57 Wheeler Ave - 2024 - INTERIOR TI. CHANGE OF USE FROM RETAIL TO MEDICAL OFFICE
CODE COMPLIANCE NOTES PANELBOARD NOTES 1. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. 2. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION, EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED. 3. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS, FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN. 4. NOTIFY THE ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS-BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS. 5. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK. 6. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY. 7. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE. 8. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES. 9. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE. 10. ALL REMOVED MATERIALS AND EQUIPMENT WHICH IS SALVAGED MATERIALS SHALL REMAIN IN THE PROPERTY OF THE OWNER. DELIVER SUCH SALVAGED MATERIALS AND EQUIPMENT ON THE PREMISES AS DIRECTED BY OWNER AND NEATLY PILE OR STORE THEM AND PROTECT FROM DAMAGED. DISPOSE OF ALL HAZARDOUS MATERIAL PER GUIDELINE OF THE STATE OF CALIFORNIA, DEPARTMENT OF HEALTH SERVICES AND OTHER AGENCIES HAVING JURISDICTION. 11. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE. REMOVE UNUSED WIRING. DEMOLITION NOTES GENERAL CONDUIT NOTES 1. USE RIGID METAL CONDUIT IN ALL AREAS EXPOSED TO WEATHER. 2. USE GROUND WIRE INSIDE ALL FLEXIBLE METAL CONDUIT. 3. METAL CONDUIT SHALL NOT BE INSTALLED IN CONTACT WITH EARTH. BUILDING STANDARDS OF THE STATE OF CALIFORNIA (CALIFORNIA CODE OF REGULATIONS, TITLE 24): ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE FOLLOWING CODES: BUILDING REGULATIONS ARE SPECIFIED IN ARTICLE VIII, SECTIONS 8010-8991 OF ARCADIA MUNICIPAL CODE. ·2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE (CAC) PART 1, TITLE 24, CA CODE OF REGULATIONS (CCR) ·2022 CALIFORNIA BUILDING CODE (CBC), BASED ON 2021 INTERNATIONAL BUILDING CODE (IBC). ·2022 CALIFORNIA ELECTRICAL CODE (CEC), BASED ON 2020 NATIONAL ELECTRICAL CODE (NEC). ·2022 CALIFORNIA MECHANICAL CODE (CMC), BASED ON 2021 UNIFORM MECHANICAL CODE (UMC). ·2022 CALIFORNIA PLUMBING CODE (CPC), BASED ON 2021 UNIFORM PLUMBING CODE (UPC). ·2022 CALIFORNIA FIRE CODE (CFC), BASED ON 2021 INTERNATIONAL FIRE CODE (IFC). ·2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSC), TITLE 24, PART 11 ·2019 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE ·2021 NFPA 99 HEALTH CARE FACILITIES CODE ·2021 NFPA 101 LIFE SAFETY CODE ·2022 NFPA 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS ·2022 CALIFORNIA ENERGY CODE REFERENCES & ABBREVIATIONS RELOCATED(R) 60 A CO CONDUIT ONLY W/PULL ROPE MAIN LUGS ONLY WEATHERPROOF MLO CU WP COPPER UNLESS OTHERWISE NOTED ABOVE FINISHED FLOOR KITCHEN EQUIPMENT DESIGNATION KEYNOTE REFERENCE DETAIL REFERENCE LIGHTING FIXTURE DESIGNATION UON AFF GROUNDG EM NL AFC VL ABOVE FINISHED COUNTER VERIFY LOCATION EMERGENCY NIGHT LIGHT GROUND FAULT INTERRUPTER FLA GFI A V C MCB FULL LOAD AMPS AMPS VOLTS CONDUIT MAIN CIRCUIT BREAKER EXISTING TO REMAIN(E) 1 E-1 1 123 (X) EXISTING TO BE DEMOLISHED ON CENTEROC NEW(N) (ER) EXISTING TO BE RELOCATED SCOPE OF WORK THIS PROJECT INCLUDES THE DEMOLITION OF ALL EXISTING LIGHTING FIXTURES, CONTROLLERS, RECEPTACLES, TELEPHONE/DATA DEVICES, FIRE ALARM DEVICES, SECURITY DEVICES, AND MINOR CONNECTIONS TO MECHANICAL EQUIPMENT, WITH ASSOCIATED CONDUIT AND WIRING TO EXISTING PANELBOARDS, WITHIN THE PROPOSED RENOVATED AREA. DURING THE RENOVATION PHASE OF THE PROJECT, THE NEW LIGHTING FIXTURES WILL BE PROVIDED IN NEW CEILINGS SPECIFIED IN THE ARCHITECTURAL SECTION. THE FIXTURES SHALL BE OF THE ENERGY SAVING LED TYPE AND SHALL BE CONTROLLED VIA WALL MOUNTED 0-10V DIMMING SWITCHES RECONNECTED TO NEW PANELBOARDS VIA A PROGRAMMABLE TOUCH-SCREEN TYPE LIGHTING CONTROL PANEL WITH 120/277VAC CONTACTS AND TIMECLOCK. ALL NEW LIGHTING SHALL CONFORM TO THE STATE OF CALIFORNIA TITLE 24 REGULATIONS. THE RENOVATION PHASE SHALL ALSO INCLUDE THE PROVISION OF 20AMP, 120VAC "SPECIFICATION-GRADE" RATED RECEPTACLES WITH CONDUIT AND WIRING BRANCH CIRCUITRY TO PANELBOARD LOCATED WITHIN THE SUITE. 4/S ROUGH-IN BOXES, FLUSH IN WALLS AND CEILINGS, WILL BE PROVIDED FOR DEFERRED APPROVAL CONTRACTS FOR TELEPHONE AND DATA OUTLETS, AS WELL AS FIRE ALARM AND NURSE CALL SYSTEM DEVICES. THE OUTLET BOXES SHALL HAVE A 3/4" CONDUIT STUBBED INTO THE ACCESSIBLE CEILING WITH PULLING LINE AND END BUSHINGS FOR PROVISION OF DEVICES, COVERPLATES AND WIRING IN OTHER DEFERRED APPROVAL CONTRACTS. BARRIERED PULL BOXES WILL BE PROVIDED ABOVE THE SECURITY DOORS IN THE SUITE FOR 120VOLT POWER AND LOW VOLTAGE WIRING FROM A TRANSFORMER FURNISHED AND INSTALLED BY THE SECURITY CONTRACTOR. POWER FOR ANY NEW MECHANICAL HVAC EQUIPMENT SHALL BE INCLUDED IN THIS ELECTRICAL SECTION AS REQUIRED. CONTROL MODULE FIRE TERMINAL CABINET DOOR HOLD OPEN DEVICE TAMPER SWITCH WATER FLOW SWITCH MONITOR MODULE SUPERVISION RELAY PHOTOELECTRIC SENSOR IN-DUCT DETECTOR PROVIDED BY MECHANICAL HEAT SENSOR W/ RATE-OF-RISE FIRE SYSTEM ANNUNCIATOR +48" A.F.F. TO TOP OF DEVICE FIRE CONTROL PANEL +72" A.F.F. TO TOP OF DEVICE PULL STATION +48" A.F.F. TO TOP OF DEVICE RELAY MODULE CONTROL RELAY, SPDT, W/ LED REMOTE POWER SUPPLY +72" A.F.F. TO TOP OF DEVICE 24VDC HORN +90" A.F.F. TO TOP OF DEVICE 24VDC AUDIBLE/STROBE UNIT (15CD) +80" A.F.F. TO TOP OF DEVICE (CD=CANDELA) 24VDC STROBE UNIT (15CD) +80" A.F.F. TO TOP OF DEVICE (CD=CANDELA) DETECTOR 120 VAC W/9VDC BATTERY FIRE SMOKE DAMPER IN MECHANICAL DUCTWORK INITIATED VIA SMOKE DETECTOR (PROVIDED BY MECHANICAL) FIRE ALARM SYSTEM SYMBOLS FIRE ALARM SYSTEM DEFERRED APPROVAL NOTES NURSE CALL SYSTEM DEFERRED APPROVAL NOTES NURSE CALL SYSTEM SYMBOLS CEILING PUBLIC ADDRESS SPEAKER NURSE CALL CODE BLUE EMERGENCY PULL STATION NURSE CALL EMERGENCY DOME LIGHT (ABOVE DOOR) STAFF EMERGENCY NURSE CALL STATION DUTY STAFF NURSE CALL STATION CB NURSE CALL CORD PULL STATION 1. DESIGN BUILD NURSE CALL SYSTEM: CONTRACTOR SHALL PROVIDE ALL NURSE CALL COMPONENTS REQUIRED BY CITY, COUNTY AND STATE CODES, ALONG WITH ANY OWNER REQUIREMENTS. DRAWINGS ARE INTENDED TO INDICATE NURSE CALL REQUIREMENTS AND SHALL NOT BE INTERPRETED AS A FINAL DESIGN OR USED FOR TAKE-OFF PURPOSES BY THE CONTRACTOR. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETED NURSE CALL DESIGN INCLUDING ALL NURSE CALL DEVICES, CONDUIT AND WIRING, WHETHER DEPICTED ON THE BID DOCUMENTS OR NOT. 2. THE NURSE CALL SYSTEM SHALL CONFORM TO ARTICLE 517 OF THE CALIFORNIA ELECTRIC CODE. 3. PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS WILL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES AND MUST BE UL LISTED. 4. A MINIMUM OF 48 HOURS NOTICE SHALL BE REQUIRED FOR ANY INSPECTION AND/OR TESTING. 5. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF THE INSPECTOR OF RECORD. 6. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE TENANT IMPROVEMENT IN THE BUILDING IN ACCORDANCE WITH THE 2022 EDITION OF TITLE 24, CALIFORNIA CODE OF REGULATIONS. 7. CORDS FOR TOILET AND SHOWER PULL CORD STATIONS SHALL BE WITHIN 12 INCHES OF THE FINISHED FLOOR. 8 NEW CONDUIT AND BACKBOXES TO BE INSTALLED BY ELECTRICAL CONTRACTOR. 9. A UNIQUE AUDIBLE AND VISUAL ALARM/SIGNAL WILL BE PROVIDED AT THE ATTENDING NURSES STATION AND VISUAL DEVICE ABOVE EACH PATIENT UNIT OR ROOM FOR CODE BLUE PER CEC 517-123(C)(3). THE CODE BLUE WILL BE THE FIRST PRIORITY ALARM ON THE NURSE CALL MASTER CONSOLE. 10. NURSE CALL DEVICES SHOWN AT A HEAD WALL LOCATION WHERE THERE IS NO HEADWALL ASSEMBLY, ARE TO BE MOUNTED FLUSH IN THE WALL AS DIRECTED BY THE ARCHITECT. 11. THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER. THE SYSTEM HAVE AN F RATING/T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED WITHIN THE CAVITY OF A WALL ABOVE THE FLOOR AND BELOW THE FLOOR DO NOT REQUIRE A T-RATING. CBC 713..4.1.1.2. 12. THE NURSE CALL IS NOT BEING INTEGRATED TO THE FIRE ALARM SYSTEM BECAUSE IT IS A STAND-ALONE SYSTEM WITH ANNUNCIATION OUTSIDE THE PATIENT ROOMS. 1. DESIGN BUILD FIRE ALARM SYSTEM: CONTRACTOR SHALL PROVIDE ALL FIRE ALARM COMPONENTS REQUIRED BY CITY, COUNTY AND STATE CODES ALONG WITH ANY OWNER REQUIREMENTS. 2. CONTRACTOR SHALL COMPLY WITH THE LATEST ADOPTED CITY, COUNTY AND STATE CODES. 3. CONTRACTOR SHALL PROVIDE ARCHITECT, ENGINEER AND OWNER WITH FULL SET OF FIRE ALARM DRAWINGS AND SUBMITTAL BOOKLET FOR REVIEW. 4. CONTRACTOR SHALL BE REQUIRED TO HAVE PRIOR APPROVAL OF THE FIRE ALARM DESIGN FROM THE ARCHITECT, ENGINEER AND OWNER PRIOR TO SUBMITTING FOR PERMIT. 5. CONTRACTOR SHALL OBTAIN PERMIT PRIOR TO STARTING ANY WORK. 6. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATING BUILDING STANDARD REQUIREMENTS WITH OWNER'S REPRESENTATIVE PRIOR TO THE START OF WORK. ANY SPECIFIED OR OPERATIONAL FEATURE NOT SPECIFICALLY ADDRESSED PRIOR TO THE BID DATE WILL BE REQUIRED TO BE MET WITHOUT EXCEPTION/CHANGE ORDER. 7. THE FIRE ALARM VENDOR/CONTRACTOR/DESIGN BUILDER SHALL PROVIDE ALL OF THE APPLICATION ENGINEERING, DOCUMENTATION, AND TESTING REQUIRED OBTAIN LOCAL AND STATE FIRE MARSHAL'S APPROVAL AND SYSTEM ACCEPTANCE. 8. CONTRACTOR SHALL PROVIDE THE EQUIPMENT AND DEVICES INDICATED HEREIN AND ON THE DRAWINGS AND VARIOUS OTHER COMPONENTS INCLUDING FIRE ALARM PANEL, FIRE SYSTEM ANNUNCIATOR, REMOTE POWER SUPPLIES, ADDRESSABLE SMOKE DETECTORS, ADDRESSABLE HEAT DETECTOR, ADDRESSABLE RELAY MODULE, ETC. AS REQUIRED. 9. CONTRACTOR SHALL PROVIDE A SYSTEM DIAGRAM INCLUDING RISER DIAGRAMS AND FLOOR PLANS INDICATING ALL CONDUIT AND WIRE SIZES AND QUANTITIES BETWEEN ALL DEVICES. COLOR CODING FOR DEVICE WIRINGS SHALL MATCH THE EXISTING INSTALLATIONS. 10. CONTRACTOR SHALL PROVIDE ALL CONDUITS, WIRES AND CABLES AS REQUIRED AND RECOMMENDED BY FIRE ALARM MANUFACTURER. CONTRACTOR SHALL INSTALL AND CONNECT ALL SYSTEM COMPONENT IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. 11. CONTRACTOR SHALL PROVIDE VOLTAGE DROP AND BATTERY BACK-UP CALCULATIONS REQUIRED BY THE APPROVED AGENCIES. 12. CONTRACTOR SHALL SUBMIT CATALOG CUTS, TECHNICAL DATA, CONDUCTOR TYPE AND DESCRIPTIVE LITERATURE ON ALL COMPONENTS TO BE FURNISHED INCLUDING STATE FIRE MARSHAL LISTINGS (CALIFORNIA). 13. CONTRACTOR SHALL SUBMIT CALIBRATION AND TESTS REPORTS PRIOR TO FINAL ACCEPTANCE. 14. CONTRACTOR SHALL PROVIDE ADDITIONAL DEVICES REQUIRED BY THE FIRE MARSHAL FOR THE FINAL ACCEPTANCE TEST, IT SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST. 15. CONTRACTOR SHALL PROVIDE A MINIMUM 1 YEAR GUARANTEE CERTIFICATE FOR LABOR AND MATERIALS, INSTRUCTIONS AND MAINTENANCE MANUAL WITH A 24 HOUR FACTORY REPRESENTATIVE SUPPORT PHONE NUMBER. PROVIDE 8 HOURS OF INSTRUCTION TIME TO SHOW THE OWNER'S REPRESENTATIVE THE FUNCTION OF THE SYSTEM. SS DS NC 1. PROVIDE NEW BREAKERS AS REQUIRED. EXISTING BREAKERS MAY BE REQUIRED TO BE REARRANGED. ALL NEW DEVICES TO MATCH EXISTING EQUIPMENT MANUFACTURER. ALL EXISTING EQUIPMENT RE-USED ON THIS PROJECT SHALL BE WARRANTED AS SAME AS NEW FOR PERIOD OF ONE YEAR. CONTRACTOR SHALL HAVE OPTION TO PROVIDE NEW EQUIPMENT. 2. NEW CIRCUIT BREAKERS IN EXISTING PANEL BOARD OR SWITCHBOARD BE 100% RATED SHORT CIRCUIT DUTY FOR AVAILABLE FAULT. 3. NEW PANEL BOARDS 208/120VAC ARE BASED ON SQUARE D NQOB SERIES, WITH COPPER BUSES. ALL BRANCH C.B. SHALL BE RATED FOR 10 KAIC MINIMUM, U.O.N. AND SHALL HAVE MAIN CIRCUIT BREAKER RATED FOR 22 KAIC, UNLESS OTHERWISE NOTED. 4. NEW PANELBOARDS SHALL HAVE FLUSH LOCKABLE DOOR KEY TO MATCH EXISTING FACILITY MASTER KEY. 5. ALL CIRCUIT BREAKERS IN THE PANEL BOARD SHALL HAVE PADLOCK OFF DEVICES AND ALL CIRCUIT BREAKERS FEEDING ESSENTIAL LOAD SHALL HAVE LOCK-ON DEVICES AS INDICATED BY (*). 6. PANELBOARDS SHALL BE PROVIDED WITH PANEL FRONT WITH CONTINUOUS PIANO HINGE. CD CD L R1 DH T W P I Zr Zc FSA FTC RPS FCP S F M WALL MOUNTED LOW LEVEL EXIT SIGN. DIRECTIONAL ARROW AS INDICATED IN PLANS. POWERED, NON-POWERED OR 90 MINUTE MINIMUM EM BATTERY PACK PER LIGHTING FIXTURE SCHEDULE. WALL MOUNTED LOW LEVEL EXIT SIGN. DIRECTIONAL ARROW AS INDICATED IN PLANS. POWERED, NON-POWERED OR 90 MINUTE MINIMUM EM BATTERY PACK PER LIGHTING FIXTURE SCHEDULE. WALL MOUNTED EXIT SIGN. NUMBER OF FACES AND DIRECTIONAL ARROWS AS INDICATED IN PLANS. POWERED, NON-POWERED OR 90 MINUTE MIN EM BATTERY PACK PER LIGHTING FIXTURE SCHEDULE. CEILING MOUNTED EXIT SIGN. NUMBER OF FACES AND DIRECTIONAL ARROWS AS INDICATED IN PLANS. POWERED, NON-POWERED OR 90 MINUTE MINIMUM EM BATTERY PACK PER LIGHTING FIXTURE SCHEDULE. LIGHT LINEWEIGHT REPRESENTS WORK WHICH IS EXISTING TO REMAIN UNDISTURBED. HEAVY LINEWEIGHT REPRESENTS WORK TO BE COMPLETED AS PART OF THIS PACKAGE. DASHED LINEWEIGHT REPRESENTS WORK WHICH IS DEMO TO BE DEMOLISHED. CONTROL ENCLOSURE FOR LIGHTING, BUILDING AUTOMATION SYSTEM , EQUIPMENT CONTROL, ETC.. AS INDICATED ON PLANS. BRANCH CIRCUIT PANELBOARD, FLUSH MOUNTED. VOLTAGE AND NUMBER OF CIRCUITS PER PANEL SCHEDULE. WALL MOUNTED 120V BUZZER. PROVIDE EDWARDS #1064-N5 OR EQUAL. 6" WALL MOUNTED 120V BELL. PROVIDE EDWARDS #340-6N5 OR EQUAL. ab - INDICATES QUANTITY OF SWITCHES TO BE LOCATED AT THIS LOCATION AND THEIR CONTROL IDENTIFICATION 3 - INDICATES 3-WAY SWITCH COMBINATION DISCONNECT SWITCH/MAGNETIC MOTOR STARTER, AMPS, POLES, FUSE CLASS (SIZE AS INDICATED), AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -UON, AND H-O-A (HAND-OFF-AUTO) SWITCH. WP - INDICATES NEMA 3R ENCLOSURE FUSED DISCONNECT SWITCH, AMPS, POLES AND FUSE CLASS (SIZE AS INDICATED). OPEN - INDICATES NON-FUSED WP - INDICATES NEMA 3R ENCLOSURE INDICATES CONDUIT RISER WITHIN BUILDING WALL. REFER TO CONDUIT SYMBOL ABOVE. INDICATES CONDUIT DROP WITHIN BUILDING WALL. REFER TO CONDUIT SYMBOL ABOVE. HOMERUN TO DESTINATION AS INDICATED. REFER TO CONDUIT SYMBOL ABOVE. CONDUIT ROUTED BELOW FINISHED GRADE AND / OR CONCRETE SLAB. TICK MARKS INDICATE QUANTITY OF #12 THHN / THWN CONDUCTORS -UON. CONDUITS SHOWN WITH NO TICK MARKS INDICATE 2 #12 THHN / THWN CONDUCTORS -UON. CONDUIT SHALL BE 3/4" MINIMUM -UON. INCLUDE CODE SIZED COPPER BOND CONDUCTOR (NOT SHOWN ON PLAN) IN ALL CONDUIT RUNS. CONDUIT CONCEALED WITHIN BUILDING WALLS OR CEILING SPACE. TICK MARKS INDICATE QUANTITY OF #12 THHN / THWN CONDUCTORS -UON. CONDUIT SHOWN WITH NO TICK MARKS INDICATE 2 #12 THHN / THWN CONDUCTORS -UON. CONDUIT SHALL BE 3/4" MINIMUM -UON. INCLUDE CODE SIZED COPPER BOND CONDUCTOR (NOT SHOWN ON PLAN) IN ALL CONDUIT RUNS. SERVICE ENTRANCE OR DISTRIBUTION EQUIPMENT AS SPECIFIED. BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED. VOLTAGE AND NUMBER OF CIRCUITS PER PANEL SCHEDULE. MOTOR OUTLET, HP OR FLA -VOLTS & PHASE AS INDICATED. VERIFY ELECTRICAL CHARACTERISTICS AND CONNECTION REQUIREMENTS WITH INSTALLED EQUIPMENT MANUFACTURER PRIOR TO ANY ROUGH-IN WORK. MAGNETIC MOTOR STARTER, POLES AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -UON, AND H.O.A. (HAND-OFF-AUTO) SWITCH. STANDARD 20A, 120V-1Ø GROUNDING TYPE SIMPLEX RECEPTACLE MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE QUAD RECEPTACLE MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE FLUSH MOUNTED IN CEILING. STANDARD 20A, 120V-1Ø GROUNDING TYPE QUAD RECEPTACLE FLUSH MOUNTED IN CEILING. STANDARD 20A, 120V-1Ø GROUNDING TYPE SIMPLEX RECEPTACLE, SWITCHED OR DIMMED (AS NOTED), MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE - MOUNTED @ +18" AFF STANDARD 20A, 120V-1Ø GROUNDING TYPE "GROUND FAULT INTERRUPTER" (G.F.I.) RECEPTACLE MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE QUAD RECEPTACLE, MOUNTED AT +18" AFF - UON. STANDARD 20A, 120V-1Ø GROUNDING TYPE QUAD RECEPTACLE, "GROUND FAULT INTERRUPTER" (GFI) MOUNTED AT +18" AFF - UON. SPECIAL RECEPTACLE MOUNTED AT +18" AFF - UON. AMPS, VOLTS & PHASE AS INDICATED ON PLANS. VERIFY NEMA CONFIGURATION WITH INSTALLED EQUIPMENT SUPPLIER PRIOR TO PLACING ORDER. STANDARD 15A, 120V-1Ø GROUNDING TYPE SIMPLEX CLOCK RECEPTACLE. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED WITHIN FLUSH FLOOR BOX. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED WITHIN FLUSH FLOOR BOX. STANDARD 20A, 120V-1Ø GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED 4" ABOVE COUNTER BACK SPLASH, UON. COORDINATE FINAL HEIGHT WITH ARCHITECT / INTERIOR DESIGNER. STANDARD 20A, 120V-1Ø GROUNDING TYPE "GROUND FAULT INTERRUPTER" DUPLEX RECEPTACLE MOUNTED ABOVE 4" ABOVE COUNTER BACK SPLASH, UON. COORDINATE FINAL HEIGHT WITH ARCHITECT / INTERIOR DESIGNER. J JUNCTION BOX, CEILING OR ABOVE CEILING MOUNTED, SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS AND/OR CONDUCTORS PASSING THRU. J JUNCTION BOX MOUNTED ON CONDUIT STUB-UP, SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS AND/OR CONDUCTORS PASSING THRU. JUNCTION BOX FOR SPLICES ONLY AND SHALL CONTAIN NO DEVICES. J JUNCTION BOX, FLUSH WALL MOUNTED, SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS AND/OR CONDUCTORS PASSING THRU. SM MANUAL MOTOR STARTER SWITCH. HORSEPOWER RATED 120V-1Ø - UON. PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION. STANDARD 20A, 120V-1Ø GROUNDING TYPE QUAD RECEPTACLE, RED IN COLOR MOUNTED WITHIN FLUSH FLOOR BOX. ELECTRICAL SYMBOLS LIST EPO RED MUSHROOM TYPE PUSH BUTTON MOUNTED AT +45" AFF. PUSH BUTTON MOUNTED AT +45" AFF. PROVIDE EDWARDS #821 BUTTON WITH #149-1 STAINLESS STEEL COVER PLATE. Sab STANDARD 20A, 120/277V-1Ø SPST TOGGLE SWITCH MOUNTED AT +45" AFF. D ab SLIDING TYPE DIMMER SWITCH WITH AIR GAP OFF MOUNTED AT +45" AFF. DIMMER TO BE COMPATIBLE WITH LAMP TYPE UTILIZED AND THE CONTROL ZONE LOAD. VERIFY DE-RATING WITH MANUFACTURER'S LITERATURE. INDICATES EXISTING CONDUIT WITH WIRING AS INDICATED.(E) GENERAL NOTES 1. PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL SYSTEM. 2. COORDINATE AND OBTAIN APPROVALS FROM ALL RESPECTIVE UTILITY COMPANIES AS REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. 3. INSTALL RACEWAY SYSTEMS AS FOLLOWS: a. USE RIGID GALVANIZED STEEL IN ALL AREAS EXPOSED TO WEATHER OR PHYSICAL DAMAGE. b. USE FLEXIBLE METALLIC CONDUIT ONLY IN AREAS AS PERMITTED BY LOCAL CODE AUTHORITY. USE SEAL-TITE IN AREAS EXPOSED TO WEATHER. c. USE COMPRESSION TYPE FITTINGS FOR ELECTRICAL METALLIC TUBING WHERE UTILIZED. d. USE P.V.C. CONDUIT UNDERGROUND WITH CODE SIZED GROUND. CONDUIT RISERS AND STUBS ABOVE GRADE SHALL BE I.M.C. WITH HALF-LAPPED TAPE COVERING OR P.V.C. 4. COATING. ALL NEW WIRING SHALL BE COPPER TYPE "THHN/THWN" -UON. 5. CONDUIT FOR ROOF MOUNTED EQUIPMENT SHALL BE ROUTED BELOW THE ROOF WITHIN THE BUILDING. 6. ALL FIXTURE, DEVICE, ETC.. LOCATIONS SHALL BE VERIFIED WITH ARCHITECTURAL DRAWINGS AS WELL AS EQUIPMENT SUPPLIER REQUIREMENTS PRIOR TO ANY ROUGH-IN WORK. 7. ALL LIGHTING FIXTURES SHALL BE MOUNTED AND SUPPORTED IN ACCORDANCE WITH OSHA STANDARDS AND ALL LOCAL, STATE, AND NATIONAL ELECTRICAL CODES. 8. ELECTRONIC BALLASTS FOR FLUORESCENT LIGHTING FIXTURES SHALL HAVE A MINIMUM BALLAST FACTOR (BF) OF 0.90 OR GREATER UNLESS OTHERWISE SPECIFIED. 9. ELECTRICAL CONTRACTOR SHALL PROVIDE LIGHTING FIXTURE MOUNTING KITS AS REQUIRED TO SUIT THE EXACT TYPE OF CEILING TO WHICH THEY ARE MOUNTED. 10. THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE INTENT OF EQUIPMENT, DEVICES, ETC... TO BE CONNECTED AND THE CIRCUITS TO WHICH THEY ARE TO BE CONNECTED TO. CONTRACTOR SHALL INSTALL ALL CONDUIT, J-BOXES, ETC... AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. 11. ALL EXTERIOR EQUIPMENT SHALL BE WEATHERPROOF. 12. ELECTRICAL CONTRACTOR SHALL PERFORM ALL WORK IN STRICT ACCORDANCE WITH ALL LOCAL, STATE, AND NATIONAL GOVERNING CODES. 13. ALL EQUIPMENT SHALL BE NEW AND BEAR A "UL" LABEL -U.O.N. 14. ELECTRICAL CONTRACTOR SHALL SECURE AND PAY FOR ALL NECESSARY BUILDING PERMITS. 15. COMPLETE ELECTRICAL INSTALLATION SHALL BE GUARANTEED IN WRITING FOR A PERIOD OF (1) YEAR - UON. 16. ELECTRICAL CONTRACTOR SHALL INCLUDE IN BID -COSTS FOR ALL HVAC CONTROL COMPONENTS, CONDUITS, DEVICES, ETC... AS DEEMED NECESSARY FOR A COMPLETE AND OPERATIONAL HVAC SYSTEM. REFER TO MECHANICAL DRAWINGS, DIAGRAMS AND SPECS FOR THOSE ITEMS REQUIRED UNDER THE ELECTRICAL SECTION OF THIS CONTRACT. 17. ELECTRICAL CONTRACTOR SHALL VISIT SITE PRIOR TO BID DATE, TO VERIFY ALL EXISTING CONDITIONS TO BE ENCOUNTERED IN THE INSTALLATION OF ALL NEW EQUIPMENT, FIXTURES, DEVICES, FEEDERS, ETC.. EXACT INSTALLATION METHOD AND REQUIREMENTS SHALL BE VERIFIED AND DETERMINED PRIOR TO BID DATE. CONTRACTORS SHALL IMMEDIATELY NOTIFY THIS ENGINEER OF ANY REQUIRED MODIFICATIONS WHICH ARE NOT SHOWN ON THESE DRAWINGS. SUBMITTAL OF BID INDICATES CONTRACTOR IS AWARE OF ALL JOB SITE CONDITIONS AND WORK TO BE PERFORMED. 18. ALL ELECTRICAL EQUIPMENT CHARACTERISTICS, LOCATIONS, AND CONNECTION REQUIREMENTS SHALL BE VERIFIED PRIOR TO ANY ROUGH-IN WORK. 19. ELECTRICAL CONTRACTOR SHALL FURNISH THE FOLLOWING SHOP DRAWINGS FOR PRIOR APPROVAL: a. ALL LIGHT FIXTURES AND CONTROLS. b. ALL ELECTRICAL SERVICE EQUIPMENT, DISTRIBUTION EQUIPMENT AND PANELBOARDS. c. ALL CONDUIT AND CONDUCTORS. d.ALL DISCONNECT SWITCHES. e. ALL DEVICES. 20. THESE ITEMS SHALL BE APPROVED BY THIS OFFICE PRIOR TO ANY COMMENCEMENT OF PLACING ORDERS OR PERFORMING ANY ROUGH-IN WORK. 21. COMPLETE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH THE PRESENTLYADOPTED EDITION OF THE NEC ARTICLE 250, AND REDUNDANT GROUNDING SHALL BE UTILIZED IN EXAM ROOMS PER CEC 517. 22. PENETRATIONS OF ALL FIRE RATED WALLS OR CEILINGS SHALL BE FIRE RATED IN ACCORDANCE WITH ALL LOCAL, STATE, AND NATIONAL CODES. 23. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL MAJOR ELECTRICAL EQUIPMENT. 24. PROVIDE THE OWNER AND THIS ENGINEER WITH ONE SET OF ELECTRICAL "AS-BUILTS" AT THE COMPLETION OF JOB. 25. ALL DISCONNECT SWITCHES TO BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS. 26. ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BASE BID AND CONTRACT THE INSTALLATION AND COMMISSIONING OF ALL LIGHTING CONTROLS INCLUDING BUT NOT LIMITED TO OCCUPANCY SENSORS, TIMERS, DIMMING CONTROLS, AND DAY-LIT ZONE CONTROLS AND IS REQUIRED TO VERIFY THAT THE LIGHTING CONTROLS ARE ADJUSTED, PROGRAMMED AND FUNCTIONING IN ACCORDANCE WITH THE DESIGN AND MANUFACTURE'S INSTALLATION INSTRUCTIONS. THE CONTRACTOR IS ALSO RESPONSIBLE FOR SUBMITTING DOCUMENTATION (INSTALLATION FORMS [NRCI]) CERTIFYING THAT THE LIGHTING SYSTEMS ARE IN COMPLIANCE WITH OR EXCEED THE PERFORMANCE REQUIREMENTS. FOR PROJECTS 10,000 SQFT OR OVER, CONTRACTOR SHALL ALSO FURNISH CEC T24 REQUIRED FUNCTIONAL PERFORMANCE TESTING BY A CERTIFIED LIGHTING CONTROLS TEST TECHNICIAN (CALCATT) AND SUBMIT DOCUMENTATION (ACCEPTANCE FORMS [NRCA]) AS REQUIRED. 27. PROVIDE GREEN EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDER AND BRANCH CIRCUIT CONDUITS SIZED PER NEC 250-122. 28. ALL MULTI-WIRE BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTORS WITHIN THE CONDUIT. ALL RECEPTACLE OUTLETS AND FIXED EQUIPMENT WITHIN WET LOCATIONS SHALL HAVE GFCI PROTECTION (517.20[A]). FIXED EQUIPMENT INSTALLED IN WET LOCATIONS WHERE AN ISOLATED POWER SYSTEM IS UTILIZED SHALL BE LISTED FOR THE PURPOSE AND INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF SECTION 517-160 FOR ISOLATED POWER SYSTEMS. (517.20{B}). LIGHTING FIXTURES IN EACH ROOM AND PASSAGEWAY SHALL BE EQUIPPED WITH A PROTECTIVE LENS OR DIFFUSER. (517.22{C}). SWITCHES CONTROLLING LIGHTING FIXTURES AND RECEPTACLE OUTLETS POWERED BY AN EMERGENCY SOURCE SHALL BE IDENTIFIED CONSPICUOUSLY AND PERMANENTLY IN A MANNER SUCH AS RED COLORED COVERPLATES AND/OR RED COLORED DEVICES. (517.45{E}). ALL CONDUIT ON THIS PROJECT SHALL BE EITHER EMT OR GALAVANIZED RIGID STEEL PIPE AS REQUIRED. NO PVC CONDUIT SHALL BE USED ON THIS PROJECT. 29. 30. 31. 32. 33. A 60 123 1 E-1 1 ON CENTEROC EXISTING TO BE RELOCATED (E) (ER) EXISTING TO REMAIN MAIN CIRCUIT BREAKER CONDUIT VOLTS AMPS FULL LOAD AMPS MCB C V A GFI FLA GROUND FAULT INTERRUPTER NIGHT LIGHT EMERGENCY VERIFY LOCATION ABOVE FINISHED COUNTER VL AFC NL EM G GROUND AFF UON LIGHTING FIXTURE DESIGNATION DETAIL REFERENCE KEYNOTE REFERENCE KITCHEN EQUIPMENT DESIGNATION ABOVE FINISH FLOOR UNLESS OTHERWISE NOTED COPPER WP CU MLO WEATHERPROOF MAIN LUGS ONLY CONDUIT ONLY W/PULL ROPECO NEW(N)(R) RELOCATED (X) EXISTING TO BE DEMOLISHED REFERENCES & ABBREVIATIONS Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N IAELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States 12" = 1'-0" E0.0 ELECTRICAL SYMBOL, NOTES AND SHEET INDEX 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 Sheet List - Electrical Sheet Number Sheet Name E0.0 ELECTRICAL SYMBOL, NOTES AND SHEET INDEX E0.2 SINGLE LINE DIAGRAM AND LOAD CALCULATIONS E0.3 PANEL SCHEDULES E0.4 LIGHTING FIXTURE SCHEDULE & MECHANICAL CONNECTION SCHEDULE E1.0 ELECTRICAL OVERALL PLAN - LEVEL 01 E1.1 DEMOLITION - POWER AND SIGNAL PLAN - LEVEL 01 E2.1 POWER PLAN - LEVEL 01 E2.2 SIGNAL PLAN - LEVEL 01 E2.3 LIGHTING PLAN - LEVEL 01 E2.4 ELECTRICAL ROOF PLAN E2.5 EMERGENCY LIGHTING PHOTOMETRICS E2.6 ELECTRICAL/MECHANICAL PLAN - LEVEL 01 E2.7 FIRE ALARM PLAN - LEVEL 01 E2.8 TITLE 24 CONFORMANCE E3.1 ELECTRICAL DETAILS E3.2 ELECTRICAL DETAILS E4.1 LIGHTING CONTROLS 2 01.19.2024 Plan Check Resubmittal #2 THIS FACILITY IS A MINOR TENANT IMPROVEMENT FOR GENERAL APPOINTMENT EXAMINATIONS ONLY WITH ANCILLARY OFFICE AND RECEPTION AREAS. THEREFORE, THIS FACILITY IS CLASSIFIED AS "GENERAL EXAMINATION AND CONSULTATION" AS DEFINED BY THE MAY 8, 2022 HCAi REQUIREMENTS AND THE STATE OF CALIFORNIA ELECTRICAL CODE SECTION 517.30. ADDITIONALLY, PARTIAL ITEMS ARE ALSO BEING ADDED TO THE PROJECT THAT ARE BEYOND THE REQUIREMENTS OF THOSE DOCUMENTS, TO INCLUDED A NURSE CALL SIGNALING AND REDUNDANT GROUNDING WITHIN EXAMINATION ROOMS. LOAD CALCULATIONS: GENERAL NOTES: SHEET NOTES: MMMMMM 3000A 3P 3P 1000A M 3P 600A M 3P 600A M 3P 1600A M 3P 200A "DP2" PANEL PANEL "H" 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 200A 3P 1000A - - PANEL "HP-1V" PANEL "HP-1L" HOUSE (E) HOUSE (E) PANEL "HP-1P" HOUSE (E) PANEL "EV1" (E) VEH. CHGRDIST. (E) PANEL "UNIT 2ABC" PANEL "D" (E) "H" PANEL (R) PANEL "D" M (E) PANEL "F" M (N)(E) F F (E)(E) (E) (E) (E) (E) (E) (E)(E)(E)(E) (E) (E) (E) (E) (E) (E) (E) EXISTING 3,000A SERVICE FROM UTILITY COMPANY TRANSFORMER (TO REMAIN) UGPS 3,000A EXISTING 1"C-1#3/0CU. BONDED TO COLD WATER PIPE PER NEC 250.104(A) (TO REMAIN) EXISTING 1"C-1#3/0CU. GROUND PER NEC 250.50, 250.52 (A1-3), 250.53 (C & D) A B C HOUSE (E) MAIN SWITCHBOARD "MSA" 3000A, 208/120V, 3∅ - 4W, 65kAIC FEEDER SCHEDULE 023 NOM. AMPS 3 - PHASE, 3 WIRE SYMBOL 20 3/4"C-3#12 AWG CONDUCTOR CONDUCTOR 3/4"C-4#12 AWG SYMBOL 3 - PHASE, 4 WIRE 024 025 3 - PHASE, 5 WIRE (200%N) SYMBOL 3/4"C-3#12 AWG & 1#8 N CONDUCTOR NOTE: ALL WIRE TYPE DUAL RATED THHN/THWN, 90 C,600V, COPPER U.O.N. GROUND EQUIPMENT #12 #103/4"C(3)#10 AWG &(1)#6 (N)0350343/4"C(4)#10 AWG3/4"C(3)#10 AWG30 033 04340 3/4"C(3)#8 AWG 1"C(4)#8 AWG044 045 1"C(3)#8 & (1)#4 (N)#10 #101-1/4"C(3)#4 AWG & (1)#1 (N)065064 1-1/4"C(4)#4 AWG1-1/4"C(3)#4 AWG60 063 05350 1-1/4"C(3)#6 AWG 1-1/4"C(4)#6 AWG054 055 1-1/4"C(3)#6 AWG & (1)#4 (N)#10 #81-1/2"C(3)#2 & (1)#1/0 (N)095094 1-1/2"C(4)#2 AWG1-1/4"C(3)#2 AWG90 093 07370 1-1/4"C(3)#4 AWG 1-1/4"C(4)#4 AWG074 075 1-1/4"C(3)#4 & (1)#1/0 (N)#8 #81-1/2"C(3)#1 & (1) #3/0 (N)1051041-1/2"C(4)#1 AWG1-1/2"C(3)#1 AWG100 103 123125 1-1/2"C(3)#1/0 AWG 2"C(4)#1/0 AWG124 125 2"C(3)#1/0 & (1)#250 KCML (N)#6 #44"C(5)#350KCMIL305304 4"C(4)#350KCMIL4"C(3)#350KCMIL300 303 253250 3"C(3)#250KCMIL 3"C(4)#250KCMIL254 255 3"C(5)#250KCMIL #4 #62-1/2"C(5)#3/0 AWG205204 2"C(4)#3/0 AWG2"C(3)#3/0 AWG200 203 223225 2"C(3)#4/0 AWG 2-1/2"C(4)#4/0 AWG224 225 2-1/2"C(5)#4/0 AWG #4 #62"C(5)#1/0 AWG155154 2"C(4)#1/0 AWG1-1/2"C(3)#1/0 AWG150 153 173175 2"C(3)#2/0 AWG 2"C(4)#2/0 AWG174 175 2"C(5)#2/0 AWG #6 #2/0(3)4"C(5)#400 KCMIL10051004 (3)4"C(4)#400 KCMIL(3)4"C(3)#400 KCMIL1000 1003 803800 (2)4"C(3)#600 KCMIL (2)4"C(4)#600 KCMIL804 805 (2)4"C(5)#600 KCMIL #1/0 #4/0(4)4"C(5)#600 KCMIL16051604 (4)4"C(4)#600 KCMIL(4)4"C(3)#600 KCMIL1600 1603 12031200 (3)4"C(3)#600 KCMIL (3)4"C(4)#600 KCMIL1204 1205 (3)4"C(5)#600 KCMIL #3/0 250(5)4"C(5)#600 KCML20052004 (5)4"C(4)#600 KCML(5)4"C(3)#600 KCML2000 2003 25032500 (6)4"C(3)#600 KCML (6)4"C(4)#600 KCML2504 2505 (6)4"C(5)#600 KCML 350 #1/0(2)4"C(5)#500 KCMIL705704 (2)4"C(4)#500 KCMIL(2)4"C(3)#500 KCMIL700 703 603600 (2)4"C(3)#350KCMIL (2)4"C(4)#350KCMIL604 605 (2)4"C(5)#350KCMIL #1 #2(2)2-1/2"C(5)#4/0 AWG455454 (2)2-1/2"C(4)#4/0 AWG(2)2"C(3)#4/0 AWG450 453 503500 (2)3"C(3)#250 KCMIL (2)3"C(4)#250 KCMIL504 505 (2)3"C(5)#250 KCMIL #2 #24"C(5)#500 KCMIL355354 4"C(4)#500 KCMIL4"C(3)#500 KCMIL350 353 403400 4"C(3)#600 KCMIL 4"C(4)#600 KCMIL404 405 4"C(5)#500 KCMIL #2 40034000 (10)4"C(3)#600 KCML (10)4"C(4)#600 KCML4004 4005 (10)4"C(5)#600 KCML 500 30033000 (8)4"C(3)#500 KCML (8)4"C(4)#500 KCML3004 3005 (8)4"C(5)#500 KCML 400 EXISTING ELECTRICAL ITEMS TO REMAIN. MAINTAIN CIRCUIT CONTINUITY. SEE PANEL SCHEDULES, SHEET E0.3. PROVIDE UPDATED TYPE WRITTEN PANEL DIRECTORY. PROVIDE ENGRAVED NAMEPLATE ON DOOR WITH NAME AND VOLTAGE. DISCONNECT AND RELOCATE EXISTING SURFACE PANELBOARD. DISCONNECT AND REMOVE EXISTING RECESSED PANELBOARD. PROVIDE NEW PANELBOARD AND RECONNECT. EXISTING SCE UTILITY METER #259000-088391. PROVIDE ENGRAVED NAMEPLATE ON BRANCH CIRCUIT BREAKER(S). INTERCEPT EXISTING UNDERGROUND FEEDER. PROVIDE 24" x 24" x 6" NEMA 1 PULLBOX AND EXTEND NEW FEEDER AS INDICATED. DISCONNECT AND REMOVE FEEDER , CUT CONDUIT BELOW SLAB AND ABANDON IN PLACE. PROVIDE ELECTRONIC KW RECORDING METER (EMONDEMON #DAE 0294-200S-KIT OR EQUAL). DISCONNECT AND REMOVE PARTIAL FEEDER IN WALL - SEE NOTE 10. PROVIDE NEW CONDUIT/CONDUCTORS AND RECONNECT TO EXISTING CIRCUIT BREAKER IN "DP2". DISCONNECT AND REMOVE CIRCUIT BREAKER. INSTALL NEW CIRCUIT BREAKER TO MATCH AIC RATING AND MANUFACTURER. 1 2 3 4 5 6 7 (E)MAIN SWITCHBOARD "MSA": 3000A, 208/120V-3∅-4W (E)AS BUILT CONNECTED LOAD DELETED LOAD (PANEL "F") DELETED LOAD (PANEL "H") DELETED LOAD (PANEL "D") ADDED LOAD (PANEL "D") ADDED LOAD (PANEL "H") TOTAL 8 9 10 1. ALL ITEMS INDICATED ON THIS SHEET ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED. 2. FEEDER LENGTHS SHOWN ARE FOR CALCULATION PURPOSES ONLY AND SHALL NOT BE USED FOR BIDDING OR MATERIAL TAKE-OFF. 3. ALL CONDUCTORS ARE TYPE THHN AWG COPPER. (N) PANEL "D": 225A, 208/120V-3∅-4W CONNECTED LOAD TOTAL 1 (E) MULTI-METER SECTION "MG-1" 1000A, 208/120V, 3∅ - 4W 1 22 4 22 4 SPARE 1 2 3 4 5 6 7 8 9 10 1 1 22 4 1 SPARE 22 4 1 (E) ELEV. #1 22 4 (E) ELEV. #2 22 4 BUSSED SPACE 1 111 (E)(E) 65432432 NEW KECK MEDICINE CLINIC (57 WHEELER) 1 EXISTING TENANT PANEL ( SECOND - FOURTH FLOORS) 10 0 4 60 4 60 4 25 4 (N) 10 (N) 8 9 (N) 6 11 (N)(N)1212 11 7 5 25 4 25 4 11 22 4 12 3 4 9 13 10 0 4 (E)200/3 13 597.2KVA = 72.2KVA = 61.9KVA = 10.2KVA = 62.0KVA = 50.7KVA = 563.7KVA = 1565.8AMPS = 62.0KVA = 62.0KVA = 172.2AMPS (N) (N) 14 25 4 14 (E)DISTRIBUTION PANEL "DP2": 600A, 208/120V-3∅-4W CONNECTED LOAD DELETED LOAD (PANEL "F") DELETED LOAD (PANEL "H") DELETED LOAD (PANEL "D") ADDED LOAD (PANEL "D") ADDED LOAD (PANEL "H") TOTAL = 144.3KVA = 72.2KVA = 61.9KVA = 10.2KVA = 62.0KVA = 50.7KVA = 112.7KVA = 313.0AMPS 15 (1 9 5 L F = 1 . 1 0 V D ) (2 0 9 L F = 1 . 5 4 V D ) (E)200/3 (N)225/315 CONTRACTOR SHALL PROVIDE 30-DAY LOAD RECORDING TO CONFIRM MAIN SWITCHBOARD "MSA" TOTAL LOAD. Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E0.2 SINGLE LINE DIAGRAM AND LOAD CALCULATIONS 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2 2 Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E0.3 PANEL SCHEDULES 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 Notes: Total Est. Demand:172 A Total Conn.:168 A Total Est. Demand:61975 VA Lighting 5732 VA 125.00% 7165 VA Total Conn. Load:60542 VA Power - General 54810 VA 100.00% 54810 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:206 A 175 A 135 A Total Load:24024 VA 20356 VA 16162 VA 71 Space -- 1 -- -- 1 -- Space 72 69 Space -- 1 -- -- 1 -- Space 70 67 Space -- 1 -- -- 1 -- Space 68 65 Spare 20 A 1 0 0 1 20 A Spare 66 63 Spare 20 A 1 0 0 1 20 A Spare 64 61 Spare 20 A 1 0 0 1 20 A Spare 62 59 Spare 20 A 1 0 0 1 20 A Spare 60 57 Power TEAM STATION 137 20 A 1 1080 0 1 20 A Spare 58 55 Power TEAM STATION 137 20 A 1 1080 100 1 20 A NCP NURSE CALL PANEL 56 53 -- -- -- 5000 100 1 20 A LCP-1 54 51 -- -- -- 5000 0 1 20 A MFACP 52 49 WH-1 60 A 3 5000 100 1 20 A Power - CARD READER 50 47 GD - STAFF BREAKROOM 131 20 A 1 180 100 1 20 A Power - CARD READER 48 45 RECEPTS - STAFF BREAKROOM 131 20 A 1 920 150 1 20 A Power - CARD READER 46 43 Power TEAM STATION 137 20 A 1 1080 480 1 20 A Lighting EXAM 13 124 44 41 RECEPTS - TEAM STATION 115 20 A 1 1080 180 1 20 A Power POC SPECIMEN PROCESSING 108 42 39 RECEPTS - TEAM STATION 115 20 A 1 720 180 1 20 A Power POC SPECIMEN PROCESSING 108 40 37 RECEPTS - EXAM 7 119 20 A 1 1440 180 1 20 A Power POC SPECIMEN PROCESSING 108 38 35 RECEPTS - EXAM 10 120 20 A 1 1620 100 1 20 A Security Panel "SP-1"36 33 RECEPTS - EXAM 10 120 20 A 1 1440 1440 1 20 A Power FRONT DESK 100A 34 31 RECEPTS - EXAM 6 116 20 A 1 1440 1440 1 20 A Power FRONT DESK 100A 32 29 RECEPTS - EXAM 9 117 20 A 1 1260 1500 1 20 A Power STAFF LOCKERS 138B, COPIER 30 27 RECEPTS - SOIL 126 20 A 1 1440 1543 1 20 A Lighting STAFF LOCKERS 138C 28 25 RECEPTS - EXAM ROOM HALLWAY A 102A 20 A 1 1440 1260 1 20 A RECEPTS - TOUCHDOWN 102B.1 26 23 RECEPTS - EXAM 13 124 20 A 1 1080 1080 1 20 A RECEPTS - EXAM 1 112 24 21 Spare 20 A 1 0 1620 1 20 A RECEPTS - WOMEN'S HEALTH EXAM 4 113 22 19 Power TEAM STATION 137 20 A 1 900 200 1 20 A NCAP-1, 2 20 17 RECEPTS - STAFF BREAKROOM 131 20 A 1 360 180 1 20 A RECEPTS - WAITING 101 18 15 LAV SENSOR - STAFF TOILET 132 20 A 1 180 1260 1 20 A RECEPTS - CONSULT 104 16 13 RECEPTS - STAFF BREAKROOM 131 20 A 1 180 1440 1 20 A RECEPTS - WAITING 101 14 11 RECEPTS - STAFF TOILET 132 20 A 1 1080 180 1 30 A RECEPTS - IDF 106, UPS 12 9 RECEPTS - OFFICE 135 20 A 1 900 720 1 20 A RECEPTS - IDF 106 10 7 RECEPTS - OFFICE 135 20 A 1 1080 1080 1 20 A RECEPTS - IDF 106 8 5 RECEPTS - WORKROOM 136 20 A 1 360 722 1 20 A Lighting SOIL 126 6 3 RECEPTS - WORKROOM 136 20 A 1 360 1403 1 20 A Lighting EXAM ROOM HALLWAY A 102A 4 1 RECEPTS - Room 136, 137 20 A 1 2520 1584 1 20 A Lighting EXAM 1 112 2 NOTE CK T Circuit Description Trip Poles A B C Poles Trip Circuit Description CK T NOTE Notes: Enclosure:Type 1 MCB Rating:225 A Mounting:Surface Wires:4 Mains Rating:225 A Supply From: Phases:3 Mains Type:MCB Location:ELEC. RM. 130 Volts:120/208 Wye A.I.C. Rating:35,000 NEW Branch Panel: PANEL D (E) MANUFACTURER: EATON II SLA-094730-004 Notes: Total Est. Demand:141 A Total Conn.:131 A Total Est. Demand:50702 VA Power - General 1056 VA 100.00% 1056 VA Total Conn. Load:47327 VA Motor 46271 VA 107.29% 49646 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:140 A 133 A 124 A Total Load:16588 VA 15865 VA 14875 VA 41 Space -- 1 -- -- 1 --Space 42 39 Space -- 1 -- -- 1 --Space 40 37 Space -- 1 -- -- 1 --Space 38 35 Space -- 1 -- -- 1 --Space 36 33 ---- -- 1768 -- 1 --Space 34 31 (N) HP-7 30 A 2 1768 -- 1 --Space 32 29 ---- -- 2122 -- 1 --Space 30 27 (N) HP-6 30 A 2 2122 -- 1 --Space 28 25 ---- -- 2900 -- 1 --Space 26 23 (N) HP-5 30 A 2 2900 -- 1 --Space 24 21 ---- -- 2122 -- 1 --Space 22 19 (N) HP-4 30 A 2 2122 -- 1 --Space 20 17 ---- -- 2900 -- 1 --Space 18 15 (N) HP-3 40 A 2 2900 -- 1 --Space 16 13 ---- -- 2122 -- 1 --Space 14 11 (N) HP-2 30 A 2 2122 -- 1 --Space 12 9 ---- -- 2122 -- 1 --Space 10 7 (N) HP-1 30 A 2 2122 696 1 20 A (N) CIRC PUMP/TIMECLOCK 8 5 ---- -- 4500 333 -- ----6 3 ---- -- 4500 333 2 20 A (N) EF-1 4 1 (N)DOAS-1 50 A 3 4500 360 1 20 A (N) ROOF RECEPTACLE 2 NOTE CK T Circuit Description Trip Poles A B C Poles Trip Circuit Description CK T NOTE Notes: Enclosure:Type 1 MCB Rating:200 A Mounting:Surface Wires:4 Mains Rating:200 A Supply From: Phases:3 Mains Type:MCB Location:ELEC. RM. 130 Volts:120/208 Wye A.I.C. Rating:35,000 RELOCATED Branch Panel: PANEL H 1 PROVIDE TYPEWRITTEN PANEL DIRECTORY. PROVIDE ENGRAVED NAMEPLATE ON DOOR. CONNECT TO EXISTING CIRCUIT BREAKER. PROVIDE NEW CIRCUIT BREAKER IN SPACE. MATCH EXISTING MANUFACTURER AND AIC RATING. REMOVE EXISTING CIRCUIT BREAKERS AND PROVIDE NEW. MATCH EXISTING MANUFACTURER AND AIC RATING. PROVIDE CIRCUIT BREAKER IN BOTTOM SEPARATE SECTION OF PANEL. 2 3 4 5 1 212 6 5 4 3 6 MSA 2 01.19.2024 Plan Check Resubmittal #2 LARGEST MOTOR : 13,500VA x 0.25% = 3,375VA TOTAL: 50,702VA 2 2 MECHANICAL/PLUMBING EQUIPMENT CONNECTION SCHEDULE LIGHTING FIXTURE SCHEDULE DOAS 1 EF 1 HP 1 HP 2 HP 3 HP 4 HP 5 HP 6 FCU 1 FCU 2 FCU 4 FCU 3 FCU 5 FCU 6 KS 1 WH 1 CP 1 AQ 1 FCU 7 HP 7 1. FIXTURES SHALL HAVE APPROPRIATE UL LABEL, DAMP, OR WET AS REQUIRED BY CODES AND ORDINANCES. 2. LIGHTING FIXTURE CATALOG NUMBERS ARE SERIES TYPE ONLY. PROVIDE ALL NECESSARY HARDWARE AS REQUIRED BY THE SPECIFICATIONS, DRAWINGS, AND PROJECT CONDITIONS FOR A COMPLETE AND OPERABLE INSTALLATION. 3. PRIOR TO ORDERING ANY LIGHTING EQUIPMENT, THE CONTRACTOR SHALL COORDINATE ALL FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND CEILING CAVITY DEPTHS. 4. CONTRACTOR SHALL VERIFY FIXTURE VOLTAGES AND CEILING TRIM COMPATIBILITY PRIOR TO ORDERING FIXTURE. 5. PROVIDE APPROVED FIRE-RATED ENCLOSURES FOR ALL LIGHTING FIXTURES LOCATED IN FIRE-RATED CEILINGS. 6. UPON INITIAL ENERGIZING OF ALL NEW LED FIXTURES, A CONTINUOUS PERIOD OF 30 HOURS SHALL OCCUR PRIOR TO DE-ENERGIZING OF LAMPS OR LED'S, FOR MANUFACTURER REQUIRED BURN-IN AND MAXIMUM LIFE. 7. ENSURE COMPATIBILITY OF ALL LIGHTING SYSTEM COMPONENTS SUCH AS DIMMING SYSTEMS. FIXTURES, LEDS, DRIVERS AND DIMMING SYSTEMS/INDIVIDUAL CONTROLS MUST BE FACTORY CERTIFIED COMPATIBLE FOR FULL RANGE OF MANUFACTURER REQUIREMENTS. 8. PROVIDE CLEARANCES FROM COMBUSTIBLES A MINIMUM OF 1/2'' (OTHER THAN AT POINTS OF SUPPORT) AND 3' FROM INSULATION FOR RECESSED LIGHTING FIXTURES WHICH MUST BE NON-IC RATED. 9. PROVIDE A MINIMUM OF TWO (2) #12 SUPPORT WIRES ATTACHED TO BUILDING FRAME IN ADDITION TO T-BAR CLIPS FOR FIXTURES RECESSED IN SUSPENDED T-BAR CEILING. 10. PROVIDE (4) SHEET METAL SCREWS, ONE INSTALLED IN EACH CORNER OF THE FIXTURE ATTACHING THE FIXTURE TO THE GRID. SCREWS SHALL NOT BE VISIBLE NOR IMPEDE INSTALLATION OF GRID PANELS. 11. PROVIDE DOOR-TO-FRAME AND LENS-TO-DOOR GASKETING, INVERTED LENS, AND FOOD SERVICE RATING FOR ALL FIXTURES LOCATED IN FOOD SERVICE AREAS. 12. LAMPS AND LEDS SHALL BE PROVIDED AND INSTALLED ACCORDING TO THIS FIXTURE SCHEDULE AND PROJECT SPECIFICATIONS. ENSURE COMPATIBILITY BETWEEN FIXTURE, LAMP AND BALLAST(S), LEDS AND DRIVERS. 13. FIXTURES SHALL BE ORDERED WITH APPROPRIATE BALLAST(S) THAT HAVE UL AND CBM LABELS. ALL BALLASTS MUST CONFORM TO TITLE 24 REQUIREMENTS FOR PERFORMANCE AND EFFICIENCY. 14. LED DRIVERS SHALL BE 0-10VOLT DIMMING TYPE AS INDICATED. 15. FIXTURES, TRIMS, REFLECTORS, AND LAMPS SHALL BE CLEANED FREE FROM DIRT, DUST, LABEL ADHESIVE, AND FINGER PRINTS. 16. ALL LIGHT FIXTURES SHALL BE MOUNTED AND SUPPORTED IN ACCORDANCE WITH OSHA STANDARDS AND ALL LOCAL, STATE, AND NATIONAL ELECTRICAL CODES. PROVIDE ALL REQUIRED SEISMIC 17. PROVIDE LIGHT FIXTURE MOUNTING KITS AS REQUIRED TO SUIT THE EXACT TYPE OF CEILING TO WHICH THEY ARE MOUNTED. 18. FOR LED FIXTURES, THE DRIVER, LED AND FIXTURE SHALL BE FULLY UL CERTIFIES AS A SYSTEM, INCLUDING ANY OPTIONAL EMERGENCY BATTERY PACKS, SPECIAL DRIVERS (DIMMING). COMPONENTS LISTED DISCRETELY SHALL NOT BE PERMITTED. 19. PHOTOMETRIC TESTING FOR ALL LED FIXTURES SHALL BE FOR IES LM-70-80 AND TEST REPORTS SHALL BE INCLUDED WITH ALL FIXTURES SUBMITTALS. 20. LUMEN MAINTENANCE REPORTS (IES LM-80) REPORTS ARE ALSO REQUIRED WITH ALL LED FIXTURE SUBMITTALS. LM-80 RESULTS ARE TO INCLUDE A MINIMUM OF 10,000 HOURS TESTING AND REFERENCED TO TM-21 FOR TOTAL LUMEN MAINTENANCE. NO EXTRAPOLATED L-70 ESTIMATES WILL BE ACCEPTED. 21. PROVIDE A MINIMUM 5 YEAR WARRANTY ON AN LED FIXTURES. 22. PROVIDE STANDARD DEVIATION OF COLOR MATCHING (SDCM) BASED ON THE MAC ADAM ELLIPSE, AND NUMBER'S OR QUANTITIES OF ELLIPSE VARIATIONS FOR LED COLOR ACCURACY. 23. ALL LED FIXTURES SUBMITTALS SHALL INCLUDE DATA ON LED CHIP MANUFACTURER AND CHIP DATA, AS WELL AS DRIVER MANUFACTURER, DATA AND CUT SHEETS. LIGHTING FIXTURE GENERAL NOTES: MECHANICAL/PLUMBING EQUIPMENT CONNECTION NOTES: 1. ALL ELECTRICAL EQUIPMENT ON ROOF OR EXPOSED TO DAMP/WET CONDITIONS SHALL BE PROVIDED WITH WEATHERPROOF HARDWARE/ACCESSORIES AND/OR NEMA 3R RATED ENCLOSURES. 2. FINAL CONNECTION TO MECHANICAL/PLUMBING EQUIPMENT SHALL BE MADE WITH FLEXIBLE METAL CONDUIT OR LIQUID TIGHT FLEX WHERE REQUIRED. 3. ALL OVER CURRENT AND OVERLOAD PROTECTIVE DEVICES SHALL BE SIZED PER MECHANICAL EQUIPMENT MANUFACTURER'S NAMEPLATE INCLUDING FUSES AND CIRCUIT BREAKERS. 4. ALL OVER CURRENT PROTECTIVE DEVICES SHALL BE RATED 300V OR 600V, AS REQUIRED, HEAVY-DUTY TYPE. 5. PROVIDE ALL REQUIRED 120V (AND ABOVE VOLTAGES) WIRING AND RACEWAY FOR MECHANICAL EQUIPMENT INTERLOCK, CONTROLS, FIRE ALARM, ENERGY MANAGEMENT AND TEMPERATURE CONTROL SYSTEMS AS DEEMED NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM. COORDINATE ALL REQUIREMENTS WITH MECHANICAL SYSTEM DOCUMENTS AND DIVISION 15 SPECIFICATIONS PRIOR TO START OF WORK. 6. REFER TO MECHANICAL CONSTRUCTION DRAWINGS FOR LOCATION OF ALL MECHANICAL EQUIPMENT. COORDINATE LOCATION IN FIELD PRIOR TO ROUGH-IN. 7. ALL BRANCH CIRCUIT PENETRATIONS THROUGH RATED WALLS, FLOORS OR CEILINGS SHALL BE SEALED WITH UL LISTED AND APPROVED RATED SEALANTS/ASSEMBLIES. PERFORM PENETRATIONS SUCH THAT FIRE RATING OF ROOF AND/OR WALLS IS MAINTAINED. 8. ELECTRICAL CONTRACTOR SHALL VERIFY MECHANICAL EQUIPMENT VOLTAGES AND PHASE, AND COORDINATE WITH MECHANICAL CONSTRUCTION DRAWINGS AND EQUIPMENT SHOP DRAWINGS. 9. MOUNT DISCONNECT SWITCHES SUCH THAT NEC REQUIRED WORKING CLEARANCE IS MAINTAINED. 10. PROVIDE 120V CONNECTIONS TO ALL DUCT/SMOKE DETECTORS UNLESS OTHERWISE NOTED OR INDICATED BY EQUIPMENT MANUFACTURER IF DEVICE IS MANUFACTURER INSTALLED AND WIRED INTERNALLY. HP DESCRIPTION VOLTS EQUIPMENT RATING PHASE VOLTAMPS MOCPMCA CONNECTION DATA STARTER SIZE WIRE SIZE DISCONNECT SWITCH TAG NOTES 208 3 44.1 -50 NOTE: ALL MECHANICAL AND PLUMBING INFORMATION SHOWN IS FOR REFERENCE ONLY AND MUST BE VERIFIED WITH LATEST MECHANICAL OR PLUMBING DRAWINGS AND ACTUAL PURCHASED EQUIPMENT PRIOR TO ANY ROUGH-IN, MATERIALS ORDERING, AND FINAL CONNECTIONS. - 3/4"C-2#12,1#12GND.3.2 3.7 15208 1EXHAUST FAN 1/4 208 1 -30 3/4"C-2#10,1#10GND. REMARKSVOLTSLAMP QTY.TYPE MANUFACTURER CATALOG WATTAGE& TYPE A1 X1 1202(1) 2W LED 22(1) 22W LED (3000K) 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 120 X2 1202(1) 2W LED CEILING MOUNTED RECESSED BRUSHED ALUMINUM TRIM LED EXIT SIGN WITH SINGLE MIRROR GREEN LETTERS (ARROWS AS INDICATED) COOPER LIGHTING #EUX-1-G-*-2C (2836L) B1 DAY-BRITE LIGHTING #2FGX-G-30L-830-2-DS- UNV-DIM HEAT PUMP UNIT 37.5 -3/4"C-3#6,1#10GND. 30AS/5AF * LENGTHS VARY. VERIFY WITH ARCHITECTURAL DRAWINGS PRIOR TO PURCHASE. PROVIDE AND INSTALL ALL NECESSARY HARDWARE FOR A COMPLETE INSTALLATION 20.4 CEILING MOUNTED RECESSED BRUSHED ALUMINUM TRIM LED EXIT SIGN WITH DOUBLE MIRROR GREEN LETTERS AND (ARROWS AS INDICATED) A2 34(1) 34W LED (3000K) 120 (4220L) A3 AC PACKAGE UNIT 24.1 - 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 44(1) 44W LED (3000K) 120 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER A1E 22(1) 22W LED (3000K) 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER (EMERGENCY CIRCUIT-HALF SHADED FIXTURES) 120 (2836L) A2E 34(1) 34W LED (3000K) 120 (4220L) A3E 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER (EMERGENCY CIRCUIT-HALF SHADED FIXTURES) 44(1) 44W LED (3000K) 120 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER. (EMERGENCY CIRCUIT-HALF SHADED FIXTURES) COOPER LIGHTING #EUX-2-G-*-2C ROOF DAY-BRITE LIGHTING #2FGX-G-30L-830-2-DS- UNV-DIM (5164L) (5164L) DAY-BRITE LIGHTING #2FGX-G-54L-830-2-DS- UNV-DIM DAY-BRITE LIGHTING #2FGX-G-54L-830-2-DS- UNV-DIM DAY-BRITE LIGHTING #2FGX-G-45L-830-2-DS- UNV-DIM DAY-BRITE LIGHTING #2FGX-G-45L-830-2-DS- UNV-DIM 30(1) 30W LED (3500K) (3880L) LITHONIA LIGHTING #ZL1D-L48-3000LM-FST- MVOLT-35K-80CRI- 4'-0" LED STRIP LIGHT, ACRYLIC LENS, BUILT-IN 0-10VAC 1% DIMMING DRIVER AND NICAD BATTERY 120 7 (3500K) GOTHAM LIGHTING #EVO6-35/05-AR-LSS-MD- -MVOLT-EZ1 120(1) 6.2W LED (519L) C1 9 (3500K) GOTHAM LIGHTING #EVO6-35/07-AR-LSS-MD- MVOLT-EZ1 6" ROUND RECESSED LED DOWNLIGHT AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 120(1) 8.2W LED (776L) C2 13(1) 13W LED (3000K) 120 4" X 4' RECESSED LINEAR LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER. (1500L) FOCAL POINT SEEM 4 #FSM4L-FL-375-35-UNV- LD1-NF-WH-4FT B2 39(1) 39W LED (3000K) 120 4" X 12' RECESSED LINEAR LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER. (4500L) FOCAL POINT SEEM 4 #FSM4L-FL-375-35-UNV- LD1-NF-WH-12FT D1E 30(1) 30W LED (3500K) (3880L) LITHONIA LIGHTING #ZL1D-L48-3000LM-FST- MVOLT-35K-80CRI- 4'-0" LED STRIP LIGHT, ACRYLIC LENS AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 120 D1 8(1) 7.3W LED (3000K) (413L) LITHONIA LIGHTING #UCLD-12IN-30K-90CRI- WHITE 4" X 12" LED UNDERCABINET FIXTURE WITH WHITE ACRYLIC DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVERUC1 120 10(1) 9.7W LED (3000K) (585L) LITHONIA LIGHTING #UCLD-12IN-30K-90CRI- WHITE 4" X 18" LED UNDERCABINET FIXTURE WITH WHITE ACRYLIC DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVERUC2 120 13(1) 12.5W LED (3000K) (740L) LITHONIA LIGHTING #UCLD-12IN-30K-90CRI- SWR-WHITE 4" X 24" LED UNDERCABINET FIXTURE WITH WHITE ACRYLIC DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVERUC3 120 18(1) 18W LED (3500K) 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 120 (2078L) LITHONIA LIGHTING #2TL2-20L-FW-A12-MVOLT- EZ1-LP835-N80E1 60AS/50AF 60AS/30AF 208 1 -30HEAT PUMP UNIT 20.4 24.1 -60AS/30AF 208 1 -40HEAT PUMP UNIT 32.8 -60AS/35AF 208 1 -30 3/4"C-2#10,1#10GND.HEAT PUMP UNIT 24.1 -60AS/30AF 208 1 -40HEAT PUMP UNIT 32.8 -60AS/35AF 208 1 -30HEAT PUMP UNIT 24.1 -30AS/25AF 27.9 20.4 27.9 20.4 ROOF ROOF ROOF ROOF ROOF ROOF ROOF 208 1FAN COIL 208FAN COIL 208FAN COIL 208FAN COIL 208FAN COIL 208FAN COIL 1 1 1 1 1 - - - - - - - - - - - - 3/4"C-2#10,1#10GND. 3/4"C-2#8,1#10GND. 3/4"C-2#8,1#10GND. 3/4"C-2#10,1#10GND. CEILING- PWR @ HP3/4"C-2#10,1#10GND. 3/4"C-2#8,1#10GND. 3/4"C-2#8,1#10GND. 30AS/25NF 60AS/35NF 60AS/35NF 30AS/25NF CEILING- PWR @ HP CEILING- PWR @ HP CEILING- PWR @ HP CEILING- PWR @ HP CEILING- PWR @ HP 9(1) 9W LED (3000K) SINGLE DECORATIVE PENDANT LED FIXTURE WITH SHADE AND TRIAC/ELV DIMMING DRIVER 120 (460L) SONNEMAN LIGHTING PAILLONS #2901.25-AWF1 6" ROUND FLANGED LED DOWNLIGHT AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 15 (3500K) GOTHAM LIGHTING #EVO6-35/15-AR-LSS-MD- MVOLT-EZ1 120(1) 14.7W LED (1471L) C4 6" ROUND RECESSED LED DOWNLIGHT AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 13.8120COMPACT DISPOSER 1 - - 3/4 - - 3/4"C-2#12,1#12GND. RECEPTACLE 15KW208ELECTRIC TANK WATER HEATER 3 - - - -3/4"C-3#6,1#8GND.60AS/NF 5.8120CIRCULATION PUMP 1 - - 1/2 -3/4"C-2#12,1#12GND.MANUAL STARTER 1.0120AQUASTAT1 - - - -3/4"C-2#10,1#10GND.MANUAL STARTER A4 48(1) 48W LED (3000K) 120 2' X 2' T-GRID DIRECT LED FIXTURE WITH WHITE DIFFUSER AND BUILT-IN 0-10VAC 1% DIMMING DRIVER (5529L) DAY-BRITE LIGHTING #2FGX-G-60L-830-2-DS- UNV-DIM 9 (3500K) GOTHAM LIGHTING #EVO6-35/07-AR-LSS-MD- MVOLT-EZ1-E10WCP 6" ROUND RECESSED LED DOWNLIGHT BUILT-IN 0-10VAC 1% DIMMING DRIVER AND BUILT-IN NICAD BATTERY 120(1) 8.2W LED (776L) C2E 9 (3500K) GOTHAM LIGHTING #EVO6-35/07-AR-LSS-MD- MVOLT-EZ1 6" ROUND FLANGED LED DOWNLIGHT AND BUILT-IN 0-10VAC 1% DIMMING DRIVER 120(1) 8.2W LED (776L) C3 9 (3500K) GOTHAM LIGHTING #EVO6-35/07-AR-LSS-MD- MVOLT-EZ1-E10WCP 6" ROUND FLANGED LED DOWNLIGHT, BUILT-IN 0-10VAC 1% DIMMING DRIVER AND NICAD BATTERY 120(1) 8.2W LED (776L) C3E 15 (3500K) GOTHAM LIGHTING #EVO6-35/15-AR-LSS-MD- MVOLT-EZ1-E10WCP 120(1) 14.7W LED (1471L) C4E 6" ROUND RECESSED LED DOWNLIGHT, BUILT-IN 0-10VAC 1% DIMMING DRIVER AND NICAD BATTERY 3/4"C-2#10,1#10GND. 3/4"C-2#10,1#10GND. 3/4"C-2#10,1#10GND. - - - 30AS/35NF 30AS/25NF 208FAN COIL 1 --CEILING- PWR @ HP3/4"C-2#10,1#10GND.30AS/25NF 208 1 -30HEAT PUMP UNIT 20 -30AS/20AF17.0 ROOF3/4"C-2#10,1#10GND. PROVIDE NEMA 3R DISCONNECT SWITCH * * * * * * * * * B1E 13(1) 13W LED (3000K) 120 4" X 4' RECESSED LINEAR LED FIXTURE WITH WHITE DIFFUSER, BUILT-IN 0-10VAC 1% DIMMING DRIVER AND BUILT-IN NICAD BATTERY.(1500L) FOCAL POINT SEEM 4 #FSM4L-FL-375-35-UNV- LD1-NF-WH-4FT-EM - - - - - - - - - - - - - -** * * * * * * * * * * FAN COILS RECEIVE POWER FROM HEAT PUMP UNITS** ** ** ** ** ** ** 36(1) 36W LED (3000K) DECORATIVE DIMMABLE HORIZONTAL MIRROR120 (2700L) LIGHTOLOGY LIGHTING L03D MATRIX MIRROR #MAT674366G1 CORRIDORS TREATMENT, EXAM TOILETS NURSE STATION ELECTRICAL, IDF ROOMS HOUSEKEEPING SOILED, STORAGE TREATMENT, EXAM NURSE STATION WORKROOMS/OPEN OFFICE CORRIDORS OFFICES OFFICES CORRIDORS STAFF LOUNGE STAFF LOUNGE WAITING RECEPTION WORKROOMS/OPEN OFFICE ELECTRICAL, IDF ROOMS EVS RECEPTION Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E0.4 LIGHTING FIXTURE SCHEDULE & MECHANICAL CONNECTION SCHEDULE 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2 44" TS 44"44"44" CRCR CR PB PB SINGLE CORRAL SHORT-TERM BIKE SINGLE CORRAL SHORT-TERM BIKE SINGLE CORRAL SHORT-TERM BIKE SINGLE CORRAL SHORT-TERM BIKE SINGLE LOCKER LONG-TERM BIKE SINGLE LOCKER LONG-TERM BIKE SINGLE LOCKER LONG-TERM BIKE SINGLE LOCKER LONG-TERM BIKE RECYCLETRASH TRASH TRASH TRASH RECYCLE RECYCLE STRETCHER STRETCHER EXITEXIT CR CR CR CR 44" TS CR CR C R J 1. COORDINATE ROUGH-IN LOCATION OF DEVICES WITH ARCHITECTURAL ELEVATIONS, DETAILS AND PLANS. INSTALL DEVICES FLUSH WITH FINISHED SURFACE. 2. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN; WHERE DEVICES ARE SHOWN IN GYPSUM BOARD CEILINGS, INSTALL CONDUIT FROM DEVICE TO ABOVE ACCESSIBLE CEILING IN NEARBY CORRIDOR. 3. THE CONTRACTOR SHALL NOTE THAT THE DRAWING IS DIAGRAMMATIC. EXACT ROUTING OF NEW CONDUITS AND LOCATION OF JUNCTION BOXES AND PULL BOXES SHALL BE COORDINATED AND DETERMINED IN THE FIELD. NEW CONDUIT, JUNCTION BOXES AND PULL BOXES SHALL BE ROUTED CONCEALED IN THE CEILING SPACE AND IN SUCH A MANNER AS TO AVOID INTERFERENCE WITH EXISTING BUILDING STRUCTURES, UTILITIES AND THE WORK BEING PERFORMED BY OTHER TRADES. 4. REFER TO GENERAL NOTES, SHEET E0.0 FOR ADDITIONAL REQUIREMENTS. 5. ALL BRANCH CIRCUITS TO CONTAIN SEPARATE NEUTRAL CONDUCTORS PER CEC 210.4. 6. REFER TO ARCHITECTURAL PLANS FOR ALL MOUNTING HEIGHTS. 7. COORDINATE EQUIPMENT FURNISHED BY OWNER AND VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO ROUGH-IN. 8. PROVIDE ENGRAVED COVERPLATES FOR ALL RECEPTACLES AND LIGHTING SWITCHES WITH PANEL AND CIRCUIT NUMBERS. 9. PROVIDE ENGRAVED COVERPLATES FOR ALL TEL/DATA OUTLETS. COORDINATE WITH IT DEPARTMENT. 10. USE RIGID METAL CONDUIT IN ALL AREAS EXPOSED TO WEATHER 11. USE GROUND WIRE INSIDE ALL FLEXIBLE METAL CONDUIT. 12. METAL CONDUIT SHALL NOT BE INSTALLED IN CONTACT WITH EARTH. 13. PROVIDE THE INFRASTRUCTURE WITH ROUGH- IN BOXES AND CONDUIT ONLY FOR THE DEFERRED APPROVAL NURSE CALL SYSTEM FOR THE PROJECT. ALL DEVICES, COVERPLATES, EQUIPMENT PANELS AND ANNUNCIATION PANELS WITH WIRING SHALL BE PROVIDED IN THE NURSE CALL CONTRACT. 14. A METALLIC RACEWAY/CABLE TYPE LISTED FOR GROUNDING AND CONTAINING A FULL- SIZED INSULATED EQUIPMENT GROUND CONDUCTOR. 15. PROVIDE A POSITIVE CONNECTION OF THE EQUIPMENT GROUNDING CONDUCTOR TO BOTH THE METALLIC OUTLET BOX AND THE GROUNDING TERMINAL OF THE OUTLET DEVICE. 16. THE CONTRACTOR SHALL TRACE ALL EXISTING CIRCUITS AND PERFORM MODIFICATIONS AS REQUIRED FOR A COMPLETE SYSTEM CONFORMING TO THE 2020 CEC. 1 2 3 4 5 6 7 8 910 11 12 1314 15 16 17 PL-E PL-W BL-EBL-W H G F E D C B A1 A MAIN ELECTRICAL ROOM (E)PANEL "DP-2"3 AREA OF WORK 1 (TYP.) (E)DP2-2 (E) 3 (RELOCATED PANEL "H")DP2-1 (PANEL "D") 3 5 1 PANEL D PANEL H 32 32 FIRE ALARM TERMINAL CABINET "FATC-1" (SEE SHEET E2.1) SECURITY PANEL "SP-1" (SEE SHEET E2.2) 4 1 1 4 7 (E) MPOE ROOM 1907 (FIRST PARKING LEVEL BELOW) (E) MAIN SWITCHBOARD "MSA" 3 6 IDF ROOM 106 Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES GENERAL NOTES Ref North © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States As indicated E1.0 ELECTRICAL OVERALL PLAN - LEVEL 01 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 ELECTRICAL ITEMS IN THIS AREA ARE TO REMAIN. MAINTAIN CONTINUITY. SEE PANEL SCHEDULE, SHEET E0.3. SEE SINGLE LINE DIAGRAM, SHEET E0.2. PROVIDE 24" X 24" X 6" NEMA 3R PULLBOX HIGH ON WALL ABOVE RAMP. PROVIDE GRS CONDUIT WITH FEEDER SECURED TO CEILIG AND EXTEND TO "DP-2". STUB OUT (1) 3" CONDUIT ONLY WITH PULLING LINE AND END BUSHINGS ON "MTBB-1". EXTEND ABOVE CEILINGS TO EXISTING MPOE. PROVIDE (1) 3" GRS CONDUIT ONLY WITH PULLING LINES AND END BUSHINGS SECURED TO PARKING LEVEL 1 STRUCTURE. STUB DOWN ON EXISITNG IT RACKS IN MPOE (WIRING AND FINAL CONNECTIONS IN IT CONTRACT). 1 2 3 4 5 6 SCALE:1" = 10'-0" ELECTRICAL OVERALL LEVEL1 7 2 01.19.2024 Plan Check Resubmittal #2 M 5 6 7 8 9 10 11 12 13 14 15 16 17PL-EBL-E H G F E D 8 3 9 PANEL "F" DP2-3 3 10 2 11 PANEL "H" 12 DP2-2 3 12 4 LF-10 LF-10 LF-10 LF-10 6(TYP.) 7 +84" +72" +84" +72" 6(TYP.) 7 14 6(TYP.) (TYP. UON) 8 D-1 D-6 +90" D-6 D-6 D-7 6 (TYP.) (TYP. UON) D-9 D-11 D-13 6D-1 7 1 8 1 8 D-15D-15D-18 D-18 D-15 D-15 DP-1 3 13 3 9 PANEL "D" D-1D-1 (E) SUITE C (TO REMAIN) (E) SUITE A (TO REMAIN) 15 6 (TYP.) 5 (TYP.) 5 1. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. 2. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION, EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED. 3. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS, FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN. 4. NOTIFY THE ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS-BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS. 5. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK. 6. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY. 7. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE. 8. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES. 9. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE. 10. ALL REMOVED MATERIALS AND EQUIPMENT WHICH IS SALVAGED MATERIALS SHALL REMAIN IN THE PROPERTY OF THE OWNER. DELIVER SUCH SALVAGED MATERIALS AND EQUIPMENT ON THE PREMISES AS DIRECTED BY OWNER AND NEATLY PILE OR STORE THEM AND PROTECT FROM DAMAGED. DISPOSE OF ALL HAZARDOUS MATERIAL PER GUIDELINE OF THE STATE OF CALIFORNIA, DEPARTMENT OF HEALTH SERVICES AND OTHER AGENCIES HAVING JURISDICTION. 11. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE. REMOVE UNUSED WIRING. 12. THE CONTRACTOR SHALL TRACE ALL EXISTING CIRCUITS AND PERFORM MODIFICATIONS AS REQUIRED FOR A COMPLETE SYSTEM CONFORMING TO THE 2019 CEC. Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES GENERAL NOTES Ref North © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States As indicated E1.1 DEMOLITION - POWER AND SIGNAL PLAN - LEVEL 01 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 SCALE:3/16" = 1'-0" DEMOLITION POWER & SIGNAL - LEVEL 011 EXISTING ELECTRICAL ITEMS TO REMAIN. MAINTAIN CIRCUIT CONTINUITY. SEE REVISED PANEL SCHEDULE, SHEET E0.3. SEE SINGLE LINE DIAGRAM, SHEET E0.2. DISCONNECT AND REMOVE EMONDEMON RECORDING METER WITH CONDUIT AND WIRING. DISCONNECT AND REMOVE FAN COIL UNIT WITH CONDUIT WIRING. DISCONNECT AND REMOVE ALL LIGHTING FIXTURES WITH CONDUIT, WIRE AND CONTROLLERS. DISCONNECT AND REMOVE ALL UNSED CONDUIT, WIRE LIGHTING OUTLETS AND PULLBOXES. DISCONNECT AND REMOVE FLUSH OR SURFACE RECEPTACLE WITH CONDUIT AND WIRING. FOR FLUSH OUTLETS, REMOVE ALL WIRING WITH CONDUIT ABOVE CEILING. ABANDON UNUSED CONDUITS FLUSH IN WALL. DISCONNECT AND REMOVE FLUSH PANELBOARD WITH ALL CONDUIT AND WIRING. CUT 3"CONDUIT BELOW FLOOR; REMOVE CONDUCTORS BACK TO "DP2". PATCH FLOOR TO MATCH. REMOVE SURFACE PANELBOARD AND RELOCATE PER SHEET E2.1. RECONNECT CONDUIT WITH FEEDER TO NEW PULLBOX IN NEW FURRING ON WALL. SEE SHEET E2.1. DISCONNECT AND REMOVE SURFACE PANELBOARD WITH CONDUIT AND WIRING. 1 2 3 4 5 6 7 8 9 10 11 12 13 2 01.19.2024 Plan Check Resubmittal #2 J J J 1 2 3 4 5 6 7 8 910 11 12 1314 15 16 17 PL-E PL-W BL-EBL-W H G F E D C B A1 A PANEL H-1,3,5 PANEL H-31,33 PANEL H-11,13 PANEL H-7,9 PANEL H-15,17 PANEL H-19,21 PANEL H-23,25 PANEL H-27,29 HP 1 HP 2 HP 7 DOAS 1 HP 3 HP 6 HP 4 HP 5 4 7 (TYP.) (TYP.) 2 2 PANEL H-2 10 (TYP.) 2 6 11 (TYP.) (TYP.) 2 3 8 (TYP.) PANEL H-4,6 EF 1 1 2 2 2 2 2 2 10 2 13 2 9 12 (TYP.) Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES GENERAL NOTES © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States 1/8" = 1'-0" E2.4 ELECTRICAL ROOF PLAN 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 SCALE:1/8" = 1'-0" ELECTRICAL ROOF PLAN1 1 EXISTING ELECTRICAL ITEMS IN THIS AREA TO REMAIN. MAINTAIN CIRCUIT CONTINUITY. SEE PANEL SCHEDULE, SHEET E0.3. PROVIDE 3/4"-2#10, 1#12GND. (ROUTE BELOW ROOF). SEE MECHANICAL EQUIPMENT SCHEDULE, SHEET E0.4. NEW HVAC UNIT - COORDINATE WITH MECHANICAL ENGINEER. SEAL ALL ROOF PENETRATIONS WITH PITCH POCKETS. PROVIDE 3/4"C.O. WITH PULLING LINE AND END BUSHINGS STUBBED OUT IN ACCESSIBLE CEILING OF THE TENANT SPACE. PROVIDE 20A, 2P, 3W, 120VAC GFI TYPE RECEPTACLE WITH WEATHERPROOF IN-USE COVER. MOUNT ON GALVANIZED CHANNEL SECURED TO ROOF. (UNISTRUT P-1000). ROUTE ALL CONDUITS BELOW ROOF EXCEPT FOR LAST 6LF SEAL-TITE FLEXIBLE CONDUIT CONNECTION TO EQUIPMENT. MOUNT ALL ELECTRICAL ITEMS ON PREFORMED GALVANIZED CHANNEL SUPPORT STRUCTURE SECURED TO ROOF INDEPENDANT OF MECHANICAL UNIT. SEE DETAIL 5/E3.2. PROVIDE ENGRAVED NAMEPLATE WITH PANEL AND CIRCUIT NUMBER INDICATED. PROVIDE SEAL-TITE CONDUIT WITH WIRING AND CONNECT FROM DISCONNECT SWITCH TO UNIT. DISCONNECT AND REMOVE ALL ELECTRICAL MATERIALS AND CONNECTIONS TO EXISTING THREE (3) HEAT PUMP UNITS PER MECHANICAL PLAN, M1.2. 2 3 4 5 6 9 10 11 1.THE CONTRACTOR SHALL NOTE THAT THE DRAWING IS DIAGRAMMATIC. EXACT ROUTING OF NEW CONDUITS AND LOCATION OF JUNCTION BOXES AND PULL BOXES SHALL BE COORDINATED AND DETERMINED IN THE FIELD. NEW CONDUIT, JUNCTION BOXES AND PULL BOXES SHALL BE ROUTED CONCEALED IN THE CEILING SPACE AND IN SUCH A MANNER AS TO AVOID INTERFERENCE WITH EXISTING BUILDING STRUCTURES, UTILITIES AND THE WORK BEING PERFORMED BY OTHER TRADES. 2. REFER TO GENERAL NOTES, SHEET E-0.0 FOR ADDITIONAL REQUIREMENTS. 3.ALL BRANCH CIRCUITS TO CONTAIN SEPARATE NEUTRAL CONDUCTORS PER CEC 210.4. 4.COORDINATE EQUIPMENT FURNISHED BY OWNER AND VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO ROUGH-IN. 5.PROVIDE ENGRAVED COVERPLATES FOR ALL RECEPTACLES WITH PANEL AND CIRCUIT NUMBERS. 6.ROUTE ALL NEW CONDUITS BELOW ROOF. NO EXPOSED CONDUITS ALLOWED ON ROOF WITH EXCEPTION OF 6LF MAXIMUM SEAL-TITE FLEXIBLE CONDUIT FOR EQUIPEMENT OR DEVICE CONNECTIONS. 7 8 12 13 NOTE: ALL ITEMS ON ROOF AR WEATHERPROOF. 2 01.19.2024 Plan Check Resubmittal #2 ? Statistics Description Symbol Avg Max Min Max/Min Avg/Min Corridor 4.0 fc 6.2 fc 0.3 fc 20.7:1 13.3:1 Team Work Room 3.9 fc 6.7 fc 0.4 fc 16.8:1 9.8:1 Waiting 3.3 fc 7.7 fc 1.6 fc 4.8:1 2.1:1 WorkRoom 136 1.8 fc 3.9 fc 0.7 fc 5.6:1 2.6:1 CONSULT 104 COPY/PRINT 100B EXAM ROOM HALLWAY A 102A RECEPTION 100 WAITING 101 PUBLIC TOILET 105 IDF 106 EXAM ROOM HALLWAY A 102A POC SPECIMEN PROCESSING 108 PATIENT TOILET 109 EXAM 3 110 EXAM 2 111 EXAM 1 112 WOMEN'S HEALTH EXAM 4 113 EXAM 7 119 EXAM 8 118 EXAM 5 114 EXAM 6 116 EXAM 9 117 EXAM 10 120 EXAM 11 121 EXAM 12 122 PATIENT TOILET 123 TEAM STATION 115 EXAM 13 124 EXAM 14 125 SOIL 126 BARIATRIC EXAM 15 127 EVS 128 CLEAN/SUPPLY 129 ELEC. RM. 130 STAFF BREAKROOM 131 STAFF TOILET 132 OFFICE 133 SHARED OFFICE 134 OFFICE 135 WORKROOM 136 5 6 7 8 910 11 12 1314 15 16 17PL-EBL-E H G F E D B1E B1E B1E B1E C2EC2EC2EC2EC2EC2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C2E C4E C2E B1E 5.7 4.2 2.6 5.8 4.1 0.6 0.8 4.8 5.5 5.1 3.2 2.1 4.8 2.6 0.5 0.6 3.1 4.2 2.1 3.3 6.1 4.0 3.7 6.2 3.9 3.3 3.0 4.2 2.2 6.3 0.6 4.4 5.8 5.4 5.1 1.9 5.5 5.6 3.0 1.7 5.1 5.3 1.9 5.3 5.4 1.9 5.3 5.4 4.1 4.9 1.5 5.9 5.5 2.5 5.1 4.5 5.9 2.4 4.4 5.7 3.3 5.5 5.4 1.9 5.4 5.5 1.9 5.4 5.4 2.4 4.5 5.9 2.4 4.6 5.9 2.4 4.5 6.1 7.5 2.1 2.3 2.1 3.5 6.6 5.4 2.4 2.2 2.4 3.1 2.9 1.7 1.9 2.4 2.4 3.9 2.8 1.4 0.8 3.5 2.6 1.4 0.8 1.9 1.6 1.2 0.9 1.1 1.2 1.2 1.2 0.8 1.2 1.8 2.3 0.8 1.3 2.6 3.8 0.8 1.3 2.4 3.5 Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States 12" = 1'-0" E2.5 EMERGENCY LIGHTING PHOTOMETRICS 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 SCALE:12" = 1'-0" EMERGENCY LIGHTING PHOTOMETRICS1 2 01.19.2024 Plan Check Resubmittal #2 44" T S 44"44"44" CR CR CR PB PB CR CR CR CR 44" T S CR C R C R J S M 5 6 7 8 9 10 11 12 13 14 15 16 17PL-EBL-E H G F E D FCU 2 FCU 1 FCU 4 FCU 6 FCU 3 FCU 5 5 5 4 4 4 4 (N) (N) (N) (N) (N) (N) PANEL D PANEL H 21 21 4 4 5 5 5 5 6 6 6 6 6 6 PANEL D-49,51,53 WH 1 FCU 7 4 6 8 PANEL H-8 CP 1 TIMECLOCK 44 4 AQ 1 4 1 3 1. COORDINATE ROUGH-IN LOCATION OF DEVICES WITH ARCHITECTURAL ELEVATIONS, DETAILS AND PLANS. INSTALL DEVICES FLUSH WITH FINISHED SURFACE. 2. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN; WHERE DEVICES ARE SHOWN IN GYPSUM BOARD CEILINGS, INSTALL CONDUIT FROM DEVICE TO ABOVE ACCESSIBLE CEILING IN NEARBY CORRIDOR. 3. THE CONTRACTOR SHALL NOTE THAT THE DRAWING IS DIAGRAMMATIC. EXACT ROUTING OF NEW CONDUITS AND LOCATION OF JUNCTION BOXES AND PULL BOXES SHALL BE COORDINATED AND DETERMINED IN THE FIELD. NEW CONDUIT, JUNCTION BOXES AND PULL BOXES SHALL BE ROUTED CONCEALED IN THE CEILING SPACE AND IN SUCH A MANNER AS TO AVOID INTERFERENCE WITH EXISTING BUILDING STRUCTURES, UTILITIES AND THE WORK BEING PERFORMED BY OTHER TRADES. 4. REFER TO GENERAL NOTES, SHEET E0.0 FOR ADDITIONAL REQUIREMENTS. 5. ALL BRANCH CIRCUITS TO CONTAIN SEPARATE NEUTRAL CONDUCTORS PER CEC 210.4. 6. REFER TO ARCHITECTURAL PLANS FOR ALL MOUNTING HEIGHTS. 7. COORDINATE EQUIPMENT FURNISHED BY OWNER AND VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO ROUGH-IN. 8. PROVIDE ENGRAVED COVERPLATES FOR ALL RECEPTACLES AND LIGHTING SWITCHES WITH PANEL AND CIRCUIT NUMBERS. 9. PROVIDE ENGRAVED COVERPLATES FOR ALL TEL/DATA OUTLETS. COORDINATE WITH IT DEPARTMENT. 10. USE RIGID METAL CONDUIT IN ALL AREAS EXPOSED TO WEATHER 11. USE GROUND WIRE INSIDE ALL FLEXIBLE METAL CONDUIT. 12. METAL CONDUIT SHALL NOT BE INSTALLED IN CONTACT WITH EARTH. 13. PROVIDE THE INFRASTRUCTURE WITH ROUGH- IN BOXES AND CONDUIT ONLY FOR THE DEFERRED APPROVAL NURSE CALL SYSTEM FOR THE PROJECT. ALL DEVICES, COVERPLATES, EQUIPMENT PANELS AND ANNUNCIATION PANELS WITH WIRING SHALL BE PROVIDED IN THE NURSE CALL CONTRACT. 14. A METALLIC RACEWAY/CABLE TYPE LISTED FOR GROUNDING AND CONTAINING A FULL- SIZED INSULATED EQUIPMENT GROUND CONDUCTOR. 15. PROVIDE A POSITIVE CONNECTION OF THE EQUIPMENT GROUNDING CONDUCTOR TO BOTH THE METALLIC OUTLET BOX AND THE GROUNDING TERMINAL OF THE OUTLET DEVICE. 16. THE CONTRACTOR SHALL TRACE ALL EXISTING CIRCUITS AND PERFORM MODIFICATIONS AS REQUIRED FOR A COMPLETE SYSTEM CONFORMING TO THE 2020 CEC. Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES GENERAL NOTES Ref North © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States As indicated E2.6 ELECTRICAL/MECHANICAL PLAN - LEVEL 01 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 SCALE:3/16" = 1'-0" ELECTRICAL/MECHANICAL PLAN - LEVEL 011 SEE PANEL SCHEDULE, SHEET E0.3. SEE SINGLE LINE DIAGRAM, SHEET E0.2. PROVIDE 20A, 120VAC 7-DAY TIMECLOCK AND CONNECT TO CIRCULATION PUMP AND AQUASTAT (SEE PLUMBING DRAWINGS). SEE MECHANICAL EQUIPMENT SCHEDULE, SHEET E0.4. ALL FAN COILS ABOVE CEILINGS (LOW VOLATAGE CONTROL WIRING IN MECHANICAL SECTION). EXTEND CONDUIT/WIRING UP TO ASSOCIATED HEAT PUMP ON ROOF (SEE SHEET E2.4). 1 2 3 4 5 6 2 01.19.2024 Plan Check Resubmittal #2 C FA T C C CCC C C P P P P C C C C C C C C C CC C C C C C C C 5 6 7 8 9 10 11 12 13 14 15 16 17PL-EBL-E H G F E D CONSULT 104 COPY/PRINT 100B EXAM ROOM HALLWAY A 102A WAITING 101 PUBLIC TOILET 105IDF 106 EXAM ROOM HALLWAY A 102A POC SPECIMEN PROCESSING 108 PATIENT TOILET 109 EXAM 3 110 EXAM 2 111 EXAM 1 112 WOMEN'S HEALTH EXAM 4 113 EXAM 7 119 EXAM 8 118 EXAM 5 114 EXAM 6 116 EXAM 9 117 EXAM 10 120 EXAM 11 121 EXAM 12 122 PATIENT TOILET 123 TEAM STATION 115 EXAM 13 124 EXAM 14 125 SOIL 126 BARIATRIC EXAM 15 127 EVS 128 CLEAN/SUPPLY 129 ELEC. RM. 130 STAFF BREAKROOM 131 STAFF TOILET 132 OFFICE 133 SHARED OFFICE 134 OFFICE 135 WORKROOM 136 (N)FIRE ALARM TERMINAL CABINET "FATC-1" (N)FIRE ALARM ANNUNCIATOR PANEL "FAAP" 5 2 4 (TYP.) 3 (TYP.) PANEL H PANEL D8 8 1 6 7 1 7 (TYP.) 1. COORDINATE ROUGH-IN LOCATION OF DEVICES WITH ARCHITECTURAL ELEVATIONS, DETAILS AND PLANS. INSTALL DEVICES FLUSH WITH FINISHED SURFACE. 2. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN; WHERE DEVICES ARE SHOWN IN GYPSUM BOARD CEILINGS, INSTALL CONDUIT FROM DEVICE TO ABOVE ACCESSIBLE CEILING IN NEARBY CORRIDOR. 3. THE CONTRACTOR SHALL NOTE THAT THE DRAWING IS DIAGRAMMATIC. EXACT ROUTING OF NEW CONDUITS AND LOCATION OF JUNCTION BOXES AND PULL BOXES SHALL BE COORDINATED AND DETERMINED IN THE FIELD. NEW CONDUIT, JUNCTION BOXES AND PULL BOXES SHALL BE ROUTED CONCEALED IN THE CEILING SPACE AND IN SUCH A MANNER AS TO AVOID INTERFERENCE WITH EXISTING BUILDING STRUCTURES, UTILITIES AND THE WORK BEING PERFORMED BY OTHER TRADES. 4. REFER TO GENERAL NOTES, SHEET E0.0 FOR ADDITIONAL REQUIREMENTS. 5. REFER TO DETAIL 9/E3.1 FOR ALL MOUNTING HEIGHTS. 6. COORDINATE EQUIPMENT FURNISHED BY OWNER AND VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO ROUGH-IN. 7. PROVIDE IDENTIFICATION NUMBER ON ALL DEVICES. 8. SEE SHEET E0.0 FOR FIRE ALARM DEFERRED APPROVAL NOTES. 9. PROVIDE THE INFRASTRUCTURE WITH ROUGH-IN BOXES AND CONDUIT ONLY FOR THE DEFERRED APPROVAL FIRE ALARM SYSTEM FOR THE PROJECT. ALL DEVICES, COVERPLATES, EQUIPMENT PANELS AND ANNUNCIATION PANELS WITH WIRING SHALL BE PROVIDED IN THE FIRE ALARM CONTRACT. THE MANUFACTURER OF THE FIRE ALARM SYSTEM SHALL BE "FIRE-LITE" TO MATCH EXISTING BUILDING STANDARD. 10. ALL "CONDUIT-ONLY" INSTALLATION SHALL HAVE PULLING LINE AND END BUSHINGS. Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 SHEET NOTES GENERAL NOTES Ref North © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States As indicated E2.7 FIRE ALARM PLAN - LEVEL 01 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 SCALE:3/16" = 1'-0" FIRE ALARM - LEVEL 011 EXISTING ELECTRICAL ITEMS TO REMAIN. MAINTAIN FIRE ALARM SYSTEM CONTINUITY. SEE 9/E3.2 FOR MOUNTING DETAILS OF ALL DEVICES. PROVIDE FIRE RATED INSULATED OUTLET BOXES IN RATED WALLS PER DETAIL . PROVIDE ROUGH-IN BOXES FLUSH IN CEILINGS OR WALLS WITH CONDUIT-ONLY TO NEW "FATC-1" ON FIRST FLOOR LEVEL CONDUCTORS, DEVICES AND FINAL CONNECTIONS IN FIRE ALARM CONTRACT. PROVIDE ANNUNCIATION PANEL FLUSH IN WALL WITH 1" CONDUIT ONLY WITH PULLING LINE AND END BUSHINGS TO "FATC-1" (EQUAL TO FIRE-LITE AND TO MATCH EXISTING). EXISTING MAIN FIRE ALARM PANEL FOR BUILDING (FIRE-LITE HOMWRUN 1000) LOCATED IN MAIN IT ROOM -TO REMAIN (SEE SHEET E1.0). CONNECT NEW FIRE ALARM TERMINAL CABINET "FATC-1". SEE SHEET E0.1 FOR FIRE ALARM SYSTEM DEFERRED APPROVAL NOTES. SEE PANEL SCHEDULE, SHEET 0.3 AND SINGLE LINE DIAGRAM, SHEET E0.2. 1 2 3 4 5 6 7 8 2 01.19.2024 Plan Check Resubmittal #2 Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E2.8 TITLE 24 CONFORMANCE 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2 Part Number Description Weight Shipping 3/8" DIA. 9/32" DIA. 10622-010 10" x 4" Bus Bar Kit 5 LB 18" 1 1/8" 4 " 4" 1" CR JJ CR 3 2 1 5 4 8 7CARD READER DETAIL 6 OUTLET MOUNTING DETAILS FIRE ALARM SYSTEM DEVICE MOUNTING HEIGHTS ( PER NFPA 72 ) CONDUIT ROOF PENETRATION DETAIL PANELBOARD MOUNTING DETAILS CONDUIT PENETRATION DETAIL TELECOM GROUNDING BAR ELECTRIFIED FURNITURE DETAIL9 BACKBOARD MOUNTING DETAIL10 12" 1/2"C.O. 42"AFF 1/2"C.O. INTERIOR CEILING 12" 42"AFF MULLION STYLE CARD READER (SECURE SIDE) AT MULLION STUB CONDUIT INTO DOOR FRAME VOID TO NEAREST ACCESS CONTROL PANEL 1/2"C.O. FINISHED FLOOR CEILING LINE 3/4" CONDUIT 3/4" CONDUIT STUBBED INTO FRAME BEHIND HINGE EXIT DEVICE W/BUILT-IN REQUEST-TO-EXIT SWITCH NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: 1. ALL SWITCHES SHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE OUTLET BOX TO THE LEVEL OF THE FINISHED FLOOR OR WORKING PLATFORM. 2. ALL RECEPTACLES AND COMMUNICATION SYSTEM SHALL BE LOCATED NOT LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE OUTLET BOX TO THE LEVEL OF THE FINISHED FLOOR OR WORKING PLATFORM. 3. PROVIDE ONE-HOUR PROTECTION AT ALL OUTLETS AND SWITCHES LOCATED IN ONE-HOUR RATED PARTITIONS. PHONE WALL TYP. TELEPHONE JACK TYP. DUPLEX OUTLET FACEPLATE GANGED IN SINGLE SWITCHES TO BE NOTE: TWO OR MORE SWITCH 44 " 6" 15 " 6" 48 " 48 " CEILING FIRE FIRE FIRE ALARM PULL DOWN SIMPLEX SIMPLEX REF. 80" MIN. (IBC) (2032mm MIN.) REF. 96" MAX. (IBC) (2440mm MAX.) ABOVE FINISHED FLOOR SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW. NFPA 72 2016 EDITION (SECTION A-4-4.4.1.1(1)) NFPA 72 2016 EDITION (SECTION 7.5.4.1.2) (SECTION 7.5.4.2.7) NFPA 72 2016 EDITION (SECTION A.7.5.4.5) 24" (610mm) TO TOP OF LENS MIN. DISTANCE HANDICAP BEDROOM STROBE CEILING MOUNTED SMOKE/HEAT DETECTOR 3' (MIN.) (914mm MIN.) A/C SUPPLY OR RETURN DIFFUSER AUDIO/VISUAL AND VISUAL ONLY DEVICES 96" MAX (NFPA) (2440mm MAX) ABOVE FINISHED FLOOR REFER TO THE PROPER DEVICE INSTALLATION INSTRUCTIONS FOR BACKBOX MOUNTING HEIGHT. NOTE: 80" (ADA) 80" MIN (NFPA) NFPA 72 2016 EDITION (SECTION 4-4.4) NFPA 72 2016 EDITION (SECTION 7.5.4) NFPA 72 2016 EDITION (SECTION 7.5.4.1) (2032mm MIN) (2032mm) FIRE PHONE JACK MANUAL PULL STATION MAGNETIC DOOR HOLDER TO EXIT DOOR 5' (MAX.) (1524mm) DOOR WIDTH LESS 3" (76mm) FINISHED FLOOR (SECTION 5.13.4) NFPA 72 2016 EDITION (SECTION 5.12.4) NFPA 72 2016 EDITION (SECTION 2-8.1) NFPA 72 2016 EDITION 42" MIN/48" MAX (NFPA) 48" MAX (ADA) (1219mm) (1067mm MIN/1372mm MAX)FINISHED WALL WALL MOUNTED SMOKE/HEAT DETECTOR 6" (152mm) ACCEPTED HERE NEVER HERE 4" (102mm) NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST EDGE OF THE DETECTOR. 4" (102mm) 12" (MAX) (305mm MAX) 1/2" U-BOLT STRUCTURAL SUPPORT RIGID STEEL CONDUIT ROOF EQ EQ FLASHING SUPPLIED BY ELECTRICAL CONTRACTOR INSTALLED BY ROOFING CONTRACTOR TO 120V POWER FOR ACCESS CONTROL 12"SQ x 4"DP SECTIONALIZED JUNCTION BOX ABOVE ACCESSIBLE CEILING TO 120V POWER FOR ACCESS CONTROL 3/4"C.O. TO SECURITY PANEL LOCATION 4/S JUNCTION BOX FOR CARD READER 12"SQ x 4"DP SECTIONALIZED JUNCTION BOX ABOVE ACCESSIBLE CEILING FIRE RATED CONCRETE FLOOR SLAB UL SYSTEM #CAJ1001 W/STEEL SLEEVE THROUGH CONCRETE FLOOR NOTE: PENETRATION FIRESTOP-10"MAX. DIA. METAL PIPE/CONDUIT CONDUIT METAL PIPE OR DAMMING MATERIAL 3M FIRE BARRIER CP 25 CAULK (TYP.) STEEL SLEEVE CONDUIT 3/4" FLEXIBLE CONDUIT 1" FLEXIBLE HARDWARE FITTING AND CONDULET STATION WALL PREFAB-WORK FITTING POWER ENTRY DIRECT CONNECT COVERPLATE OUTLET W/SPLIT POWER ENTRY COVERPLATE OUTLET W/SPLIT TELECOMMUNICATION NONE SCALE: BACKBOARD ANCHORAGE TO SURFACE BEHIND. CONCRETE BLOCK WALL: 3/16"DIA POWERS TAPPER+PFH@16"O.C.E.W. W/1.5" MIN EMBED. (ICC-ES ESR#3196) AT METAL STUD WALL: #10 WOOD TO METAL TEK SCREWS @16"O.C.E.W. TO STUD CENTERLINE OR BACKING. PROVIDE METAL STUD BACKING AS REQUIRED 16" O.C. TO STUD VERTICAL (TYP.) GROUND BAR PER SPECIFICATIONS 3/4"C.-1#6GND COPPER TO GROUND BUS IN "MSB"3/4"PLYWOOD TELEPHONE BOARD PER PLANS & SPECIFICATIONS (ONE EACH CORNER) EACH SIDE & EACH "SIMPSON" (A-34) 2" x 4" BLOCKING END. IN LENGTH MIN. 2 1/2" #12 O.H.W.S. PANEL WOOD STUD WALL 1/8" THICK STEEL (TYPICAL) PLATE WELDED TO METAL STUDS 48"H x 16"W x METAL STUD WALL TAPPING SCREW TEXS/5 SELF #12 H.W.H. PANEL METAL MOUNTING WOOD MOUNTING NONE SCALE: Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E3.1 ELECTRICAL DETAILS 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2 4' - 0 " 12 " 12 " LENGTH AS REQUIRED EARTHQUAKE CLIP (1 EACH SIDE) #12 AWG STEEL WIRE CONNECTOR ATTACH TO PERMANENT STRUCTURE TYP. 4 PLACES. REFER TO ARCHITECTURAL DETAIL "B" 3.1.4 2'X 4' FIXTURE SCALE: NONE MAIN RUNNERS 55LBS SCALE: NONE OUTLET BOX #12 AWG FIXTURE SUPPORT CHANNEL1 1/2" CEILING MATERIAL WIRES (ONE EACH CORNER) ARMS (2 EACH SIDE) ADJUSTABLE MOUNTING MOUNTING BRACKET FIXTURE FLANGE #12 AWG STEEL WIRE CONNECTOR ATTACH TO PERMANENT STRUCTURE (TYP. 4 PLACES) ATTCHED J-BOX FURNISHED WITH FIXTURE LIGHTING FIXTURE TYPE AS INDICATED ON PLANS LESS THAN 40 LBS. J-BOX ON SLAB ABOVE SCALE: NONE SCALE: NONE SCALE: NONE NONE SCALE: NONE P-1000 GALVANIZED PREFORMED SUPPORT CHANNEL PERMANENTLY ATTACHED TO WALL OR CEILING AT 8'-0"O.C. (PREFORMED CHANNELS TO BE SIZED FOR CONDUIT LOADING) CONDUIT CLAMPS SUPPORTED FROM ABOVE ADJUSTABLE PIPE HANGER. CONDUIT TO EXISTING CONCRETE SLAB THREADED STEEL ROD SECURED PROVIDE 1/2" DIAMETER (HILTI KB-TZ2 WITH WASHER) RECESSED LIGHTING IN HARD CEILING WALL PENETRATION DETAIL RECESSED DOWNLIGHT DETAIL 15 MULTIPLE CONDUIT SUPPORT DETAIL RECESSED LIGHTING FIXTURE DETAIL 710 FIRE STOPPING OUTLET BOX DETAILS SINGLE CONDUIT SUPPORT DETAILS 9 2 3 4 6 DISCONNECT MOUNTING DETAIL SINGLE CONDUIT SUPPORT DETAILS 8SINGLE CONDUIT SUPPORT DETAILS UL SYSTEM #WL1001 CP25WB CAULK 1/4"(6MM) MINIMUM DIAMETER BEAD OF 3M FIRE BARRIER CP 25N/S CAULK WOOD OR STEEL STUD 1-2 HOUR FIRE RATED GYPSUM WALL BOARD SCALE: NONE NONE SCALE: SCALE: METAL PIPE OR CONDUIT NONE SCALE: 3"± (E)4x12 UNISTRUT P1026 ANGLE CLIP OR EQUAL WITH 1/2"∅ LAG SCREW WITH 3" EMBEDMENT SCREW CAPACITY = .9 X 3_ 4 X 280lb = 189lb > 120lb 3/8"DIA 120lb HANGER ROD LOAD (MAX) INSTALLATIONS CONCEALED ABOVE CEILINGS ONLY DISCONNECT SWITCH (WP) 1/4"BOLT TYP SECURE TO ROOF 4/S W.P. JUNCTION BOX (HVAC CONTROLS) 2" CHANNEL GALV. 2" ANGLE GALV. (TYP.) 3/8" NUT T&B CONDUITS (6'-0" ON CENTER) P-1000 HS UNISTRUT REQUIRED) ROD (LENGTH AS UNISTRUT PIPE STRAP SIZE AS 3/8" THREADED REQUIRED (TYP.) EXISTING CONCRETE SLAB (TYP.) 3/8" DIA. COUPLER NUT (TYP.) 4'-0" MAX. (TYP.) (SEE NOTE 1) UNISTRUT (P1063 TYP.) (HILTI KB-TZ2 W/ WASHER) 2"EMB (TYP.) 1"MAX. (TYP.) CL LOW FLUTE NOTES: THE TOTAL UNIFORM OF ALL COINDUIT AT TRAPEZE SHALL NOT EXCEED 10.0 PLF. 1. 2. PROVIDE CONDUIT SUPPORT AT 6'-0" MAXIMUM SPACING AND 2'-0" MAXIMUM WHERE CONDUIT CHANGES DIRECTIONS. 3. THE MAXIMUM DIAMETER OF CONDUITS AHLL BE 2 1/2" MAXIMUM. INSTALLATIONS CONCEALED ABOVE CEILINGS ONLY Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E3.2 ELECTRICAL DETAILS 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2 PC OS D D D WS WS COS DRC PC PC OSOS LIGHTING CONTROL SYSTEM LEGEND DRC NOTES: MUST BE INTERLOCKED WITH A BUILDING LIGHTING CONTROL PANEL. IS/ARE NOT REQUIRED TO BE INTERLOCKED WITH A BUILDING LIGHTING CONTROL PANEL. LIGHTING CONTROL SYSTEM SPECIFICATIONSTYPICAL ROOM CONTROLLER WIRING DIAGRAM LIGHTING CONTROL PANEL x x (DIGITAL ROOM CONTROLLER) TO NEXT LIGHT FIXTURE TO NEXT " " TO NEXT " " TO NEXT " " NOTES: PURCHASED / INSTALLED DEVICES MUST BE COMPATIBLE WITH SELECTED LIGHTING CONTROL SYSTEM MANUFACTURER. LIGHTING CONTROL SYSTEM SEQUENCE OF OPERATIONS DIGITAL ROOM CONTROLLER. MINIMUM 2-RELAY POWER PACK TYPE ROOM CONTROLLER (1 RELAY FOR LIGHTING, 1 RELAY FOR POWER MINIMUM). TO BE MOUNTED ABOVE DOOR SERVING AS ENTRANCE TO SPACE IN WHICH LIGHTING IS CONTROLLED BY THIS DRC. LOCATE IN ACCESSIBLE T-BAR SPACE ABOVE DOOR. WHERE CEILING IS HARD-LID, INSTALL IN CEILING AND PROVIDE ACCESS PANEL. PLENUM RATED LOW-VOLTAGE WIRE PER SELECTED MANUFACTURER SPECIFICATIONS AND REQUIREMENTS. CABLING TO BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. CEILING MOUNTED INDOOR PHOTOCELL. PROGRAMMABLE CONTACT INPUT 3/4"C.-2#10 + 1#10G. 1. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED LOW-VOLTAGE CABLING, HARDWARE, ACCESSORIES, MODULES, DEVICES, CONTROLLERS, ETC. (SHOWN OR NOT SHOWN) FOR A COMPLETE AND OPERABLE SYSTEM TO ACCOMMODATE THE TOTAL NUMBER OF CONTROL POINTS AND MEET THE DESIGN INTENT IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS, INCLUDING THE SEQUENCE OF OPERATIONS. 2. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL PLANS ASSOCIATED WITH THE LIGHTING AND CONTROLS SYSTEMS (FIXTURE SCHEDULE, PLANS, DETAILS, ETC.) TO THE REQUIRED PARTIES (DISTRIBUTORS, VENDORS, ETC.) FOR AN ACCURATE ALL-INCLUSIVE BID. 3. CONTROLS SYSTEM LAYOUT: THE FLOOR/CEILING PLANS IDENTIFIED IN THIS DETAIL SHEET ARE TYPICAL ONLY. ELECTRICAL CONTRACTOR AND SELECTED MANUFACTURER ARE RESPONSIBLE FOR ADAPTING THE ACTUAL LIGHTING AND CONTROLS SYSTEM TO THE ACTUAL CONDITIONS OF THIS PROJECT. 4. SYSTEM CONTROLLING MULTIPLE SPACES: A SYSTEM CONTROLLING MULTIPLE SPACES (I.E., ONE CONTROLLER FOR TWO OFFICES, CLASSROOMS, ETC.) IS ACCEPTABLE HOWEVER A MAXIMUM OF TWO SPACES PER CONTROLLER SHALL NOT BE EXCEEDED. IN ALL CASES, PROPER SIGNAGE SHALL BE PROVIDED WITHIN THE SPACE TO IDENTIFY LOCATION OF IT'S CONTROLLER. 5. ACCEPTABLE MANUFACTURER'S AND SYSTEMS: a. ACUITY CONTROLS 7. SUBMITTALS: SUBMITTALS FOR THE LIGHTING CONTROL PACKAGE MUST BE PROVIDED TO INCLUDE THE FOLLOWING INFORMATION: a. PROPOSED MANUFACTURER AND SYSTEM IN ACCORDANCE WITH THESE SPECIFICATIONS. b. PROPOSED CONTROLS SYSTEM LAYOUT SHOWING TYPES AND LOCATIONS FOR ALL DEVICES, LOW-VOLTAGE CABLING, ETC. ASSOCIATED WITH AND SPECIFIC TO THIS PROJECT. c. RISER/SINGLE LINE DIAGRAMS SHOWING COMPLETE SYSTEM LAYOUT AND CONNECTIVITY. d. OWNER'S DESIRED ON / OFF TIME SCHEDULES FOR ALL INTERIOR AND EXTERIOR CONTROL ZONES. 8. WARRANTY, SUPPORT, AND COMMISSIONING: IN ADDITION TO MINIMUM 1-YEAR MANUFACTURER'S WARRANTY, INCLUDE IN BID ALL REQUIRED TECHNICAL SUPPORT AND COMMISSIONING BY THE MANUFACTURER TO SUCCESSFULLY EXECUTE AND MEET THE DESIGN INTENT OF THIS COMPLETE CONSTRUCTION DOCUMENT PACKAGE. 9. ALTERNATES: APPROVAL FOR ALTERNATE SYSTEMS IS REQUIRED PRIOR TO BID. SUBMIT PRIOR (15) DAYS PRIOR TO BID DEADLINE FOR PROPOSED ALTERNATE SYSTEM ALL INFORMATION IDENTIFIED IN ITEM #7 ABOVE. 10. EMERGENCY LIGHTING: FURNISH AND INSTALL COMPONENTS AND WIRING NECESSARY TO PROVIDE A COMPLETE AND OPERABLE EMERGENCY LIGHTING SYSTEM IN ACCORDANCE WITH THE SELECTED MANUFACTURER'S REQUIREMENTS TO ACCOMMODATE THE BACKUP POWER SOURCE(S) PROVIDED IN THIS PROJECT [GENERATOR VS. BATTERY PACKS VS. INVERTER]. INCLUDE SHUNT RELAY DEVICES AND/OR SEPARATE DRC DEVICES AS NEEDED. INSTALLED LIGHTING CONTROL SYSTEM SHALL BE WIRED, CONFIGURED, PROGRAMMED, AND PROVIDED SUCH THAT DESIGNATED EMERGENCY LIGHTS RETURN TO FULL-BRIGHTNESS AUTOMATICALLY IN THE EVENT OF A POWER LOSS. REQUIRED SCOPE WHEN INTERLOCKING TO BUILDING LIGHTING CONTROL PANEL PROVIDE (N) RELAY IN LIGHTING CONTROL PANEL FOR EACH DRC. 120V OR 277V 120V OR 277V (LIGHTING) DIGITAL CEILING MOUNT OCCUPANCY SENSOR CONNECTED TO LOCAL ROOM CONTROLLER WALL-MOUNTED DIMMER STATION. REFER TO SYMBOLS LIST FOR SPECIFICATIONS. LINE-VOLTAGE WIRING - REFER TO ELECTRICAL SYMBOLS LIST FOR SPECIFICATIONS. 1. IT IS ACCEPTABLE FOR LOW VOLTAGE WIRING TO BE INSTALLED WITHIN THE SAME RACEWAY AS THE LINE VOLTAGE WHERE ALLOWED BY CODE AND THE SYSTEM MANUFACTURE AS LONG AS THE LOW-VOLTAGE CABLING IS RATED FOR 600V CLASS. 2. RELAYS PROVIDED FOR CONTROLLED RECEPTACLES MUST BE RATED FOR 20A AND 1-HP MOTORS. 3. DRC FOR SELECTED MANUFACTURER MUST CONTAIN CONTACT RELAY FOR INTERFACING WITH LIGHTING CONTROL PANEL, BUILDING MANAGEMENT SYSTEM, OR DEMAND RESPONSE. 4. THE DIAGRAM ABOVE SHOWS POSSIBLE WIRING CONFIGURATIONS - NOT ALL THAT IS / ARE REQUIRED. FURNISH AND INSTALL WIRING IN ACCORDANCE WITH THE SELECTED MANUFACTURER'S SYSTEM REQUIREMENTS FOR A COMPLETE AND OPERABLE SYSTEM. 5. THE ROOM CONTROLLER(S) ASSOCIATED WITH THIS PROJECT: 1. INTERIOR DAYLIGHT HARVESTING: LIGHTING WITHIN DAYLIGHT ZONES [SKYLIT, PRIMARY, AND SECONDARY] SHALL BE PROGRAMMED SUCH THAT ARTIFICIAL DAYLIGHT AUTOMATICALLY DIMS AS NEEDED WHEN AVAILABLE NATURAL DAYLIGHT CONTRIBUTION RESULTS IN LIGHT LEVELS WITHIN SPACE EXCEEDING 50-FOOTCANDLES AT 30-INCHES AFF. ARTIFICIAL LIGHTING POWER SHALL AUTOMATICALLY INCREASE AS NATURAL DAYLIGHT DECREASES AND LIGHT LEVELS FALL BELOW 50-FOOTCANDLES. 2. TIME SCHEDULES: PRIOR TO PROJECT COMPLETION, PROGRAM AND COMMISSION THIS SYSTEM IN ACCORDANCE WITH THE OWNER'S FURNISHED SCHEDULE FOR ALL INTERIOR AND EXTERIOR LIGHTING ZONES. 3. CORRIDOR LIGHTING: SYSTEM SHALL BE PROGRAMMED SUCH THAT CORRIDOR LIGHTS ARE DIMMED DOWN 50% WHEN NO ACTIVITY IS DETECTED BY THE CORRIDOR OCCUPANCY SENSOR(S). LIGHTS SHALL RETURN TO 100% UPON OCCUPANCY BEING DETECTED. WALL MOUNTED COMBINATION OCCUPANCY SENSOR/ DIMMER LUTRON #MS-Z101-XX OR EQUAL. DIGITAL CEILING MOUNT PARTIAL-OFF OCCUPANT OR MOTION SENSOR, WITH CORRIDOR TYPE COVERAGE, CONNECTED TO LOCAL ROOM CONTROLLER. SENSOR TO AUTOMATICALLY REDUCE LIGHTING BY 50% WHEN AREA IS UNOCCUPIED AND TURN LIGHTING FULLY ON WHEN AREA IS OCCUPIED. INSTALL PER CCR T24 Part 6 130.1(c)7 Exp. 09/30/24 No. 13442 R O Y L.LOP EZ S T ATE OF CA L I F O R N I AELECTRICAL REGIST E R E D P R OFESSIONA L E N G I NEER Irvine 8825 Research Drive Irvine, CA 92618 © Gensler Date Description Project Name Project Number Description Scale Seal / Signature 2017 Tel 949.863.9434 Fax 949.553.1676 4675 MacArthur Court Suite 100 Newport Beach, CA 92660 United States E4.1 LIGHTING CONTROLS 007.3850.000 Keck Medicine 57 Wheeler USC Keck Medicine 57 Wheeler 57 Wheeler Arcadia, CA 91006 2 01.19.2024 Plan Check Resubmittal #2