIBLE. ALL LINES
NOT CONCEALED SHALL BE SECURED 6" OFF THE FLOOR AND 3/4" FROM THE
WALLS USING STANDOFF BRACKETS
THE WATER SAVING PERFORMANCE STANDARDS FOR A PLUMBING FIXTURE ARE THOSE ESTABLISHED BY THE
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), CURRENT REVISION, OR THE FOLLOWING STANDARDS,
WHICHEVER ARE THE MORE RESTRICTIVE
1-THE MAXIMUM FLOW FROM A SINK OR LAVATORY FAUCET OR A FAUCET AERATOR SHALL NOT EXCEED 0 5
GALLONS OF WATER PER MINUTE AT A PRESSURE OF 60 POUNDS PER SQUARE INCH WHEN TESTED IN
ACCORDANCE WITH ANSI TESTING PROCEDURES.
2- THE MAXIMUM VOLUME OF WATER PER FLUSH FROM A TOILET SHALL NOT EXCEED AN AVERAGE OF 1 28
GALLONS WHEN TESTED IN ACCORDANCE WITH ANSI TESTING PROCEDURES
3- THE MAXIMUM VOLUME OF WATER PER FLUSH FROM A URINAL AND THE ASSOCIATED FLUSH VALVE, IF
ANY, SHALL NOT EXCEED AN AVERAGE OF ONE GALLON WHEN TESTED IN ACCORDANCE WITH ANSI
TESTING PROCEDURES
NOTES:
WATER SAVING STANDARDS
SPECIAL NOTICE TO CONTRACTORS
GENERAL NOTES PLUMBING LEGEND
SYMBOL
PLUMBING SPECIFICATIONS
SHEET TAG TITLE SCALE
P 0.00 PLUMBING GENERAL NOTES AND SPECIFICATIONS.
P 0.01
P 1.01
P 2.01
NTS
NTS
3/8"=1'-0"
PLUMBING CODE CHECKING.
FIRST FLOOR WATER SUPPLY LAYOUT.
PLUMBING LIST OF DRAWINGS (LoD):
FIRST FLOOR SEWER LAYOUT.3/8"=1'-0"
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
P0.00
PLUMBING GENERAL NOTES
AND SPECIFICATIONS.
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
CALIFORNIA PLUMBING CODE CHECKING:
PIPE SUPPORTS:
WATER CONVERSION & WATER CONSUMPTION:
TABLE 313.3
HANGERS AND SUPPORTS
For SI units; 1 inch = 25.4 mm, 1 foot = 304.8 mm
Notes:
1 Support adjacent to joint, not to exceed 18 inches (457 mm)
2 Brace not to exceed 40 foot (12 192 mm) intervals to prevent horizontal movement.
3 Support at each horizontal branch connection.
4 Hangers shall not be placed on the coupling.
5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansion and contraction, where
first approved by the Authority Having Jurisdiction.
MATERIALS TYPES OF JOINTS HORIZONTAL VERTICAL
Cast
Lead and Oakum 5 feet, except 10 feet where 10 foot
length are installed1, 2, 3 Base and each floor,
not to exceed 15 feet
Compression Gasket Every other joint, unless over 4 feet
then support each joint1, 2, 3 Base and each floor,
not to exceed 15 feet
Cast-Iron Hubless Shielded Coupling Every other joint, unless over 4 feet
then support each joint1, 2, 3, 4
Base and each floor,
not to exceed 15 feet
Copper & Copper
Alloys
Soldered, Brazed, Threaded, or
Mechanical
1 12 inches and smaller, 6 feet;
2 inches and larger, 10 feet Each floor, not to exceed 10 feet5
Steel Pipe for Water or
DWV Threaded or Welded 34 inch and smaller, 10 feet;
1 inch and smaller, 12 feet
Every floor,
not to exceed 25 feet5
Steel Pipe for Gas Threaded or Welded
12 inch, 6 feet; 34 inch and 1 inch,
8 feet; 1 14 inches and larger, 10 feet
12 inch, 6 feet; 34 inch and 1 inch,
8 feet; 1 14 inches every floor level
Schedule 40 PVC and
ABS DWV Solvent Cemented All sizes, 4 feet; allow
for expansion every 30 feet3
Base and each floor; provide
mid-story guides; provide
for expansion every 30 feet
CPVC Solvent Cemented 1 inch and smaller, 3 feet;
1 14 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
CPVC-AL-CPVC Solvent Cemented 12 inch, 5 feet; 34 inch, 65 inches;
1 inch, 6 feet
Base and each floor;
provide mid-story guides
Lead Wiped or burned Continuous Support Not to exceed 4 feet
Steel Mechanical In accordance with standards acceptable to the Authority Having Jurisdiction
PEX Cold Expansion, Insert
and Compression
1 inch and smaller, 32 inches;
1 14 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
PEX-AL-PEX Metal Insert and Metal
compression
12 inch
34 inch All sizes 98 inches
1 inch
Base and each floor;
provide mid-story guides
PE-AL-PE Metal Insert and Metal
compression
12 inch
34 inch All sizes 98 inches
1 inch
Base and each floor;
provide mid-story guides
PE-RT Insert and Compression 1 inch and smaller, 32 inches;
1 14 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
Polypropylene (PP)
Fusion weld (socket, but, sad-
dle, electrofusion), threaded
(metal threads only), or
mechanical
1 inch and smaller, 32 inches;
1 14 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
}
}
WATER CONSERVING PLUMBING FIXTURES AND FITTINGS
Plumbing fixtures and fittings shall comply with the following:
(2019 CGBSC, California Plumbing Code (CPC) and Table 1401.1 of the CPC)
4303.1.1 All Water closets: <1.28 gal/flush
Tank type water closet shall be certified to the performance criteria of the
U.S. EPA WaterSense Specification for Tank-type Toilets.
4303.1.2 Urinals: <0.5 gal/flush
4303.1.3.1 Single showerheads: <1.8 gpm @ 80 psi
4303.1.3.2 Multiple showerheads: combined flow rate of all showerheads and/or other
shower outlets controlled by a single valve shall not exceed 1.8 gpm @ 80 psi
or only one shower outlet is to be in operation at a time.
4303.1.4.1 Residential Lavatory Faucets: 0.8 gpm @ 20 psi < Flow Rate <1.2 gpm @ 60 psi
4303.1.4.2 Lavatory Faucets in common and Public Use Areas (outside of dwellings or
sleeping units) in residential buildings:
<0.5 gpm @ 60 psi
4303.1.4.3 Metering Faucets: <0.25 gallons per cycle
4303.1.4.4 Kitchen Faucets: <1.8 gpm @ 60 psi; Maximum Flow Rate of 1.8 gpm
PLUMBING FIXTURE CERTIFICATION REQUIRED:
A plumbing fixture certification must be completed and signed by either a licensed general
contractor, or a plumbing subcontractor, or the building owner certifying the flow rate of the
fixtures installed. A copy of the certification can be obtained from the development services
department.
407.3 Limitation of Hot water Temperature for Public Lavatories.
Hot water delivered from public-use lavatories shall be limited to a maximum
temperature of 120°F (49°C) by a device that complies with ASSE 1070/ASME
A112.1070/CSA B125.70. The water heater thermostat shall not be considered
a control for meeting this provision.
407.5 Waste Outlet. Lavatories shall have a waste outlet
and fixtures tailpiece not less than 1 14 inches (32 mm) in diameter.
409.4 Limitation of Hot Water in Bathtubs and
Whirlpool Bathtubs. The maximum hot water temperature discharging from the bathtub and
whirlpool bathtub filler shall be limited to 120°F (49°C) by a device that complies with ASSE
1070/ASME A112.1070/CSA B125.70. The water heater thermostat shall not be considered a
control for meeting this provision.
501.1 Applicability.
The minimum capacity for storage water heaters shall be in
accordance with the first-hour rating listed in Table 501.1(2).
Number of Bathrooms 1 to 1.5 2 to 2.5 3 to 3.5
Number of Bedrooms 1 2 3 2 3 4 5 3 4 5 6
First hour rating,2 Gallons 38 49 49 49 62 62 74 62 74 74 74
For SI units: 1 gallon = 3.785 L.
Notes:
1 The first-hour rating is found on the "Energy Guide" label.
2 Solar water heaters shall be sized to meet the appropriate first-hour rating as shown in the table.
WATER HEATER:
504.0 Water Heater Requirements.
504.1 Location. Water heater installations in bedrooms and
bathrooms shall comply with one of the following [NFPA54:10.27.1]:
(1)Fuel-burning water heaters shall be permitted to be installed in a closet located in the bedroom or
bathroom provided the closet is equipped with a listed, gasketed door assembly and a listed
self-closing device. The self- closing door assembly shall meet the requirements of Section 504.1.1.
The door assembly shall meet the requirements of Section 504.1.2. Combustion air for such
installations shall be obtained from the outdoors in accordance with Section 506.4. The closet shall
be for the exclusive use of the water heater.
(2)Water heater shall be of the direct vent type. [NFPA 54: 10.27.1(2)]
504.2 Vent. Water heaters of other than the direct-vent type shall be located as close as practical
to the chimney or gas vent.
507.2 Seismic provisions. Water heaters shall be anchored or strapped to resist horizontal displacement
due to earthquake motion. Strapping shall be at points within the upper one third (13) and lower one-third
(13) of its vertical dimensions. At the lower point, a minimum distance of four (4) inches (102 mm) shall be
maintained above the controls with the strapping.
507.4 Ground Support. A water heater supported from the earth shall rest on level concrete or other
approved base extending not less than 3 inches (76 mm) above the adjoining ground level.
507.5 Drainage Pan. Where a water heater is located in an attic, in or on an attic ceiling assembly,
floor-ceiling assembly, or floor-subfloor assembly where damage results from a leaking water heater, a
watertight pan of corrosion-resistant materials shall be installed beneath the water heater with not less
than 3 4 of an inch (20 mm) diameter drain to an approved location. Such pan shall be not less than 1 12
(38 mm) in depth.
507.13 Installation in Residential Garages. Appliances in residential garages and in adjacent spaces
that open to the garage and are not part of the living space of a dwelling unit shall be installed so that all
burners and burner-ignition devices are located not less than 18 inches (457 mm) above the floor unless
listed as flammable vapor ignition resistant. [NFPA 54:9.1.10.1]
508.4.4 Lighting and Convenience Outlet. A permanent 120 V receptacle outlet and a lighting fixture
shall be installed near the appliance. The switch controlling the lighting fixture shall be located at the
entrance to the passageway. [NFPA 54:9.5.3]
508.2.1 Installation at roof: Clearance. Appliances shall be installed on a well-drained surface of the
roof. At least 6 feet (1829 mm) of clearance shall be available between any part of the appliance, and
the edge of a roof or similar hazard, or rigidly fixed rails, guards, parapets, or other building structures at
least 42 inches (1067 mm) in height shall be provided on the exposed side. [NFPA 54:9.4.2.2]
TABLE 611.4
SIZING OF RESIDENTIAL WATER SOFTENERS4
REQUIRED SIZE OF
SOFTENER CONNECTION
(inches)
NUMBER OF BATHROOM
GROUPS SERVED1
3 4 up to 22
1 up to 43
For Si units: 1 inch = 25 mm
Notes:
1 Installation of a kitchen sink and dishwasher, laundry tray, and automatic clothes washer
permitted without additional size increase.
2 An additional water closet and lavatory permitted.
3 Over four bathroom groups, the softener size shall be engineered for the specific installation.
4 See also Appendix A, Recommended Rules for Sizing the Water Supply Systems, and Appendix
C, Alternate Plumbing Systems, for alternate methods of sizing water supply systems.
A backflow preventer shall not be required to separate a stand-alone sprinkler syste from the water
distribution system where the sprinkler system material is in accordance with the requirements of Section
604.0.
WATER SUPPLY:
606.1 General. Valves up to and including 2 inches (50 mm) in size shall be copper alloy or other approved
material. Sizes exceeding 2 inches (50 mm) shall be permitted to have cast iron or copper alloy bodies. Each
gate or ball valve shall be a fullway or full-port type with working parts of the non-corrosive material. Valves
carrying water used in potable water systems intended to supply drinking water shall comply with the
requirements of NSF 61 and ASME A112.4.14, ASME B16.34, ASTM F1970, ASTM F2389 AWWA C500, AWWA
C504, AWWA C507, IAPMO Z1157, MSS SP-67, MSS SP- 70, MSS SP-71, MSS SP-72, MSS SP-78, MSS SP-80, MSS
SP-110, MSS SP-122, or NSF 359.
608.4 Pressure Relief Valves. Each pressure relief valve shall be an approved automatic type with drain,
and each such relief valve shall be set at a pressure of not more than 150 psi (1034 kPa). No shutoff valve
shall be installed between the relief valve and the system.
DRAINAGE:
TABLE 703.2: MAXIMUM UNIT LOADING AND MAXIMUM LENGTH OF DRAINAGE AND VENT PIPING
SIZE OF PIPE (inches)1 14 1 12 2 3 4 5 6 8 10 12
Maximum Units
Drainage Piping1
Vertical
Horizontal
1
1
22
1
163
83
484
354
256
2165
600
4285
1380
7205
3600
26405
5600
46805
8400
82005
Maximum Length
Drainage Piping
Vertical
Horizontal
45 65 85 212 300 390 510 750 ––
Vent Piping
Horizontal and Vertical 6
Maximum Units
Maximum Lengths, (feet)
1
45
83
60
24
120
84
212
256
300
600
390
1380
510
3600
750
––
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
Notes:
1 Excluding trap arm.
2 Except for sinks, urinals, and dishwashers – exceeding 1 fixture unit.
3 Except for six-unit traps or water closets.
4 Only four water closets or six-unit traps allowed on a vertical pipe or stack, and not to exceed three water closets or six-unit traps on a horizontal branch or drain.
5 Based on 14 inch per foot (20.8 mm/m) slope, For 18 of an inch per foot (10.4 mm/m) slope, multiply horizontal fixture units by a factor of 0.8.
6 The diameter of an individual vent shall be not less than 1 14 inches (32 mm) nor less than one-half the diameter of the drain to which it is connected. Fixture
unit load values for drainage and vent piping shall be computed from Table 702.1 and Table 702.2(2). Not to exceed one third of the total permitted length
of a vent shall be permitted to be installed in a horizontal position. Where vents are increased one pipe size for their entire length, the maximum length lim-
itations specified in this table do not apply. This table is in accordance with the requirements of Section 901.3.
706.0 Changes in Direction of Drainage Flow.
706.1 Approved Fittings. Changes in the direction of drainage piping shall be made by the approximate use of
approved fittings and shall be of the angles presented by a one-sixteenth bend, one-eight bend, or one-sixth bend,
or other approved fittings of equivalent sweep.
706.2 Horizontal to Vertical. Horizontal drainage lines, connecting with a vertical stack, shall enter through 45
degree (0.79 rad) wye branch, 60 degree (1.05 rad) wye branches, combination wye and one-eighth bend
branches, sanitary tee or sanitary tapped tee branches, or other approved fittings of equivalent sweep.
706.4 Vertical to Horizontal. Vertical drainage lines con necting with horizontal drainage lines shall enter through
45 degree (0.79 rad) wye branches, combination wye and one-eighth bend branches, or other approved fittings of
equiva- lent sweep. Branches, or other approved fittings of equiva- lent sweep. Branches or offsets of 60 degrees
(1.05 rad) shall be permitted to be used where installed in a true vertical posi- tion.
707.4 Location. Each horizontal drainage pipe shall be provided with a cleanout at its upper terminal, and each run of
piping, that s more than 100 feet (30 480 mm) in total developed length, shall be provided with a cleanout for each 100
feet (30 480 mm), or fraction thereof, in length of such piping. An additional cleanout shall be provided in a drainage
line for each aggregate horizontal change in direction exceeding 135 degrees (2.36 rad). A cleanout shall be installed
above the fixture connecting fitting, serving each urinal, regardless of the location of the urinal in the building.
Exceptions
(1)Cleanouts shall be permitted to be omitted on a horizontal drain line less than 5 feet (1524 mm) in length unless such
line is serving sinks or urinals
707.5 Cleaning. Each cleanout shall be installed so that it opens to allow cleaning in the
direction of flow of the soil or waste or at right angles thereto and, except in the case of wye
branch and end-of-line cleanouts, shall be installed vertically above the flow line of the pipe.
708.0 Grade of Horizontal Drainage Piping.
708.1 General. Horizontal drainage piping shall be run in practical alignment and a uniform
slope of not less than 14 inch per foot (20.8 mm/m) or 2 percent toward the point of disposal
provided that, where it is impractical due to the depth of the street sewer, to the structural
features, or to the arrangement of a building or structure to obtain a slope of 14 inch per foot
(20.8 mm/m) or 2 percent, such pipe or piping 4 inches (100 mm) or larger in diameter shall be
permitted to have a slope of not less than 18 inch per foot (10.4 mm/m) or 1 percent, where first
approved by the Authority Having Jurisdiction.
719.0 Cleanouts.
719.1 Locations. Cleanouts shall be placed inside the build ing near the connection between the building drain and
the building sewer or installed outside the building at the lower end of the building drain and extended to grade.
Additional building sewer cleanouts shall be installed at intervals not to exceed 100 feet (30 480 mm) in straight runs
and for each aggregate horizontal change in direction exceeding 135 degrees (2.36 rad)
719.2 No additional Cleanouts. Where a building sewer or a branch thereof does not exceed 10 feet (3048 mm) in
length and is a straight-line projection from a building drain that is provided with a cleanout, no cleanout will be
required at its point of connection to the building drain.
721.0 Location.
721.1 Building Sewer. Except as provided in Section 721.2, no building sewer shall be located in a lot other than the
lot that is the site of the building or structure served by such sewer nor shall a building sewer be located at a point
having less than the minimum distances referenced in Table 721.1.
TABLE 721.1
MINIMUM HORIZONTAL DISTANCE REQUIRED FROM BUILDING SEWER (feet)
Buildings or structures1 2
Property line adjoing private property Clear2
Water supply wells 503
Streams 50
On-site domestic water service line 14
Public water main 105, 6
906.0 Vent Termination.
906.1 Roof Termination. Each vent pipe or stack shall extend through its flashing and
shall terminate vertically not less than 6 inches (152 mm) above the roof nor less than 1
foot (305 mm) from a vertical surface. ABS and PVC piping exposed to sunlight shall be
protected by water based synthetic latex paints.
906.2 Clearance. Each vent shall terminate not less than 10 feet (3048 mm) from, or
not less than 3 feet (914 mm) above, an openable window, door, opening, air intake, or
vent shaft, or not less than 3 feet (914 mm) in every direction from a hot line, alley and
street excepted.
909.0 Special Venting for Island Fixtures.
909.1 General. Traps for island sinks and similar equipment shall be roughed in above
the floor and shall be permitted to be vented by extending the vent as high as possible,
but not less than the drainboard height and then returning it down- ward and
connecting it to the horizontal sink drain immediately downstream from the vertical
fixture drain. The return vent shall be connected to the horizontal drain through a
wye-branch fitting and shall, in addition, be provided with a foot vent taken off the
vertical fixture vent by means of a wye branch immediately below the floor and
extending to the nearest partition and then through the roof to the open air, or shall be
permitted to be connected to other vents at a point not less than 6 inches (152 mm)
above the flood-level rim of
the fixtures served. Drainage fittings shall be used on the vent below the floor level, and
a slope of not less than 14 inch per foot (20.8 mm/m) back to the drain shall be
maintained. The return bend used under the drainboard shall be a one-piece fitting or
an assembly of a 45 degree (0.79 rad), a 90 degree (1.57 rad), and a 45 degree (0.79
rad) elbow in the order named. Pipe sizing shall be as elsewhere required in this code.
The island sink drain, upstream of the returned vent, shall serve no other fixtures. An
accessible cleanout shall be installed in the vertical portion of the foot vent.
VENT:
FIRESTOP PROTECTION
1404.0 Combustible Piping Installations.
1404.2 Fire-Resistance Rating. Where penetrating a fire-resistance-rated wall, partition, floor,
floor-ceiling assembly, roof-ceiling assembly, or shaft enclosure, the fire-resistance rating of the
assembly shall be restored to its original rating.
1404.3 Firestop Systems. Penetrations shall be protected by an approved penetration firestop system
installed as tested in accordance with ASTM E119, ASTM E814, UL 263, or UL 1479 with a positive pressure
differential of not less than 0.01 of an inch of water (0.002 kPa). Systems shall have and F rating of not less than
1 hour but not less than the required fire-resistance rating of the assembly being penetrated. Systems
protecting floor penetrations shall have a T rating of not less than 1 hour but not less than the required
fire-resistance rating of the floor penetrations shall have a T rating of not less than 1 hour but not less than the
required fire-resistance rating of the floor being penetrated. Floor penetrations contained within the cavity of
a wall at the location of the floor penetration do not require a T rating. No T rating shall be required for floor
penetrations by piping that is not in direct
contact with combustible material.
1404.6 Sleeves. Where sleeves are used, the sleeves shall be securely fastened to the fire-resistance-rated
assembly. The (inside) annular space between the sleeve and the fire-resistance-rated assembly shall be
firestopped in accordance with this chapter.
1405.0 Noncombustible Piping Installations.
1405.3 Firestop Systems. Penetrations shall be protected by an approved penetration firestop system
installed as tested in accordance with ASTM E119, ASTM E814, UL 263, or UL 1479 with a positive pressure
differential of not less than 0.01 of an inch of water (0.002 kPa). Systems shall have an F rating of not less than 1
hour but not less than the required fire-resistance rating of the assembly being penetrated. Systems protecting
floor penetrations shall have a T rating of not less than 1 hour but not less than the required fire-resistance rating
of the floor being penetrated. Floor penetrations contained within the cavity of a wall at a location of the floor
penetration do not require a T rating. No T rating shall be required for floor penetrations by piping that is not in
direct contact with combustible material.
1405.6 Sleeves. Where sleeves are used, the sleeves shall be securely fastened to the fire-resistance-rated
assembly. The (inside) annular space between the sleeve and the penetrating item and the (outside) annular
space between the sleeve and the fire-resistance-rated assembly shall be firestopped in accordance with this
chapter.
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
P0.01
PLUMBING CODE
CHECKING.
3/31/24
MAISON KOSE, SANTA ANITA
PROJECT:
IM
CUBE
1/
2
"
H
W
P
1/
2
"
C
W
P
GENERAL NOTES:
1.PRIOR TO PERFORMING WORK, CONTRACTOR TO COORDINATE EXACT
PIPE SIZES, INVERT ELEVATIONS, PRESSURES FOR LOCATIONS OF ANY
SEWER, WATER PIPING AND WATER METER WITH CIVIL UTILITIES
DRAWINGS, AND ANY OTHER ENGINEER AS APPLICABLE.
2.PRIOR TO PERFORMING WORK, CONTRACTOR TO COORDINATE PIPE
ROUTING WITH ALL OTHER TRADES AND EXISTING FIELD CONDITIONS.
3.REFER TO MECHANICAL PLANS FOR PLUMBING SPECIFICATION OF
MATERIAL, INSULATION AND INSTALLATION REQUIREMENTS.
4.CONTRACTOR IS RESPONSIBLE FOR ROUGH-IN COORDINATION AND
LOCATIONS. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS AND
FIXTURES.
5.CONTRACTOR IS RESPONSIBLE FOR ANY REQUIRED CUTTING AND
PATCHING.
6.ALL NOTCHING, BORING, AND CUTTING OF HOLES IN WALL STUDS AND
FLOOR JOISTS SHALL BE PERFORMED BASED ON THE LATEST ADOPTED
AND APPROVED EDITION OF THE BUILDING CODE.
7.ALL PLUMBING FIXTURES SHALL BE OF WATER CONSERVATION TYPE AS
REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION.
8.ALL WATER PIPING SHALL BE INSTALLED ON INTERIOR SIDE OF THE
BUILDING WALL INSULATION.
9.CONTRACTOR SHALL PROVIDE VALVES LOCATED ABOVE LAY-IN CEILING
OR 24"x24" CEILING ACCESS PANEL COORDINATE FINAL LOCATION AND
SIZE WITH ARCHITECT. PROVIDE BALANCING VALVES FOR HOT WATER
RETURN SYSTEM AS REQUIRED.
10.ALL SANITARY DRAINAGE PIPING 3" AND SMALLER SHALL BE SLOPED AT 1
4"
PER FOOT. PIPING 4" AND LARGER SHALL BE SLOPED AT 1
8" PER FOOT.
11.ALL CONDENSATE DRAIN PIPING SHALL BE SLOPED AT 1
8" PER FOOT AND
PROVIDE ACCESSIBLE CLEANOUTS AT ALL CHANGES OF DIRECTION.
12.VENTS THAT TERMINATE AT THE ROOF SHALL BE A MINIMUM OF 10' FROM
ANY FRESH AIR INTAKE.
13.REFER TO THE PLUMBING DIAGRAMS FOR GUIDANCE OF INSTALLATION
INTENT. CONTRACTOR IS TO PROVIDE ALL COMPONENTS NECESSARY TO
MEET THE DESIGN INTENT, WHETHER SHOWN IN DIAGRAM OR NOT.
DCW, DHW RISE TO HIGH LEVEL.
DCW/DHW/RHW TO FIXTURE CONNECTION.
WATER SUPPLY SHEET NOTES:
1
2
(E)WATER
HEATER
3/
4
"
C
W
P
FIXTURE W.S.F.U QTY.TOTAL
W.S.F.U
FROM 2022 CPC - TABLE 610.3:
WATER SUPPLY FIXTURE UNITS LOADS:
WATER CLOSET 2.5 1 2.5
LAVATORY 1.0 1 1.0
AS PER 2022CPC -TABLE 610.4
-LONGEST RUN IS APPRX3 40 FT.
-W/M PRESSURE RANGE 30-45 PSI
-MAIN CWP NOT LESS THAN 3/4" Ø
-W/M SIZE NOT LESS THAN 3/4" Ø
TOTAL BUILDING WSFU =3.5
1/
2
"
C
W
P
2 2
W/M 3/4" CWP
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
P1.01
FIRST FLOOR WATER
SUPPLY LAYOUT.
3/31/24
IM
C
U
B
E
I
M
C
U
B
E
MAISON KOSE, SANTA ANITA
PROJECT:
GENERAL NOTES:
1.PRIOR TO PERFORMING WORK, CONTRACTOR TO COORDINATE EXACT
PIPE SIZES, INVERT ELEVATIONS, PRESSURES FOR LOCATIONS OF ANY
SEWER, WATER PIPING AND WATER METER WITH CIVIL UTILITIES
DRAWINGS, AND ANY OTHER ENGINEER AS APPLICABLE.
2.PRIOR TO PERFORMING WORK, CONTRACTOR TO COORDINATE PIPE
ROUTING WITH ALL OTHER TRADES AND EXISTING FIELD CONDITIONS.
3.REFER TO MECHANICAL PLANS FOR PLUMBING SPECIFICATION OF
MATERIAL, INSULATION AND INSTALLATION REQUIREMENTS.
4.CONTRACTOR IS RESPONSIBLE FOR ROUGH-IN COORDINATION AND
LOCATIONS. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS AND
FIXTURES.
5.CONTRACTOR IS RESPONSIBLE FOR ANY REQUIRED CUTTING AND
PATCHING.
6.ALL NOTCHING, BORING, AND CUTTING OF HOLES IN WALL STUDS AND
FLOOR JOISTS SHALL BE PERFORMED BASED ON THE LATEST ADOPTED
AND APPROVED EDITION OF THE BUILDING CODE.
7.ALL PLUMBING FIXTURES SHALL BE OF WATER CONSERVATION TYPE AS
REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION.
8.ALL WATER PIPING SHALL BE INSTALLED ON INTERIOR SIDE OF THE
BUILDING WALL INSULATION.
9.CONTRACTOR SHALL PROVIDE VALVES LOCATED ABOVE LAY-IN CEILING
OR 24"x24" CEILING ACCESS PANEL COORDINATE FINAL LOCATION AND
SIZE WITH ARCHITECT. PROVIDE BALANCING VALVES FOR HOT WATER
RETURN SYSTEM AS REQUIRED.
10.ALL SANITARY DRAINAGE PIPING 3" AND SMALLER SHALL BE SLOPED AT 1
4"
PER FOOT. PIPING 4" AND LARGER SHALL BE SLOPED AT 1
8" PER FOOT.
11.ALL CONDENSATE DRAIN PIPING SHALL BE SLOPED AT 1
8" PER FOOT AND
PROVIDE ACCESSIBLE CLEANOUTS AT ALL CHANGES OF DIRECTION.
12.VENTS THAT TERMINATE AT THE ROOF SHALL BE A MINIMUM OF 10' FROM
ANY FRESH AIR INTAKE.
13.REFER TO THE PLUMBING DIAGRAMS FOR GUIDANCE OF INSTALLATION
INTENT. CONTRACTOR IS TO PROVIDE ALL COMPONENTS NECESSARY TO
MEET THE DESIGN INTENT, WHETHER SHOWN IN DIAGRAM OR NOT.
SANITARY SHEET NOTES:
WASTE DROP AND 2" VENT RISE.
3" VENT STACK TO ABOVE.
4" FLOOR CLEAN-OUT.
WALL CLEAN-OUT.
1
2
3
4
IM
CUBE
FIXTURE D.F.U QTY.TOTAL
D.F.U
FROM 2022 CPC - TABLE 702.1:
DRAINAGE FIXTURE UNIT VALUES (DFU)
WATER CLOSET 3.0
LAVATORY 1.0
TOTAL BUILDING DFU =4.0
1
1 3.0
1.0
41
2
2
TO MAIN
SEWER LINE
3
2"
S
4" S
4"
S
2"
V
4"
S
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
P2.01
FIRST FLOOR
SEWER LAYOUT.
3/31/24
IM
C
U
B
E
I
M
C
U
B
E
MAISON KOSE, SANTA ANITA
PROJECT:
MAISON KOSE, SANTA ANITA
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH BALDWIN AVENUE
ARCADIA , CA 91007
T24.01
T24.01
MAISON KOSE, SANTA ANITA
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH BALDWIN AVENUE
ARCADIA , CA 91007
T24.02
T24.02
MAISON KOSE, SANTA ANITA
DRAWING NO.REV.
PROJ. NO.PROJ. ENGR.SCALE @ 24X36:
TITLE:
PROJECT:
REV. NO.DESCRIPTION DATE BY
Address: Foxbrough pl
Pleasanton, CA. 94566
Phone: (424) 414-0997
Web site: www.innodez.com
Email: hello@innodez.com
NOTES:
ADDRESS:
CLIENT:
CONFIDENTIALITY STATEMENT:
ALL DRAWINGS AND WRITTEN MATERIALS
APPEARING HEREIN CONSTITUTE THE
ORIGINAL AND UNPUBLISHED WORK OF THE
DESIGNER AND THE SAME MAY NOT BE
DUPLICATED, USED OR DISCLOSED WITHOUT
CONSENT OF THE DESIGNER.
Inno Dez
SPACE K3, 400 SOUTH BALDWIN AVENUE
ARCADIA , CA 91007
T24.03
T24.03
3/31/24
STRUCTURAL
BUILDING DEPARTMENT SUBMITTAL
SUBMITTED TO:
FOR:
DEYI CONSULTANT, INC.
2725 WHISPERING TRL.
IRVINE, CA 92602
949-656-6134
JUNFEI.CHEN@DEYICONSULTANTS.COM
ROSS ADDITION8187 ROSS ST.
EASTVALE, CA 92880
11/05/2023PROJECT NO. 23198
EXP. DATE: 09/30/2024
MAISON KOSE
SPACE K3, 400 S. BALDWIN AVE.
ARCADIA, CA 91007
CITY OF ARCADIA
11/6/23, 10:50 AM U.S. Seismic Design Maps
https://www.seismicmaps.org 1/3
USGS web services were down for some period of time and as a result this tool wasn't operational, resulting in timeout error.USGS web services are now operational so this tool should work as expected.
400 S Baldwin Ave, Arcadia, CA 91007, USA
Latitude, Longitude: 34.1347003, -118.051589
Date 11/6/2023, 10:50:00 AM
Design Code Reference Document ASCE7-16
Risk Category II
Site Class D - Default (See Section 11.4.3)
Type Value Description
SS 2.018 MCER ground motion. (for 0.2 second period)
S1 0.721 MCER ground motion. (for 1.0s period)
SMS 2.422 Site-modified spectral acceleration value
SM1 null -See Section 11.4.8 Site-modified spectral acceleration value
SDS 1.614 Numeric seismic design value at 0.2 second SA
SD1 null -See Section 11.4.8 Numeric seismic design value at 1.0 second SA
Type Value Description
SDC null -See Section 11.4.8 Seismic design category
Fa 1.2 Site amplification factor at 0.2 second
Fv null -See Section 11.4.8 Site amplification factor at 1.0 second
PGA 0.878 MCEG peak ground acceleration
FPGA 1.2 Site amplification factor at PGA
PGAM 1.054 Site modified peak ground acceleration
TL 8 Long-period transition period in seconds
SsRT 2.018 Probabilistic risk-targeted ground motion. (0.2 second)
SsUH 2.278 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration
SsD 2.256 Factored deterministic acceleration value. (0.2 second)
S1RT 0.745 Probabilistic risk-targeted ground motion. (1.0 second)
S1UH 0.838 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration.
S1D 0.721 Factored deterministic acceleration value. (1.0 second)
PGAd 0.905 Factored deterministic acceleration value. (Peak Ground Acceleration)
Page 1
11/6/23, 10:50 AM U.S. Seismic Design Maps
https://www.seismicmaps.org 2/3
Type Value Description
PGAUH 0.878 Uniform-hazard (2% probability of exceedance in 50 years) Peak Ground Acceleration
CRS 0.886 Mapped value of the risk coefficient at short periods
CR1 0.889 Mapped value of the risk coefficient at a period of 1 s
CV 1.5 Vertical coefficient
Page 2
11/6/23, 10:50 AM U.S. Seismic Design Maps
https://www.seismicmaps.org 3/3
DISCLAIMER
While the information presented on this website is believed to be correct, SEAOC /OSHPD and its sponsors and contributors assume no responsibility or
liability for its accuracy. The material presented in this web application should not be used or relied upon for any specific application without competent examination
and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. SEAOC / OSHPD do not intend that the use of this
information replace the sound judgment of such competent professionals, having experience and knowledge in the field of practice, nor to substitute for the
standard of care required of such professionals in interpreting and applying the results of the seismic data provided by this website. Users of the information from
this website assume all liability arising from such use. Use of the output of this website does not imply approval by the governing building code bodies responsible
for building code approval and interpretation for the building site described by latitude/longitude location in the search results of this website.
Page 3
KOSE Wall Shelving
SCOPE:
The purpose of this analysis is to show that the following light duty storage fixtures complies with the specifications
set forth in Section 2209 of the 2022 CBC and Section 15.5.3 of ASCE 7-16 .
The storage racks are prefabricated and are to be field installed only without any field welding.
PARAMETERS:
The system will be analyzed for seismic loading utilizing the following equation:
V =Cs x W
Cs =SDS x I / R
SDS =2/3 x Fa x Ss
I =1
R =4
Fa =1.20
Ss =2.02
SPECIFICATIONS:
Steel -Fy = 50,000 psi
Bolts -ASTM A307 unless otherwise noted
Anchors -1/2"Ø x 4" MIN. EMBED. SIMPSON TITEN HD (ICC ESR-2713)
Slab -12" x 5,000 psi
Soil -1,000 psf
1
Page 4
Loads & Distribution:
Fa =1.20 <=== ASSUMED SITE CLASS D
Ss =2.02
SDS =2/3*Fa*Ss
=1.61
I =1 <=== IN AREA NOT OPEN TO THE PUBLIC
R =4
Cs =SDS * I / R
=0.403 Depth =24.0 IN
# of Levels=5
Shelf PL =150 lb/Level
Shelf DL =20 lb/Level
Seismic Shear:
Vtotal =Cs*Ws
=0.403 x 850 LB
=243 LB
Level Ws hx wx hx Fi Movt
1 170.0 LB 24.0 IN 4,080 IN-LB 23.1 LB 555 IN-LB
2 170.0 LB 36.0 IN 6,120 IN-LB 34.7 LB 1,249 IN-LB
3 170.0 LB 48.0 IN 8,160 IN-LB 46.2 LB 2,220 IN-LB
4 170.0 LB 60.0 IN 10,200 IN-LB 57.8 LB 3,469 IN-LB
5 170.0 LB 84.0 IN 14,280 IN-LB 80.9 LB 6,799 IN-LB
850.0 LB 42,840 IN-LB 243 LB 14,291 IN-LB
Vtop =Cs*Ws,top
=0.403 x 550 LB
=222 LB
Level Ws hx wx hx Fi Movt
1 20 LB 24.0 IN 480 IN-LB 3.1 LB 75 IN-LB
2 20 LB 36.0 IN 720 IN-LB 4.7 LB 170 IN-LB
3 170 LB 48.0 IN 8,160 IN-LB 53.4 LB 2,565 IN-LB
4 170 LB 60.0 IN 10,200 IN-LB 66.8 LB 4,009 IN-LB
5 170 LB 84.0 IN 14,280 IN-LB 93.5 LB 7,857 IN-LB
550 LB 33,840 IN-LB 222 LB 14,676 IN-LB
Pcol-static =425 LB
1
Page 5
Overturning Analysis
Fully loaded:
Movt =14,291 IN-LB
MDL =100 LB x 24 IN / 2
=1,200 IN-LB
d =24.0 IN
MPL =150 LB x 24 IN / 2
=1,800 IN-LB
Vcol =Vtotal/2
=121 LB
Puplift =[Movt - (0.9-0.2SDS) x MDL - (0.9-0.2SDS) x MPL] / d
=[14291 - (0.9-0.2*1.61)*1200 - (0.9-0.2*1.61)*1800] IN-LB / 24 IN
=523 LB <=== UPLIFT
Top shelf loaded only:
Movt =14,676 IN-LB
MDL =1,200 IN-LB
d =24.0 IN
MPL =150 LB x 24 IN / 2
=1,800 IN-LB
Vcol =Vtop/2
=111 LB
Puplift =[Movt - (0.6-0.14SDS) x MDL - (0.6-0.14SDS) x MPLapp] / d
=[14676 - (0.9-0.2*1.61)*1200 - (0.9-0.2*1.61)*1800] IN-LB / 24 IN
=539 LB <=== UPLIFT
1
Page 6
Company:Date:11/6/2023
Engineer:Page:1/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.1.2303.1
1.Project information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
Project description:
Location:
Fastening description:
2. Input Data & Anchor Parameters
GeneralDesign method:ACI 318-19
Units: Imperial units
Anchor Information:
Anchor type: Concrete screw
Material: Carbon Steel
Diameter (inch): 0.500
Nominal Embedment depth (inch): 4.000Effective Embedment depth, hef (inch): 2.990
Code report: ICC-ES ESR-2713
Anchor category: 1
Anchor ductility: No
hmin (inch): 6.25
cac (inch): 4.50
Cmin (inch): 1.75
Smin (inch): 3.00
Base MaterialConcrete: Normal-weight
Concrete thickness, h (inch): 12.00
State: Uncracked
Compressive strength, f’c (psi): 2500
Ψc,V: 1.4
Reinforcement condition: Supplementary reinforcement not present
Supplemental edge reinforcement: No
Reinforcement provided at corners: NoIgnore concrete breakout in tension: No
Ignore concrete breakout in shear: No
Ignore 6do requirement: Not applicable
Build-up grout pad: No
Base Plate
Length x Width x Thickness (inch): 6.00 x 5.50 x 0.25
Yield stress: 36000 psi
Profile type/size: HSS2X2X1/8
Recommended Anchor
Anchor Name: Titen HD® - 1/2"Ø Titen HD, hnom:4" (102mm)
Code Report: ICC-ES ESR-2713
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Page 7
Company:Date:11/6/2023
Engineer:Page:2/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.1.2303.1
Load and Geometry
Load factor source: ACI 318 Section 5.3
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: Not applicable
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: No
Strength level loads:
Nua [lb]: 539
Vuax [lb]: 0
Vuay [lb]: 111
Mux [ft-lb]: 1223
Muy [ft-lb]: 0
Muz [ft-lb]: 0
<Figure 1>
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Page 8
Company:Date:11/6/2023
Engineer:Page:3/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.1.2303.1
<Figure 2>
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Page 9
Company:Date:11/6/2023
Engineer:Page:4/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.1.2303.1
3. Resulting Anchor Forces
Anchor Tension load,
Nua (lb)
Shear load x,
Vuax (lb)
Shear load y,
Vuay (lb)
Shear load combined,
√(Vuax)²+(Vuay)² (lb)
1 0.0 0.0 27.8 27.8
2 2018.6 0.0 27.8 27.8
3 0.0 0.0 27.8 27.8
4 2018.6 0.0 27.8 27.8
Sum 4037.3 0.0 111.0 111.0
Maximum concrete compression strain (‰): 0.16
Maximum concrete compression stress (psi): 675
Resultant tension force (lb): 4037
Resultant compression force (lb): 3498
Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00
Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00
Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00
<Figure 3>
4. Steel Strength of Anchor in Tension (Sec. 17.6.1)
Nsa (lb)f fNsa (lb)
20130 0.65 13085
5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.6.2)
Nb = kclaÖf’chef1.5 (Eq. 17.6.2.2.1)
kc la f’c (psi)hef (in)Nb (lb)
24.0 1.00 2500 2.990 6204
fNcbg =f (ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.5.1.2 & Eq. 17.6.2.1a)
ANc (in2)ANco (in2)ca,min (in)Yec,N Yed,N Yc,N Ycp,N Nb (lb)f fNcbg (lb)
107.37 80.46 -1.000 1.000 1.00 1.000 6204 0.65 5381
8. Steel Strength of Anchor in Shear (Sec. 17.7.1)
Vsa (lb)fgrout f fgroutfVsa (lb)
7455 1.0 0.60 4473
10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.7.3)
fVcpg = fkcpNcbg = fkcp(ANc / ANco)Yec,NYed,NYc,NYcp,NNb (Sec. 17.5.1.2 & Eq. 17.7.3.1b)
kcp ANc (in2)ANco (in2)Yec,N Yed,N Yc,N Ycp,N Nb (lb)f fVcpg (lb)
2.0 143.28 80.46 1.000 1.000 1.000 1.000 6204 0.70 15467
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Page 10
Company:Date:11/6/2023
Engineer:Page:5/5
Project:
Address:
Phone:
E-mail:
Anchor Designer™
Software
Version 3.1.2303.1
11. Results
Interaction of Tensile and Shear Forces (Sec. 17.8)
Tension Factored Load, Nua (lb)Design Strength, øNn (lb)Ratio Status
Steel 2019 13085 0.15 Pass
Concrete breakout 4037 5381 0.75 Pass (Governs)
Shear Factored Load, Vua (lb)Design Strength, øVn (lb)Ratio Status
Steel 28 4473 0.01 Pass
Pryout 111 15467 0.01 Pass (Governs)
Interaction check Nua/fNn Vua/fVn Combined Ratio Permissible Status
Sec. 17.8.1 0.75 0.00 75.0%1.0 Pass
1/2"Ø Titen HD, hnom:4" (102mm) meets the selected design criteria.
12. Warnings
- Designer must exercise own judgement to determine if this design is suitable.
- Refer to manufacturer’s product literature for hole cleaning and installation instructions.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
Page 11
Page 12
5
4
F E
A3
A2
A4
HS
S
4
x
4
x
1
/
4
HS
S
4
x
4
x
1
/
4
Column loading:
Lateral:5psf x 15'=75plf
Gravity: 300lbs
Steel Column
LIC# : KW-06017322, Build:20.23.08.30 VCA CONSULTANTS, INC (c) ENERCALC INC 1983-2023
DESCRIPTION:--None--
VCA Structural
1845 W. Orangewood Ave. #200
Orange County
CA 92868
Project File: 11.ec6
Project Title:Engineer:Project ID:Project Descr:
.Code References
Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16
Load Combinations Used : ASCE 7-16
General Information
Steel Stress Grade
Top & Bottom PinnedAnalysis Method :
15Overall Column Height
Top & Bottom FixityAllowable Strength
Fy : Steel Yield
ksi29,000.0
ksi
Steel Section Name :HSS4x4x1/4
36.0
ft
E : Elastic Bending Modulus Unbraced Length for buckling ABOUT X-X Axis = 15 ft, K = 1.0
Unbraced Length for buckling ABOUT Y-Y Axis = 15 ft, K = 1.0
Brace condition :
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Column self weight included : 183.150 lbs * Dead Load Factor
AXIAL LOADS . . .
Axial Load at 15.0 ft, E = 0.30 k
BENDING LOADS . . .
Lat. Uniform Load creating Mx-x, E = 0.0750 k/ft
.DESIGN SUMMARY
PASS Max. Axial+Bending Stress Ratio =0.1809
Location of max.above base 7.450 ft
0.3932 k
34.721 k
1.477 k-ft
Load Combination +D+0.70E
Load Combination +D+0.70E
8.425 k-ft
Bending & Shear Check Results
PASS Maximum Shear Stress Ratio =
0.3938 k
0.01979 : 1
Location of max.above base 0.0 ftAt maximum location values are . . .
: 1
At maximum location values are . . .
k
8.425 k-ft
0.0 k-ft
Pa : Axial
Pn / Omega : Allowable
Ma-x : Applied
Mn-x / Omega : Allowable
Ma-y : Applied
Mn-y / Omega : Allowable
Va : AppliedVn / Omega : Allowable
Maximum Load Reactions . .
Top along X-X 0.0 k
Bottom along X-X 0.0 k
Top along Y-Y 0.5625 k
Bottom along Y-Y 0.5625 k
Maximum Load Deflections . . .
Along Y-Y 0.3817 in at 7.550ft above base
for load combination :E Only
Along X-X 0.0 in at 0.0ft above base
for load combination :
19.896
.
Maximum Axial + Bending Stress Ratios Maximum Shear Ratios
Load Combination Stress Ratio Location Stress Ratio Status LocationStatus
Load Combination Results
Cbx Cby KxLx/Ry KyLy/Rx
D Only PASS PASS0.00 0.000 0.00 ftft0.005 1.14 1.00 118.42 118.42
+0.60D PASS PASS0.00 0.000 0.00 ftft0.003 1.14 1.00 118.42 118.42
+D+0.70E PASS PASS7.45 0.020 0.00 ftft0.181 1.14 1.00 118.42 118.42
+D+0.5250E PASS PASS7.55 0.015 0.00 ftft0.136 1.14 1.00 118.42 118.42
+0.60D+0.70E PASS PASS7.45 0.020 0.00 ftft0.180 1.14 1.00 118.42 118.42
.
k k-ft
Note: Only non-zero reactions are listed.
Load Combination
X-X Axis Reaction Y-Y Axis ReactionAxial Reaction
@ Base @ Top@ Base @ Base @ Top
Maximum Reactions
@ Base @ Base@ Top @ Top
Mx - End Moments My - End Moments
D Only 0.183
+0.60D 0.110
+D+0.70E 0.3940.393 0.394
+D+0.5250E 0.2950.341 0.295
+0.60D+0.70E 0.3940.320 0.394
E Only 0.5620.300 0.563
Page 13
Steel Column
LIC# : KW-06017322, Build:20.23.08.30 VCA CONSULTANTS, INC (c) ENERCALC INC 1983-2023
DESCRIPTION:--None--
VCA Structural
1845 W. Orangewood Ave. #200
Orange County
CA 92868
Project File: 11.ec6
Project Title:Engineer:Project ID:Project Descr:
k k-ft
Item
X-X Axis Reaction Y-Y Axis ReactionAxial Reaction
@ Base @ Top@ Base @ Base @ Top
Extreme Reactions
Extreme Value @ Base @ Base@ Top @ Top
Mx - End Moments My - End Moments
MaximumAxial @ Base 0.3940.393 0.394
Minimum"0.110
MaximumReaction, X-X Axis Base 0.183
Minimum"0.183
MaximumReaction, Y-Y Axis Base 0.5620.300 0.563
Minimum"0.183
MaximumReaction, X-X Axis Top 0.183
Minimum"0.183
MaximumReaction, Y-Y Axis Top 0.183
Minimum"0.183
MaximumMoment, X-X Axis Base 0.183
Minimum"0.183
MaximumMoment, Y-Y Axis Base 0.183
Minimum"0.183
MaximumMoment, X-X Axis Top 0.183
Minimum"0.183
MaximumMoment, Y-Y Axis Top 0.183
Minimum"0.183
.Maximum Deflections for Load Combinations
Max. Deflection in X dir Max. Deflection in Y dir DistanceLoad Combination Distance
D Only 0.0000 0.000 0.000 ftftinin0.000
+0.60D 0.0000 0.000 0.000 ftftinin0.000
+D+0.70E 0.0000 0.267 7.550 ftftinin0.000
+D+0.5250E 0.0000 0.200 7.550 ftftinin0.000
+0.60D+0.70E 0.0000 0.267 7.550 ftftinin0.000
E Only 0.0000 0.382 7.550 ftftinin0.000
.Steel Section Properties :HSS4x4x1/4
R xx =
1.520
in
Depth =4.000 in
R yy =
1.520
in
J =12.800 in^4
Width =4.000 in
Wall Thick
=
0.250 in Zx =4.690 in^3
Area
=
3.370 in^2
Weight =12.210 plf
I xx =7.80 in^4
S xx =3.90 in^3Design Thick =0.233 in
I yy =7.800 in^4 C =6.560 in^3
S yy =3.900 in^3
Ycg =0.000 in
Page 14
Steel Column
LIC# : KW-06017322, Build:20.23.08.30 VCA CONSULTANTS, INC (c) ENERCALC INC 1983-2023
DESCRIPTION:--None--
VCA Structural
1845 W. Orangewood Ave. #200
Orange County
CA 92868
Project File: 11.ec6
Project Title:Engineer:Project ID:Project Descr:
Sketches
Page 15