Loading...
HomeMy WebLinkAbout123 W Huntington Dr - 2024 - Hilton Hotel GeneratorSpecification Name:Generators CSI Code:26 32 13 -004 - R1 Detail Description:Updated Emergency Generator Anchorage Status:For Approval Category:Shop Drawings Submittal Pkg. #:271 Date:6/27/2024 Due Date:7/3/2024 REVIEWED AND FORWARDED FOR APPROVAL REVIEWED WITH EXCEPTIONS NOTED NONCONFORMING, REVISED & RESUBMITTED The Submittals have been reviewed for general conformation to the design intent of the contract documents with regard to type and quality and not quantity and/or dimensions, which are the responsibility of the subcontractor and/or supplier making the submittal. The subcontractor and/or supplier is responsible for coordination of their work with other trades. Review of submittals and/or shop drawings does not relieve the subcontractor's and/or supplier's responsibility for any errors, omissions and/or changes for the requirements of the contract documents, nor for errors and/or omissions made by subcontractor and/or supplier in bad submittals and/or shop drawings. R.D. OLSON CONSTRUCTION BY:Moheb Bottros DATE:6/27/2024 JOB:Hilton - Arcadia (230100)SPEC:26 32 13 -004 - R1 Project Name:Hilton - Arcadia Project Number: 230100 Comment: Please find attached Submittal 263213-004 R1 - Updated Emergency Generator Anchorage for your review and approval. Submittal Transmittal 400 SPECTRUM CENTER DRIVE, SUITE 1200 IRVINE, CALIFORNIA 92618 TEL: 949-474-2001 WEBSITE: WWW.RDOLSON.COM Page 1 of 1 NO EXCEPTION TAKEN REJECTED MAKE CORRECTIONS NOTED REVISE AND RESUBMIT SUBMIT SPECIFIED ITEM Review is only for conformance with the design concept of the project and general compliance with information given in the contract documents. Any action indicated is subject to the requirements of the contract documents. Contractor is responsible for: dimensions to be confirmed and correlated at the job site, information that pertains solely to fabrication processes and to techniques of construction, coordination of his work with that of all other trades, and the satisfactory performance of his work. By: Date: MHP, INC. STRUCTURAL ENGINEERS 3900 COVER STREET LONG BEACH, CA 90808 x GL 07/01/2024 Hilton Arcadia Hotel 125 W. Huntington Drive Arcadia CA 91006 AJK JOB #1078 Generator Detail Deferred Submittal Date: 6.6.2024 For city submission NOTE: *Generator is Natural Gas not requiring : Separate Permit due to no fuel tank. A. J. Kirkwood & Associates, Inc. ▪ 4300 N Harbor Blvd. ▪ Fullerton, CA 92835 ▪ 714.505.1977 ▪ Fax: 714.505.7030 ▪ A B C D A B C D 12345678 12345678 R R 2868 113[ ] 2380 94[ ] 1196 47[ ] 102 4[ ] 1771 69.7[ ] 400 15.7[ ] 2X 196 7.7[ ] 730 28.7[ ] 1120 44.1[ ] COOLING AIR INLET CLEARANCE (MINIMUM) 750 29.5[ ] 2X 968 38.1[ ] 2X 761 30[ ] 168 6.6[ ] 52 2[ ] COOLING AIR OUTLET CLEARANCE (WEATHER ENCLOSURE MINIMUM) 969 38.2[ ] 200 7.9[ ] ( )1836 72[ ] 1016 40[ ] 991 39[ ] 25 1[ ] 1111 43.7[ ] 1846 72.7[ ] 3062 120.6[ ] Part Number A055J590 Part Noun Name OUTLINE,GENSET Cummins Inc. R DIMENSIONS ARE IN: MILLIMETERS [ ] ARE IN: INCHES SIZE:D SCALE:1/16 DIMENSIONING AND TOLERANCING PER: ASME Y14.5-2009 THIRD ANGLE PROJECTION CAD SYSTEM PTC Creo Parametric LAST DATUM LETTER USED: - LAST REFERENCE LETTER USED: - MODEL/PLATFORM: ARROW THIS PART IS SIMILAR TO: - UNLESS OTHERWISE SPECIFIED THE FOLLOWING SHALL APPLY ANG. TOL.: # 1 $ SURFACE FINISH PER: - SURFACE FINISH:- WALL THICKNESS: - DRAFT ANGLES: - EDGE RADII: - FILLET RADII:- DIMENSIONAL TOLERANCES:X # 1 .X # 0.8 .XX # 0.38 HOLE SIZE 0.00-4.99 TOL. +0.15/-0.08 HOLE SIZE 5.00-9.99 TOL. +0.20/-0.10 HOLE SIZE 10.00-17.49 TOL. +0.25/-0.13 HOLE SIZE 17.50-24.99 TOL. +0.30/-0.13 GENSET MODEL OUTLINE ENCLOSURE INSTALLATION CHASSIS INSTALLATION ENCLOSURE LIST SHIPPING PARTS INSTALLATION SKID PAN KIT ENCLOSURE C125N6, C200N6, C175N6B, C200N6B A055V238 (F216-2) A053K978 (F179)-2 A054F443 (P176-2) A055D562 (A322-2)A054Y470 (F250-2)NAA054Z702 (P176-2) A055F203 (A322-2) NOTES: 1. DIMENSIONS IN [ ] ARE IN INCHES. GENERATOR SET BASE HAS A FLANGE THICKNESS OF 3.42 MM. ALLOW EXTRA LENGTH ON HARDWARE FOR UNEVENESS OF MOUNTING SURFACE. GENERATOR SET BASE PERIMETER IS SHOWN. FOUNDATION SHOULD BE EXTENDED BEYOND THIS PERIMETER. SEE (T030) APPLICATION MANUAL. FUEL SIDE INLET CLEARANCE. (NOTE REMOVED) 6. FOR IBC SEISMIC CERTIFIED INSTALLATION. SEE GENSET IBC SEISMIC INSTALLATION REQUIREMENTS DRAWING. HOLES IN GENERATOR SET BASE AT THESE LOCATIONS ARE INTENDED FOR ATTACHMENT TO THE MOUNTING SURFACE. REFER TO CIRCUIT BREAKER OUTLINE DRAWING FOR COMPLETE ELECTICAL STUB-UP INFORMATION FOR SPECIFIC BREAKERS AND BREAKER POSITIONS. 3D VIEW 3D - GENSET WITH SHIPPING SKID ACCESSORY WIRE STUB-UP (AC) GENSET CONTROL WIRE STUB-UP (DC) CIRCUIT BREAKER STUB-UP 6X M16 OR 5/8 BOLT OR STUD 2 3 4 5 7 8 4 4 8 2 7 7 7 77 7 Cummins Data Classification: Cummins Confidential This document (and the information shown thereon) is Confidential and Proprietary and shall not be disclosed to others in hard copy or electronic form, reproduced by any means, or used for any purpose without written consent of Cummins Inc. Part Number: A055J590 Part Revision: E Part Name: OUTLINE,GENSET Drawing Category: Detail State: Released D o c u m e n t G e n e r a t e d : 1 7 A U G 2 0 2 2 1 9 : 5 6 G M T Sheet 1 of 4 STATEMENT OF GENERAL CONFORMANCE FOR PROJECTS WHICH UTILIZE "DEFERRED SUBMITTAL" PLANS, INCLUDING BUT NOT LIMITED TO SHOP DRAWINGS,PREPARED BY OTHER LICENSED DESIGN PROFESSIONALS AND/OR CONSULTANTS, NOT UNDER RESPONSIBLE CHARGE/DIRECTION OF THE DESIGNATED ARCHITECT/ENGINEER OF RECORD (CITY PERMIT NO. _____________________________________) o THE DRAWINGS OR SHEETS LISTED ON THE COVER OR INDEX SHEEToTHIS DRAWING, PAGE OF SPECIFICATIONS/CALCULATIONS HAVE BEEN PREPARED BY OTHER DESIGN PROFESSIONALS OR CONSULTANTS WHO ARE LICENSED AND/OR AUTHORIZED TO PREPARE SUCHDRAWINGS IN THIS STATE. IT HAS BEEN EXAMINED BY ME FOR: 1.DESIGN INTENT AND APPEARS TO MEET THE APPROPRIATE REQUIREMENTS OF TITLE 24, CALIFORNIA CODE OF REGULATIONS AND THE PROJECT SPECIFICATIONS PREPARED BY ME, AND 2.COORDINATION WITH MY PLANS AND SPECIFICATIONS AND IS ACCEPTABLE FOR INCORPORATION INTO THE CONSTRUCTION OF THIS PROJECT. THE STATEMENT OF GENERAL CONFORMANCE SHALL NOT BE CONSTRUED AS RELIEVING ME, OR THE PERSON UNDER WHOSE DIRECTSUPERVISION THESE DOCUMENTS WERE PREPARED, OF OUR RIGHTS, DUTIES, AND RESPONSIBILITIES UNDER APPLICABLE SECTIONS OF THECALIFORNIA BUILDING CODE. I CERTIFY THAT:ALL DRAWINGS OR SHEETS LISTED ON THE COVER OR INDEX SHEETTHIS DRAWING OR PAGE IS/ARE IN GENERAL CONFORMANCE AND HAVE BEEN COORDINATED SIGNATURE DATE ARCHITECT / ENGINEER IN GENERAL RESPONSIBLE CHARGE OR DELEGATED STRUCTURAL ENGINEER PRINT NAME LICENSE NUMBER EXPIRATION XX X Kenneth D. O'Dell 2024-10-22 S4101 - California 6/30/2025 X A B C D A B C D 12345678 12345678 R R 2868 113[ ] 102 4[ ] 1196 47[ ] 2380 94[ ] COOLING AIR INLET CLEARANCE (MINIMUM) 750 29.5[ ] 2X 968 38.1[ ] 2X 761 30[ ] 168 6.6[ ] 2X 52 2[ ] 2X 196 7.7[ ] 730 28.7[ ] 2X 1120 44.1[ ] 1771 69.7[ ] 400 15.7[ ] COOLING AIR OUTLET CLEARANCE (WEATHER ENCLOSURE MINIMUM) 969 38.2[ ] 200 7.9[ ] 1016 40[ ] 25 1[ ] 991 39[ ] ( )1836 72[ ] DUCT OUTLET (SOUND ENCLOSURE) 753 30[ ] DUCT INLET 440 17.3[ ] 3816 150.2[ ] 1111 43.7[ ] 1846 72.7[ ] Part Number A055J590 Part Noun Name OUTLINE,GENSET Cummins Inc. R DIMENSIONS ARE IN: MILLIMETERS [ ] ARE IN: INCHES SIZE:D SCALE:1/16 DIMENSIONING AND TOLERANCING PER: ASME Y14.5-2009 THIRD ANGLE PROJECTION CAD SYSTEM PTC Creo Parametric MODEL/PLATFORM: ARROW THIS PART IS SIMILAR TO: - UNLESS OTHERWISE SPECIFIED THE FOLLOWING SHALL APPLY ANG. TOL.: # 1 $ DIMENSIONAL TOLERANCES:X # 1 .X # 0.8 .XX # 0.38 HOLE SIZE 0.00-4.99 TOL. +0.15/-0.08 HOLE SIZE 5.00-9.99 TOL. +0.20/-0.10 HOLE SIZE 10.00-17.49 TOL. +0.25/-0.13 HOLE SIZE 17.50-24.99 TOL. +0.30/-0.13 GENSET MODEL OUTLINE ENCLOSURE INSTALLATION CHASSIS INSTALLATION ENCLOSURE LIST SHIPPING PARTS INSTALLATION SKID PAN KIT ENCLOSURE C125N6, C150N6 A055V240 (F217-2) A053K978 (F179-2) A055B203 (P176-2) A055D560 (A322-2) OR A055F201 (A322-2) A054Y470 (F250-2) A054F439 (L260-2)A055B207 (P176-2) 3D VIEW 3D - GENSET WITH SHIPPING SKID ACCESSORY WIRE STUB-UP (AC) GENSET CONTROL WIRE STUB-UP (DC) CIRCUIT BREAKER STUB-UP 6X M16 OR 5/8 BOLT OR STUD KIT,ENCLOSURE (SL2 DUCT) (L260-2) 4 4 8 2 7 7 7 7 7 7 C175N6B, C200N6B A055V240 (F217-2) A053K978 (F179-2) A071T324 (P176-2) A055D560 (A322-2) OR A055F201 (A322-2) A054Y470 (F250-2) A071T341 (L260-2) A071T340 (P176-2) Cummins Data Classification: Cummins Confidential This document (and the information shown thereon) is Confidential and Proprietary and shall not be disclosed to others in hard copy or electronic form, reproduced by any means, or used for any purpose without written consent of Cummins Inc. Part Number: A055J590 Part Revision: E Part Name: OUTLINE,GENSET Drawing Category: Detail State: Released D o c u m e n t G e n e r a t e d : 1 7 A U G 2 0 2 2 1 9 : 5 6 G M T Sheet 2 of 4 A B C D A B C D 12345678 12345678 R R COOLING AIR INLET CLEARANCE (MINIMUM) 750 29.5[ ] 2X 196 7.7[ ] 730 28.7[ ] 2X 1120 44.1[ ] 1771 69.7[ ] 400 15.7[ ] COOLING AIR OUTLET CLEARANCE (WEATHER ENCLOSURE MINIMUM) 969 38.2[ ] DUCT OUTLET (SOUND ENCLOSURE) 753 30[ ] 200 7.9[ ] 2X 968 38.1[ ]2X 761 30[ ] 2X 52 2[ ] 2X 168 6.6[ ] ( )1836 72[ ] 1016 40[ ] 25 1[ ]991 39[ ] 2868 113[ ] 102 4[ ] 1196.13 47.1[ ] 2380 94[ ] 3816 150.2[ ] 1111 43.7[ ] 1846 72.7[ ] Part Number A055J590 Part Noun Name OUTLINE,GENSET Cummins Inc. R DIMENSIONS ARE IN: MILLIMETERS [ ] ARE IN: INCHES SIZE:D SCALE:1/16 DIMENSIONING AND TOLERANCING PER: ASME Y14.5-2009 THIRD ANGLE PROJECTION CAD SYSTEM PTC Creo Parametric LAST DATUM LETTER USED: - LAST REFERENCE LETTER USED: - MODEL/PLATFORM: ARROW THIS PART IS SIMILAR TO: - UNLESS OTHERWISE SPECIFIED THE FOLLOWING SHALL APPLY ANG. TOL.: # 1 $ SURFACE FINISH PER: - SURFACE FINISH:- WALL THICKNESS: - DRAFT ANGLES: - EDGE RADII: - FILLET RADII:- DIMENSIONAL TOLERANCES:X # 1 .X # 0.8 .XX # 0.38 HOLE SIZE 0.00-4.99 TOL. +0.15/-0.08 HOLE SIZE 5.00-9.99 TOL. +0.20/-0.10 HOLE SIZE 10.00-17.49 TOL. +0.25/-0.13 HOLE SIZE 17.50-24.99 TOL. +0.30/-0.13 GENSET MODEL OUTLINE ENCLOSURE INSTALLATION CHASSIS INSTALLATION ENCLOSURE LIST SHIPPING PARTS INSTALLATION SKID PAN KIT ENCLOSURE C125N6, C150N6, C175N6B, C200N6B A055V240 (F217-2) A053K978 (F179-2) A054F447 (P176-2) A055D560 (A322-2) OR A055F201 (A322-2) A054Y470 (F250-2)NA A054Z704 (P176-2) 3D VIEW 3D - GENSET WITH SHIPPING SKID ACCESSORY WIRE STUB-UP (AC) GENSET CONTROL WIRE STUB-UP (DC) CIRCUIT BREAKER STUB-UP 6X M16 OR 5/8 BOLT OR STUD 4 4 8 2777 7 7 7 Cummins Data Classification: Cummins Confidential This document (and the information shown thereon) is Confidential and Proprietary and shall not be disclosed to others in hard copy or electronic form, reproduced by any means, or used for any purpose without written consent of Cummins Inc. Part Number: A055J590 Part Revision: E Part Name: OUTLINE,GENSET Drawing Category: Detail State: Released D o c u m e n t G e n e r a t e d : 1 7 A U G 2 0 2 2 1 9 : 5 6 G M T Sheet 3 of 4 Part Number: A055J590 Change Notice CN00063836 Alternates Manufacturer Part (MEP)No Usage Production Only Release Phase Code Production (P)Number: A055J590_DET External Regulations No External Regulation Drawing Specification Revision: E 3D image provided when available for visual reference only. Associated Specifications Number Title Type Category Sub-Category ESA030B356 Prohibited and Restricted Substances Engineering Specification Material Specification Prohibited And Restricted|prohibited And Restricted Drawing Revision Information Description of Change(s) Note: Change information is provided for reference only and does not supersede the drawing's primary content. SHT 1 ZN A3 ADDED C175N6B & C200N6B TO TABLE SHT 1 ZN A1 RMV N/A FROM INSTALLATION SKID PAN COLUMN SHT 2 ZN A3 ADDED C175N6B AND C200N6B ROW TO TABLE SHT 3 ZN A3 ADDED C175N6B AND C200N6B TO TABLE ADMINISTRATIVE CHANGE(S) TO PART ATTRIBUTES, BILL OF MATERIAL, OR ASSOCIATED SPECIFICATIONS. Drawing Authorization Drafter John A Peterson Date 17AUG2022 Checker Luke Robert Staples Date 17AUG2022 Approver Luke Robert Staples Date 17AUG2022 Cummins Data Classification: Cummins Confidential This document (and the information shown thereon) is Confidential and Proprietary and shall not be disclosed to others in hard copy or electronic form, reproduced by any means, or used for any purpose without written consent of Cummins Inc. Part Number: A055J590 Part Revision: E Part Name: OUTLINE,GENSET Drawing Category: Detail State: Released D o c u m e n t G e n e r a t e d : 1 7 A U G 2 0 2 2 1 9 : 5 6 G M T Sheet 4 of 4 AXIS Architecture + Design October 22, 2024 MHP JN: 19-0283-01 700 Flower St, Suite 520 Los Angeles, CA 90017 by MHP, Inc. Structural Engineers 3900 Cover St. Long Beach, California 90808 STRUCTURAL CALCULATIONS EMERGENCY GENERATOR ANCHORAGE for Hilton Arcadia Hotel 125 W. Huntington Drive Arcadia CA 91006 for Exp. 6-30-25 S No.4101IS GE R OF C TA ST E R EF D P R O TE E I RE E N AINRFOILA A ONS L E N G I KE N N E T H D.O'DEL L U R A LTSRUCT SEISMIC FACTORS FOR EQUIPMENT ANCHORAGE Site: Floor (Level): Equipment: Seismic Design Force Factors: ap* Rp* Ωo Ip z h SDS** amp factor response mod factor Omega (overstrength) Factor importance factor height of attach point average roof height design parameter at short periods 1 2.5 2 1.0 1 1 1.321 * ASCE 7-16, Table 13.5-1, 13.6-1 **See seismic coefficients on US Seismic Design Maps output Seismic Design Force for Equipment Anchorage 0.63 Wp (ASCE 7-16, Equation 13.3-1) 2.11 Wp (ASCE 7-16, Equation 13.3-2) 0.40 Wp (ASCE 7-16, Equation 13.3-3) Seismic Design Force Fp(H) =0.63 Wp 0.44 Wp Fp (V) = .2SDS 0.26 Wp 0.18 Wp (ASCE 7-16, Section 13.3.1.2) Overstrength Forces (Anchorage into Concrete (LRFD)) Ωo*Fp(H)=1.27 Wp 0.89 Wp *No overstrength required for Fp(V) ASD (0.7 x LRFD)LRFD LRFD ASD (0.7 x LRFD) Hilton Arcadia Hotel Ground 𝐹௣ =0.4𝑎௣𝑆஽ௌ𝑊௣ 𝑅௣/𝐼௣ 1 + 2 𝑧 ℎ= 𝐹௣(min)= 0.3𝑆஽ௌ𝐼௣𝑊௣ = 𝐹௣(max)= 1.6𝑆஽ௌ𝐼௣𝑊௣ = H:\2019\190283\_19-0283-01 Hilton Arcadia Hotel (New Design)\4_Engineering\2.0_Building D\Equipment Anchorage\190283-01.Generator 3900 Cover Street, Long Beach, CA 90808 562.985.3200 P 562.985.1011 F www.mhpse.com EMERGENCY GENERATOR ANCHORAGE 10/22/2024 GL 19-0283-01 1/7 Floor Mounted Equipment Anchor Forces (LRFD) Unit Properties Unit Wp =4129 lbs Anchorage Width, W =39 in Anchorage Length, L =89 in Height, H =72 in CG =48 in Anchor Layout Nanchors, W = Each Side, Parallel to W 2 Nanchors, L = Each Side, Parallel to L 3 Shared Corner Anchors (If YES, then 100+30 considered)YES NAnchors, Total = 6 Forces on Unit (LRFD) Fp(H) =1.27 *Wp=5236 lb Fp(V) =0.26 *Wp=1091 lb Mult =Fp(H)*CG =251 k-in Mresist (OT Parallel to W) =.9*Wp*W/2 =72 k-in Mresist (OT Parallel to L) =.9*Wp*L/2 =165 k-in Forces on Anchors (LRFD) Tult (OT Parallel to W) =+Fp(V)=1711 lbs NAnchors, Total Tult (OT Parallel to L) =+Fp(V)=665 lbs NAnchors, Total Tult (100+30) ==1910 lbs Tult (LRFD) =Tult (100+30) ==1910 lbs Vult (LRFD) =Fp(H) / NAnchors, Total =873 lbs Provide Hilti KB TZ2 - 5/8" dia (4" embed) at each anchor hole. See Hilti print out for calc. Generator 1.0*Tmax+0.3*Tmin ( Mult - Mresist (OT parallel to W) ) (W * Nanchors, L) (Mult - Mresist (OT parallel to L) ) (L * Nanchors, W) H:\2019\190283\_19-0283-01 Hilton Arcadia Hotel (New Design)\4_Engineering\2.0_Building D\Equipment Anchorage\190283-01.Generator 3900 Cover Street, Long Beach, CA 90808 562.985.3200 P 562.985.1011 F www.mhpse.com 2/7 www.hilti.com Hilti PROFIS Engineering 3.1.4 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Oct 22, 2024 Page: Specifier: E-Mail: Date: 1 10/22/2024 Specifier's comments: 1 Input data Anchor type and diameter: Kwik Bolt TZ2 - CS 5/8 (4) hnom3 Item number: 2210272 KB-TZ2 5/8x5 1/2 Specification text: Hilti KB-TZ2 stud anchor with 4.5 in embedment, 5/8 (4) hnom3, Carbon steel, installation per ESR-4266 Effective embedment depth: hef,act = 4.000 in., hnom = 4.500 in. Material: Carbon Steel Evaluation Service Report: ESR-4266 Issued I Valid: 12/1/2023 | 12/1/2025 Proof: Design Method ACI 318-14 / Mech Stand-off installation: Profile: Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 12.000 in. Installation: Hammer drilled hole, Installation condition: Dry Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar 3/7 www.hilti.com Hilti PROFIS Engineering 3.1.4 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Oct 22, 2024 Page: Specifier: E-Mail: Date: 2 10/22/2024 Geometry [in.] & Loading [lb, in.lb] 4/7 www.hilti.com Hilti PROFIS Engineering 3.1.4 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Oct 22, 2024 Page: Specifier: E-Mail: Date: 3 10/22/2024 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 1,910; Vx = 873; Vy = 0; Mx = 0; My = 0; Mz = 0; no 40 5/7 www.hilti.com Hilti PROFIS Engineering 3.1.4 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Oct 22, 2024 Page: Specifier: E-Mail: Date: 4 10/22/2024 2 Proof I Utilization (Governing Cases) Design values [lb]Utilization Loading Proof Load Capacity bN / bV [%]Status Tension Concrete Breakout Failure 1,910 4,842 40 / -OK Shear Concrete edge failure in direction x+873 3,390 - / 26 OK Loading bN bV z Utilization bN,V [%]Status Combined tension and shear loads 0.394 0.258 5/3 32 OK 3 Warnings • Please consider all details and hints/warnings given in the detailed report! Fastening meets the design criteria! 6/7 www.hilti.com Hilti PROFIS Engineering 3.1.4 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Oct 22, 2024 Page: Specifier: E-Mail: Date: 5 10/22/2024 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. 7/7