HomeMy WebLinkAbout400 S Baldwin AVe - 2025 - Dave & Busters kitchen remodelDAVE AND BUSTER'S
STORE #34
400 South Baldwin Avenue
Arcadia, CA 91007
LOCATION INFO.
SHEET TITLE
SHEET NO.
NO. REVISION NOTES DATE
TRU BUILD SURVEYS
AS - BUILT SURVEY FIRM
SCALE
APPROVED BY
DRAWN BY
DATE
PROJECT NO.
TB
34
10.15.2024
BAP
AMD
DAVACO
A CRANE COMPANY
4050 Valley View Lane | Suite150 |
Irving, TX 75038
tel (214) 373-4700 | toll free (877) 732-8226
PERMIT SET SUBMIT 10/15/2024
COVER
SHEET
G0.0
NOT TO SCALE
GENERAL NOTES
DRAWING LIST
PE
R
M
I
T
S
E
T
S
U
B
M
I
T
T
A
L
1
0
-
1
5
-
2
0
2
4
RE
V
1
1
-
2
1
-
2
0
2
5
GENERAL
G0.0 Cover Sheet
G0.1 Code Analysis and Egress Plan
ARCHITECTURAL
A1.0 Demolition Plan
A2.0 Depictive Floor Plan
ELECTRICAL
E0.0 Electrical Legend and Specs
E1.0 Electrical Power Plan
E2.0 Electrical Riser and Panels
PLUMBING
MP.1 Plumbing Specifications
P1.0 Plumbing Plans
FOOD SERVICE EQUIPMENT
K1 Index Sheet
K2 Kitchen Equipment, Schedule & Elevations Plan
K5 Kitchen Electrical/Pos, Schedules & Elevations Plan
K8 Kitchen Plumbing & Gas, Schedules & Elevations Plan
K13 Kitchen Critical, Schedules & Elevations Plan
1. IN ALL INSTANCES, "OWNER" REFERS TO DAVE & BUSTERS. "LANDLORD" REFERS
TO RELATED. "CONTRACTOR" REFERS TO D&B CONTRACTOR.
2. ALL MATERIALS AND LABOR FOR ALL WORK NOTED OR DEPICTED IN THE
CONTRUCTION DOCUMENTS SHALL BE PROVIDED AND INSTALLED BY THE
CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
3. THE CONTRACTOR IS INFORMED THAT THIS PROJECT IS A FIT OUT AND
RENOVATION OF AN EXISTING FACILITY. CONTRACTOR IS RESPONSIBLE FOR
REVIEWING ALL OF THE CONSTRUCTION DOCUMENTS AND OBSERVING EXISTING
CONDITIONS AT THE PRE-BID MEETING.
4. CONTRACTOR'S BASE BID SHALL INCLUDE ALL WORK REQUIRED TO ACHIEVE
DESIGN INTENT. CONTRACTOR SHALL SUBMIT REQUEST FOR INFORMATION (RFI)
DURING BID PROCESS FOR ANY CONCERNS WITH RECONCILING EXISTING
CONDITIONS TO ACHIEVE DESIGN INTENT.
5. IN THE EVEN OF CONFLICTS OF INFORMATION ON THE CONSTRUCTION
DOCUMENTS, THE MORE DETAILED AND STRICTEST INTERPRETATION SHALL
GOVERN, DURING BIDDING CONTRACTOR SHALL SUBMIT REQUEST FOR
INFORMATION (RFI) FOR ANY REQUESTS AND/OR CLARIFICATIONS.
6. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AND SHALL
REPORT ALL DISCREPANCIES TO THE ARCHITECT PRIOR TO COMMENCING THE
WORK.
7. THE CONTRACTOR SHALL VERIFY LOCATION OF ALL UTILITIES AND SHALL
REPORT ANY DEFECTS, DISCREPANCIES, PROBLEMS OR UNCERTAINTIES TO THE
ARCHITECT FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK
AFFECTED.
8. ALL WORK SHALL BE IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL
CODES, ORDINANCES AND ANY APPLICABLE AMENDMENTS.
9. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY BRACING AS
REQUIRED TO ENSURE THE VERTICAL AND LATERAL STABILITY OF THE ENTIRE
STRUCTURE OR A PORTION THEREOF DURING CONSTRUCTION.
10. THE CONTRACTOR SHALL PROVIDE OPENINGS AND CORES, NOT SPECIFICALLY
SHOWN ON THE DRAWING, AS REQUIRED FOR MECHANICAL AND ELECTRICAL
EQUIPMENT, VENTS, DUCTS, AND TYPICAL DETAILS.
11. THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES, INCLUDING
ADVISING ALL TRADES OF FEATURES OF CONSTRUCTION AND PROVIDING
BLOCKS, HOLES, DEPRESSIONS, ETC, AS REQUIRED, FOR A COMPLETE JOB.
REFER TO ALL DRAWINGS FOR SLAB DEPRESSIONS, SLOPES, CURBS, DRAINS,
OPENINGS, ETC.
12. THE CONTRACTOR IS TO BUILD AND MAINTAIN CONSTRUCTION BARRICADES (ALL
NECESSARY LIGHTS, SIGNS, ETC.) FOR THE PROTECTION OF THE PUBLIC, AS PER
LOCAL ORDINANCES AND LANDLORD REQUIREMENTS.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OR REPLACEMENT FOR
ANY DAMAGE CAUSE BY THEM OR THEIR SUBCONTRACTORS TO EXISTING WORK
IN PLACE.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MISCELLANEOUS PERMITS,
FEES, AND INSPECTIONS AS MAY BE REQUIRED FOR COMPLETION OF THE JOB
AS PER ALL GOVERNING AGENCIES.
15. NO STRUCTURAL CHANGES FROM THE APPROVED PLANS SHALL BE MADE IN THE
FIELD WITHOUT PRIOR WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
IF CHANGES ARE MADE WITHOUT WRITTEN APPROVAL, SUCH CHANGES SHALL
BE THE LEGAL AND FINANCIAL RESPONSIBILITY OF THE CONTRACTOR TO
REPLACE OR REPAIR AS DIRECTED BY THE STRUCTURAL ENGINEER.
16. ALL CONTRACTORS SHALL PROVIDE LIABILITY INSURANCE AND WORKERS
COMPENSATION BENEFITS IN ACCORDANCE WITH STATE LAW FOR ALL
WORKERS AND AGENTS WHO WILL BE ON THE SITE AT ANY TIME. OWNERS'
CONTRACTOR TO PROVIDE INSURANCE PER CONTRACT AND INSURANCE
CERTIFICATE WITH COVERAGE'S AND ADDITIONAL INSURANCE AS REQUIRED BY
LANDLORD PRIOR TO CONSTRUCTION START.
17. THE CONTRACTOR AND THEIR SUBCONTRACTORS SHALL BE FULLY ACQUAINTED
WITH SCOPE OF THE WORK TO BE PERFORMED AND SHALL INSPECT SITE
CONDITIONS PRIOR TO BID SUBMITTAL. BID SHALL INCLUDE ALL LABOR AND
MATERIALS REQUIRED TO COMPLETE THE SCOPE OF WORK.
18. IT IS UNDERSTOOD THAT THE OWNER MAY BE PURCHASING AND/OR INSTALLING
MATERIALS, EQUIPMENT, AND FURNISHINGS UNDER SEPARATE CONTRACTS. THE
CONTRACTOR AND HIS SUBCONTRACTORS SHALL COOPERATE WITH THE
OWNER TO ALLOW THE DELIVERY AND INSTALLATION OF SUCH MATERIALS,
EQUIPMENT, AND FURNISHINGS BY OTHER CONTRACTORS AND SUPPLIERS
WHICH MAY COMMENCE PRIOR TO FINAL ACCEPTANCE OF THE REMODELED
SPACE BY THE OWNER SO AS TO ASSURE THE OWNER OF THE EARLIEST
POSSIBLE COMPLETION DATE.
19. NO CHANGE ORDERS WILL BE ALLOWED FOR CLAIMS DUE TO UNFORESEEN OR
UNANTICIPATED CONDITIONS WHICH COULD HAVE BEEN DISCOVERED BY THE
BIDDING CONTRACTOR DURING INSPECTION OF THE SITE DURING THE BIDDING
PERIOD AND PRIOR TO THE COMMENCEMENT OF THE WORK.
20. THESE DRAWINGS ARE NOT TO BE SCALED. IF REQUIRED DIMENSIONS FOR
INFORMATION CANNOT BE FOUND WITHIN THE DRAWINGS OR SPECIFICATIONS,
THE ARCHITECT SHALL BE REQUESTED TO INTERPRET THE DOCUMENT, WHICH
SHALL BE FINAL AND BINDING.
21. ANY PURPOSED SUBSTITUTIONS SHALL BE SUBMITTED TO THE OWNER,
LANDLORD AND THE ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO
INCORPORATION INTO THE WORK. THE CONTRACTOR SHALL BE TOTALLY
RESPONSIBLE FOR ANY CHANGES TO DETAILS OR CONDITIONS MADE
NECESSARY BY ANY SUBSTITUTION.
22. CONTRACTOR TO PROVIDE AND INSTALL FIRE-STOPPING AT ALL PENETRATIONS
AND ALL RATED ASSEMBLIES PER DRAWINGS AND PER CODE.
23. IF CONTRACTOR PROCEEDS WITH ANY WORK ON WHICH THERE IS DISCREPANCY
IN INFORMATION PRIOR TO SEEKING AND RECEIVING CLARIFICATION FROM THE
OWNER OR ARCHITECT, IT IS THE CONTRACTOR'S RISK. OWNER RETAINS RIGHT
FOR REMEDY AT NO ADDITIONAL COST.
CONTACT INFO
DAVE AND BUSTER'S
DAVE AND BUSTER'S
122 SOUTH BELTLINE ROAD
SUITE 500
COPPELL, TEXAS 75019
PHONE: 616.499.2250
CONTACT: ADAM DALY
GENERAL CONTRACTOR
DAVACO
4050 VALLEY VIEW LANE
SUITE 150
IRVING, TX 75039
PHONE: 214.373.4700
PHONE (TOLL FREE): 877.732.8226
ARCHITECT
AGI
15 WEST SEVENTH ST.
COVINGTON, KY 41011
PHONE: 859.261.5400
CONTACT: TIM SEAMAN - tseaman@agi-us.com
KITCHEN RENOVATION CONSTRUCTION DOCUMENT SET
LOCATION/SITE DESCRIPTION
DAVE AND BUSTER'S
STORE #: 34
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
CONSTRUCTION TYPE: III-A
OCCUPANCY TYPE: A-2
SCOPE OF WORK: MINOR KITCHEN RENOVATION INCLUDING
REPLACEMENT OF EQUIPMENT, CUT AND CAP OF PLUMBING AND
ELECTRICAL AS PER PLANS. NO CHANGES TO PARTITIONS OR
EXHAUST. NO CHANGE TO USE, EGRESS, OR OCCUPANCY UNDER
THIS APPLICATION.
TOTAL AFFECTED AREA: 772 SQFT.
1 CONS DOCUMENTS 1/21/2025
GENERAL DEMO NOTES
1. CONTRACTOR IS RESPONSIBLE FOR ALL ASPECTS AND SCOPE OF DEMOLITION
TO ACHIEVE AND ACCOMMODATE THE CONSTRUCTION AND INSTALLATION OF
THE COMPLETE AND FINAL DESIGN CONDITION, WHETHER OR NOT EACH
ELEMENT OF DEMOLITION IS SPECIFICALLY NOTED OR GRAPHICALLY DEPICTED.
2. CONTRACTOR IS TO VERIFY AND FAMILIARIZE THEMSELVES WITH EXISTING
CONDITIONS AND DESIGN INTENT AND SUBMIT REQUEST FOR INFORMATION (BID
CLARIFICATION) FOR ANY UNCERTAIN SCOPE PRIOR TO SUBMISSION OF BIDS.
HAZMAT NOTE
IN THE EVENT OF HAZARDOUS MATERIALS OR OTHER TOXIC SUBSTANCE EXPOSURE
OR THE SUBSTANCE EXPOSURE OR THE SUBSTANTIAL RISK THEREOF, CLIENT WILL HAVE
THE DUTY TO INFORM ARCHITECT OF SUCH RISKS KNOWN OR REASONABLY KNOWABLE
TO CLIENT. IF HAZARDOUS MATERIALS OR ANY OTHER TOXIC SUBSTANCE, OR RISKS TO
THE EXPOSURE THEREOF IS DISCOVERED BY ARCHITECT DURING WORK ON THE
PROJECT, ARCHITECT SHALL, IN ITS SOLE DISCRETION, HAVE THE RIGHT TO SUSPEND
WORK ON THE PROJECT. CLIENT SHALL HAVE THE DUTY PROMPTLY TO RETAIN A
QUALIFIED EXPERT SAFELY TO RENDER OR SUPERVISE THE REMOVAL OF SUCH
HAZARDOUS MATERIALS. CLIENT SHALL INDEMNIFY AND HOLD ARCHITECT, ITS AFFILIATES
AND SUB-CONTRACTORS, AND THEIR OFFICERS, AGENTS AND EMPLOYEES HARMLESS
FROM ANY AND ALL LIABILITY ON PART OF OR DAMAGE TO SUCH ENTITIES OR PERSONS,
INCLUDING THE COST OF LEGAL FEES AND EXPENSES, AS SUCH FEES AND EXPENSES
ARE INCURRED, WHICH MAY RESULT FROM HAZARDOUS MATERIALS EXPOSURE ON THE
PROJECT.
APPLICABLE CODES
BUILDING CALIFORNIA EXISTING BUILDING CODE 2022
(IEBC 2021 AMENDED)
CALIFORNIA BUILDING CODE 2022 (IBC 2021
AMENDED)
MECHANICAL CALIFORNIA MECHANICAL CODE 2022
(IMC 2021 AMENDED)
ELECTRICAL CALIFORNIA ELECTRICAL CODE 2022
(NFPA 70, 2020 AMENDED)
PLUMBING CALIFORNIA PLUMBING CODE 2022
(UPC 2021 AMENDED)
FIRE CODE CALIFORNIA FIRE CODE 2022 (IFC 2021 AMENDED)
ENERGY CALIFORNIA ENERGY CODE 2022 (CEC 2022)
- ISSUED FOR APPROVAL/CONSTRUCTION
- ISSUED FOR REFERENCE ONLY
SITE LOCATION
PROJECT SITE
1
KCL-INS: ("MTR-SLIMJ
"
"
V
2
D
"
)
W=0.0000 - X=11.0000
-
Y
=
2
0
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2D")W=0.0000 - X=11.0000 - Y=20.000
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2D")W=0.0000 - X=11.0000 - Y=20.000
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V
2
D
"
)
W=0.0000 - X=11.0000 - Y=
2
0
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2
D
"
)
W=0.0000 - X=11.0000 - Y=
2
0
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
TRAVEL DISTANCE 149'-4"
TRA
V
E
L
D
I
S
T
A
N
C
E
2
1
4
'
-
7
"
DAVE AND BUSTER'S
STORE #34
400 South Baldwin Avenue
Arcadia, CA 91007
LOCATION INFO.
SHEET TITLE
SHEET NO.
NO. REVISION NOTES DATE
TRU BUILD SURVEYS
AS - BUILT SURVEY FIRM
SCALE
APPROVED BY
DRAWN BY
DATE
PROJECT NO.
TB
34
10.15.2024
BAP
AMD
DAVACO
A CRANE COMPANY
4050 Valley View Lane | Suite150 |
Irving, TX 75038
tel (214) 373-4700 | toll free (877) 732-8226
PERMIT SET SUBMIT 10/15/2024
CODE
ANALYSIS
AND EGRESS
PLAN
G0.1
NOT TO SCALE
1 EGRESS PLAN
NOT TO SCALE
PLUMBING FIXTURE COUNT - NO CHANGE
CODE INFORMATION & EGRESS PLAN LEGEND
STAIR (.3) /DOOR (.2)EXITING PATH LEGEND
DOOR
36"
MAX
EXPT
EXPECTED LOAD
MAX. LOAD
EXIT WIDTH PROVIDED
EGRESS LOADS MARKER
DESIGN TRAVEL DISTANCE
SECOND MEANS OF EGRESS PATH
SPRINKLER REQUIREMENTS:
FIRE ALARM REQUIREMENTS:
SECTION 1017
TABLE 1017.2
EGRESS
TABLE 1006.2.1 COMMON PATH OF EGRESS TRAVEL
SEATING AREA
ALL OTHER AREAS
EXIT ACCESS TRAVEL DISTANCE
EXIT ACCESS TRAVEL DISTANCE
A-2/A-3 ASSEMBLY
EXIT ACCESS TRAVEL DISTANCE PROVIDED
250' (WITH SPRINKLER SYSTEM)
150'
SECTION 903
TOTAL OCCUPANT LOAD - 1,868 (NO
CHANGE)
GENERAL CONSTRUCTION DATA
SECTION 302
NO CHANGE
< 250'
SECTION 602
TABLE 803.13
BUILDING USE AND OCCUPANCY GROUP
CONSTRUCTION CLASSIFICATION (FOLLOW SHELL BUILDING)
EXIT PASSAGEWAYS AND EXIT ENCLOSURES
CORRIDORS
ROOMS AND ENCLOSED SPACES
AUTOMATIC SPRINKLER SYSTEM
BUILDING HEIGHT AND AREA
ALLOWABLE HEIGHT AND BUILDING AREASTABLE 506.2
AUTOMATIC SPRINKLER - EXISTING
ACTUAL AREA
STORIES ABOVE GRADE PLANE
FEET ABOVE GRADE PLANE
A-2, A-3 ASSEMBLY
III-A
INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY
B
B
C
FULLY SPRINKLERED
903.2.1.2, GROUP A-2
ALLOWED PROVIDED
EXISTING
2
EXISTING
EXISTING
BUILDING FIRE RESISTANCE RATINGS
TABLE 601
BEARING WALLS
INTERIOR
EXTERIOR
NON-BEARING WALLS AND PARTITIONS
EXTERIOR
NON-BEARING WALLS AND PARTITIONS
INTERIOR
FLOOR CONSTRUCTION
INCLUDING SUPPORTING BEAMS AND JOIST
ROOF CONSTRUCTION
INCLUDING SUPPORTING BEAMS AND JOIST
2
NO CHANGE
FIRE RESISTANT RATING REQUIREMENTS FOR BUILDING ELEMENTS
STRUCTURAL FRAME
REQUIRED
0 HOURS
0 HOURS
2 HOURS
0 HOURS
0 HOURS
0 HOURS
0 HOURS
TABLE 504.3/504.4
TABLE 504.3/504.4
EXISTING
FIRE/LIFE SAFETY NOTES
1. ILLUMINATED EXIT SIGNS SHALL BE PROVIDED THROUGHOUT THE BUILDING. ALL EXIT SIGNS SHALL HAVE BATTERY BACKUP.
2. THIS BUILDING SHALL BE PROVIDED WITH APPROVED BATTERY POWERED EMERGENCY LIGHTING TO ILLUMINATE ALL REQUIRED MEANS OF EGRESS.
3. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED, SHALL NOT
REQUIRE THE USE OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE.
4. EMERGENCY LIGHTING UNITYS SHALL BE WIRED INTO THE NORMAL LIGHTING CIRCUIT AND ARRANGED AS TO PROVIDE THE REQUIRED ILLUMINATION
AUTOMATICALLY IN THE EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING SUCH AS ANY FAILURE OF PUBLIC UTILITY OR OUTSIDE ELECTRICAL POWER
SUPPLY, OPENING OF A CIRCUIT BREAKER OR FUSE, OR ANY MANUAL ACTS INCLUDING ACCIDENTAL OPENING OF SWITCH CONTROLLING NORMAL LIGHTING
FACILITIES.
5. EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CHILDREN CAN OPEN THE DOOR FROM THE INSIDE OF THE CLOSETS.
6. EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
SHALL BE READILY ACCESSIBLE TO ANYONE OUTSIDE THE DOOR.
7. THE ELEVATION OF THE FLOOR SURFACES ON BOTH SIDES OF A DOOR SHALL NOT VARY BY MORE THAN 1/2". THE ELEVATION SHALL BE MAINTAINED ON BOTH
SIDES OF THE DOORWAY FOR A DISTANCE NOT LESS THAN THE WIDTH OF THE WIDEST LEAF. THRESHOLDS AT THE DOORWAYS SHALL NOT EXCEED 1/2" IN
HEIGHT. RAISED THRESHOLDS AND FLOOR LEVEL CHANGES IN EXCESS OF 1/4" SHALL BE BEVELED WITH A SLOPE OF NOT STEEPER THAN 1 IN 2.
8. A LATCH OR OTHER FASTENING DEVICE ON A DOOR SHALL BE PROVIDED WITH A RELEASING DEVICE HAVING AN OBVIOUS METHOD OF OPERATION AND THAT IS
READILY OPERATED UNDER ALL LIGHTING CONDITIONS. THE RELEASING MECHANISM FOR ANY LATCH SHALL BE NOT LESS THAN 34", AND NOT MORE THAN 48"
ABOVE FINISH FLOOR. DOORS SHALL BE OPERABLE WITH NOT MORE THAN ONE RELEASING OPERATION.
9. PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED, INSPECTED, AND MAINTAINED IN ACCORDANCE WITH NFPA STANDARDS OR LOCAL FIRE DEPARTMENT
REQUIREMENTS GOVERNING PORTABLE FIRE EXTINGUISHERS.
SCOPE OF WORK
LOCATION
EXIT
EXIT SIGN
EXIT SIGN
EXIT COMPLIANCE
NO CHANGE OF USE & NO CHANGE OF EXIT PATH OR TRAVEL DISTANCE
EXIT
75' MAX.
SECTION 1006.1 MIN. NUMBER OF EXITS REQUIRED 4 REQUIRED (4 PROVIDED)
FIRE SAFETY PERMITTING
UNDER SEPARATE PERMIT
1 PERMIT NOTIFICATION 1/21/2025
1
PREP LINE
COOK LINE
EXPO LINE
PERIMETER OF SCOPE OF WORK:
OCCUPANCY AND EGRESS UNCHANGED
DAVE AND BUSTER'S
STORE #34
400 South Baldwin Avenue
Arcadia, CA 91007
LOCATION INFO.
SHEET TITLE
SHEET NO.
NO. REVISION NOTES DATE
TRU BUILD SURVEYS
AS - BUILT SURVEY FIRM
SCALE
APPROVED BY
DRAWN BY
DATE
PROJECT NO.
TB
34
10.15.2024
BAP
AMD
DAVACO
A CRANE COMPANY
4050 Valley View Lane | Suite150 |
Irving, TX 75038
tel (214) 373-4700 | toll free (877) 732-8226
PERMIT SET SUBMIT 10/15/2024
DEMOLITION
PLAN
A1.0
3/8" = 1'-0"
1. EXPO LINE EXISTING EQUIPMENT TO REMAIN.
2. PREP LINE EXISTING EQUIPMENT TO REMAIN.
3. EXISTING FLOOR DRAINS AND FLOOR SINKS TO REMAIN.
REPAIR OR REPLACE AS REQUIRED. THOROUGHLY
CLEAN EACH FIXTURES AND PROVIDE NEW GRATE TO
MATCH EXISTING SIZE AND STYLE.
4. EXISTING CONCRETE CURBS TO BE REMOVED IN THEIR
ENTIRETY. GC TO PATCH, REPAIR AND FILL ALL
CONCRETE SURFACES WHERE CONCRETE WAS
REMOVED. GC TO PREPARE FOR NEW EPOXY COATING
TO MATCH EXISTING.
5. PREP WALL SURFACES FOR ANY NEW APPLICATIONS
WHERE NECESSARY.
KEY NOTES
1
1 DEMO - FLOOR PLAN
3/8" = 1'-0"
GENERAL NOTES
1. CONTRACTOR IS TO COORDINATE REQUIRED LOCATION FOR ALL IN-WALL
BLOCKING. CONTRACTOR IS TO PROVIDE FIRE TREATED IN-WALL BLOCKING,
BACKING AND SUBSTRATES FOR MILLWORK, SHELVING, PANELS, SIGNS, TV'S,
ETC. REFER TO K-SHEETS FOR MORE INFORMATION.
2. ALL DIMENSIONS ARE NOMINAL AND ARE FROM FACE OF SUBSTRATE, UNLESS
NOTED OTHERWISE.
3. CONTRACTOR TO VERIFY EXISTING SITE CONDITIONS BEFORE ANY WORK IS TO
BEGIN, NOTIFY ARCHITECT OF DISCREPANCIES. THE DRAWINGS SHALL BE READ
IN CONJUNCTION WITH STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND
OTHER CONSULTANT DRAWINGS AND SPECIFICATIONS AND WITH SUCH OTHER
WRITTEN INSTRUCTIONS OR SKETCHES AS MAY BE ISSUED DURING THE COURSE
OF THE CONTRACT. ANY DISCREPANCIES SHALL BE REFERRED TO THE
SUPERINTENDENT AND ARCHITECT BEFORE PROCEEDING WITH ANY WORK.
4. ALL WORK TO BE DONE IN ACCORDANCE WITH ALL GOVERNING STATE AND
LOCAL CODES AND ORDINANCES.
5. ALL EQUIPMENT ROOMS TO BE VENTILATED AS REQUIRED BY CODE. SEE
MECHANICAL SHEETS FILED UNDER SEPARATE APPLICATION.
6. ALL NEW PARTITIONS WITH SINKS AND/OR "WET EQUIPMENT" TO HAVE 5/8"
WATER RESISTANT GYPSUM BOARD UNLESS NOTED OTHERWISE, WITH 5/8"
CEMENT BOARD BASE TO 12" A.F.F.
DEMOLITION NOTES
1. SEE MEP & STRUCTURAL DRAWINGS FOR ADDITIONAL DEMOLITION SCOPE AND
NOTES.
2. CONTRACTOR TO VERIFY EXTENT OF ALL REMOVALS AND DIMENSIONS IN THE
FIELD. GC TO NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO
COMMENCEMENT OF WORK.
3. CUT & CAP EXISTING ABANDONED SANITARY & VENT LINES AT SLAB & FILL SLAB
OPENING. COORDINATE WITH PLUMBING DRAWINGS.
4. ALL EXISTING STRUCTURE (BEAMS, GIRDERS, COLUMNS, DECKING, ETC.) TO
REMAIN, UON.
5. PROTECT ALL SURFACES, SUBSTRATES AND CONSTRUCTION WHICH IS NOT
SCHEDULED FOR DEMOLITION.
1. WHEREVER PATCHING OR REPAIRS TO EXISTING FLOOR
ARE NECESSARY AS A RESULT OF WORK DONE GC TO
PROVIDE THE FOLLOWING:
- CONTINUOUS WATERPROOFING 12" UP THE WALL AND
12" OUT ONTO THE FLOOR WHERE APPLICABLE.
- AN APPLIED EPOXY SYSTEM WITH INTEGRAL COVE
BASE AND J-BEAD MOLDING TO RECEIVE WALL
FINISH.
- ALL MATERIALS TO MATCH EXISTING AND BE
INSTALLED PER MANUFACTURERS INSTRUCTIONS
TO ENSURE COMPLETELY WATERPROOF
SURFACE.
6
2
1
2
3
3
4
4 4
4
5
5
5
6
6 6
3
PREP LINE
COOK LINE
EXPO LINE
14
K2
12
K2
12
K2
14
K2
KCL-INS: ("MTR-SLIMJ" "V2D
"
)
W=0.0000 - X=11.0000 - Y=2
0
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2D")W=0.0000 - X=11.0000 - Y=20.0000
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2D")W=0.0000 - X=11.0000 - Y=20.0000
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ" "V2D
"
)
W=0.0000 - X=11.0000 - Y=20
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
KCL-INS: ("MTR-SLIMJ"
"
V
2
D
"
)
W=0.0000 - X=11.0000 -
Y
=
2
0
.
0
0
0
0
-
Z
=
3
0
.
0
0
0
0
DAVE AND BUSTER'S
STORE #34
400 South Baldwin Avenue
Arcadia, CA 91007
LOCATION INFO.
SHEET TITLE
SHEET NO.
NO. REVISION NOTES DATE
TRU BUILD SURVEYS
AS - BUILT SURVEY FIRM
SCALE
APPROVED BY
DRAWN BY
DATE
PROJECT NO.
TB
34
10.15.2024
BAP
AMD
DAVACO
A CRANE COMPANY
4050 Valley View Lane | Suite150 |
Irving, TX 75038
tel (214) 373-4700 | toll free (877) 732-8226
PERMIT SET SUBMIT 10/15/2024
DEPICTIVE
FLOOR
PLAN
A2.0
3/8" = 1'-0"
1. NO CHANGE TO EXISTING EXHAUST OR FIRE
SUPPRESSION WILL BE REQUIRED TO ACCOMMODATE
THE KITCHEN EQUIPMENT BEING REPLACED.
2. NO CHANGE TO EXISTING OCCUPANCY OR EGRESS
WILL BE REQUIRED TO ACCOMMODATE THE KITCHEN
EQUIPMENT BEING REPLACED.
3. EXISTING HAND SINK TO REMAIN.
KEY NOTES
1
1 DEPICTIVE FLOOR PLAN
3/8" = 1'-0"
GENERAL NOTES
1. CONTRACTOR IS TO COORDINATE REQUIRED LOCATION FOR ALL IN-WALL
BLOCKING. CONTRACTOR IS TO PROVIDE FIRE TREATED IN-WALL BLOCKING,
BACKING AND SUBSTRATES FOR MILLWORK, SHELVING, PANELS, SIGNS, TV'S,
ETC. REFER TO K-SHEETS FOR MORE INFORMATION.
2. ALL DIMENSIONS ARE NOMINAL AND ARE FROM FACE OF SUBSTRATE, UNLESS
NOTED OTHERWISE.
3. CONTRACTOR TO VERIFY EXISTING SITE CONDITIONS BEFORE ANY WORK IS TO
BEGIN, NOTIFY ARCHITECT OF DISCREPANCIES. THE DRAWINGS SHALL BE READ
IN CONJUNCTION WITH STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND
OTHER CONSULTANT DRAWINGS AND SPECIFICATIONS AND WITH SUCH OTHER
WRITTEN INSTRUCTIONS OR SKETCHES AS MAY BE ISSUED DURING THE COURSE
OF THE CONTRACT. ANY DISCREPANCIES SHALL BE REFERRED TO THE
SUPERINTENDENT AND ARCHITECT BEFORE PROCEEDING WITH ANY WORK.
4. ALL WORK TO BE DONE IN ACCORDANCE WITH ALL GOVERNING STATE AND
LOCAL CODES AND ORDINANCES.
5. ALL EQUIPMENT ROOMS TO BE VENTILATED AS REQUIRED BY CODE. SEE
MECHANICAL SHEETS FILED UNDER SEPARATE APPLICATION.
6. ALL NEW PARTITIONS WITH SINKS AND/OR "WET EQUIPMENT" TO HAVE 5/8"
WATER RESISTANT GYPSUM BOARD UNLESS NOTED OTHERWISE, WITH 5/8"
CEMENT BOARD BASE TO 12" A.F.F.
2
2 2
1
1
3
3
1
TC
OS
OS
SOS
SWP
ST
SM
SD
S4
T
X
A, AMPS AMPERES
A/C AIR CONDITIONER
AC ALTERNATING CURRENT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE
AL ALUMINUM
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BKBD BACKBOARD
CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CU COPPER
DIST DISTRIBUTION
DN DOWN
DP DISTRIBUTION PANEL
DWG DRAWING
ELR END-OF-LINE RESISTOR
EWC ELECTRIC WATER COOLER
<E> EXISTING
<EX> EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GND GROUND
GALV GALVANIZED
GRS GALVANIZED RIGID STEEL
GFCI GROUND FAULT
HD HEAT DETECTOR
HP HORSEPOWER
IMC INTERMEDIATE METAL CONDUIT
ISC INTERRUPTING SHORT CIRCUIT
IG ISOLATED GROUND
INST INSTANTANEOUS
JB JUNCTION BOX
KAIC KILO (THOUSAND) AMPERES
KCMIL KILO (THOUSAND)
KV KILO (THOUSAND) VOLTS
KVA KILO (THOUSAND)
KW KILO (THOUSAND) WATTS
KWH KILO (THOUSAND) WATT-HOURS
MCB MAIN CIRCUIT BREAKER
MCM THOUSAND CIRCULAR MILS
MCCB MOLDED CASE
MLO MAIN LUGS ONLY
NEUTRAL
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN,
NTS NOT TO SCALE
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED
SCA SHORT CIRCUIT
SWBD SWITCHBOARD
TBD TO BE DETERMINED
TCP TEMPERATURE CONTROL
TD TIME DELAY
TEL TELEPHONE
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE
UNDERGROUND PULLBOX
VOLTS
VA VOLT-AMPERES
VFD VARIABLE
WH WATER HEATER
WP WEATHERPROOF
WT WATERTIGHT
XFMR TRANSFORMER
ELECTRICAL LEGEND
T
X
SURGE SUPPRESSION
C
(NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS AND ARE USED AS APPLICABLE TO THIS PROJECT)
V
N
EC EMPTY CONDUIT
FAA FIRE ALARM ANNUNCIATOR
NEC NATIONAL ELECTRICAL
RMC RIGID METALLIC
RNC RIGID NON-METALLIC
FREQUENCY DRIVE
INTERRUPTING CURRENT
LED TROFFER, TYPE AS NOTED
SWGR SWITCHGEAR
RMS ROOT-MEAN-SQUARE
NESC NATIONAL ELECTRICAL
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
EB ENCASED BURIAL
EEW ENERGIZED ELECTRICAL WORK
EGC EQUIPMENT GROUNDING
<ER> EXISTING TO REMAIN
CONDUCTOR
PANEL
TVSS TRANSIENT VOLTAGE
STEEL CONDUIT
CONDUIT (GALVANIZED)
SAFETY CODE
VOLT-AMPERES
LIQUID-TIGHT FLEXIBLE
CIRCULAR MILS
INTERRUPTING CAPACITY
CIRCUIT INTERRUPTER
AVAILABLE
CONDUIT
NUMBER
CODE
S3
PC
S
X
SSS
SS
SS3 3
GFI GROUND FAULT INTERRUPTER
RECESSED CAN FIXTURE, TYPE AS NOTED
LED STRIP FIXTURE
WALL MOUNTED FIXTURE, TYPE AS NOTED
TRACK LIGHT FIXTURE, TYPE AS NOTED
EMERGENCY LIGHT
EXIT/EMERGENCY LIGHT COMBINATION
CEILING MOUNTED EXIT SIGN
WALL MOUNTED EXIT SIGN
SINGLE POLE SWITCH, 44" AFF
THREE WAY SWITCH, 44" AFF
FOUR WAY SWITCH, 44" AFF
WEATHER PROOF SWITCH, 44" AFF
MOTOR RATED SWITCH, 44" AFF OR AS NOTED
COMBINATION SWITCH AND OCCUPANCY SENSOR, 44" AFF
DIGITAL TIMER SWITCH, 44" AFF
CEILING MOUNTED OCCUPANCY SENSOR
WALL MOUNTED OCCUPANCY SENSOR, 44" AFF
TIME CLOCK
PHOTO CELL
PROVIDE WITH EMERGENCY BALLAST
LED TROFFER, TYPE AS NOTED
LED TROFFER, TYPE AS NOTED
PROVIDE WITH EMERGENCY BALLAST
LED TROFFER, TYPE AS NOTED
PROVIDE WITH EMERGENCY BALLAST
RECESSED CAN FIXTURE, TYPE AS NOTED
FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF
TWO SINGLE POLE SWITCHES GANGED TOGETHER
FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF
TWO THREE WAY SWITCHES GANGED TOGETHER
LIGHTING CONTACTORLC
S
S
EC TO PROVIDE BLACK SPEAKER
8" CONE SPEAKER IN CEILING
EC TO PROVIDE BLACK SPEAKER
8" CONE SPEAKER IN WALL
TELEVISION/CABLE OUTLET
DOOR HOLD-OPEN DEVICE
TRANSFORMER, SEE ONE LINE
SMOKE DETECTOR
HORN
DUCT MOUNTED SMOKE DETECTOR
WPWP
18" AFF OR AS NOTED, NEMA 5-20R
DUPLEX RECEPTACLE
18" AFF OR AS NOTED, NEMA 5-20R
WEATHER PROOF DUPLEX RECEPTACLE
ABOVE COUNTER OR AS NOTED, NEMA 5-20R
DUPLEX RECEPTACLE
18" AFF OR AS NOTED, NEMA 5-20R
QUAD RECEPTACLE
IG
18" AFF OR AS NOTED, NEMA 5-20R
DUPLEX RECEPTACLE
J JJJ WALL / CEILING MOUNTED JUNCTION BOX
60/3/1
F
60/3/3R/40
60/3/1
F
60/3/3R/40
RATING/POLES/NEMA RATING
UNFUSED DISCONNECT SWITCH
RATING/POLES/NEMA RATING/FUSE SIZE
FUSED DISCONNECT SWITCH
TVTV
SINGLE GANG PLASTER RING, 3/4" C ABOVE CEILING
TELEPHONE OUTLET, PROVIDE 4" BOX
SINGLE GANG PLASTER RING, 3/4" C ABOVE CEILING
DATA OUTLET, PROVIDE 4" BOX
FLUSH IN FLOOR, 3/4" C ABOVE CEILING
TELEPHONE OUTLET, PROVIDE 4" BOX
FLUSH IN FLOOR, 3/4" C ABOVE CEILING
DATA OUTLET, PROVIDE 4" BOX
18" AFF OR AS NOTED, SEE SCHEDULE
SPECIAL PURPOSE RECEPTACLE
CCTVCCTV
S
S
CEILING / WALL MOUNT
FIRE ALARM STROBE, MIN 75 CANDELA
SPEAKER STROBE
HEAT DETECTOR
TAMPER SWITCH
H
TS
FLOW SWITCHFS
PULL STATION
MOTOR
GROUND
M
TVSS
TRANSFORMER
UTILITY GRADE METER
TRANSIENT VOLTAGE SURGE SUPPRESSOR
4'X8' UNLESS NOTED OTHERWISE
PLYWOOD EQUIPMENT BACKBOARD
RACEWAY CONCEALED IN WALL OR ABOVE CEILING
RACEWAY EXPOSED
BELOW SLAB OR GRADE, OR UNDER RAISED ACCESS FLOOR
RACEWAY CONCEALED IN FLOOR SLAB, BELOW SLAB OR GRADE
STUB UP
DENOTES CONDUIT TURNING DOWN IN PLAN VIEW
DENOTES CONDUIT TURNING UP IN PLAN VIEW
ABBREVIATIONS
VOLUME CONTROLV
PENDANT FIXTURE, TYPE AS NOTED
PROVIDE WITH EMERGENCY BALLAST
PENDANT FIXTURE, TYPE AS NOTED
44" AFF
WALL BOX DIMMER 1000W UNLESS NOTED DIFFERENTLY
44" AFF
THREE SINGLE POLE SWITCHES GANGED TOGETHER
CLOSED CIRCUIT TELEVISION CAMERA
ELECTRICAL SPECIFICATIONS
A. DEFINITIONS:
1. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR OPERATION.
2. "INSTALL": RECEIVE, MOUNT, AND CONNECT, COMPLETE AND READY FOR OPERATION.
3. "FURNISH": SUPPLY, DELIVER TO JOB SITE, PROTECT AND STORE.
B. WORK INCLUDED: PROVIDE ALL LABOR, TOOLS, MATERIAL, EXCAVATION, BACKFILL, CUTTING, PATCHING, TESTING,
ADJUSTING, AND TRADE COORDINATION REQUIRED FOR A COMPLETE AND FULLY OPERATIONAL INSTALLATION, AS
DESCRIBED ON THE DRAWINGS OR IN THE SPECIFICATIONS.
C. CODES, RULES, AND REGULATIONS: COMPLY WITH ALL CODES ENFORCED BY THE LOCAL INSPECTION AUTHORITY,
THE 2020 EDITION OF THE NATIONAL ELECTRICAL CODE (N.E.C) BEING ENFORCED FOR THIS PROJECT BY THE LOCAL
INSPECTION AUTHORITY, ALL APPLICABLE LAWS AND ORDINANCE, NFPA FIRE CODES, STANDARD BUILDING CODE.
GIVE ALL NECESSARY NOTICES, OBTAIN ALL REQUIRED PERMITS, AND PAY ALL INSPECTION AND OTHER FEES
REQUIRED BY AUTHORITIES HAVING JURISDICTION OVER THE WORK.
D.MATERIALS: ALL MATERIAL SHALL BE NEW, AND SHALL COMPLY WITH THE INDICATED STANDARDS. ALL MATERIAL
SHALL BE U/L LABELED OR U/L LISTED. ALL MATERIAL SHALL BE OF A SUITABLE TYPE AND RATING FOR THE
INTENDED USE, AND SHALL BE INSTALLED IN CONFORMANCE WITH THE INSTRUCTIONS AND RECOMMENDATIONS OF
THE MANUFACTURER.
E.DRAWINGS
1. THE DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL OF THE REQUIRED DETAILS OF THE
WORK. ALL MATERIALS CUSTOMARILY CONSIDERED TO BE A PART OF THE ELECTRICAL WORK AND REQUIRED
FOR A COMPLETE AND OPERATIONAL INSTALLATION SHALL BE PROVIDED WITHOUT ADDITIONAL COST TO THE
OWNER.
2. THE CONTRACTOR SHALL REFER ALSO TO THE ARCHITECTURAL DRAWINGS AND TO THE DRAWINGS OF ALL
OTHER TRADES TO COORDINATE THE ELECTRICAL INSTALLATION. WHERE ELECTRICAL EQUIPMENT IS SHOWN
ON ARCHITECTURAL DRAWINGS OR DETAILS, THE EQUIPMENT SHALL BE INSTALLED AS SHOWN ON THE
ARCHITECTURAL DRAWINGS.
3. EQUIPMENT OF OTHER TRADES IS SHOWN SCHEMATICALLY ON THE ELECTRICAL DRAWINGS. THE
CONTRACTOR SHALL EXAMINE THE DRAWINGS OF THE TRADE PROVIDING THE EQUIPMENT BEFORE
ROUGHING IN THE CONNECTIONS FOR IT. THE CONTRACTOR SHALL CONNECT THE EQUIPMENT WHERE
ACTUALLY INSTALLED, INCLUDING WIRING THROUGH ANY LINE VOLTAGE CONTROLLERS, WITHOUT ANY
ADDITIONAL COST TO THE OWNER.
4. PRIOR TO ROUGHING IN CIRCUITS FOR EQUIPMENT FURNISHED BY OTHER TRADES, AND PRIOR TO RELEASING
FOR MANUFACTURE PANELBOARDS, STARTERS OR MOTOR CONTROL CENTERS FEEDING SUCH EQUIPMENT,
THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL PROVISIONS BEING PLANNED WITH THE TRADE
PROVIDING THE EQUIPMENT AND SUBMIT ANY CONFLICTS IN WRITING TO THE ARCHITECT.
5. THE ARCHITECT MAY DIRECT THE RELOCATION OF ANY ELECTRICAL OUTLET, FIXTURE, OR OTHER EQUIPMENT
TO A LOCATION WITHIN 10 FEET OF THE LOCATION SHOWN ON THE DRAWINGS AT NO ADDITIONAL COST TO
THE OWNER PROVIDED SUCH RELOCATION IS DIRECTED PRIOR TO THE INSTALLATION OF THE OUTLET,
FIXTURE OR EQUIPMENT BEING RELOCATED.
F. SUBMITTAL DOCUMENTS: PRODUCT DATA AND SHOP DRAWINGS SHALL BE SUBMITTED IN SIX COPIES TO THE
ARCHITECT FOR REVIEW PRIOR TO THE RELEASE OF THE MATERIAL FOR MANUFACTURE. REVIEW OF SUBMITTALS
BY THE ARCHITECT WILL BE ONLY FOR GENERAL CONFORMANCE WITH THE DRAWINGS AND SPECIFICATIONS.
REVIEW WILL BE MADE ONLY OF INFORMATION CLEARLY AND SPECIFICALLY INDICATED IN THE SUBMITTAL, AND
DOES NOT IMPLY THE ACCEPTABILITY OF DETAILS WHICH ARE NOT SO DESCRIBED IN THE SUBMITTAL. REVIEW OF
THE SUBMITTAL DOCUMENTS BY THE ARCHITECT DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO
COMPLY WITH ALL REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. SUBMITTAL IS REQUIRED FOR
PANELBOARDS AND LOADCENTERS, LIGHT FIXTURES, WIRING DEVICES, FIRE ALARM DEVICES, AND SURFACE
ALUMINUM RACEWAY.
G.AS-BUILT DRAWINGS: AS-BUILT DRAWINGS SHALL BE MAINTAINED AT THE JOBSITE, AND SHALL BE AVAILABLE FOR
REVIEW DURING CONSTRUCTION. AS-BUILT DRAWINGS SHALL BE KEPT CURRENT DURING THE COURSE OF
CONSTRUCTION OF THE WORK. SUBMIT AS-BUILT DRAWINGS TO THE ARCHITECT AT THE COMPLETION OF THE
PROJECT.
H. TESTING: TEST ALL PARTS OF THE WORK TO VERIFY COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS.
VERIFY TIGHTNESS OF ALL MECHANICAL AND ELECTRICAL CONNECTIONS. VERIFY INTEGRITY OF ALL WIRING
SYSTEMS TO ASSURE CONTINUITY, ABSENCE OF UNINTENTIONAL GROUNDS, AND INTEGRITY OF REQUIRED
GROUNDS.
I. CHANGE REQUEST (CHANGE ORDER) APPROVAL: CHANGE REQUESTS WILL NOT BE CONSIDERED UNLESS THE
CONTRACTOR'S DETAILED LABOR AND MATERIAL ESTIMATE DESCRIBING THE CHANGE IS SUBMITTED TO THE
ARCHITECT ALONG WITH THE CHANGE REQUEST, WITH MATERIAL PRICES AND LABOR UNITS ASSIGNED TO EACH
LINE ITEM OF THE ESTIMATE. MATERIAL PRICES SHALL BE THE ACTUAL PRICE PAID BY THE CONTRACTOR FOR
MATERIAL PURCHASED OR THE ACTUAL PRICE QUOTED TO THE CONTRACTOR BY THE MATERIAL VENDOR
PROPOSED BY THE CONTRACTOR.
J.COORDINATION WITH THE WORK OF OTHERS: COORDINATE WITH EACH TRADE FURNISHING EQUIPMENT REQUIRING
ELECTRICAL SERVICE TO INSURE THAT THE CHARACTERISTICS SHOWN ON THE DRAWINGS FOR THE CIRCUIT
SERVING THE EQUIPMENT ARE COMPATIBLE WITH THE REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED.
CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND ASSOCIATED BRANCH CIRCUITS SHOWN ON THE
DRAWINGS TO FEED HVAC EQUIPMENT, KITCHEN EQUIPMENT, ELEVATOR MOTORS, AND OTHER EQUIPMENT HAVE
BEEN SELECTED BASED UPON THE CHARACTERISTICS OF EQUIPMENT BY ONE MANUFACTURER AND MAY NOT BE
CORRECT FOR THE EQUIPMENT BEING PROVIDED BY THE CONTRACTOR. THE CONTRACTOR SHALL DETERMINE THE
OPERATING CHARACTERISTICS OF THE EQUIPMENT ACTUALLY BEING PROVIDED AND SHALL PROVIDE AT NO
ADDITIONAL COST TO THE OWNER CIRCUIT BREAKERS, FUSES, DISCONNECT SWITCHES AND BRANCH CIRCUITS AS
REQUIRED BY THAT EQUIPMENT.
K.EXISTING WORK: THE EXISTING ELECTRICAL INSTALLATION SHALL REMAIN AS-IS AND IN OPERATION EXCEPT WHERE
OTHERWISE REQUIRED. GIVE WRITTEN NOTICE OF ANY UNFORESEEN EXISTING CONDITIONS WHICH MAY AFFECT
THE WORK. WORK INVOLVING EXISTING SYSTEMS OR EXISTING SPACES SHALL BE ACCOMPLISHED WITH MINIMUM
INCONVENIENCE TO THE OWNER, AND SHALL BE DONE IN A MANNER AND TIME APPROVED BY THE OWNER. ANY
INTERRUPTIONS SHALL BE DURING TIMES DESIGNATED BY THE OWNER.
L. DEMOLITION: IN THE AREA SHOWN ON THE ARCHITECTURAL DRAWINGS TO BE DEMOLISHED REMOVE ALL EXISTING
CONDUITS, CONDUCTORS, BOXES, FIXTURES, SERVICE ENTRANCE CONDUCTORS, DISTRIBUTION EQUIPMENT, AND
ALL OTHER ELECTRICAL EQUIPMENT NOT SHOWN TO REMAIN. UNLESS OTHERWISE INDICATED, MATERIAL BEING
REMOVED INCLUDING WIRE, CONDUIT, AND HANGING MATERIALS BEING REMOVED SHALL BECOME THE PROPERTY
OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES. EQUIPMENT NOTED TO REMAIN THE
PROPERTY OF THE OWNER SHALL BE STORED ON SITE AS DIRECTED BY THE ARCHITECT. COORDINATE WITH OTHER
TRADES AND DISCONNECT MOTORS, HEATERS, OR OTHER EQUIPMENT AS REQUIRED FOR THE DEMOLITION OF
OTHER TRADES WORK. CUT OFF ALL IN FLOOR CONDUITS, GRIND SMOOTH WITH FLOOR AND PREPARE FOR
PATCHING BY OTHERS. REMOVE CONDUCTORS AND DEVICES FROM WALL AND CEILING OUTLETS AND PREPARE
OUTLET FOR PATCHING BY OTHERS. CONTRACTOR SHALL DENOTE ALL DEMOLISHED CIRCUITS ON EXISTING PANEL
DIRECTORIES AND NOTE ALL SPARE BREAKERS.
3. ALL PENETRATIONS OF FIRE RATED WALLS, SLABS, PARTITIONS, AND CEILINGS SHALL BE FIREPROOFED WITH
A U.L. LISTED SYSTEM THAT WILL MAINTAIN THE ORIGINAL FIRE RATING OF THE PENETRATED STRUCTURE.
ALL FIREPROOFING MATERIALS APPLIED AT ANY ONE PENETRATION SHALL BE THE PRODUCT OF ONE
MANUFACTURER AND SHALL BE APPLIED AS DESCRIBED BY THE U.L. FIREPROOFING SYSTEM BEING
CONSTRUCTED. FIREPROOFING OF SLEEVES, CABLE TRAYS, TROUGHS, AND NIPPLES TO BE USED FOR LOW
VOLTAGE CABLES SHALL BE INDEFINITELY NON-HARDENING AND REMOVABLE WITH COMMON HAND TOOLS.
4. BACKBOARDS SHALL BE 8 FT. HIGH BY LENGTH SHOWN ON THE DRAWINGS AND SHALL BE U/L LABELED FIRE
TREATED PLYWOOD.
5. PROVIDE ALL POWER WIRING AND CONNECTIONS FOR ALL ELECTRICALLY OPERATED EQUIPMENT. POWER
WIRING INCLUDES WIRING THROUGH ANY LINE VOLTAGE CONTROL DEVICES, SUCH AS THERMOSTATS AND
MANUAL STARTERS. INSTALL ALL STARTERS AND CONTACTORS EXCEPT THOSE FURNISHED AS AN
INTEGRAL PART OF THE EQUIPMENT.
6. CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT NOT INSTALLED IN A
PLENUM SPACE SHALL BE MADE WITH A SHORT LENGTH OF LIQUIDTIGHT FLEXIBLE CONDUIT, MINIMUM 18",
INSTALLED IN A MANNER TO PERMIT MOVEMENT OF EQUIPMENT.
7. PERFORM ALL EXCAVATING, BACKFILLING, CUTTING AND REPAIRING REQUIRED FOR INSTALLATION OF
ELECTRICAL WORK.
8. CONTRACTOR SHALL X-RAY FLOOR SLABS PRIOR TO ALL CORE DRILLINGS.
N.CONDUIT: FEEDERS AND BRANCH CIRCUIT HOME RUNS SHALL BE CONSTRUCTED OF EMT WITH ALL STEEL
SET-SCREW FITTINGS. CONNECTORS SHALL BE INSULATED THROAT TYPE. PROVIDE METALLIC BUSHINGS WITH
PLASTIC INSERTS FOR 3" OR LARGER. CONDUITS FEEDING OR CONNECTING TO EQUIPMENT PROVIDED BY OTHER
TRADES SHALL NOT BE INSTALLED UNTIL SUCH EQUIPMENT IS INSTALLED OR UNTIL SPECIFIC ROUGH-IN
INSTRUCTIONS ARE PROVIDED BY THE TRADE PROVIDING THE EQUIPMENT. UNLESS OTHERWISE INDICATED,
CONDUITS SHALL BE CONCEALED. RACEWAYS INSTALLED IN OR UNDER SLABS, ON GRADE, OR AS EXTERIOR DUCT
BANKS SHALL BE PVC COATED RMC. RUN EXPOSED CONDUITS PARALLEL OR PERPENDICULAR TO STRUCTURAL
ELEMENTS. TWO OR MORE RACEWAYS RUN TOGETHER SHALL BE INSTALLED ON GANG TRAPEZE TYPE HANGERS.
SUCH RACEWAYS ASSEMBLIES SHALL BE RUN PARALLEL OR PERPENDICULAR TO STRUCTURAL ELEMENTS.
CONDUITS EMBEDDED IN SLABS SHALL HAVE A MINIMUM OF 1" COVER OF CONCRETE ON ALL SIDES. OUTSIDE
DIAMETER OF CONDUIT SHALL NOT EXCEED 1/3 OF THE SLAB THICKNESS, AND SHALL NOT BE LARGER THAN 1 1/4".
PROVIDE 0.25" NYLON PULL TAPE IN ALL EMPTY CONDUITS. BRANCH CIRCUITS MAY UTILIZE TYPE MC ARMORED
CABLE ASSEMBLY WITH COPPER CONDUCTORS AND FULL SIZE EQUIPMENT GROUNDING CONDUCTORS FOR
INDIVIDUAL DROPS TO DEVICES. TYPE MC CABLE SHALL BE SUPPORTED A 48" INTERVALS AND SHALL NOT LAY ON
THE CEILING GRID OR INTERFERE WITH THE REMOVAL OF CEILING SIZE EQUIPMENT GROUNDING CONDUCTORS.
O.CONDUCTORS: ALL BUILDING WIRE SHALL BE 600 VOLT RATED THHN OR THWN COPPER, STRANDED FOR SIZES
$8AWG AND LARGER, SOLID FOR SIZES 10 AND SMALLER UNLESS APPLIED FOR CONTROL. ALL BUILDING WIRE AND
SPECIAL CABLES FOR SYSTEMS SHALL BE INSTALLED IN A RACEWAY. ALL WIRE AND CABLE SHALL BE DELIVERED TO
THE JOBSITE IN ORIGINAL UNBROKEN PACKAGES, CARTONS OR REELS, WITH THE MANUFACTURERS NAME, UL
LABEL, AND CHARACTERISTICS OF THE PRODUCT PLAINLY VISIBLE. ALL WIRE AND CABLE SHALL BE MANUFACTURED
IN THE UNITED STATES OF AMERICA. WIRES SHALL BE COLOR CODED AS FOLLOWS (A,B,C,N,G): 120/208-BLACK, RED,
BLUE, WHITE, GREEN; 480/277 - BROWN, ORANGE, YELLOW, GRAY, GREEN. SPLICES SHALL BE COMPRESSION TYPE.
CONTROL CONDUCTORS SHALL BE TERMINATED WITH INSULATED CONNECTORS, T&B STAKON. 120 VOLT CIRCUITS
WITH HOMERUN LENGTH OVER 100 FEET AND 277 VOLT CIRCUITS WITH A HOMERUN LENGTH OVER 200 FEET SHALL
HAVE #10 MINIMUM HOMERUN CONDUCTORS. ALL THREE PHASE BRANCH CIRCUITS WITH A COMMON NEUTRAL
SHALL HAVE #10 MINIMUM NEUTRAL.
P.BOXES: OUTLET BOXES SHALL BE SHEET STEEL, MINIMUM 4" SQUARE, MINIMUM 1.5" DEEP, WITH PLASTER RING IN
PLASTER OR BRICK CONSTRUCTION. OUTLETS BOXES IN POURED CONCRETE SHALL BE CONCRETE RINGS.
MASONRY BOXES SHALL BE USED IN MASONRY OR TILE CONSTRUCTION. OUTLET BOXES FOR SURFACE ALUMINUM
RACEWAY SHALL BE 4-11/16 WITH PLASTER RINGS ORIENTED HORIZONTALLY. BOXES SHALL BE SECURELY
ANCHORED IN PLACE, AND SHALL BE SUPPORTED INDEPENDENT OF THE RACEWAY SYSTEM. PULL BOXES SHALL BE
GALVANIZED SHEET STEEL, MINIMUM 12 GAUGE, WITH SCREW COVERS, AND WELDED CONSTRUCTION. WELDS
SHALL BE COLD GALVANIZED. USING PERMANENT WATER PROOF WIDE BLACK MARKER, CLEARLY LABEL COVER OF
ALL BRANCH CIRCUIT JUNCTION AND PULL BOXES WITH PANEL AND CIRCUIT NUMBER OF CIRCUITS CONTAINED IN
OR PASSING THROUGH THE BOX. BRANCH CIRCUIT AND FEEDER JUNCTION AND PULL BOXES USED WITH
EMERGENCY FEEDERS AND CIRCUITS SHALL BE PAINTED RED. PROVIDE ENGRAVED LAMINATED PLASTIC LABEL ON
COVER OF EACH FEEDER PULL OR JUNCTION BOX INDICATING FEEDER DESIGNATION, SOURCE, LOAD, AND
VOLTAGE.
Q.WIRING DEVICES: SWITCHES FOR LIGHTING CIRCUITS SHALL BE 120/277 VOLT, 20 AMP, A.C. ONLY, QUIET TYPE, WITH
GROUND BONDING SCREW, SPECIFICATION GRADE. MOMENTARY CONTACT SWITCHES SHALL BE SINGLE POLL
DOUBLE THROW, CENTER OFF GE #5935 OR EQUAL. DUPLEX RECEPTACLES SHALL BE 15 AMP HUBBELL 5262 OR
EQUAL. DEDICATED DUPLEX RECEPTACLES SHALL BE 20AMP HUBBELL IG5362 OR EQUAL. SPECIAL RECEPTACLES
SHALL BE OF SIMILAR CONSTRUCTION. FACE PLATES SHALL BE SMOOTH NYLON OR THERMOSET PLASTIC.
ADJACENT OUTLETS SHALL BE INSTALLED IN MULTI-GANG BOXES WITH A SINGLE MULTI-GANG FACE PLATE.
RECEPTACLES CONNECTED TO AN EMERGENCY CIRCUIT SHALL BE RED. COORDINATE COLOR OF DEVICES AND
FACEPLATE WITH ARCHITECT.
R.GROUNDING: ALL FEEDERS AND BRANCH CIRCUITS SHALL BE PROVIDED WITH INSULATED GREEN EQUIPMENT
GROUNDING CONDUCTOR.
S.LIGHTING: SPARE FLUORESCENT LAMPS SHALL MATCH BUILDING STANDARD UNLESS NOTED OTHERWISE.
INCANDESCENT LAMPS SHALL BE 130VOLT. NEW BALLASTS SHALL BE SOILD STATE ELECTRONIC. EXIT FIXTURES
SHALL MATCH BUILDING STANDARD. FIXTURE LOCATIONS SHALL BE AS SHOWN ON THE REFLECTED CEILING PLAN.
PROVIDE LAY-IN FIXTURES WITH TWO REMOVABLE CLIPS ATTACHING FIXTURE TO CEILING GRID. FLANGED
FIXTURES SHOWN TO BE INSTALLED IN CONTINUOUS ROWS SHALL NOT HAVE INTERMEDIATE FLANGES. ALL
PENDANT FIXTURES SHALL BE MOUNTED TO STRUCTURE. SEISMIC SUPPORT WIRES AND/OR COMPRESSION STRUTS
FOR LAY-IN FIXTURES SHALL BE SUBJECT TO LOCAL AHJ LATEST REQUIREMENTS.
T.PANELBOARDS: DEAD FRONT PANEL CONSTRUCTION WITH SEPARATELY MOUNTED INTERIOR TRIM. MAIN AND
BRANCH DEVICES SHALL BE BOLT-ON. MULTI-POLE BREAKERS SHALL BE COMMON TRIP. WIDTH SHALL NOT EXCEED
22" FOR PANELBOARD AND ENCLOSURE SHALL MATCH BUILDING STANDARD. PROVIDE GROUND BUS IN PANELBOARD
AND PROVIDE DEVICE MOUNTING HARDWARE WHERE A SPACE IS SCHEDULED. PANEL AND OCPD SHORT CIRCUIT
RATINGS SHALL BE AT LEAST 10% GREATER THAN AVAILABLE SHORT CIRCUIT CURRENT AT PANELBOARD.
U.DRY-TYPE TRANSFORMERS: TRANSFORMERS SHALL BE DRY-TYPE, ENCLOSED, SELF-COOLED, VENTILATED TYPE,
DEAD-FRONT DRIP PROOF. PRIMARY AND SECONDARY TAPS SHALL BE ACCESSIBLE FROM THE FRONT.
TRANSFORMERS SHALL MEET OR EXCEED BUILDING STANDARD TRANSFORMERS SPECIFICATIONS. PROVIDE AN
EQUIPMENT GROUNDING CONDUCTOR IN THE PRIMARY FEED TO THE TRANSFORMER, SUPPLEMENTAL GROUND TO
NEAREST ACCESSIBLE PRIMARY STRUCTURAL MEMBER OR EQUIPMENT ROOM GROUND BUS BAR. SIZE PER NEC
AND RUN IN CONDUIT WITH BOND BUSHING AT EACH END. NEUTRAL AND GROUNDING CONDUCTOR SHALL BE
BONDED TO ENCLOSURE.
SHORT CIRCUIT AVAILABLE CURRENTXXXX
LFMC
METAL CONDUIT
USB
AFF AS NOTED, NEMA 5-20R W/ USB CHARGER
WEATHER PROOF DUPLEX RECEPTACLE
TYPE WSD OR EQUAL
M. BASIC MATERIALS AND METHODS:
1. ALL WORK SHALL BE SUPPORTED FROM STRUCTURAL ELEMENTS OF THE BUILDING, EXCEPT CEILING
MOUNTED EQUIPMENT SUCH AS LIGHT FIXTURES, DETECTORS, REMOTE LAMPS, ETC. CEILING MOUNTED
EQUIPMENT SHALL BE SUPPORTED FROM CEILING STRUCTURAL MEMBERS, INDEPENDENT OF CEILING TILES.
SIZE AND SPACING OF SUPPORTS SHALL BE DETERMINED BY THE LOAD TO BE SUPPORTED SUCH THAT THE
WORKING LOAD OF SUPPORTS WILL NOT EXCEED A SAFETY FACTOR OF 4:1. PLASTIC ANCHORS ARE NOT
ACCEPTABLE. ELECTRICAL WORK SHALL NOT BE SUPPORTED FROM PIPING, DUCTS, OR WORK OF OTHER
TRADES.
2. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL SWITCHBOARDS, PANELBOARDS, MOTOR CONTROL
CENTERS, STARTERS, DISCONNECTS, PRIMARY SELECTOR SWITCHES, AND TRANSFORMERS. INDICATE
EQUIPMENT NAME, CIRCUIT SOURCE AND NUMBER, CIRCUIT SIZE, AMPERE RATING, VOLTAGE AND PHASE.
NAMEPLATES SHALL BE BLACK BACKGROUND LAMACOID PLASTIC WITH 0.25" WHITE LETTERS.
E0.0
ELECTRICAL
LEGEND AND
SPECS
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
GUID O O AL
RE
Z
REGI
S
TRE D
E
P R OF ESSIONALE
N
G
IN
E
E
R
ELECT R I C A L
A
TATEOF I R NIA
C F OL
N
S
I A A
F
R
R
F
R
R
ELECTRICAL POWER PLAN
1/4" = 1'-0"
ELECTRICAL POS PLAN
1/4" = 1'-0"
E7
2
B
E7
0
.
2
KD
S
5
4
A
KD
S
5
4
B
GFCI NOTE:
ALL 125-VOLT THROUGH 250-VOLT RECEPTACLES
SUPPLIED BY SINGLE-PHASE BRANCH CIRCUITS RATED 150
VOLTS OR LESS TO GROUND, 50 AMPERES OR LESS, AND
ALL RECEPTACLES SUPPLIED BY THREE-PHASE BRANCH
CIRCUITS RATED 150 VOLTS OR LESS TO GROUND, 100
AMPERES OR LESS IN KITCHENS AND FOOD PREP AREAS
SHALL USE GFCI BREAKER TYPE. GFCI BREAKERS SHALL
BE INSTALLED IN ACCORDANCE WITH 2020 NEC ARTICLE
210.8.
ALL 125-VOLT THROUGH 250-VOLT RECEPTACLES
SUPPLIED BY SINGLE-PHASE BRANCH CIRCUITS RATED 150
VOLTS OR LESS TO GROUND, 50 AMPERES OR LESS, AND
ALL RECEPTACLES SUPPLIED BY THREE-PHASE BRANCH
CIRCUITS RATED 150 VOLTS OR LESS TO GROUND, 100
AMPERES OR LESS IN RESTROOMS, WITHIN 6 FEET FROM
A SINK, OR ON EXTERIOR SHALL BE INSTALLED IN
ACCORDANCE WITH 2020 NEC ARTICLE 210.8 AND BE
READY ACCESSIBLE. FOR EQUIPMENT THAT WOULD HAVE
TO BE MOVED TO RESET THE RECEPTACLE PER THE NEC
DEFINITION. A GFCI BREAKER SHALL BE UTILIZED IN LIEU
OF A RECEPTACLE.
KITCHEN ELECTRICAL SCHEDULE
ITEM
#V/ɸ AMPS H.P.KW TYPE LOCATION A.F.F.NEMA REMARKS
EDCO 120V/1 PH 15.0 EACH --D.C.O.WALL 48"5-20R CONVENIENCE OUTLET - (2) RIP'S
E45 115V/1 PH 5.2 0.35 -D.C.O.WALL 24"5-15P UNDER COUNTER FREEZER - E.C. TO SUPPLY & INSTALL GFCI PROTECTED DUPLEX
E49 115V/1 PH 4.7 0.25 -D.C.O.WALL 24"5-15P PIZZA STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E49B 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P SAUTE STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E54 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P BREADING STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E55 120V/1 PH CONTROLS - 1.0,
FILTER - 8.0 --QUAD WALL 24"5-20R FRYER ASSEMBLY w/FILTER - DEDICATED 20A CIRCUIT BREAKER
E58 120V/1 PH .6 EACH --D.C.O.WALL 24"5-15P COUNTER TOP PLANCHA - (2) RIP'S
E59 115V/1 PH 12.0 --D.C.O.WALL 24"5-15P SHORTY REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E60 120V/1 PH 15.9 EACH -
1910
WATTS
EACH
D.C.O.WALL 48"5-20P FRY WARMING STATION - (2) RIP'S
E64 115V/1 PH 2.9 --D.C.O.WALL 24"5-15P SHORTY REFRIGERATOR - E.C. TO SUPPLY & INSTALL GFCI PROTECTED DUPLEX
E66 208V/1 PH 13.6 EACH -
1700
WATTS
EACH
S.P.O.WALL 72"6-20P MICROWAVE - (3) RIP'S
E66A 208V/1 PH 13.6 -1700
WATTS S.P.O.WALL 72"6-20P MICROWAVE - REUSE EXISTING OUTLET
E70.2 115V/1 PH 5.5 0.55 -D.C.O.WALL 72"5-15P REACH-IN FREEZER
E71 115V/1 PH 4.2 0.22 -D.C.O.WALL 90"5-15P REACH-IN REFRIGERATOR - REUSE EXISTING OUTET
E71A 115V/1 PH 4.2 0.22 -D.C.O.WALL 72"5-15P REACH-IN REFRIGERATOR
E72A 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P FRY REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E72B 115V/1 PH 6.5 (2) 0.20 -D.C.O.WALL 24"5-15P DISH-UP REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E72C 115V/1 PH 6.5 --D.C.O.WALL 24"5-15P PIZZA PREP REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E73 120V/1 PH 3.3 -400 WATTS D.C.O.WALL 48"5-15P COUNTER TOP WARMER
E74 120V/1 PH 15.0 -1800
WATTS
D.C.O./
JBOX WALL 52"5-15P CONVEYOR TOASTER - REUSE EXISTING OUTLET
E75 120V/1 PH 7.5 -900 WATTS D.C.O.WALL 24"5-15P WARMING DRAWER - NARROW 2-TIER
E76 120V/1 PH 12.0 -1440
WATTS D.C.O.WALL 24"5-15P CVAP HOLDING DRAWER
E125 208V/3 PH 30.0 EACH -9600
WATTS S.P.O.WALL 48"15-30P CONVECTION OVEN - (2) RIP'S - E.C. INSTALL 4S BOX
E143 120V/1 PH 10.0 EACH -
1200
WATTS
EACH
D.C.O.WALL 48"5-15P HOT FOOD WELL - (2) RIP'S
E143A 120V/1 PH 10.0 -1200
WATTS D.C.O.WALL 24"5-15P HOT FOOD WELL
KITCHEN POS ELECTRICAL SCHEDULE
ITEM #V/ɸ AMPS TYPE LOCATION A.F.F.REMARKS
KDS54A 120V/ 1 PH 20.0 D.C.O.WALL 66"KDS SYSTEM - DEDICATED CIRCUIT - VERIFY REQUIREMENTS w/OWNER
KDS54B DATA JBOX WALL 66"DATA/KDS CABLE - 2" x 4" EMPTY BOX w/CONDUIT TO 6" ABOVE CEILING LINE -
VERIFY REQUIREMENTS w/OWNER
KDS64A 120V/ 1 PH 20.0 D.C.O.WALL 72"KDS SYSTEM - REUSE EXISTING OUTLET
KDS64B DATA JBOX WALL 72"DATA/KDS CABLE - REUSE EXISTING OUTLET
KDS72C 120V/ 1 PH 20.0 EACH D.C.O.WALL 86"KDS SYSTEM - DEDICATED CIRCUIT - VERIFY REQUIREMENTS w/OWNER
KDS72D DATA JBOX WALL 86"DATA/KDS CABLE - 2" x 4" EMPTY BOX w/CONDUIT TO 6" ABOVE CEILING LINE -
VERIFY REQUIREMENTS w/OWNER
KDS72E 120V/ 1 PH 20.0 EACH D.C.O.WALL VARIES KDS SYSTEM - (4) RIP'S - REUSE EXISTING OUTLET
KDS72F DATA VARIES WALL VARIES DATA/KDS CABLE - (4) RIP'S - REUSE EXISTING OUTLET
POWER NOTES:
1.COORDINATE DISCONNECTION OF POWER TO EQUIPMENT
BEING DEMOLISHED/REMOVED/RELOCATED PRIOR TO
START OF WORK.
2.FOR KITCHEN EQUIPMENT BEING REMOVED/REPLACE:
REUSE EXISTING ELECTRICAL DEVICES AND CIRCUITRY IF
IS IN GOOD WORKING CONDITION AND MEET
REQUIREMENTS OF NEW/REPLACED KITCHEN EQUIPMENT.
OTHERWISE, REMOVE DEVICES AND CAP AND ABANDON
EXISTING WIRING, DISCONNECT FEEDER AT PANELBOARD,
TURN OFF AND LABEL BREAKER AS "SPARE".
3.REFER TO KITCHEN ELECTRICAL EQUIPMENT FOR
ROUGH-IN LOCATIONS AND ADDITIONAL REQUIREMENTS
.
4.REFER TO ARCHITECTURAL FOR EXACT ELECTRICAL
OUTLETS LOCATION OF KITCHEN ELECTRICAL EQUIPMENT.
5.PROPOSED GFCI BANK LOCATION AS PER GFCI NOTE ON
THIS SHEET. ALL GFCI DEVICES SHALL BE ACCESSIBLE.
COORDINATE FINAL LOCATION WITH KITCHEN EQUIPMENT.
SEE DETAIL.
6.G.C SHALL PROVIDE LITTEL FUSE INDUSTRIAL SHOCK
BLOCK GFCI CLASS A SB5000 OR SIMILAR TO ALL 208V
SINGLE AND THREE PHASE EQUIPMENT WITHIN THE
KITCHEN AREA.
E7
6
ED
C
O
E7
1
E6
6
E7
4
E6
0
E7
2
A
E7
2
C
E7
5
E1
4
3
E1
2
5
E1
2
5
E6
6
A
E6
6
E4
9
GFCI BANK #1 DETAIL
NTS
GFCI BANK #2 DETAIL
NTS
KB-7
EDCO
NOTE 5
NOTE 5
GFCI
BANK #1
GFCI
BANK #2
E71 E72B E74 E76 E60 E72A
E72C E75 E143 E49 KDS KDSE58
E5
4
E1
4
3
A
E5
5
E6
0
E4
5
E7
3
E5
8
E5
9
E5
8
E1
4
3
E4
9
B
E6
6
E6
4
E7
1
A
KD
S
7
2
E
KD
S
7
2
F
KD
S
7
2
E
KD
S
7
2
F
KD
S
7
2
F
KD
S
7
2
E
KD
S
7
2
D
KD
S
7
2
C
KD
S
7
2
E
KD
S
7
2
F
KD
S
6
4
A
KD
S
6
4
B
E54 E143A EDCO E55 E60 E45 E73
KB
-
3
1
,
3
3
,
3
5
NO
T
E
6
KB
-
2
5
,
2
7
,
2
9
NO
T
E
6
KB
-
1
4
,
1
6
NO
T
E
6
KB
-
2
KB
-
4
KB
-
6
KB
-
1
0
,
1
2
NO
T
E
6
KB
-
1
7
,
1
9
NO
T
E
6
KB
-
1
8
KB
-
2
0
KB
-
2
2
KB
-
8
KB
-
2
4
KB
-
7
KB
-
4
0
KB
-
7
2
KB-40 KB-24 KB-72 KB-8 KB-22 KB-20
KB-18 KB-4 KB-6 KB-2
KB
-
2
6
ED
C
O
KB
-
9
,
1
1
NO
T
E
6
E59 E143 E49B E64 E71A
E70.2
KDS
KB-26
KB
-
2
1
KB-21
KB
-
7
4
KB-74 KB-79
KB
-
7
9
KB
-
4
4
KB
-
4
8
KB
-
5
2
KB
-
5
6
KB
-
6
0
KB
-
6
0
KB
-
6
8
KB
-
6
4
KB
-
7
1
KB
-
7
8
KB
-
8
2
KB-44 KB-48 KB-52 KB-56
KB-60 KB-68 KB-64 KB-71 KB-78 KB-82 LAV-24
LA
V
-
2
6
LA
V
-
2
6
LA
V
-
2
8
LA
V
-
2
8
LAV-26 LAV-28
KDS
LAV-30
LA
V
-
3
0
LA
V
-
2
4
LA
V
-
2
4
E1.0
ELECTRICAL
POWER PLAN
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
GUID O O AL
RE
Z
REGI
S
TRE D
E
P R OF ESSIONALE
N
G
IN
E
E
R
ELECT R I C A L
A
TATEOF I R NIA
C F OL
N
S
I A A
RISER DIAGRAM
NO SCALE
EXISTING
PANEL KB
SEC 1
400A
MLO
208/120V
EXISTING
PANEL KB
SEC 2
400A
MLO
208/120V
IT ROOM
EXISTING
PANEL
LAV SEC 1
225A
MCB
208/120V
TO EXISTING
PANEL DPLC
300A BREAKER
EXISTING
FEED THRU
LUGS
GENERAL NOTES:
1.PROVIDE PULL STRINGS IN ALL EMPTY CONDUITS.
2.ALL JUNCTION BOXES, CONDUITS, AND WIRES SHALL
BE SIZED PER NEC.
3.PROVIDE A CONSTANT HOT FORM PANEL BOARD
DIRECTLY TO ALL EMERGENCY BATTERY
PACKS/BALLASTS IN ALL EMERGENCY LIGHTING
FIXTURES.
4.REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION & MOUNTING HEIGHTS OF ALL LIGHTING
FIXTURES SHOWN ON THIS DRAWING.
5.REFER TO DETAIL SHEET FOR SYMBOLS,
SPECIFICATIONS AND ABBREVIATIONS.
6.ALL DEVICES AND EQUIPMENT OUTSIDE THE SCOPE OF
WORK ARE EXISTING TO REMAIN U.O.N.
7.ELECTRICAL CONTRACTOR SHALL NOTIFY THE
ENGINEER OF ANY PROBLEMS PERTAINING TO CIRCUIT
AVAILABILITY, EXISTING CONDITIONS OR LOAD
CAPACITY PRIOR TO COMMENCEMENT OF WORK.
RISER DIAGRAM NOTES:
1.ALL EQUIPMENT AND OTHER ELECTRICAL
MATERIALS/WORK SHOWN AS EXISTING IN THE RISER
DIAGRAM SHALL BE VERIFIED BY CONTRACTOR TO BE
EXISTING. WHERE THE METER, DISCONNECT, FEEDER
OR OTHER COMPONENTS OF THE TENANT FEEDER DO
NOT EXIST AS SHOWN. THE CONTRACTOR SHALL
PROVIDE.
2.G.C SHALL COORDINATE WITH EXISTING PLANS.
ELECTRICAL ROOM
TO EXISTING
XFMR 45KVA
TLAV
EXISTING
PANEL
LAV SEC 2
225A
MLO
208/120V
EXISTING
FEED THRU
LUGS
E2.0
ELECTRICAL
RISER AND
PANELS
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
GUID O O AL
RE
Z
REGI
S
TRE D
E
P R OF ESSIONALE
N
G
IN
E
E
R
ELECT R I C A L
A
TATEOF I R NIA
C F OL
N
S
I A A
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
No. M34196
JU S T I R.HARD
Y
REGI
S
TRE D
E
P R O F ESSIONAL
E
N
G
IN
E
E
R
EXP.
MECH A N I C A L
A
TATE OF I R N I
A
C F OL
N
S
9/30/2026
MP.1
PLUMBING
SPEC.
I.GENERAL PROVISIONS
A.OVERVIEW
1.ALL WORK DONE UNDER THIS CONTRACT SHALL COMPLY WITH ALL STATE AND LOCAL CODES HAVING
JURISDICTION AND WITH THE REQUIREMENTS OF THE UTILITY COMPANIES WHOSE SERVICES MAY BE USED. ALL
MODIFICATIONS REQUIRED BY THESE CODES SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL
CHARGES. WHERE CODE REQUIREMENTS ARE LESS THAN THOSE SHOWN ON THE PLANS OR IN THE
SPECIFICATIONS, THE PLANS AND SPECIFICATIONS SHALL BE FOLLOWED. WHERE APPLICABLE, NFPA
REQUIREMENTS SHALL BE MET.
2.IN CASE OF ANY CONFLICTS BETWEEN CONTRACT DOCUMENTS, THE STRICTER/MORE STRINGENT SHALL
GOVERN.
3.THE CONTRACTOR SHALL OBTAIN ALL PERMITS, INSPECTIONS, AND APPROVALS AS REQUIRED BY ALL
AUTHORITIES HAVING JURISDICTION AND DELIVER CERTIFICATES OF APPROVAL TO THE ENGINEER. ALL FEES
AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND APPROVALS
MUST BE ASSUMED AND PAID BY THE CONTRACTOR.
4.THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE PROVISIONS OF O.S.H.A.
5.THE WORKMANSHIP AND MATERIALS COVERED BY THESE SPECIFICATIONS SHALL CONFORM TO ALL
ORDINANCES AND REGULATIONS OF THE CITY, COUNTY AND/OR OTHER AUTHORITIES HAVING JURISDICTION.
6.CONTRACTOR SHALL VISIT THE SITE AND EXAMINE EXISTING CONDITIONS BEFORE SUBMITTING BID. NO
ALLOWANCE WILL BE MADE FOR LACK OF KNOWLEDGE OF EXISTING CONDITIONS WHEN SUCH CONDITIONS CAN
BE DETERMINED BY OBSERVATION.
7.PRIOR TO SUBMITTING DATA FOR OR PURCHASING EQUIPMENT REQUIRING ELECTRICAL SERVICE, THE
CONTRACTOR SHALL VERIFY THAT ELECTRICAL CHARACTERISTICS OF EQUIPMENT SUBMITTALS COMPLY WITH
ELECTRICAL SERVICE PROVIDED FOR THE SPECIFIED ITEMS OF EQUIPMENT.
8.UPON RECEIPT OF THE CONTRACTOR OF REVIEWED SUBMITTALS FOR EQUIPMENT PROVIDED UNDER THIS
DIVISION, THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL SERVICE REQUIREMENTS, I.E., MOTOR
HORSEPOWER AND FULL LOAD AMPS, ELECTRICAL SERVICE CHARACTERISTICS (VOLTAGE AND PHASE), AND
NUMBER OF SERVICES FOR EACH ITEM OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS WITH THE
ELECTRICAL DRAWINGS AND SPECIFICATIONS.
9.ITEMS ON OR PROJECTING THROUGH THE CEILING SHALL BE COORDINATED WITH OTHER TRADES.
E.EXECUTION
2.THE PLANS DO NOT GIVE EXACT ELEVATIONS OR LOCATIONS OF LINES, NOR DO THEY SHOW ALL THE OFFSETS,
CONTROL LINES, OR OTHER INSTALLATION DETAILS. THE CONTRACTOR SHALL CAREFULLY LAY OUT HIS WORK
AT THE SITE TO CONFORM TO THE STRUCTURAL CONDITIONS, TO PROVIDE PROPER GRADING OF LINES, TO
AVOID ALL OBSTRUCTIONS, TO CONFORM TO DETAILS OF INSTALLATION SUPPLIED BY THE MANUFACTURERS OF
THE EQUIPMENT TO BE INSTALLED, AND TO THEREBY PROVIDE AN INTEGRATED, COORDINATED AND
SATISFACTORY OPERATING INSTALLATION. DO NOT SCALE DRAWINGS.
3.IF THE CONTRACTOR PROPOSES TO INSTALL EQUIPMENT, INCLUDING PIPING AND DUCTWORK, REQUIRING
SPACE CONDITIONS OTHER THAN THOSE SHOWN, OR TO REARRANGE THE EQUIPMENT, HE SHALL ASSUME FULL
RESPONSIBILITY FOR THE REARRANGEMENT OF THE SPACE AND CONNECT ARRANGEMENT AT NO ADDITIONAL
COST TO THE OWNER, AND SHALL HAVE THE ENGINEER REVIEW THE CHANGE BEFORE PROCEEDING WITH THE
WORK. THE REQUEST FOR SUCH CHANGES SHALL BE ACCOMPLISHED BY SHOP DRAWINGS OF THE SPACE IN
QUESTION.
4.TEMPORARY FILTERS SHALL BE PROVIDED FOR FANS THAT ARE USED DURING CONSTRUCTION. AT THE TIME OF
STARTING THE BALANCING OF THE AIR DISTRIBUTION SYSTEM, NEW FILTERS SHALL BE INSTALLED.
5.THE CONTRACTOR IS RESPONSIBLE FOR THE PROPER LOCATION AND SIZE OF ALL SLOT, HOLES OR OPENINGS
IN THE BUILDING STRUCTURE PERTAINING TO HIS WORK, AND FOR THE CORRECT LOCATION OF SLEEVES,
INSERTS, CORES, ETC.
6.THE CONTRACTOR SHALL SO COORDINATE THE WORK OF THE SEVERAL VARIOUS TRADES THAT IT MAY BE
INSTALLED IN THE MOST DIRECT AND WORKMANLIKE MANNER WITHOUT HINDERING OR HANDICAPPING THE
OTHER TRADES. PIPING INTERFERENCES SHALL BE HANDLED BY GIVING PRECEDENCE TO PIPE LINES WHICH
REQUIRE A STATED GRADE FOR PROPER OPERATION. FOR EXAMPLE SEWER LINES AND CONDENSATE PIPING
SHALL TAKE PRECEDENCE OVER WATER LINES IN DETERMINATION OF ELEVATIONS. WHERE THERE IS
INTERFERENCE BETWEEN SEWER LINES AND CONDENSATE LINES, THE SEWER LINES SHALL HAVE PRECEDENCE
AND PROVISIONS SHALL BE MADE IN THE CONDENSATE LINES FOR LOOPING THEM AROUND THE SEWER LINES.
IN ALL CASES, LINES REQUIRING A STATED GRADE FOR THEIR PROPER OPERATION SHALL HAVE PRECEDENCE
OVER ELECTRICAL CONDUIT AND DUCTWORK.
7.ALL PIPING AND DUCTWORK IN FINISHED AREAS- EXCEPT WHERE NOTED TO THE CONTRARY- SHALL BE
INSTALLED IN A CHASE, FURRED SPACE, OR ABOVE CEILINGS, ETC. IN ALL CASES, PIPES AND DUCTS SHALL BE
INSTALLED AS HIGH AS POSSIBLE. RUNS OF PIPING SHALL BE GROUPED WHENEVER IT IS FEASIBLE TO DO SO.
8.PIPING SHALL BE INSTALLED TO PASS INSPECTIONS BY LOCAL PLUMBING INSPECTION DEPARTMENT, STATE AND
FEDERAL AUTHORITIES AND INSURANCE COMPANY HAVING JURISDICTION. ANY CHANGES OR ADDITIONS WHICH
MAY BE NECESSARY TO OBTAIN SUCH INSPECTIONS AND APPROVAL SHALL BE MADE BY THE CONTRACTOR AS
PART OF THIS CONTRACT AND WITHOUT ADDITIONAL COST TO THE OWNER.
9.PIPING, DUCTWORK OR EQUIPMENT SHALL NOT BE INSTALLED IN ELECTRICAL EQUIPMENT ROOMS OR ELEVATOR
MACHINE ROOMS EXCEPT AS SERVING ONLY THOSE ROOMS. OUTSIDE OF ELECTRICAL EQUIPMENT ROOMS, DO
NOT RUN PIPING OR DUCTWORK OR LOCATE EQUIPMENT, WITH RESPECT TO SWITCHBOARDS, PANEL BOARDS,
POWER PANELS, MOTOR CONTROL CENTERS, DRY TYPE TRANSFORMERS OR ROOF TOP AIR CONDITIONING UNIT
ELECTRICAL PANELS.
10.PROVIDE ACCESS TO EQUIPMENT AND APPARATUS REQUIRING OPERATION, SERVICE OR MAINTENANCE WITHIN
THE LIFE OF THE SYSTEM. INCLUDING, BUT NOT LIMITED TO, MOTORS, VALVES, FILTERS, DAMPERS, SHOCK
ABSORBERS, ETC. EQUIPMENT LOCATED ABOVE LAY-IN TYPE CEILINGS IS CONSIDERED ACCESSIBLE.
11.DAMAGED EQUIPMENT SHALL BE REPAIRED OR REPLACED AT THE OPTION OF THE ARCHITECT
H.ACCESS DOORS
7.FURNISH AND INSTALL ACCESS DOORS AT EACH POINT REQUIRED TO PROVIDE ACCESS TO CONCEALED
VALVES, CLEANOUTS AND OTHER DEVICES REQUIRING OPERATION, ADJUSTMENT OR MAINTENANCE. ACCESS
DOORS SHALL BE 16 GAUGE STEEL, PRIME COAT FINISH, WITH MOUNTING STRAPS, CONCEALED HINGES AND
SCREWDRIVER LOCKS, DESIGNED FOR THE DOORS TO OPEN 180 DEGREES.
8.ACCESS DOORS INSTALLED IN FIRE WALLS OR PARTITIONS SHALL BE UL LABELED TO MAINTAIN THE FIRE RATING
OF THE WALL OR PARTITION.
II.INSULATION
A.GENERAL PIPE INSULATION
1.FIBERGLASS SHALL BE ACCEPTABLE FOR INDOOR HOT & COLD DOMESTIC; HYDRONIC PIPING; AND INSULATED
DRAINAGE PIPING. PROVIDE PREFABRICATED FITTINGS FOR ELBOWS AND TEE'S. PROVIDE PREFAB PVC
FITTINGS OR WHITE ALL SERVICE (INTEGRAL TO PREFAB PIPING ELBOW) PIPING ELBOW JACKETING. PROVIDE
PIPE LABELING FOR ALL INSULATED, JACKETED INDOOR PIPING. PVC JACKETING SHALL NOT BE PERMITTED IN
RETURN PLENUM AREAS. ALL JACKEING SEAMS SHALL BE SEALED AIR-TIGHT FOR CONTINUOUS VAPOR BARRIER.
2.FITTINGS AND VALVES SHALL BE INSULATED WITH PRE-FORMED FITTINGS, FABRICATED SECTIONS OF PIPE
INSULATION, TANK INSULATION, BLANKET INSULATION, OR INSULATING CEMENT. THICKNESS SHALL BE EQUAL
TO ADJACENT PIPE INSULATION. FINISH SHALL BE WITH PRE-FORMED PVC FITTING COVERS OR AS OTHERWISE
SPECIFIED ON CONTRACT DRAWINGS.
3.FLANGES, COUPLINGS AND VALVE BONNETS SHALL BE COVERED WITH AN OVERSIZED PIPE INSULATION
SECTION SIZED TO PROVIDE THE SAME INSULATION THICKNESS AS ON THE MAIN PIPE SECTION. AN OVERSIZED
INSULATION SECTION SHALL BE USED TO FORM A COLLAR BETWEEN THE TWO INSULATION SECTIONS WITH
LOW-DENSITY BLANKET INSULATION BEING USED TO FILL GAPS. JACKETING SHALL MATCH THAT USED ON
STRAIGHT PIPE SECTIONS. ROUGH CUT ENDS SHALL BE COATED WITH SUITABLE WEATHER OR VAPOR
RESISTANT MASTIC AS DICTATED BY THE SYSTEM LOCATION AND SERVICE. ON HOT SYSTEMS WHERE FITTINGS
ARE TO BE LEFT EXPOSED, INSULATION ENDS SHOULD BE BEVELED AWAY FROM BOLTS FOR EASY ACCESS.
B.INSULATION THICKNESS
1.DOMESTIC COLD WATER INSULATION SHALL BE 1” MINIMUM OR AS REQUIRED BY LOCAL ENERGY CODES.
2.FOR MEDIA BELOW 60 DEGREES INSULATION SHALL BE 1” UP TO 1-¼” PIPE SIZE; 1.5” THICK UP TO 3” PIPE SIZE;
AND 2” THICK BEYOND 3” PIPE SIZE.
3.CHILLED WATER PIPING INSULATION SHALL BE 1” UP TO 1-1/4” PIPE SIZE, 1.5” UP TO 3”.
4.PROVIDE MINIMUM PIPE INSULATION RATING PER INSULATION TABLE 403.2.10 ON THIS SHEET.
C.FIBERGLASS PIPE INSULATION
1.ONE PIECE FIBROUS GLASS PIPE INSULATION WITH FACTORY APPLIED ALUMINUM FOIL AND WHITE KRAFT PAPER
FLAME RETARDANT VAPOR BARRIER JACKET.
2.PROVIDE SELF_SEALING LONGITUDINAL JACKET LAPS AND BUTT STRIPS. AVERAGE THERMAL CONDUCTIVITY:
0.23 BTU/IN. PER SQUARE FOOT PER DEGREES F PER HOUR AT 75 DEGREES F MEAN TEMPERATURE.
3.PROVIDE INSULATION CEMENT, FIBERGLASS REINFORCEMENT FABRIC, VAPOR BARRIER COATING, FOR
CONTINUOUS, AIR-TIGHT INSULATION WITH VAPOR BARRIER.
E.FOAMGLASS PIPE INSULATION
1.FOAM GLASS TYPE PIPE INSULATION SHALL HAVE MAXIMUM K_FACTOR OF 0.38 AT 50 DEGREES F MEAN
TEMPERATURE. MINIMUM DENSITY SHALL BE 8 LB/CU. FT., 1 1/2" THICK MINIMUM. PROVIDE MASTIC, FIBERGLASS
REINFORCED STRAPPING TAPE TO ASSURE AIR-TIGHT MOISTURE-PROOF INSULATION. PROVIDE WITH ALUMINUM
JACKETING THAT SHALL BE 0.016" THICK WITH FITTING COVERS 0.024" THICK. PROVIDE WITH 5 WATT/FT HEAT
TRACING BELOW INSULATION FOR OUTDOOR, ABOVE-GROUND INSTALLATION.
2.PROVIDE FOAM GLASS INSERTS AT PIPE HANGERS, CLAMPS, OR OTHER SUPPORTS IN FIBERGLASS OR
ELASTOMERIC PIPE INSULATION INSTALLATIONS INSERTS SHALL BE SAME THICKNESS AS ADJOINING PIPE
INSULATION. VAPOR SEAL SHALL BE AS HEREINBEFORE SPECIFIED. ALUMINUM JACKETING SHALL NOT BE
REQUIRED FOR INDOOR INSERTS (PVC OR WHITE ALL-SERVICE FOIL/KRAFTJACKETING MEDIA SHALL BE USED).
E.ELASTOMERIC (CLOSED CELL FOAM) PIPE INSULATION
1.ELASTOMERIC SHALL BE PROVIDED FOR ALL REFRIGERANT PIPING AND OUTDOOR INSULATED PIPING AND MAY
BE USED FOR INDOOR DOMESTIC OR CONDENSATE PIPING. PIPING WILL REQUIRE JACKETING- ALUMINUM FOR
OUTDOOR PIPING OR FOIL/WHITE KRAFT MEDIA OR PVC FOR INDOOR PIPING. PROVIDE WITH FULL ADHESIVE
ADHERING SEAMS AND JOINTS FOR CONTINUOUS VAPOR BARRIER. ELBOWS SHALL BE FORMED BY CUTTING
SEGMENTS AT 30 DEGREE ANGLES (3 SEGMENTS AT EACH 90 DEGREE BEND) WITH MASTIC AT ALL SEAMS.
PROVIDE PREFORMED JACKETING ELBOWS AT ALL PIPING ELBOW
VI.PIPING
A.USE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED TOGETHER.
B.DOMESTIC WATER & PUMPED CONDENSATE
1.UNDERGROUND WATER SERVICE PIPING 3" IN SIZE AND LARGER SHALL BE CLASS 50 DUCTILE IRON PIPE, AWWA
C151, WITH HUB AND SPIGOT, PUSH_ON JOINTS, AND CLASS 50 OR GREATER MECHANICAL JOINT DUCTILE IRON
FITTINGS ALL CEMENT LINED PER AWWA C104. MECHANICAL JOINTS FOR DUCTILE IRON PIPE SHALL BE MADE
WITH A FOLLOWER GLAND, GASKET, BOLTS AND NUTS. PUSH-ON JOINTS FOR DUCTILE PIPE SHALL BE MADE
WITH A ONE PIECE LUBRICATED COMPRESSION RUBBER GASKET AS PER AWWA C111.
2.UNDERGROUND STEEL PIPE AND FITTINGS INCLUDING THE PORTION THROUGH THE FLOOR SHALL BE
PROTECTED AGAINST CORROSION BY APPLICATION OF PROTECTIVE COATINGS. PRIOR TO COATING, PIPE AND
FITTINGS SHALL BE CLEANED OF ALL RUST, SCALE, DIRT AND OIL. PIPES AND FITTINGS SHALL BE GIVEN TWO
COATS OF A COAL-TAR BASE BITUMINOUS PROTECTIVE COATING, EACH HAVING A DRY FILM THICKNESS OF 7-9
MILS. THE COMBINED THICKNESS OF BOTH COATS COMBINED SHALL BE 15-18 MILS.
3.UNDERGROUND WATER SERVICE PIPING 2 1/2" IN SIZE AND SMALLER (TO A POINT 1'-0" ABOVE THE FINISHED
FLOOR) SHALL BE. TYPE "K" HARD DRAWN COPPER TUBING, ASTM B88, WITH BRAZED JOINTS AND WROUGHT
COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. . BRAZED JOINTS SHALL BE MADE
USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX.
4.ABOVE-GROUND WATER PIPING - 4" AND SMALLER SHALL BE. TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88,
WITH SOLDERED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET
FITTINGS. SOLDER JOINTS SHALL BE MADE USING A 95-5 TIN-ANTIMONY SOLDER (NO-LEAD SOLDER) WITH A
COMPATIBLE FLUX.
5.UNDERGROUND WATER PIPING TO TRAP PRIMERS OR HVAC CONDENSATE PUMP DISCHARGE SHALL BE. TYPE “L”
SOFT DRAWN COPPER TUBING, ASTM B88, WITHOUT FITTINGS.
6.FLANGED JOINT SHALL BE MADE WITH RING TYPE NON-METALLIC GASKETS, BOLTS AND NUTS.
7.THREADED JOINTS AT EQUIPMENT CONNECTIONS SHALL BE MADE UP WITH TEFLON TAPE. AFTER CUTTING BUT
PRIOR TO THREADING, PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED.
8.GROOVED MECHANICAL JOINTS: GROOVED JOINTS FOR COPPER AND GALVANIZED STEEL PIPES SHALL BE
INSTALLED USING BOLTED MECHANICAL COUPLING, PRESSURE-RESPONSIVE GASKET ALONG WITH GROOVED
AND FITTINGS. LAYOUT BASIS SHALL BE ANVIL GRUV-LOCK,
9.DIELECTRIC ADAPTERS SHALL BE PROVIDED BETWEEN COPPER AND IRON PIPE CONNECTIONS AND BETWEEN
FERROUS AND NONFERROUS PIPING OR EQUIPMENT.
10.UNDERGROUND WATER PIPING SHALL HAVE A MINIMUM COVER OF 3'- 0" TO THE TOP OF THE PIPE.
11.INSTALL WATER HAMMER ARRESTORS ABOVE CEILING ON THE HOT AND COLD WATER BRANCH LINES SERVING
A BATTERY OF FIXTURES; ON THE COLD WATER BRANCH LINES SERVING INDIVIDUAL FLUSH VALVE WATER
CLOSETS AND URINALS; AND ELSEWHERE AS INDICATED ON THE DRAWINGS. PROVIDE ACCESS PANEL FOR WHA
LOCATED ABOVE HARD CEILINGS.
12.VACUUM BREAKERS SHALL BE PROVIDED ON ALL HOSE OUTLETS, HOSE BIBS AND HYDRANTS UNLESS THE
DRAWINGS INDICATE THAT A BACKFLOW PREVENTER IS TO BE PROVIDED ON THE PIPING SERVING THE OUTLET.
13.INSTALL 1/2" CW LINE FROM NEAREST CW MAIN OR BRANCH LINE TO ALL FLOOR DRAINS WITH TRAP PRIMER FOR
TRAP PRIMING. UNDERGROUND PIPING FROM TRAP PRIMER TO FLOOR DRAINS SHALL BE INSTALLED WITHOUT
FITTINGS. TRAP PRIMERS SHALL BE PROVIDED FOR ALL FLOOR DRAINS AND HUB DRAINS.
14.CONNECT HOT AND COLD WATER PIPING SYSTEM TO EQUIPMENT AS INDICATED, AND COMPLY WITH EQUIPMENT
MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE SHUT-OFF BALL VALVE AND UNION FOR EACH
CONNECTION, PROVIDE DRAIN VALVE ON DRAIN CONNECTIONS. PROVIDE SINGLE SHUTOFF BALL VALVE FOR
HEADERS SERVING HOT OR COLD WATER TO MULTIPLE FIXTURES WITHIN A SINGLE WALL OR CHASE. PROVIDE
ACCESS PANEL FOR VALVES INSTALLED ABOVE HARD CEILINGS.
15.ALL DOMESTIC WATER SERVICE AND SUPPLY PIPING INSTALLED UNDER THIS DIVISION SHALL BE DISINFECTED
WITH CHLORINE BEFORE IT IS PLACED INTO OPERATION. THE CHLORINATING MATERIAL SHALL BE LIQUID
CHLORINE CONFORMING TO FED. SPEC. BB-C-120 AND SHALL BE INTRODUCED TO THE SYSTEM BY EXPERIENCED
OPERATORS ONLY. THE CHLORINE SOLUTION APPLIED TO THE PIPING SECTIONS OR SYSTEM SHALL CONTAIN
AT LEAST FIFTY PARTS PER MILLION OF AVAILABLE CHLORINE AND SHALL REMAIN IN THE SECTIONS OR SYSTEM
FOR A PERIOD OF NOT LESS THAN SIXTEEN (16) HOURS. DURING THE DISINFECTION PERIOD ALL VALVES SHALL
BE OPENED AND CLOSED AT LEAST FOUR TIMES. AT THE END OF THE RETENTION PERIOD, NO LESS THAN 50
PPM OF CHLORINE SHALL BE PRESENT IN THE EXTREME END OF THIS SYSTEM. AFTER THE DISINFECTION
PERIOD THE CHLORINATED WATER SHALL BE FLUSHED FROM THE SYSTEM WITH CLEAR WATER UNTIL THE
RESIDUAL CHLORINE CONTENT IS NOT GREATER THAN TWO-TENTHS - (0.2) - PARTS PER MILLION. THE
CONSTRUCTION MANAGER SHALL SUBMIT TO THE ARCHITECT WRITTEN CERTIFICATION THAT THE SYSTEM WAS
DISINFECTED. CERTIFICATION SHALL INCLUDE NAME OF PROJECT, NAME OF OWNER, NAME OF OPERATORS,
DATE OF DISINFECTION, TIMES OF DISINFECTION PERIOD, MAXIMUM CHLORINE LEVEL AND RESIDUAL CHLORINE
LEVEL.
C.NATURAL GAS
1.ABOVE-GROUND MAXIMUM 2-1/2” GAS PIPING SHALL BE BLACK STEEL PIPE, .SCHEDULE 40, ASTM A53 WITH
STANDARD WEIGHT WROUGHT STEEL SOCKET-WELD FITTINGS PER ASTM A234 OR THREADED CONNECTIONS.
PIPE SIZES 3" AND UP OR WITH PRESSURE ABOVE 5PSI SHALL ONLY BE PERMITTED WITH SOCKET-WELDED
JOINTS (NO THREADED CONNECTIONS).
2.STEEL GAS PIPING TO BE INSTALLED UNDERGROUND SHALL BE FURNISHED WITH A FACTORY APPLIED COATING
WHICH SHALL CONSIST OF A RESILIENT, EXTRUDED, POLYETHYLENE SLEEVE WHICH IS SEALED TO THE PIPE.
THE PLASTIC COATING SHALL BE NOT LESS THAN 25 MILS THICK AND SEALED TO THE PIPE WITH A HOT APPLIED
ADHESIVE WHICH RETAINS ITS ELASTICITY IN HOT AND COLD ENVIRONMENTS.
3.FIELD APPLIED WRAPPING TAPE FOR FITTINGS AND JOINTS SHALL BE COAL TAR WITH HEAVY VINYL OR
POLYESTER FILM BACKING MEETING FEDERAL SPECIFICATION HH-T-30A, TAPECOAT CT OR TAPECOAT 20 OR JT
JOINT COATINGS, INC., WITH PRIMER, APPLICATION PROCEDURES AND HEATING IN ACCORDANCE WITH THE
TAPE MANUFACTURER'S RECOMMENDATIONS.
4.ARRANGE WITH THE UTILITY COMPANY TO PROVIDE GAS SERVICE TO INDICATED LOCATION WITH SHUTOFF AT
TERMINATION. MAKE ALL ARRANGEMENTS WITH UTILITY AS TO THE EXTENT OF ITS WORK, AND PAY ALL COSTS,
FEES AND SECURE PERMITS INVOLVED TO OBTAIN SERVICE FOR THE BUILDING.
5.PROVIDE SHUTOFF IN GAS SERVICE PIPE AT ENTRY IN BUILDING, EXT/END PIPE TO GAS METER LOCATION
INDICATED; PROVIDE PARTS AND ACCESSORIES REQUIRED BY UTILITY TO CONNECT TO METER.
6.PROVIDE VALVE AND UNION SHALL BE PROVIDED AT EACH CONNECTION TO A PIECE OF EQUIPMENT.
EQUIPMENT PROVIDED WITH A FLANGED INLET SHALL HAVE A FLANGED CONNECTION.
7.DRIP LEGS, 6-INCHES LONG, SHALL BE PROVIDED IN GAS PIPING AT ENDS OF HORIZONTAL RUNS, AT THE BASE
OF RISERS AND AT CONNECTIONS TO EQUIPMENT. DRIP LEG CAP SHALL BE REMOVABLE WITH MINIMUM 4”
BETWEEN CAP AND WALL OR ROOF.
8.GAS PIPING WITHIN THE BUILDING SHALL BE RUN ABOVE FLOOR SLAB.
9.PRESSURE REGULATORS ARE TO BE PROVIDED ON ALL EQUIPMENT IF NOT PROVIDED AS PART OF THE
EQUIPMENT. COORDINATE INLET/OUTLET PRESSURES WITH ACTUAL DELIVERED PRESSURE AND EQUIPMENT
INLET PRESSURES. CONTRACTOR SHALL ARRANGE FOR ADJUSTMENT OF GAS PRESSURE TO PREVENT
EXCESSIVE OR INSUFFICIENT GAS PRESSURE TO ALL EQUIPMENT PIECES.
10.PROVIDE FLEX HOSE CONNECTION TO ALL INDOOR APPLIANCES NOT SUPPLIED WITH THE EQUIPMENT PIECE BY
THE OWNER OR EQUIPMENT PROVIDER.
11.THREADED JOINTS SHALL BE MADE WITH A MIXTURE OF GRAPHITE AND OIL APPLIED TO MALE THREADS ONLY.
AFTER CUTTING AND PRIOR TO THREADING, PIPE SHALL BE REAMED AND SHALL HAVE BURRS REMOVED.
12.WELDED JOINTS SHALL BE FUSION WELDED IN ACCORDANCE WITH ANSI B31, SECTION 6.
13.FLANGED JOINTS SHALL BE FACED TRUE, PROVIDED WITH GASKET AND MADE SQUARE AND TIGHT.
14.BRAZED JOINTS SHALL BE MADE UP USING BCUP-5 BRAZING ALLOY WITH A COMPATIBLE FLUX.
15.ALL STEEL FITTINGS AND JOINTS IN UNDERGROUND PIPING SHALL BE FIELD-COATED USING A PRIMER AND
FLEXIBLE POLYETHYLENE TAPE AND THE SAME MANUFACTURER AS THE PIPE COATING. DAMAGED COATING
SHALL BE REPAIRED WITH PRIMER AND TAPE AS SPECIFIED FOR FITTINGS AND JOINTS.
D.SANITARY WASTE &VENT, STORM, GREASE WASTE
1.UNDERGROUND SANITARY, WASTE AND VENT PIPING, AND STORM DRAINAGE PIPING, AND INDOOR PIPING ABOVE 8”
IN SIZE SHALL BE SERVICE WEIGHT (COATED) CAST IRON SOIL PIPE AND FITTINGS, ASTM A74, WITH GASKET HUB AND
SPIGOT JOINTS, ASTM C564. GASKET JOINTS FOR CAST IRON PIPE SHALL BE MADE WITH LUBRICATED NEOPRENE
COMPRESSION GASKETS. PVC SHALL BE PERMITTED IF ALLOWED BY LOCAL CODE. UNDERGROUND PVC PIPING SHALL BE
SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM D-2665.
2.ABOVE-GROUND SANITARY, WASTE AND VENT AND STORM DRAINAGE PIPING 8" AND SMALLER SHALL BE SERVICE
WEIGHT CAST IRON SOIL PIPE AND FITTINGS, ASTM A888 AND CISPI 301, WITH STANDARD NO-HUB COUPLINGS. PVC
SHALL BE PERMITTED OUTSIDE OF RETURN AIR PLENUMS WITH OWNER APPROVAL. NEOPRENE RUBBER GASKET AND
MINIMUM 24 GAUGE TYPE 304 STAINLESS STEEL SHIELD AND FOUR STAINLESS STEEL BANDS FOR SIZES 1 1/2" THROUGH
4", SIX BANDS MINIMUM FOR SIZED 5" AND LARGER. 6” PIPE AND UP: NEOPRENE ELASTOMERIC GASKET AND SERIES
300 STAINLESS STEEL SHIELD AND MULTIPLE DRAW BANDS AND SCREW CLAMPS CONFORMING TO ASTM C-564 AND
CISPI STANDARD 310-90. ABOVE-GROUND SANITARY PIPING, LOCATED OUTSIDE OF RETURN AIR PLENUMS MAY ALSO BE
SCHEDULE 40 PVC WITH SOLVENT WELD JOINTS MEETING ASTM D-1785 AND ASTM D-2665 PER OWNER APPROVAL.
3.ALL WASTE PIPING 1" IN SIZE AND SMALLER SHALL BE TYPE "L" HARD DRAWN COPPER TUBING, ASTM B88, WITH
SOLDERED JOINTS AND WROUGHT COPPER, ANSI B16.22, OR CAST BRONZE, ANSI B16.18, SOCKET FITTINGS. SOLDERED
JOINTS FOR TYPE 'L' COPPER TUBING AND CAST DMV BRONZE PIPE SHALL BE MADE WITH 95-5 TIN-ANTIMONY (NO
LEAD) SOLDER AND COMPATIBLE FLUX.
E.PIPING HANGERS
1.PROVIDE CLEVIS SUPPORTS WITH BEAM CLAMP, CONCRETE ANCHORS (CONCRETE STRUCTURE), SCREWED
BRACKET (WOOD STRUCTURE). PROVIDE HANGER OUTSIDE OF INSULATION WITH RIGID FOAM GLASS
INSULATION SECTION AT HANGERS. PROVIDE 16 GAUGE PIPING SADDLE AT EACH HANGER. NO WELDING OR
CUTTING OF STEEL STRUCTURAL MEMBERS SHALL BE PERMITTED. LAYOUT BASIS SHALL BE ANVIL 260.
2.PROVIDE SEISMIC HANGERS PER DRAWING REQUIREMENTS.
3.HANGER INSTALLATION FOR HOT WATER PIPING SHALL NOT PREVENT MOVEMENT FOR PIPING EXPANSION.
4.SPACING AS FOLLOWS:
STEEL PIPE: 1/2” TO 1-1/4” - 7' ; 1-1/2” TO 2-1/2” - 9' ; 3”&4” - 12' ; 6“&8” - 17' ; 10” AND UP- 22'
COPPER PIPE: 1/2” TO 1” - 5' ; 1-1/4” TO 2” - 7' ; 2-1/2” AND UP - 9'
CAST IRON: 10' WITH SUPPORT AT EACH JOINT, TAKEOFF, AND FITTING.
VII.VALVES/PUMPS
A.GENERAL
1.VALVES SHALL HAVE THE NAME OR TRADEMARK OF THE MANUFACTURER AND THE WORKING PRESSURE
STAMPED OR CAST ON THE VALVE BODY.
2.ALL VALVES IN EACH SYSTEM, EXCEPT FOR SPECIAL TYPES SHALL BE THE PRODUCT OF A SINGLE
MANUFACTURER.
3.ALL VALVES REQUIRING PACKING SHALL BE DESIGNED AND CONSTRUCTED SUCH THAT THEY CAN BE REPACKED
UNDER PRESSURE.
4.VALVE HAND WHEELS/ ACTUATOR SHALL BE MALLEABLE IRON EXCEPT WHERE SPECIFIED OTHERWISE.
5.ALL VALVES INSTALLED IN HORIZONTAL LINES SHALL BE INSTALLED WITH THE STEMS HORIZONTAL OR ABOVE.
VALVE ACTUATOR SHALL BE ORIENTED, WHEN INSTALLED, TO PROVIDE MAXIMUM ACCESSIBILITY FOR
OPERATION.
6.PROVIDE ACCESS PANELS FOR VALVES LOCATED IN WALLS OR ABOVE HARD CEILINGS.
B.VALVES FOR HYDRONIC / DOMESTIC WATER SYSTEM
1.BALL VALVES (FOR PIPING 3" AND SMALLER) SHALL HAVE BRONZE BODY, STAINLESS STEEL BALL, LEVER
HANDLE, FOR SYSTEMS UP TO 125 PSIG. GATE VALVES SHALL NOT BE PERMITTED FOR PIPES 3” AND SMALLER.
VALVE LAYOUT BASIS SHALL BE WATTS B6000-SS
2.GATE VALVES (FOR DOMESTIC PIPING 4" IN SIZE AND LARGER): VALVE SHALL HAVE IRON BODY, BRONZE TRIM,
NON-RISING STEM, SOLID WEDGE AND FLANGED ENDS FOR 200 POUND W.O.G. LAYOUT BASIS FOR VALVE SHALL
BE NIBCO F-619.
3.BUTTERFLY VALVES (FOR HYDRONIC PIPING 4” AND LARGER): VALVE SHALL HAVE DUCTILE IRON BODY,
EXTENDED NECK, GEOMETRIC DRIVE MOLDED-IN SEAT LINER, EPDM LINER AND ALUMINUM BRONZE DISC -
INSTALL BETWEEN STD. ANSI CLASS 125/150 FLANGES - CONFORMING TO MSS-SP67/MSS-SP25/API-609. LAYOUT
BASIS SHALL BE NIBCO WD 2000.
4.CHECK VALVES (4" IN SIZE AND LARGER): VALVE SHALL BE HORIZONTAL SWING TYPE WITH IRON BODY, BRONZE
TRIM AND FLANGED ENDS FOR 200 POUND W.O.G. VALVE LAYOUT BASIS SHALL BE NIBCO F-918-B.
5.CHECK VALVES (3" IN SIZE AND SMALLER): VALVE SHALL BE HORIZONTAL SWING TYPE WITH BRONZE BODY,
COMPOSITION DISC AND SOLDER ENDS FOR 200 POUND W.O.G. LAYOUT BASIS SHALL BE NIBCO S/T-413.
6.HOSE END DRAIN VALVES: VALVE SHALL BE 3/4" IN SIZE WITH BRONZE BODY, NON-RISING STEM, SOLID WEDGE,
THREADED INLET AND HOSE OUTLET WITH CAP AND CHAIN FOR 200 POUND W.O.G.
7.UNDERGROUND GATE VALVES AND VALVE BOXES: GATE VALVES (4" IN SIZE AND LARGER) SHALL BE AWWA
APPROVED WITH IRON BODY, BRONZE TRIM, NON-RISING STEM, PARALLEL SEAT DOUBLE DISC, SQUARE
OPERATING NUT AND MECHANICAL JOINT ENDS FOR 200 POUND W.W.P. VALVE BOXES SHALL BE PROVIDED
OVER EACH UNDERGROUND GATE VALVE. VALVE BOXES SHALL BE ADJUSTABLE CAST IRON ROADWAY TYPE
WITH BELLED LOWER SECTION AND REMOVABLE LID AT GRADE. LID SHALL BE LABELED "WATER" AND BOXES
NOT IN PAVED AREAS SHALL BE SET IN A 12" X 12" X 6" CONCRETE PAD. VALVE BOXES LAYOUT BASIS SHALL BE
MUELLER H-10360 PROVIDE ONE T-WRENCH FOR EACH SIZE OPERATING NUT.
C.VALVES FOR NATURAL GAS SYSTEM
1.PLUG VALVES (3" IN SIZE AND LARGER): VALVES SHALL BE THE SEMI-STEEL TYPE WITH CAST IRON BODY,
LUBRICATED CAST IRON PLUG, FLANGED ENDS AND WRENCH OPERATED FOR 175 POUND W.O.G. VALVES
LAYOUT BASIS SHALL BE WALWORTH1797F
2.PLUG VALVES (2 1/2" IN SIZE AND SMALLER): VALVES SHALL HAVE BRONZE BODY AND PLUG, THREADED ENDS
AND SQUARE HEAD FOR 175 POUND W.O.G. VALVE LAYOUT BASIS SHALL BE: WALWORTH NO. 1736
3.BALL VALVES (1/2”, 3/4”, AND 1” UP TO 1/2 PSI FOR APPLIANCE CONNECTION): VALVE SHALL BE LEVER HANDLE,
600 PSI CWP RATED - 1/2 PSI FOR INDOOR APPLIANCE CONNECTIONS PER ANSI Z21.15 & CGA 9.1A. LAYOUT BASIS
SHALL BE NIBCO GB1A.
4.LUBRICATED PLUG VALVES SHALL BE LUBRICATED AT THE FACTORY AND SEALANT SHALL BE DESIGNED FOR
NATURAL GAS. PROVIDE SIX (6) STICKS OR TUBES OF SEALANT UTILIZED AND TURN SUCH OVER TO THE OWNER.
PROVIDE ONE (1) VALVE WRENCH FOR EACH SIZE AND TYPE OF VALVE HEAD AND TURN SUCH WRENCHES OVER
TO THE OWNER.
5.PRESSURE REGULATING VALVE: VALVE SHALL HAVE INTERCHANGEABLE ALUMINUM ORIFICE, MOLDED DEEP
CONVOLUTION DIAPHRAGM WITH O-RING SEAL, PLATED STEEL DIAPHRAGM PLATE, STAINLESS STEEL LEVER PIN,
ONE PIECE MOLDED BUNA-N VALVE SEAT, DIE CAST ZINC VALVE STEM, DELRINFI VENT VALVE WITH BUNA-N
SEAT, SPRING LOADED INTERNAL RELIEF VALVE ASSEMBLY, 1" AND 3/4" THREADED VENT WITH STAINLESS STEEL
SCREEN, FIBERGLASS REINFORCED POLETHELYNE SEAL CAP WITH INTEGRAL RELIEF VALVE STOP, AND FIELD
INTERCHANGEABLE ADJUSTMENT SPRING, CSA 6-18 APPROVED. PROVIDE THREE SPRINGS AT RATED OUTLET
PRESSURE PLUS SPRING FOR NEXT HIGHES AND LOWEST PRESSURE RATING FOR BALANCING PURPOSES.
PROVIDE ALL VENTING REQUIRED BY THE MANUFACTURER FOR ALL INDOOR MOUNTED REGULATORS. LAYOUT
BASIS SHALL BE ACTARIS B42N.
6.CONTRACTOR SHALL PROVIDE REGULATORS AT ALL APPLIANCE CONNECTIONS REGARDLESS OF SUPPLY
PRESSURE UNLESS THE REQUIRED EQUIPMENT DELIVERY PRESSURE CAN BE DELIVERED WITHOUT THE USE OF
A REGULATOR.
7.CONTRACTOR TO COORDINATE INLET/OUTLET PRESSURES WITH DRAWINGS AND GAS EQUIPMENT
MANUFACTURERS REQUIREMENTS.
8.INSTALL ALL REGULATORS CLEAR OF ANY EQUIPMENT ACCESS SUCH THAT VALVE SPRINGS AND ORIFICE CAN
BE ACCESSED WITHOUT REMOVING VALVE.
1.THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED
THAT A COMPLETE PLUMBING AND FIRE PROTECTION SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT,
APPURTENANCES AND CONTROLS COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE
DOCUMENTS SHALL BE STRICTLY CONFORMED TO. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE PLUMBING AND FIRE
PROTECTION SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, LOCAL AUTHORITIES AND THESE
CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. CAREFULLY
REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS.
2.COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL TRADES. PIPE ROUTING
SHOWN IS DIAGRAMMATIC. PROVIDE ALL OFFSETS, ETC. TO AVOID INTERFERENCES WITH EQUIPMENT, PIPING, DUCT WORK,
LIGHTS, CONDUITS, AND STRUCTURAL ITEMS, ETC...
3.ALL DRAINAGE PIPING AND POTABLE WATER PIPING SHALL BE CONCEALED INSIDE WALLS AND PIPE CHASES OR ABOVE
CEILINGS AS HIGH AS POSSIBLE.
4.EXPOSED PIPING AT FIXTURES SHALL BE SECURED TO WALLS CONSTRAINED AGAINST ANY FREE-MOVEMENT OF PIPING.
5.CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL DOMESTIC WATER, SANITARY SEWERS, STORM DRAINS, FIRE SUPPLY
AND GAS SERVICES AT APPROXIMATELY 5'-0" FROM BUILDING STRUCTURE UNLESS OTHERWISE NOTED.
6.REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR LOCATION OF ALL PLUMBING FIXTURES. EXACT LOCATION OF ALL
PLUMBING FIXTURES MUST BE VERIFIED IN FIELD PRIOR TO INSTALLATION. FINAL LOCATIONS AND HEIGHTS SHALL BE AS
DIRECTED BY ARCHITECT.
7.PLUMBING CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL EQUIPMENT INDICATED ON DRAWINGS INCLUDING KITCHEN
AND LAUNDRY EQUIPMENT PER MANUFACTURER'S SPECIFIC INSTALLATION INSTRUCTIONS. FINAL CONNECTION SHALL
INCLUDE ANY ADAPTERS, NIPPLES SHUTOFF VALVES, PRESSURE REGULATING VALVES, SHOCK ABSORBERS, BACKFLOW
PREVENTION DEVICES, ETC. CONTRACTOR SHALL COMPLETELY REVIEW EACH EQUIPMENT ITEM'S INSTALLATION
INSTRUCTIONS PRIOR TO COMMENCEMENT OF WORK. ALL ITEMS REQUIRED FOR INSTALLATION ARE INCLUDED IN THE
PLUMBING CONTRACTOR'S SCOPE.
8.DO NOT RUN PLUMBING OR FIRE PROTECTION PIPING THROUGH TRANSFORMER VAULTS, ELECTRICAL CLOSETS, ELECTRICAL
SWITCHGEAR ROOMS, ELEVATOR EQUIPMENT ROOMS, COMPUTER ROOMS OR TELEPHONE ROOMS. DO NOT RUN ANY PIPING
ABOVE ELECTRICAL PANELS OR OTHER ELECTRICAL/CONTROLS COMPONENTS.
9.ALL COMMERCIAL FIXTURES SPECIFIED BY AN EQUIPMENT PROVIDER SHALL OVERRIDE ANY SPECIFIED PLUMBING FIXTURES
ON THIS PLAN. THE PLUMBER SHALL COORDINATE FINAL REQUIRED FIXTURES WITH OWNER/EQUIPMENT SUPPLIER. VERIFY
CONNECTION SIZE AND LOCATION OF ALL ITEMS WITH KITCHEN EQUIPMENT DRAWINGS.
10.PROVIDE AN EXPANSION JOINT ON ALL PIPING SYSTEMS THAT CROSS BUILDING EXPANSION JOINTS.
11.PROVIDE CONNECTION TO EXISTING WATER SERVICE WHERE AVAILABLE. PROVIDE WATER METER, PRV STATION WITH FULL
SIZE BYPASS, AND RPZ VALVE. COORDINATE METER AND BACKFLOW REQUIREMENTS WITH LOCAL AUTHORITY AND UTILTIY
COMPANIES. CONNECT TO EXISTING SANITARY AND KITCHEN WASTE STUB WHERE AVAIALBLE. CONNESTIONS TO EXISTING
UTILTIES SHALL BE COORDINATED IN THE FIELD FOR EXACT LOCATION AND INVERT AVAILABILITY.
12.PROVIDE GAS CONNECTION TO EXISTING METER WHERE POSSIBLE. PROVIDE CONNECTION TO ROOF MOUNTED EQUIPMENT
AND TO KITCHEN EQUIPMENT AS INDICATED ON KITCHEN EQUIPMENT DRAWING. PROVIDE SHUT-OFF VALVES AT ALL POINTS
OF CONNECTION. PROVIDE SOLENOID SHUT-OFF VALVE FOR GAS ITEMS UNDER KITCHEN HOODS. INTERLOCK SOLENOID WITH
HOOD FIRE PROTECTION SYSTEM. GAS PIPING SHALL NOT BE ROUTED BELOW FLOORS. PIPING INDICATED AS BELOW SLAB
SHALL BE PROVIDED IN A PREFABRICATED MODULAR STAINLESS STEEL UTILITY TRENCH.
13.ALL PLUMBING FIXTURES, PIPING, AND MATERIALS SHALL BE LISTED OR LABELED AND INSTALLED AS PER A RECOGNIZED
APPROVAL AGENCY.
14.ALL WORK WITHIN THIS SCOPE OF WORK SHALL COMPLY WITH ALL CITY, STATE AND NATIONAL PLUMBING CODES. ALL
WORK SHALL CONFORM TO BUILDING STANDARDS.
15.PLUMBING CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND WIRE SIZE OF PLUMBING EQUIPMENT REQUIRING
ELECTRICAL CONNECTION WITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASE OF EQUIPMENT
16.ALL PLUMBING UTILTIY AND SERVICE REQUIREMNTS SHALL BE COORDINATED BY THE CONTRACTOR WITH THE LOCAL CODE
AUTHORITIES AND UTILITY COMPANIES. ANY ADDITIONAL REQUIREMENTS FOR UTILTY SERVICES SHALL BE INCLUDED IN
CONTRACTOR SCOPE.
17.COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL DRAWINGS. THE PLUMBER SHALL SET SLEEVES IN FLOORS
AND WALLS AND ATTACHMENTS FOR HANGERS AS CONSTRUCTION PROGRESSES. COORDINATE THE EXACT SIZE AND
LOCATION OF ALL SLEEVES WITH STRUCTURAL ENGINEER. ALL PENETRATIONS MUST BE SEALED AND HELD AS TIGHT TO
COLUMNS OR WALLS AS POSSIBLE.
18.COORDINATE ALL UNDERGROUND PIPING WITH GRADE BEAMS, WALL FOOTINGS, COLUMN FOUNDATIONS AND OTHER
STRUCTURAL CONDITIONS.
19.ALL DRAINAGE PIPING AND VENT PIPING SHALL SLOPE AT 1/8 INCH PER FOOT UNLESS OTHERWISE NOTED.
20.FLOORS WHERE INDICATED ON ARCHITECTURAL AND /OR STRUCTURAL DRAWINGS SHALL SLOPE TO FLOOR DRAINS.
MAXIMUM SLOPE IN ANY DIRECTION SHALL NOT EXCEED ¼ INCH PER FOOT. EXACT LOCATION OF ALL FLOOR DRAINS AND
HUB DRAINS FOR EQUIPMENT MUST BE VERIFIED IN FIELD PRIOR TO INSTALLATION. FINAL LOCATION SHALL BE AS DIRECTED
BY ARCHITECT. FLOOR DRAIN SHALL BE COMPLETELY FLUSH WITH THE LOWEST LEVEL OF THE FLOOR SLOPE AND SHALL NOT
PROTRUDE BEYOND THE FLOOR SO AS TO CAUSE POOLING AROUND THE DRAIN. CUTTING OF ANY FLOOR DRAINAGE FIXTURE
GRATE SHALL NOT BE PERMITTED
21.EXACT LOCATION OF ALL CLEANOUTS MUST BE COORDINATED AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
22.COORDINATE ALL FIXTURE GRATES, ORIENTATIONS, AND REQUIRED GRATE SPACING WITH THE KITCHEN EQUIPMENT
SUPPLIER. VERIFY ALL FLOOR DRAIN AND FLOOR SINK LOCATIONS WITH THE KITCHEN CONSULTANT. HALF-GRATES SHALL BE
PROVIDED FOR HUB DRAIN COLLECTING INDIRECT SINK DISCHARGE. CONTRACTOR SHALL COORDINATE FINAL FLOOR SINK
LOCATIONS WITH SINK SUPPORT LEGS TO AVOID SUPPORTS SITTING ON GRATES.
23.SANITARY VENTS MUST TERMINATE A MINIMUM OF 10 FT. FROM OR 2 FT. ABOVE AIR INTAKES, WINDOWS OR VENT SHAFTS.
24.INDIRECT WASTE RECEPTORS MUST BE LOCATED WHERE READILY ACCESSIBLE FOR INSPECTION AND CLEANING.
25.ALL INDIRECT WASTE PIPING SHALL DISCHARGE THROUGH A CODE REQUIRED AIR GAP OR AIR BREAK INTO A WASTE
RECEPTOR. ALL INDIRECT WASTE PIPING THAT EXCEEDS 2' IN DEVELOPED LENGTH MEASURED HORIZONTALLY OR 4' IN TOTAL
DEVELOPED LENGTH SHALL BE TRAPPED.
26.ALL HOSE BIBBS AND WASHDOWN FAUCETS ARE REQUIRED TO HAVE PROPER BACKFLOW PREVENTERS WHERE HOSES ARE
ATTACHED AND LEFT UNATTENDED. CHEMICAL FEED SYSTEMS AT COMMERCIAL KITCHENS SHALL HAVE DEDICATED
BACKFLOW PREVENTERS SEPARATE FROM WASHO-DOWN OR HOSE BIB FIXTURES.
27.PVC PIPING SHALL BE PROHIBITTED IN ANY AIR PLENUM SPACES. PIPING SHALL NOT BE PROVIDED WITHING INSULATED
COOLER/FREEZER PANEL WALLS.
28.PROVIDE 12" x 12" ACCESS PANELS FOR SHOCK ABSORBERS, TRAP PRIMERS AND ALL VALVES LOCATED ABOVE
NON-ACCESSIBLE CEILINGS AND INSIDE PIPE CHASES. EXACT LOCATION MUST BE COORDINATED WITH ARCHITECTURAL
DRAWINGS AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION. ALL ACCESS PANELS SHALL BE LOCATED SO THAT THEY
ARE NOT VISIBLE TO PUBLIC VIEW.
29.WALL HYDRANTS AND HOSE BIBBS SHALL BE MOUNTED 1' - 6" ABOVE GRADE OR FLOOR LEVELS.
30.PIPING ISULATION SHALL BE PROVIDED WITH CONTIUOUS AIR-TIGHT VAPOR BARRIER WITH NO LOOSE TAPE OR EXPOSED
INSULATION MATERIAL. CONDENSATE PIPING SHALL BE PROVIDED WITH ELASTOMERIC INSULATION. ALL INSULATION AND
WRAPPING JOINTS AND SEEMS SHALL BE PROVIDED WITH 1” OVERLAP AND MANUFACTURER RECOMMENDED, AIR-TIGH
MASTIC AT ANY INSULATION OR VAPRO BARIER JOINTS. INSULATION SHALL BE INSTALLED WITH FULL THICKNESS, FREE OF
ANY INSUALTION COMPRESSION. PROVIDE RIGID INSULATION SECTION AT ALL PIPING HANGERS.
31.PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AT ALL CONNECTIONS TO MECHANICAL EQUIPMENT, KITCHEN AND
LAUNDRY EQUIPMENT, IRRIGATION AND POOL CONNECTIONS, WATER SOFTENERS, VENDING MACHINES, ETC. AS REQUIRED
BY CODE AND LOCAL AUTHORITIES. CONTRACTOR IS TO VERIFY WITH THE LOCAL AUTHORITY THE TYPE OF BACKFLOW
PREVENTION DEVICE REQUIRED FOR ALL APPLICATIONS PRIOR TO INSTALLATION. DRAINAGE FIXTURE AND PIPING (HUB
DRAIN/FLOOR DRAIN ETC) SHALL BE PROVIDED FOR EACH BFP CONTAINING A BACKFLOW DISCHARGE.
32.EXTEND ALL PVC CONDUITS CONTAINING BEVERAGE LINES, HOT AND COLD WATER PIPING, ETC. BELOW FLOOR/GROUND A
MINIMUM OF ONE INCH ABOVE FINISHED FLOOR AND SEAL AROUND PIPING TO ENSURE WATER- TIGHT CONNECTIONS.
OFFSET ALL PVC BEVERAGE CONDUITS WITH 24" MINIMUM RADIUS FITTINGS. REFER TO KITCHEN EQUIPMENT DRAWINGS FOR
ADDITIONAL DETAILS AND REQUIREMENTS. PVC CONDUITS SHALL BE FIRE WRAPPED OR ENCASED IN 5/8" GYPBOARD.
33.PROVIDE A VALVED BYPASS AT ALL EQUIPMENT INCLUDING WATER HEATERS, STORAGE TANKS WATER SOFTENERS,
BOOSTER PUMPS, FIRE PUMPS, ETC… FOR MAINTENANCE OF EQUIPMENT.
34.PROVIDE BALL VALVES AT ALL BRANCH LINES SERVING MULTIPLE FIXTURES. PROVIDE ACCESSIBLE BALL VALVE AT EACH
FIXTURE CONNECTION (IN ADDITION TO ANY EXPOSED STOPS) OR FIXTURE HEADER BRANCH CONNECTION.
35.ALL HAND-WASHING BASINS AND LAVATORIES INSTALLED SHALL BE EQUIPPED WITH HOT AND COLD WATER THROUGH A
MIXING VALVE UNLESS A TEMPERED WATER SUPPLY IS INDICATED.
36.INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF A FIXTURE SERVED WITH NO SHUT-OFF
DEVICES BEYOND THE DISCHARGE OF THE VACUUM BREAKER.
37.THE USE OF RISER CLAMPS TO SUPPORT VERTICAL PIPE ALONG WALLS, OR COLUMNS IS PROHIBITED. PROVIDE B-LINE 22
STRUT & B-2000 PIPE CLAMPS
38.CONTRACTOR SHALL HANG ALL PIPING FROM THE STRUCTURAL MEMBERS (W-SHAPES, BAR JOISTS) WITH CLAMP-TYPE
CONNECTIONS. PIPING SHALL NOT BE SUPPORTED FROM THE METAL DECK. STRUCTURAL MEMBERS SHALL NOT BE CUT OR
DRILLED.
39.ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS
FOR FOOD SERVICE AREAS.
40.ALL ANNULAR SPACES ARE TO BE CLOSED AND ESCUTCHEON PLATES AT HAND WASHING AREAS MUST BE SECURED.
41.TRAP FOR FLOOR DRAINS, FLOOR SINKS, OR HUB DRAINS ASSOCIATED WITH THE FOOD SERVICE AREAS AND NOT AS AN
INDIRECT WASTE RECEPTOR SHALL BE PROVIDED WITH A WATER SEAL OF AT LEAST 4" DEEP.
42.INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE SERVED WITH NO SHUT-OFF
DEVICES BEYOND THE DISCHARGE OF THE VACUUM BREAKER.
43.ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS
FOR FOOD SERVICE AREAS.
44.ALL DIRECT CONNECT APPLIANCES SHALL BE INDIVIDUALLY PROTECTED AGAINST BACKFLOW. "CARBONATOR" AND
CARBONATED-TYPE SODA DISPENSERS ARE CONSIDERED TO BE "HIGH HAZARD" APPLIANCES AND SHALL BE PROTECTED BY
SPECIFICALLY LISTED CO2 BACKFLOW PREVENTERS. ALL OTHER APPLIANCES SUCH AS ICE MACHINES, COFFEE MAKERS,
YOGURT DISPENSERS, AND SIMILAR EQUIPMENT WITH DIRECT CONNECTIONS TO POTABLE WATER SHALL BE PROTECTED BY
A DOUBLE CHECK VALVE TYPE BACKFLOW PREVENTER.
45.REFER TO FIRE PROTECTION SPEC FOR SPRINKLER DESIGN REQUIREMENTS FOR ALL AREAS IN CONJUNCTION WITH PIPING
AND HEADS SHOWN ON DRAWINGS.
46.GC SHALL BE RESPONSIBLE FOR ALL RISER, AND SERVICE COMPONENTS INCLUDING ALL DETECTOR CHECKS, DOUBLE
DETECTOR CHECK ASSEMBLIES, PIV, WET AND DRY RISERS, FDC, VAULTS AND OTHER DEVICES REQUIRED FOR ALL AREA
NOTED WITH SPRINKLER COVERAGE.
GENERAL PLUMBING NOTES
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
No. M34196
JU S T I R.HARD
Y
REGI
S
TRE D
E
P R O F ESSIONAL
E
N
G
IN
E
E
R
EXP.
MECH A N I C A L
A
TATE OF I R NIA
C F OL
N
S
9/30/2026
F
R
R
6" FD-1
(ETR)
6" FD-1
(ETR)
6" FD-1
(ETR)6" FD-1
(ETR)
6" FD-1
(ETR)
6" FD-1
(ETR)
6" FD-1
(ETR)6" FD-1
(ETR)
6" FD-1
(ETR)
12" FD-1
(ETR)
12" FD-1
(ETR)
12" FD-1
(ETR)
G55
3
G58
3
G58
3
G57
2
G63
2
4
4
GASGASGASGASGASGASGASGASGASGASGASGAS
GAS LINE
(ETR)
2-1/2"2-1/2"
GASGASGASGASGASGASGASGASGASGASGASGA
S
GA
S
GA
S
GA
S
GA
S
GASGAS
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GA
S
GA
S
GA
S
GAS
CAP
1
CAP
1
CAP
1 CAP
1
CAP
1
CAP
1
CAP
1CAP
1
GAS GAS GAS
3"
GAS LINE
(ETR)
2-
1
/
2
"
2-
1
/
2
"
3" GAS LINE FROM
ROOF ABOVE (ETR)
2-1/2"3"
2-1/2"
G63G57G58G58
G5
5
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
3/4"
264 CFH3/4"
120 CFH
3/4"
85 CFH
3/4"
85 CFH1"
357 CFH
GAS LINE(ETR)
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GA
S
GA
S
GA
S
GA
S
2-1/2"
GAS LINE
(ETR)
CAPEXISTING CAPEXISTING CAPEXISTING
CAPEXISTING
2-
1
/
2
"
CAPEXISTING
2-
1
/
2
"
3"2 1/2"
CAPEXISTING CAPEXISTING CAPEXISTINGCAPEXISTINGCAPEXISTING
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
54
S
o
u
t
h
A
v
e
n
u
e
Ma
r
i
e
t
t
a
,
G
A
3
0
0
6
0
40
0
-
8
0
0
-
7
9
8
8
in
f
o
@
c
o
n
v
e
r
g
e
e
n
g
i
n
e
e
r
s
.
c
o
m
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
No. M34196
JU S T I R.HARD
Y
REGI
S
TRE D
E
P R O F ESSIONALE
N
GI
N
E
E
R
EXP.
MECH A N I C A L
A
TATE OF I R NIA
C F OL
N
S
9/30/2026
PLUMBING FLOOR PLAN-SANITARY
3/8" = 1'-0"
#
P1.0
PLUMBING
PLANS
REFER TO K-SHEETS FOR KITCHEN PLUMBING
FIXTURE SCHEDULE, DIMENSIONS AND FIXTURE
BRANCH SIZES.
OVERALL KEY PLAN
N.T.S.
GAS
PIPE DROP
ROOF DRAIN
BALL VALVE
GAS PIPING
CW PIPING
HW PIPING
HOT WATER RECIRCULATION PIPING
VENT PIPING
SANITARY PIPING (LONG DASH)
GREASE WASTE (SHORT DASH)STRAINER
PRV
CHECK VALVE
METER
NAT GAS REGULATOR
3 WAY VALVE
2 WAY VALVE
BUTTERFLY VALVE
CIRCUIT SETTER
FLOW CONTROL VALVE
GAGE
PT PLUG
PUMP
DOUBLE CHECK VALVE
FLEX PIPE/CONNECTION
THERMOMETER
AUTO AIR VENT
FROSTAT
UNION
RPZ CHECK
GAS
LEGEND
NOTE:
EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS & SITE
VISITS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. FIELD
VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS.
CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER
DISCIPLINES AND EXISTING CONDITIONS.
GENERAL DEMO NOTES:
1.PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY
ACQUAINTED WITH THE EXISTING CONDITIONS OF THE PROJECT. REVIEW
THE GENERAL NOTES, SPECIFICATIONS AND OTHER DRAWINGS FOR
ADDITIONAL REQUIREMENTS WHICH MAY NOT BE SPECIFICALLY CALLED OUT
IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT,
ENGINEER AND/OR OWNER OF CONFLICTS OR DISCREPANCIES PRIOR TO
SUBMISSION OF BID.
2.EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND SITE
VISITS AND MAY NOT REFLECT EXACT “AS-BUILT” CONDITIONS. FIELD VERIFY
EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. COORDINATE NEW
WORK AND DEMOLITION WITH OTHER DISCIPLINES AND EXISTING
CONDITIONS PRIOR TO CONSTRUCTION.
3.OWNER RETAINS RIGHTS OF SALVAGE FOR EQUIPMENT AND FIXTURES TO BE
REMOVED. COORDINATE WITH THE OWNER THE EQUIPMENT AND FIXTURES
TO BE SALVAGED AND THE LOCATION FOR STORAGE. AVOID DAMAGE TO
EQUIPMENT, FIXTURES AND DEVICES DURING DEMOLITION WORK AND
DURING TRANSPORT TO OWNER'S DESIGNATED STORAGE LOCATION.
4.AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT TO REMAIN FOR
NEW INSTALLATION. REPAIR ANY DAMAGE CAUSED DURING WORK AT NO
EXTRA COST TO THE OWNER.
5.SEAL ALL PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND ROOFS
WHERE PLUMBING COMPONENTS ARE REMOVED AND WHERE THE EXISTING
PENETRATION IS NOT USED FOR THE NEW INSTALLATION. REPAIR SURFACES
TO MATCH ADJACENT AREAS.
6.INSTALL PERMANENT CAPS WHERE PIPING IS REMOVED AND THE EXISTING
TAPS ARE NOT USED FOR THE NEW INSTALLATION. INSTALL TEMPORARY
CAPS WHERE PIPING IS REMOVED AND THE EXISTING TAPS WILL BE USED
FOR THE NEW INSTALLATION TO PROTECT THE INTERIOR SURFACES UNTIL
NEW PIPING IS INSTALLED.
7.REMOVE PIPE HANGERS, PIPE SUPPORTS AND EQUIPMENT SUPPORTS
WHERE PIPING OR EQUIPMENT IS REMOVED AND THE EXISTING HANGERS
AND SUPPORTS ARE NOT USED FOR THE NEW INSTALLATION.
8.VERIFY THAT EXISTING EQUIPMENT TO REMAIN IS OPERATING PROPERLY.
NOTIFY THE ARCHITECT, ENGINEER AND/OR OWNER OF ANY DAMAGED
AND/OR MALFUNCTIONING COMPONENTS.
9.WHERE SHUTDOWN OF EXISTING ACTIVE PIPING SYSTEMS IS REQUIRED
DURING DEMOLITION PHASE OF WORK IN PREPARATION FOR NEW TIE-IN
PHASE OF WORK, COORDINATE WITH THE OWNER AND MINIMIZE DOWNTIME.
VERIFY EXISTING SYSTEMS, EQUIPMENT, AND COMPONENTS WILL BE
PROVIDED WITH BACKUP SERVICE WHERE REQUIRED. NOTIFY OWNER A
MINIMUM OF SEVEN (7) DAYS PRIOR TO INTERRUPTION OF SERVICE
KITCHEN GENERAL NOTES:
1. REFERENCE KITCHEN EQUIPMENT DRAWINGS FOR ITEMS TO BE FURNISHED
AND / OR INSTALLED AND PROVIDE ITEMS AND WORK AS REQUIRED TO
COMPLETE THE INSTALLATION OF PLUMBING SYSTEMS FOR KITCHEN
EQUIPMENT. REFERENCE THE KITCHEN EQUIPMENT DRAWINGS FOR
REQUIRED ROUGH-IN AND FINAL CONNECTIONS FOR KITCHEN EQUIPMENT.
REFERENCE THE KITCHEN EQUIPMENT SHOP DRAWINGS PRIOR TO THE
START OF INSTALLATION FOR ADDITIONAL REQUIREMENTS.
2.PROVIDE ITEMS AND WORK AS REQUIRED FOR A COMPLETE AND WORKING
PLUMBING INSTALLATION FOR EACH PIECE OF KITCHEN EQUIPMENT.
PROVIDE ROUGH-INS AND CONNECT TO THE KITCHEN EQUIPMENT WITH
TRAPS, SUPPLIES, SHUTOFF VALVES, PIPES TO THE WALL, ESCUTCHEONS,
ETC AS SHOWN, SPECIFIED AND REQUIRED.
3.VERIFY GAS LOADS AND GAS ROUGH-IN OF KITCHEN EQUIPMENT WITH THE
KITCHEN EQUIPMENT DRAWINGS PRIOR TO INSTALLING GAS PIPING. PROVIDE
GAS COCKS, UNIONS, ETC. AS SPECIFIED AND REQUIRED. INSTALL GAS
QUICK DISCONNECTS WHERE FURNISHED WITH THE KITCHEN EQUIPMENT.
4.COMPLY WITH HEALTH DEPARTMENT REGULATIONS. PROVIDE CLEARANCE
FOR CLEANING BEHIND AND UNDER EXPOSED PIPING AS REQUIRED BY
HEALTH DEPARTMENT. CONFORM TO HEALTH DEPARTMENT REQUIREMENTS
FOR LOCATIONS OF FLOOR SINKS.
5.COORDINATE LOCATION OF VENT, WATER, AND GAS PIPING TO AVOID
CONFLICT WITH OTHER TRADES.
6.LEAN INSTALLED PLUMBING FIXTURES AND EQUIPMENT.
7.SEAL AROUND INSTALLED FIXTURES AND KITCHEN EQUIPMENT WITH CAULK.
CONTRACTOR TO COORDINATE WITH ANSUL
SYSTEM INSTALLER MODIFICATIONS REQUIRED TO
EXISTING HOOD ANSULSYSTEM TO PROVIDE
PROPER COVERAGE OF ALL NEW EQUIPMENT
BENEATH EXISTING HOOD
PLUMBING FIXTURE SCHEDULE:
FIXTURES IN THIS SCHEDULE OR THEIR APPROVED EQUIVALENT ARE PROVIDED
BY THE PLUMBING CONTRACTOR. SUBMIT SHOP DRAWINGS ON EACH OF THESE
ITEMS. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION AND
INSTALLATION REQUIREMENTS. VERIFY ROUGH-IN REQUIREMENTS WITH
MANUFACTURER'S INSTALLATION INSTRUCTIONS AND INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. REFER TO THE ARCHITECTURAL
DRAWINGS FOR THE PLUMBING FIXTURE MOUNTING HEIGHTS.
THERMOSTATIC MIXING VALVE: POWERS # LFG480, SOLID LEAD
FREE BRASS BODY, THERMOSTATIC WAX ELEMENT,
CORROSION RESISTANT INTERNAL PARTS, AND INTEGRAL
CHECKS, ASSE 1070 COMPLIANT, CAPABLE OF 2.2 GPM WITH A
20 PSI DIFFERENTIAL AND A MINIMUM FLOW RATE OF 0.25 GPM.
SET MAXIMUM TEMPERATURE AS INDICATED ON PLANS.
TMV
TMV
#
PLUMBING EQUIPMENT DESIGNATION. (CONTRACTOR FURNISHED AND
INSTALLED). REFER TO PLUMBING FIXTURE OR EQUIPMENT
SCHEDULES.
PLUMBING PLAN NOTE CALLOUT
1 EQUIPMENT DESIGNATION (OWNER FURNISHED, CONTRACTOR
INSTALLED)
PLUMBING PLAN NOTE CALLOUT
(ETR)EXISTING TO REMAIN
NOTE:
CONTRACTOR SHALL VERIFY ALL GAS FIRED EQUIPMENT CONNECTION LOCATIONS IN
THE FIELD PRIOR TO INSTALLING ANY GAS PIPE MAINS OR BRANCHES. INSTALL THE GAS
TRAIN SUCH THAT ACCESS PANEL SWINGSHALL NOT BE IMPEDED.
FULL SIZE FULL PORT GAS
COCK OR BALL VALVE DRIP/DIRT POCKET
MAKE CONNECTION TO OR
APPLIANCE FLEX HOSE QUICK
CONNECTION FITTING OR UNIT
GAS MANIFOLD INSIDE CABINET
WITH GROUND JOINT UNION.
PROVIDE GROMMET IN CABINET
FOR WATER-TIGHT SEAL FOR
HVAC CONNECTIONS.
GAS PIPING EQUIPMENT CONNECTION DETAIL.
PRESSURE REGULATOR
WITH VENT LIMITER OR
VENT TO OUTDOORS.
PROVIDE AT EACH
APPLIANCE WHEN
SERVICE IS GREATER
THAN 7" W.C.
GAS RISER DIAGRAM
N.T.S.
3/4" 360° FREESPIN MALE INLET
QUICK CONNECT MALE NIPPLE PLUG
BODY
3/4" FEMALE QUICK CONNECT
COUPLING SOCKET
EXTRUDED COATED STAINLESS
BRAIDED GAS APPLIANCE CONNECTOR
3/4" 360° FREESPIN MALE OUTLET
TO GAS APPLIANCEFROM GAS SUPPLY LINE
GAS APPLIANCE QUICK DISCONNECT
KITCHEN GAS SCHEDULE
ITEM # CONNECTION
SIZE
LOOKING
UP OR
DOWN
B.T.U./
HOUR REMARKS
USE EXISTING PIPE FOR NATURAL GAS LOOP TO HANDLE: 911,000 TOTAL B.T.U./HR.:
G55 1"DOWN 357,000 FRYER ASSEMBLY w/FILTER - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY
P.C.
G57 3/4"UP 120,000 36" CHARBROILER - P.C. TO INSTALL & SUPPLY GAS PRESSURE - QUICK DISCONNECT
SUPPLIED BY K.E.C. & INSTALLED BY P.C.
G58 3/4" EACH UP 85,000
EACH 36" PLANCHA - (2) RIP'S - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY P.C.
G63 3/4"UP 264,000 48" HOT TOP RANGE - GAS PRESSURE REGULATOR SUPPLIED w/UNIT & INSTALLED BY
P.C. - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY P.C.
NOTE:
THE GAS EQUIPMENT WILL BE INITIALLY SET BY THE K.E.C. THEN THE P.C. WILL USE EXISTING GAS LINE TO VARIOUS CONNECTION
POINTS. P.C. IS TO PROVIDE SHUT-OFF'S & INSTALL ALL PRESSURE REGULATORS. P.C. IS TO INSTALL THESE COMPONENTS IN ACCESSIBLE
AREAS FOR SERVICING.
PLUMBING PLAN NOTES:
1.CAP EXISTING GAS STUB-UP FOR EXISTING EQUIPMENT AT MAIN.
2.CONNECT NEW GAS EQUIPMENT TO EXISTING GAS STUB-OUT. MAKE
CONNECTION TO EQUAL OR LARGER EXISTING STUB-OUT AS FIELD
CONDITIONS REQUIRE. REFERENCE KITCHEN EQUIPMENT DRAWINGS FOR
CONNECTION SIZE AND REQUIREMENTS.
3.CONNECT NEW GAS EQUIPMENT TO EXISTING GAS HEADER. CONNECT TO
EXISTING GAS HEADER PER MANUFACTURE'S RECOMMENDATIONS. PROVIDE
WITH NEW SHUT-OFF VALVE. EXISTING FIXTURE TO REMAIN.
4.EXISTING FIXTURE TO REMAIN.
#
ROUGH-IN SET INDEX SHEET
K1 INDEX
K2 KITCHEN PLAN, SCHEDULE & ELEVATIONS
K5 KITCHEN ELECTRICAL & POS PLAN, SCHEDULES &
ELEVATIONS
K8 KITCHEN PLUMBING & GAS PLAN, SCHEDULES &
ELEVATIONS
K13 KITCHEN CRITICAL PLAN, SCHEDULE & ELEVATIONS
IN
D
E
X
S
H
E
E
T
SHEET
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
K1
1 OF 5 SHEETS
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
F
R
R
K80K80A K72BK43B K30 K66
K76
K60 K74A K81AK74
K2
K72A K81AK81B K72C K81A
K81B K2
K46A
K75
K143
K49K43
K30
K66 K116A K125
EXISTING PASS
WINDOW TO REMAIN
EXISTING HAND
SINK TO REMAIN
K70.2
K143 K54 K79
K2 K78/
K141K47 K55
K60 K45
K73K56A
K58/B K59 K57/B
K102
K143
K78/
K141
K46
K63/B
K64
K41
K39K2
K2
EXISTING PASS
WINDOW TO
REMAIN
EXISTING PASS
WINDOW TO REMAIN EXISTING KDS
TO REMAIN
K71
K49B K66K65
RELOCATE
EXISTING KDS
FROM COOKLINE
EXISTING KDS
TO REMAIN
RELOCATE EXISTING KDS
FROM WEST END OF LINE
EXISTING KDS
TO REMAIN
K78/
K141
K78/
K141
K78/
K141
K78/
K141
K7
K7
K7
K7
K30K66
K71
K49 K116AK72CK72AK74AK72BK80
K71
K75K2K2
K66
K30
K43BK80A
K7
K76
K70.2
K54K45K59K46K49BK64K2
K2 K39
K143
K79K78
K65
K41
K55
K60K73
K58/BK57/B
K63/B
K141
K47
K56A
K102
EXISTING
HAND SINK
TO REMAIN
EXISTING KDS
TO REMAIN
K7
K7
ELEVATION "12"
DISH-UP LINE
EXISTING COLD
WINDOW TO REMAIN
ELEVATION "14"
MAIN COOK LINE
EXISTING PASS
WINDOW TO REMAIN
EXISTING PASS
WINDOW TO REMAIN
K81A
K81B
K81A
K81B
K81A
K74
K78
K141
K78
K141
K78
K141
K78
K141
K143
K7
K2
K143
K78
K141
RELOCATE
EXISTING KDS
EXISTING KDS TO REMAINRELOCATE EXISTING
KDS FROM COOK LINEEXISTING KDS TO REMAINEXISTING KDS TO REMAIN
K125
K46A
K43 K66
K60
K66
K30 K30
K71
K66
KITCHEN EQUIPMENT SCHEDULE
ITEM #QTY DESCRIPTION MANUFACTURE MODEL NUMBER PROVIDED
BY:
INSTALLED
BY:
NSF
LISTED
CUSTOM
FAB
CASTERS
/FIXED
K2 LOT TRASH RECEPTACLES RUBBER MAID #3540-SLIM JIM OWNER OWNER ---
K7 8 CORNER GUARDS @ BOH CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES -
K30 3 MICROWAVE WALL SHELF CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K39 1 HAND SINK ADVANCE
TABCO 7-PS-62-2X K.E.C.K.E.C.YES -FIXED
K39.1 2 HAND SINK SPLASH GUARDS (NOT SHOWN ON PLAN)CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K41 1 POT RACK ADVANCE
TABCO SW1-48 K.E.C.K.E.C.YES -FIXED
K43 2 PLATE SHELVES CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K43B 2 PLATE SHELVES CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K45 1 UNDER COUNTER FREEZER w/DRAWERS DELFIELD STD4532NP K.E.C.K.E.C.YES -CASTERS
K46 1 WORK COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K46A 1 WORK COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K47 1 WORK COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K49 1 PIZZA STATION DELFIELD 18660PTBMP K.E.C.K.E.C.YES -CASTERS
K49B 1 SAUTE STATION DELFIELD DA000A15P01 K.E.C.K.E.C.YES -CASTERS
K54 1 BREADING STATION DELFIELD DA000A17P01 K.E.C.K.E.C.YES -CASTERS
K55 1 FRYER ASSEMBLY w/FILTER FRYMASTER 3FQG60T K.E.C.K.E.C.YES -CASTERS
K55A 1 GAS DISCONNECT HOSE (NOT SHOWN ON PLAN)T&S BRASS HG-4E-48SK K.E.C.PLUMBER YES -FIXED
K56A 1 DOUBLE WALL SHELF w/BOWL SLIDES CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K57 1 CHARBROILER SOUTHBEND HDC-36 K.E.C.K.E.C.YES --
K57A 1 GAS DISCONNECT HOSE (NOT SHOWN ON PLAN)T&S BRASS HG-4D-48SK K.E.C.PLUMBER YES -FIXED
K57B 1 CONDIMENT RAIL CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K58 2 COUNTER TOP PLANCHA WOOD STONE WS-GPL-3636-CT01 K.E.C.K.E.C.YES --
K58A 2 GAS DISCONNECT HOSE (NOT SHOWN ON PLAN)T&S BRASS HG-4D-48SK K.E.C.PLUMBER YES -FIXED
K58B 2 CONDIMENT RAIL CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K59 1 SHORTY REFRIGERATOR DELFIELD DA000A14P K.E.C K.E.C.YES -CASTERS
K60 2 FRY WARMING STATION MERCO MCG1827NNN K.E.C.K.E.C.YES --
K63 1 48" HOT PLATE SOUTHBEND HDO-48 K.E.C.K.E.C.YES --
K63A 1 GAS DISCONNECT HOSE (NOT SHOWN ON PLAN)T&S BRASS HG-4D-48SK K.E.C.PLUMBER YES -FIXED
K63B 1 CONDIMENT RAIL CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K64 1 SHORTY REFRIGERATOR DELFIELD DA000A13P K.E.C.K.E.C.YES -CASTERS
K65 1 PAN/PLATE OVERSHELF CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K66 4 MICROWAVE OVEN PANASONIC NE-17521 K.E.C.K.E.C.YES --
K70.2 1 REACH-IN FREEZER DELFIELD 6125XL-S K.E.C.K.E.C.YES -CASTERS
K71 2 REACH-IN REFRIGERATOR DELFIELD 6025XL-S K.E.C.K.E.C.YES -CASTERS
K72A 1 FRY REFRIGERATOR DELFIELD 18648PTBMP K.E.C.K.E.C.YES -CASTERS
K72B 1 DISH-UP REFRIGERATOR DELFIELD 18699PTBMP K.E.C.K.E.C.YES -CASTERS
K72C 1 PIZZA PREP REFRIGERATOR DELFIELD DA000A?P01 K.E.C.K.E.C.YES -CASTERS
K73 1 COUNTER TOP WARMER APW WYOTT W-9 K.E.C.K.E.C.YES --
K74 1 CONVEYOR TOASTER ANTUNES VCT-2 K.E.C.K.E.C.---
K74A 1 TOASTER COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K75 1 WARMING DRAWER WELLS RWN-2 K.E.C.K.E.C.YES --
K76 1 CVAP HOLDING DRAWER WINSTON HBB0N2 K.E.C.K.E.C.YES --
K78 6 P.O.S SYSTEM UNITS - EXISTING - (2) TO RELOCATE --OWNER OWNER ---
K79 1 DOUBLE WALL SHELF w/BOWL SLIDES & CONDIMENT RAIL CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K80 1 WORK COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K80A 2 PLATE SHELVES CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K81A 3 PASS THRU CONDIMENT RAILS CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K81B 2 HEAT SHIELD CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K102 LOT WALL PANELING FOR MAIN COOK LINE CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES -
K116A 1 PIZZA OVEN COUNTER CUSTOM S/S CUSTOM S/S K.E.C.K.E.C.YES YES FIXED
K125 2 CONVECTION OVEN TURBO CHEF HHD-9500 -105-DL K.E.C.K.E.C.YES --
K141 6 POS MONITOR BRACKET - EXISTING - (2) TO RELOCATE PEERLESS SA730P OWNER OWNER --FIXED
K143 3 HOT FOOD WELL APW WYOTT W-3VI K.E.C.K.E.C.YES --
SCALE:
SHEET
K2
MAIN KITCHEN
2 OF 5 SHEETS
KI
T
C
H
E
N
E
Q
U
I
P
M
E
N
T
P
L
A
N
,
SC
H
E
D
U
L
E
&
E
L
E
V
A
T
I
O
N
S
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
ELEVATION "12"
DISH-UP LINE
EXISTING COLD
WINDOW TO REMAIN
ELEVATION "14"
MAIN COOK LINE
EXISTING PASS
WINDOW TO REMAIN
EXISTING PASS
WINDOW TO REMAIN
KITCHEN ELECTRICAL SCHEDULE
ITEM
#V/ɸ AMPS H.P.KW TYPE LOCATION A.F.F.NEMA REMARKS
EDCO 120V/1 PH 15.0 EACH --D.C.O.WALL 48"5-20R CONVENIENCE OUTLET - (2) RIP'S
E45 115V/1 PH 5.2 0.35 -D.C.O.WALL 24"5-15P UNDER COUNTER FREEZER - E.C. TO SUPPLY & INSTALL GFCI PROTECTED DUPLEX
E49 115V/1 PH 4.7 0.25 -D.C.O.WALL 24"5-15P PIZZA STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E49B 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P SAUTE STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E54 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P BREADING STATION - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E55 120V/1 PH CONTROLS - 1.0,
FILTER - 8.0 --QUAD WALL 24"5-20R FRYER ASSEMBLY w/FILTER - DEDICATED 20A CIRCUIT BREAKER
E58 120V/1 PH .6 EACH --D.C.O.WALL 24"5-15P COUNTER TOP PLANCHA - (2) RIP'S
E59 115V/1 PH 12.0 --D.C.O.WALL 24"5-15P SHORTY REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E60 120V/1 PH 15.9 EACH -
1910
WATTS
EACH
D.C.O.WALL 48"5-20P FRY WARMING STATION - (2) RIP'S
E64 115V/1 PH 2.9 --D.C.O.WALL 24"5-15P SHORTY REFRIGERATOR - E.C. TO SUPPLY & INSTALL GFCI PROTECTED DUPLEX
E66 208V/1 PH 13.6 EACH -
1700
WATTS
EACH
S.P.O.WALL 72"6-20P MICROWAVE - (3) RIP'S
E66A 208V/1 PH 13.6 -1700
WATTS S.P.O.WALL 72"6-20P MICROWAVE - REUSE EXISTING OUTLET
E70.2 115V/1 PH 5.5 0.55 -D.C.O.WALL 72"5-15P REACH-IN FREEZER
E71 115V/1 PH 4.2 0.22 -D.C.O.WALL 90"5-15P REACH-IN REFRIGERATOR - REUSE EXISTING OUTET
E71A 115V/1 PH 4.2 0.22 -D.C.O.WALL 72"5-15P REACH-IN REFRIGERATOR
E72A 115V/1 PH 4.7 --D.C.O.WALL 24"5-15P FRY REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E72B 115V/1 PH 6.5 (2) 0.20 -D.C.O.WALL 24"5-15P DISH-UP REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E72C 115V/1 PH 6.5 --D.C.O.WALL 24"5-15P PIZZA PREP REFRIGERATOR - E.C. TO PROVIDE & INSTALL GFCI PROTECTED DUPLEX
E73 120V/1 PH 3.3 -400 WATTS D.C.O.WALL 48"5-15P COUNTER TOP WARMER
E74 120V/1 PH 15.0 -1800
WATTS
D.C.O./
JBOX WALL 52"5-15P CONVEYOR TOASTER - REUSE EXISTING OUTLET
E75 120V/1 PH 7.5 -900 WATTS D.C.O.WALL 24"5-15P WARMING DRAWER - NARROW 2-TIER
E76 120V/1 PH 12.0 -1440
WATTS D.C.O.WALL 24"5-15P CVAP HOLDING DRAWER
E125 208V/3 PH 30.0 EACH -9600
WATTS S.P.O.WALL 48"15-30P CONVECTION OVEN - (2) RIP'S - E.C. INSTALL 4S BOX
E143 120V/1 PH 10.0 EACH -
1200
WATTS
EACH
D.C.O.WALL 48"5-15P HOT FOOD WELL - (2) RIP'S
E143A 120V/1 PH 10.0 -1200
WATTS D.C.O.WALL 24"5-15P HOT FOOD WELL
KITCHEN POS ELECTRICAL SCHEDULE
ITEM #V/ɸ AMPS TYPE LOCATION A.F.F.REMARKS
KDS54A 120V/ 1 PH 20.0 D.C.O.WALL 66"KDS SYSTEM - DEDICATED CIRCUIT - VERIFY REQUIREMENTS w/OWNER
KDS54B DATA JBOX WALL 66"DATA/KDS CABLE - 2" x 4" EMPTY BOX w/CONDUIT TO 6" ABOVE CEILING LINE -
VERIFY REQUIREMENTS w/OWNER
KDS64A 120V/ 1 PH 20.0 D.C.O.WALL 72"KDS SYSTEM - REUSE EXISTING OUTLET
KDS64B DATA JBOX WALL 72"DATA/KDS CABLE - REUSE EXISTING OUTLET
KDS72C 120V/ 1 PH 20.0 EACH D.C.O.WALL 86"KDS SYSTEM - DEDICATED CIRCUIT - VERIFY REQUIREMENTS w/OWNER
KDS72D DATA JBOX WALL 86"DATA/KDS CABLE - 2" x 4" EMPTY BOX w/CONDUIT TO 6" ABOVE CEILING LINE -
VERIFY REQUIREMENTS w/OWNER
KDS72E 120V/ 1 PH 20.0 EACH D.C.O.WALL VARIES KDS SYSTEM - (4) RIP'S - REUSE EXISTING OUTLET
KDS72F DATA VARIES WALL VARIES DATA/KDS CABLE - (4) RIP'S - REUSE EXISTING OUTLET
ELECTRICAL
SYMBOLS & ABBREVIATIONS
SINGLE CONVENIENCE OUTLET (SCO)Sw SWITCH AS NOTED
DOUBLE CONVENIENCE OUTLET (DCO)Sp SWITCH & PILOT LIGHT
QUAD CONVENIENCE OUTLET (QCO)EL ELEVATION A.F.F
JUNCTION BOX (JB)AMPS AMPERES
HEATING ELEMENT OR POWER V VOLTS
FLOOR RECEPTACLE AS NOTED ɸ PHASE
SPECIAL PURPOSE OUTLET (SPO)A.F.F.ABOVE FINISHED FLOOR
MOTOR OUTLET B.T.C.BRANCH TO CONNECTION POINT &
CONNECT EQUIPMENT
CONVENIENCE OUTLET - 2 CIRCUIT
120/280V - 1PH, 3 WIRE OR AS NOTED B.T.F.BRANCE TO FIXTURE, FURNISH &
INSTALL RECEPTACLE
CONDUIT AS NOTED D.F.A.DROP FROM ABOVE
SOLENOID OR CONTROL CIRCUIT S.U.STUB UP A.F.F.
DATA/PHONE H.P.HORSE POWER
PANELBOARD KW KILOWATTS
DISCONNECT SWITCH E.C.ELECTRICAL CONTRACTOR
LIGHT INDICATION R.I.P.ROUGH IN POINT
J
C
S
D
F
R
R
+72"
FS FS FSFSFSFSFSFS
G
FS FSFSFS
+72"+72"
+90"+52"
A
+52"+52"
+84"
+72"
A
+72"+72"
A
3'-
8
"
-
E
1
2
5
6'-
2
"
-
E
1
2
5
8'-
6
"
-
E
4
9
13
'
-
8
"
-
E
7
5
,
E
1
4
3
&
E
6
6
20
'
-
3
"
-
E
7
2
C
25
'
-
1
"
-
E
7
2
A
32
'
-
5
1
/
2
"
-
E7
6
(
+
2
4
"
)
&
E7
4
(
E
X
I
S
T
I
N
G
)
30
'
-
9
1
/
2
"
-
E
6
0
35
'
-
6
"
-
E
6
6
37
'
-
7
"
-
E
7
2
B
E6
4
-
9
'
-
0
"
E1
4
3
-
1
4
'
-
9
1
/
2
"
E4
9
B
-
1
3
'
-
0
"
E6
6
-
1
0
'
-
7
1
/
2
"
E7
1
A
-
4
'
-
4
"
E5
9
-
2
0
'
-
5
1
/
2
"
E5
8
-
2
2
'
-
1
0
"
E5
8
-
1
9
'
-
1
0
"
E6
0
-
2
6
'
-
9
"
E4
5
&
E
7
3
-
2
6
'
-
1
"
E5
5
-
3
0
'
-
4
1
/
2
"
ED
C
O
-
3
3
'
-
7
1
/
2
"
E5
4
-
3
8
'
-
1
0
"
E1
4
3
A
-
3
8
'
-
4
"
E7
0
.
2
-
4
0
'
-
6
"
43
'
-
6
3
/
4
"
-
ED
C
O
(
+
4
8
"
)
&
E7
1
(
E
X
I
S
T
I
N
G
)
EX
I
S
T
I
N
G
-
E
6
6
A
F
R
R
+72"+72"
+90"+90"+90"
+90"
+90"+90"+72"+72"
KD
S
7
2
D
17
'
-
2
1
/
2
"
KD
S
7
2
C
16
'
-
4
1
/
2
"
KD
S
7
2
E
EX
I
S
T
I
N
G
KD
S
7
2
F
EX
I
S
T
I
N
G
KD
S
7
2
F
EX
I
S
T
I
N
G
KD
S
7
2
E
EX
I
S
T
I
N
G
KD
S
7
2
E
EX
I
S
T
I
N
G
KD
S
7
2
F
EX
I
S
T
I
N
G
KD
S
7
2
E
EX
I
S
T
I
N
G
KD
S
7
2
F
EX
I
S
T
I
N
G
KD
S
6
4
A
EX
I
S
T
I
N
G
KD
S
6
4
B
EX
I
S
T
I
N
G
D
D
KD
S
5
4
B
33
'
-
2
1
/
8
"
KD
S
5
4
A
34
'
-
0
1
/
8
"
SCALE:
SHEET
K5
3 OF 5 SHEETS
REUSE AS MANY EXISTING UTILITIES AS POSSIBLE
KI
T
C
H
E
N
E
L
E
C
T
R
I
C
A
L
/
P
O
S
P
L
A
N
,
SC
H
E
D
U
L
E
S
&
E
L
E
V
A
T
I
O
N
S
MAIN KITCHEN
MAIN KITCHEN
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
ELEVATION "12"
DISH-UP LINE
EXISTING COLD
WINDOW TO REMAIN
ELEVATION "14"
MAIN COOK LINE
EXISTING PASS
WINDOW TO REMAIN
EXISTING PASS
WINDOW TO REMAIN
REUSE EXISTING HAND SINK WATER & DRAIN
EXISTING HAND SINK TO REMAIN
GENERAL PLUMBING NOTES
1.ALL PLUMBING OUTLETS & CONNECTIONS SHOWN ON THIS PLAN
ARE FOR FIXTURES & EQUIPMENT SHOWN RFG CONSULTING
EQUIPMENT PLAN ONLY. FOR ADDITIONAL BUILDING REQUIREMENTS
(AREA FLOOR DRAINS, ETC.) SEE OTHER DRAWINGS OR
SPECIFICATIONS BY THE ARCHITECT
2.ALL DIMENSIONS ARE GIVEN FROM FINISHED WALL AND/OR
CENTER LINE OF COLUMNS TO CENTER LINE OF OUTLET OR FROM
CENTER LINE OF OUTLET TO CENTER LINE OF OUTLET, UNLESS
OTHERWISE NOTED. ALL OUTLETS NOTED +12", +24", ETC. TO STUB
OUT OF THE WALL AT HEIGHT GIVEN. HEIGHT OF OUTLETS IS GIVEN
FROM FINISHED FLOOR (NOT TOP OF FINISHED CURB) TO CENTER
LINE OF OUTLET. OUTLETS NOTED "STUB UP" OR "STUB OUT" ABOVE
FINISHED FLOOR AT LOCATIONS SHOWN ARE TO STUB UP A
MAXIMUM OF 4" ABOVE FINISHED FLOOR OR TOP OF CURB, UNLESS
OTHERWISE NOTED. CONTRACTOR TO VERIFY ALL DIMENSIONS AT
JOB SITE.
3.ALL FOR SINKS INDICATED HALF IN & HALF OUT OF COUNTER
BODIES TO BE FLUSH w/FINISHED FLOOR. ALL FULLY OR PARTIALLY
EXPOSED FLOOR SINKS TO BE PROVIDED w/APPROPRIATE GRATE
COVERS. FLOOR SINKS HAVE BEEN LOCATED w/THE ASSUMPTION
THAT THEY WILL BE SET FLUSH w/FINISHED FLOOR (UNLESS NOTED
OTHERWISE.) IN THE EVENT LOCAL CODES REQUIRE FLOOR SINKS
TO BE ABOVE OR BELOW FINISHED FLOOR LEVEL, PLUMBER SHALL
COMPLY w/LOCAL CODES BUT NOTIFY REG CONSULTING
IMMEDIATELY.
4.PLUMBER TO CONNECT ALL WATER LINES, GAS LINES, WASTE LINES,
ETC., FOR SINK, DISHWASHERS, DISPOSERS, ETC., & RUN
INSULATED DRAIN LINE FROM ALL REFRIGERATED UNITS, ICE PANS,
ETC. TO FLOOR SINKS & DIRECT OR INDIRECT WASTE LINES TO BE
NO SMALLER THAN STUB OUT OF FIXTURES THEMSELVES.
5.ALL WORK SHOWN ON FIXTURE PLUMBING PLAN & OUTLINED IN
ABOVE NOTES TO BE PERFORMED BY PLUMBING CONTRACTOR
UNDER BUILDING CONTRACT. IT IS THE PLUMBER'S RESPONSIBILITY
TO SEE THAT THIS PHASE OF WORK MEETS, & IS INSTALLED IN
ACCORDANCE w/STANDARDS REQUIRED BY ALL GENERAL, STATE &
FEDERAL LAWS (INCLUDING HEALTH CODES), & BY ANY & ALL
CODES PECULIAR TO THE MUNICIPALITY OR AREA WHERE JOB IS
BEING INSTALLED.
6.THESE PLANS ARE FOR THE SOLE PURPOSE OF INDICATING THE
LOCATION OF OUTLETS & EQUIPMENT REQUIREMENTS
7.PLUMBER TO PROVIDE THE FOLLOWING ITEMS:
A.BALL VALVES ON ALL WATER & GAS LINES & SHOCK
ABSORBERS ON ALL SELF VALVES
B.ALL VALVES TRIM & PRESSURE REGULATORS NECESSARY TO
CONNECT ALL LINES.
C.TEMPERATURE & PRESSURE SAFETY RELEASE VALVES FOR
HOT WATER BOOSTER IF USED.
D.BACK FLOW PREVENTION DEVICES AS REQUIRED BY CODE.
E.DIALECTIC COUPLERS WHEN CONNECTION GALVANIZED IRON
PIPE TO COPPER.
F.FLOOR SINK, FUNNEL HUBS, FLOOR DRAINS, & RESPECTIVE
PROTECTIVE GRATES.
G.NECESSARY WATER LINES & GAS LINES ON ROOF FOR MAKEUP
AIR SYSTEM. FOR LOCATION & EXHAUST REQUIREMENTS, SEE
ARCHITECTURAL AND/OR HVAC PLANS.
H.ALL GRATES ON FLOOR SINKS & ALL SCREENS ON FLOOR
DRAINS.
I.ALL WATER FILTERS REQUIRED FOR ICE MACHINES, COFFEE
MAKERS, STEAMERS, ETC.
J.INDIVIDUAL BALL VALVE ON ALL DRAIN LINES FOR SOUP &
FOOD WARMERS
K.ALL DRAIN LINES, NOTE: DRAIN LINES SHALL BE RUN IN
COPPER FROM CONNECTIONS TO TERMINATION.
8.PLUMBER TO MAKE ALL FINAL CONNECTIONS
9.PLUMBER TO INSTALL AUTOMATIC GAS SHUT-OFF VALVE SUPPLIED
BY FIRE CONTROL CONTRACTOR
10.ALL DRAIN LINES FROM REFRIGERATED EQUIPMENT SHALL HAVE A
"P" TRAP. THE "P" TRAP MUST BE LOCATED OUTSIDE OF THE
REFRIGERATED CAVITY.
11.REFER TO REFRIGERATION DATA SHEET FOR ADDITIONAL PLUMBING
NOTES & REQUIREMENTS.
PLUMBING
SYMBOLS & ABBREVIATIONS
FLOOR DRAIN - 4" HIGH FUNNEL (FFD)S.R.STEAM RETURN
FLOOR DRAIN - (FD)B.H.P.BOILER HORSEPOWER
FLOOR SINK - AS NOTED - (FS)E.L.ELEVATION A.F.F
RIGHT ANGLE FLOOR DRAIN - AS NOTED P.P.H.POUNDS PER HOUR
MIXING HOSE BIB, SINGLE OUTLET P.S.I.POUNDS PER SQUARE INCH
HOSE BIB, SINGLE OUTLET S.P.STATICE PRESSURE
COLD WATER - (CW)A.F.F.ABOVE FINISHED FLOOR
HOT WATER - (HW)B.T.C.BRANCH TO CONNECTION &
CONNECT
TEMPERED WATER B.F.F.BELOW FINISHED FLOOR
DIRECT WATE D.F.A.DROP FROM ABOVE
HUB DRAIN - (HD) - SET 1" A.F.F.S.U.STUB UP A.F.F.
RETURN AIR DUCT CONNECTION W.G.INCHES OF WATER GAUGE
EXHAUST DUCT CONNECTION C.F.M.CUBIC FEET PER MINUTE
G.P.H.GALLONS PER HOUR F.P.M.FEET PER MINUTE ( VELOCITY)
G.P.M.GALLONS PER MINUTE S.S.STEAM SUPPLY
D.R.DRAIN R.I.P.ROUGH IN POINT
K.E.C.KITCHEN EQUIPMENT CONTRACTOR P.C.PLUMBING CONTRACTOR
KITCHEN GAS SCHEDULE
ITEM # CONNECTION
SIZE
LOOKING
UP OR
DOWN
B.T.U./
HOUR REMARKS
USE EXISTING PIPE FOR NATURAL GAS LOOP TO HANDLE: 911,000 TOTAL B.T.U./HR.:
G55 1"DOWN 357,000 FRYER ASSEMBLY w/FILTER - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY
P.C.
G57 3/4"UP 120,000 36" CHARBROILER - P.C. TO INSTALL & SUPPLY GAS PRESSURE - QUICK DISCONNECT
SUPPLIED BY K.E.C. & INSTALLED BY P.C.
G58 3/4" EACH UP 85,000
EACH 36" PLANCHA - (2) RIP'S - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY P.C.
G63 3/4"UP 264,000 48" HOT TOP RANGE - GAS PRESSURE REGULATOR SUPPLIED w/UNIT & INSTALLED BY
P.C. - QUICK DISCONNECT SUPPLIED BY K.E.C. & INSTALLED BY P.C.
NOTE:
THE GAS EQUIPMENT WILL BE INITIALLY SET BY THE K.E.C. THEN THE P.C. WILL USE EXISTING GAS LINE TO VARIOUS CONNECTION
POINTS. P.C. IS TO PROVIDE SHUT-OFF'S & INSTALL ALL PRESSURE REGULATORS. P.C. IS TO INSTALL THESE COMPONENTS IN ACCESSIBLE
AREAS FOR SERVICING.
Gas Quick-Disconnect Installation
NO SCALE
3" MAX.
COOKING
EQUIPMENT
INSTALL GAS MANIFOLD TIGHT TO
WALL w/1 5/8" UNISTRUT TO GAIN
MAXIMUM EQUIPMENT DEPTH
UNDER HOOD
MAIN GAS MANIFOLD BY PLUMBER -
MANIFOLD SECURED TO WALL
SHUT-OFF VALVE BY PLUMBER
GAS QUICK-DISCONNECT w/DOUBLE
SWIVELS. DISCONNECT HOSE
PROVIDED BY F.S.E.C.. INSTALLED BY
PLUMBER
BUILDING WALL
MIN 1" (VERIFY CODES)ELBOWS & FITTINGS BY PLUMBER
GAS CONNECTION
ON COOKING
EQUIPMENT
GAS PRESSURE
REGULATOR
INSTALLED BY
PLUMBER
FINISHED
FLOOR
RESTRAINING CORD, SECURED
TO WALL BLOCKING, STUD, OR
GAS MANIFOLD BY PLUMBER.
INCLUDED w/KIT.
F
R
R
G6
3
-
8
'
-
1
"
G5
7
-
1
6
'
-
6
"
G5
8
-
2
0
'
-
1
1
1
/
2
"
G5
8
-
2
3
'
-
1
1
1
/
2
"
G5
5
-
2
8
'
-
7
1
/
2
"
REUSE EXISTING HAND SINK WATER & DRAIN
EXISTING HAND SINK TO REMAIN
REPLACE EXISTING FLOOR SINK GRATES TO FULL
GRATES IN MAIN COOK LINE AND DISH UP LINE
SCALE:
SHEET
K8
4 OF 5 SHEETS
REUSE EXISTING GAS LOOP
REUSE AS MANY EXISTING
UTILITIES AS POSSIBLE
KI
T
C
H
E
N
P
L
U
M
B
I
N
G
&
G
A
S
P
L
A
N
,
SC
H
E
D
U
L
E
S
&
E
L
E
V
A
T
I
O
N
S
MAIN KITCHEN
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
ELEVATION "B"
DISH-UP LINE
ELEVATION "C"
MAIN COOK LINE
EXISTING COLD
WINDOW TO REMAIN
EXISTING PASS
WINDOW TO REMAIN
EXISTING PASS
WINDOW TO REMAIN 6
24
"9
3.1
3.2
2'-3"9'-7"24"
46
"
33
"
27
"
4'
-
1
0
"
36"41"6'-9 1/2"
6'
-
8
"
5'-8 1/2"
33
"
46
"
3
1
24
"
48
"
24"
WALL BACKING SCHEDULE
NOTE:
ARCHITECT TO DETERMINE TYPE OF WALL BACKING BASED ON LOCAL CODE REQUIREMENTS
REFER TO ARCHITECT DRAWINGS FOR ADDITIONAL INFORMATION
WALL BACKING IS FROM FINISHED WALLS
ELEV.
VIEW
#
ITEM #SIZE STARTING
A.F.F.BY TYPE REMARKS
KITCHEN:
B 1 24" x 48"24"G.C.16 GA. GALVANIZED
STEEL HAND SINK
B 3 6'-9 1/2" x 33"46"G.C.16 GA. GALVANIZED
STEEL MICROWAVE & WALL SHELVES
B 3.1 24" x 33"46"G.C.16 GA. GALVANIZED
STEEL MICROWAVE WALL SHELF
B 3.2 9'-7" x 27"
TOP OF PASS
WINDOW
(4'-10")
G.C.16 GA. GALVANIZED
STEEL WALL SHELVES
C 6 FULL WIDTH FULL HEIGHT G.C.16 GA. GALVANIZED
STEEL COOK LINE
B 9 36" x 24"
TOP OF PASS
WINDOW
(6'-8")
G.C.16 GA. GALVANIZED
STEET POS MONITOR @ DISH-UP LINE
F
R
R
33.2 93.1
6
K13B
K13C
2'-3"41"5'-8 1/2"
1
SCALE:
SHEET
K13
5 OF 5 SHEETS
REUSE AS MANY EXISTING UTILITIES AS POSSIBLE
KI
T
C
H
E
N
C
R
I
T
I
C
A
L
P
L
A
N
,
SC
H
E
D
U
L
E
&
E
L
E
V
A
T
I
O
N
S
MAIN KITCHEN
DA
V
E
&
B
U
S
T
E
R
'
S
SA
N
T
A
A
N
I
T
A
,
C
A
40
0
S
o
u
t
h
B
a
l
d
w
i
n
A
v
e
n
u
e
,
A
r
c
a
d
i
a
,
C
A
BYREVISIONS
DRAWN:
CHECKED:
DATE:
SCALE:
WWW.PUBLICHEALTH.LACOUNTY.GOV/EH
SPECIALIZED SURVEILLANCE AND ENFORCEMENT BRANCH
ENVIRONMENTAL HEALTH
DEPARTMENT OF PUBLIC HEALTHwCOUNTY OF LOS ANGELES
PLAN CHECK PROGRAM - BALDWIN PARK
5050 COMMERCE DR, BALDWIN PARK, CA 91706
PHONE: (626) 430-5560
OFFICIAL PLAN REVIEW REPORT
03/05/2025DATE EHS VICKI NGO
PLAN CHECK NUMBER SR0397249
PROGRAM ELEMENT 1702 - RESTAURANT (501-1,999 SF) -RMDL
OWNER / REQUESTER JASON COX, SR DIR OF MAINTENANCE
DBA DAVE & BUSTER'S
ADDRESS 400 S BALDWIN AVE #930U, ARCADIA, CA 91007
REVISED PLAN REVIEW STATUS: APPROVED
CORRECTIONS COMPLETED
DATE CORRECTEDCORRECTION CATEGORY DATE IDENTIFIED
03/05/2025WATER SUPPLY 01/16/2025
03/05/2025WASTE WATER/PLUMBING 01/16/2025
03/05/2025EQUIPMENT/STORAGE 01/16/2025
03/05/2025VENTILATION01/16/2025
03/05/2025PLAN SUBMITTAL/REMODEL 01/16/2025
ADDITIONAL REQUIREMENTS
NONE
Help us serve you better by completing a short survey. Visit our website at www.publichealth.lacounty.gov/eh.
Page 1 of 3EHS Signature
OFFICIAL PLAN REVIEW REPORT
03/05/2025DATE EHS VICKI NGO
PLAN CHECK NUMBER SR0397249
PROGRAM ELEMENT 1702 - RESTAURANT (501-1,999 SF) -RMDL
OWNER / REQUESTER JASON COX, SR DIR OF MAINTENANCE
DBA DAVE & BUSTER'S
ADDRESS 400 S BALDWIN AVE #930U, ARCADIA, CA 91007
COMMENTS
PLAN IS APPROVED. REMODEL SCOPE OF WORK INCLUDES REPLACING EQUIPMENT AND ADDING EQUIPMENT.
NO CHANGES IN PLUMBING.
FINAL FACILITY APPROVAL IS CONTINGENT UPON THE ON SITE INSPECTION AND APPROVAL OF THE FOOD
EQUIPMENT AND THE PREMISES.
CONTACT VICKI NGO AT 626-430-5557 OR VINGO@PH.LACOUNTY.GOV TO SCHEDULE AN APPOINTMENT FOR
FINAL FIELD INSPECTION.
CALL AT LEAST 3 TO 5 WORKING DAYS PRIOR TO ARRANGE FOR A FINAL INSPECTION. A FINAL INSPECTION
SHALL BE CONDUCTED AND A PUBLIC HEALTH PERMIT OBTAINED PRIOR TO OPENING AND OPERATING THIS
FOOD ESTABLISHMENT.
THE FOLLOWING MUST BE COMPLIED WITH PRIOR TO CALLING FOR A FINAL INSPECTION:
1. ALL BUILDING AND SAFETY (MECHANICAL, PLUMBING, ELECTRICAL AND FIRE) AND OTHER ENFORCEMENT
AGENCIES FINAL INSPECTIONS MUST BE SIGNED OFF PRIOR TO HEALTH DEPARTMENT FINAL APPROVAL IF
NEEDED.
2. THE HEALTH DEPARTMENT APPROVED PLANS MUST BE AVAILABLE AT THE JOB SITE AT THE TIME OF
INSPECTION.
3. ALL UTILITIES MUST BE ON AND OPERATIONAL. HOT WATER MUST BE AT 120F AND ABOVE. ALL
REFRIGERATION UNITS MUST BE 41F AND BELOW. EXHAUST FAN MUST BE OPERATIONAL.
4. ALL FOOD AND UTENSIL RELATED EQUIPMENT SHALL HAVE AN ANSI CERTIFICATION.
IF CONSTRUCTION IS NOT COMPLETED WITHIN TWELVE (12) MONTHS FROM THE DATE OF APPROVAL, NEW PLAN
SUBMISSION AND APPROVAL SHALL BE REQUIRED.
ONE SET OF HEALTH DEPARTMENT APPROVED PLANS SHALL BE ON THE JOB SITE AT ALL TIMES DURING
CONSTRUCTION.
ANY CHANGES TO THE APPROVED PLANS MUST BE BROUGHT TO THE PLAN CHECKERS ATTENTION
Help us serve you better by completing a short survey. Visit our website at www.publichealth.lacounty.gov/eh.
Page 2 of 3EHS Signature
OFFICIAL PLAN REVIEW REPORT
03/05/2025DATE EHS VICKI NGO
PLAN CHECK NUMBER SR0397249
PROGRAM ELEMENT 1702 - RESTAURANT (501-1,999 SF) -RMDL
OWNER / REQUESTER JASON COX, SR DIR OF MAINTENANCE
DBA DAVE & BUSTER'S
ADDRESS 400 S BALDWIN AVE #930U, ARCADIA, CA 91007
DISCLOSURES
Prior to construction and approval from the Los Angeles County Department of Public Health Environmental Health Division
(DPH-EH) Plan Check Program, final inspections must be obtained from Building and Safety (mechanical, plumbing, electrical)
and all other enforcement agencies.
Failure to obtain a Public Health Permit/ License prior to operation of the facility/establishment is a misdemeanor violation.
Construction of the food facility/ establishment must be completed and approved within twelve (12) months from the date of
approval to avoid submitting new plans.
A copy of the approved plans must be available at the time of the field construction review.
All utilities must be on and operational at the time of the field construction review.
Please contact your plan check inspector at least 3 days prior to the field construction review.
Two field inspections will be covered under the Plan Check fees assessed upon plan submission.
A charge will be assessed for each subsequent field construction review.
Help us serve you better by completing a short survey. Visit our website at www.publichealth.lacounty.gov/eh.
Page 3 of 3EHS Signature