HomeMy WebLinkAbout30 S First Ave - 2025 - Medical TIFOOTHILL CARDIOLOGY - ARCADIA SYMBOLS LEGEND FINISH BUBBLE NUMBER OF ELEVATION SET INTERIOR ELEVATION GROUPS SHEET ON WHICH SHEET ON WHICH ELEVATION IS SHOWN DETAIL NUMBER SECTION REF. SYMBOL ELEVATION REF. SYMBOL DETAIL NUMBER SHEET ON WHICH DETAIL IS SHOWN DETAIL LETTER DETAIL REF. SYMBOL 1 A-541 A A-611 2 A-601 X X XA-611 10 DETAIL IS SHOWN 2 A-601 2 A-501 DETAIL IS SHOWN SHEET ON WHICH DETAIL NUMBER BASE MATERIAL CODE XXX DOOR REF. SYMBOL DOOR NUMBER REVISION I.D. 2 SHEET ON WHICH ELEVATIONS ARE SHOWN WD-01 TARGET OR ELEVATION REF. FINISH REF. NUMBER DIAMETER or ROUND CENTER LINELC & @ #NUMBER or POUND AND AT TYPICAL NEW EXISTING TYP (N) (E) COORDINATE (TION)COORD TOP OFT.O. BOTTOM OFB.O. SIM SIMILAR APPROVEDAPPR SPECIFICATION(S) EQUALEQ PLY PLYWOOD BD BOARD GYP GYPSUM C.O.CENTER OF VERIFY IN FIELDVIF REQUIREDREQD N.I.C.NOT IN CONTRACT REFERENCE OR REFER TOREF ID IDENTIFICATION ROOMRM W/WITH OPPOSITEOPP MAX MAXIMUM MINIMUMMIN THK THICK ELV(S)ELEVATION(S) WD WOOD OFI OWNER FURNISHED ITEM UNLESS OTHERWISE NOTEDUON INTERIORINT EXT EXTERIOR GENERAL CONTRACTORGC MEP MECHANICAL ELECTRICAL PLUMBING RAD RADIUS MIDDLE (OF)MID ABBREVIATIONS PANEL JOINTPJ OFCI OWNER FURNISHED CONTRACTOR INSATALLED LOCATION UNITS (3): 261, 343, 437 UNIT TYPE NUMBER ABBREVIATION: TOTAL FLOOR LEVEL UNIT NUMBER SHEET INDEX ID-2.02 POWER & DATA PLAN ID-2.03 REFLECTED CEILING PLAN ID-5.01 INTERIOR ELEVATIONS T-01 TITLE SHEET SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-5.02 INTERIOR ELEVATIONS ID-5.03 INTERIOR ELEVATIONS ID-5.04 INTERIOR ELEVATIONS ID-5.05 INTERIOR ELEVATIONS ID-5.06 INTERIOR ELEVATIONS ID-5.07 INTERIOR ELEVATIONS ID-2.04 FLOOR FINISH PLAN ID-2.01 FLOOR PLAN ID-5.00 MATERIAL SCHEDULE ID-9.01 CASEWORK ID-9.02 CASEWORK ID-9.03 CASEWORK ID-9.04 CASEWORK ID-9.05 CASEWORK ID-9.06 CASEWORK ID-9.07 CASEWORK ID-6.02 LIGHTING SCHEDULE T-01 TITLE SHEET - -- -- -- COVERED PARKING ST A I R UP C C STORAGE RA M P U P EX I T O N L Y EX I T O N L Y SC A L E SCALE EXAM 11 EXAM 12 EXAM 13 EXAM 15 OFFICE MANAGER SURGERY SCHEDULER MEN'S RESTROOM WOMEN'S RESTROOM CONTROL ROOM PET SCANNER ROOM DEVICE CHECK STOR. / COPY / FAX ROOM NUC CAMERA 1 ME D S A M P L E S RN / NP ECHO 1 ECHO 2 ECHO 3 EXAM 1 EXAM 10EXAM 9 TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION WORK / PRINT STATION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS FAX / PRINTER FA X / PR I N T E R FAX / PRINTER EXAM 4 SINK SI N K EXIT EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE MED 8 MED 3MED 2 SINK EXAM 16 EXAM 17 EXAM 18 EXAM 14 MED 1 EX I T EXIT EXIT EXIT RR 2 STORAGE EX I T RR 1 TREADMILL 2 TREADMILL 1 EXIT MED 7 MED 6 MED 5 FA X / PR I N T E R LOCKED SHELVING OPEN SHELVING FA X / PR I N T E R 1 FA X / PR I N T E R 2 5'-6" 34" H CAB SINK SIN K TECH ROOM ST O R A G E C A B HOT LAB WAITING ROOM DRAW NUC CAM 66x85 NUC CAM 66x85NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET REF. REF. STAFF ROOM [28 SEATS] VENDING VENDING H20 CAB 18 ' - 2 " 4'- 1 0 " 13'-4"7'-7" 8' - 9 " 11 ' - 5 " 12 ' - 5 " 19'-11" 7' - 1 0 " 11 ' - 1 1 " 23'-2" 12'-9" 5' - 3 " 18 ' - 2 " 15 ' - 6 " 9'-0" 11'-6"11'-6" 11 ' - 3 " 9'- 1 " 3' - 8 " 3'- 0 " 11 ' - 1 " 8' - 6 " 6' - 0 " 11 ' - 0 " 17'-7" 8'-7"11'-7" 3'-0" 8'- 1 1 " 10'-5" 15'-2" 11 ' - 6 " 8'-0" 11 ' - 5 " 10'-0" 5' - 3 " 15'-1" 12 ' - 1 1 " 5'-10" 7'-7" 19 ' - 8 " 5'- 0 " 8'-11" 25 ' - 3 " 5'-6"8'-2" 5' - 0 " 12 ' - 3 " 7'-11" 11 ' - 0 " 5' - 0 " 5'-0" 8' - 6 " 5'-0" 8'-11" 6'-0" DOORS EQ. 4'-0" 8' - 0 " 9' - 0 " 6' - 6 " 7'-7" 2' - 0 " 8'-0"8'-0"8'-0"8'-0" 10 ' - 1 1 " 8'-2"8'-2" 9'- 0 " 14'-8" 6'-3" 8'-3" 8'-4" 8'-4"4'-5" 3'-3" 2'- 2 " 6' - 7 " 7'-3"9'-8" 4'- 6 " 9' - 3 " 9'- 3 " 9'- 3 " 13 ' - 9 " 14'-0" 7'-6" 39 ' - 1 1 " 9'- 9 " 11 ' - 5 " 8' - 9 " 8'- 1 " 8'- 0 " 5'-0" 5'-2" 7'- 4 " 8'-3"8'-3"8'-3"8'-3"8'-3"8'-3"8'-3"8'-3"8'-3" 6' - 6 " 17'-7" 3'- 0 " 3' - 0 " 7'- 0 " 5' - 0 " 12'-2"12'-2" 10 ' - 0 " 3'- 7 " 2'- 1 0 " 3'-0" 25'-7" 7'- 1 " 9'- 0 " 9'-7"28'-5" 5'-5"8'-7"2'-5"17'-7" 3'- 8 " 2'-0" 24 ' - 1 1 " 16 ' - 9 " MED 4 7'- 5 " 14 ' - 4 " 13'-7" 8'-0" 8'- 5 " 15 ' - 9 " 26'-10"13'-7" EQ. 2'-4" 1'- 2 " 1' - 2 " 8" WATER DISP. H20 CAB WATER DISP. 6' - 0 " 4' - 6 " 7' - 5 " 7'- 7 " 2'- 0 " 5'-5" 5'-0" 5'-0" 5'-0" 2'-6" 5'-0" 5'-0"5'-0" 5'-0" 5'-0" 5'-0" 5'-0" 5'-0"5'-0"5'-0"5'-0"5'-0"5'-0"5'-0"5'-0"5'-0" 5'-0" 5'-0"5'-0"5'-0"5'-0" 5'-0" 5'-0"5'-0" 5'-0" 5'-0" 5'-0" 5'-0" 5'-0" 3'-6" 2' - 6 " 2' - 6 " 4'-10" 2' - 8 " 2' - 6 " 2'- 6 " 2'- 6 " 1'-7" 5'-0" 4'-0"1'-4"3'-6" 3'-0"9"3'-0" 1'-0" 2'-0" 3'-0" 2'- 0 " 4'- 0 " 4'-0" 4'-0" 4' - 0 " 4'- 0 " 2'-0" 1 A B C D 1 BD 2 A B C D 3 A B C D 4 A B C D 5 A B C D 1 A B C D 2 A B C D 6 A B C D 3 A B C D 9 A B C 4 A B C D 5 A B C D 7 A B C D 1 A B C D 2 A B C D 1 A C D 1 A C 1 A B C 4 A B 1 A B C D 2 A B C D3 A B C D 4 A B C D 5 A B C D 2 BC 2 BC 7 A B C D 1 A B C D 1 A B C D 2 A B C D 3 A B C D 4 AB 5 A B 5 A B 1D 2 A B C D 3 A B C D 4 A B C D 6 A B C D 5 AB 6 A B C D SIM. 4 A B C D 5 A B C D 6 A B C D SIM.6 A B C D SIM.6 A B C D SIM. 7 A B C D 7 A B C D 7 A B C D8 A B C D 8 A B C D 8 A B C D 8 A B C D 9 A B C D 1 E 1 BD 3 A B C D SIM.SIM.SIM.SIM.SIM. SIM. 2 A BC 1 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 7 A B C D 8 A B C D 2 A B C D SIM. 8 A B C D SIM.8 A B C D SIM. 5 A B C D 3 A B C D 6 A B C D SIM. +34"+34"+34"+34" +34"+34"+34" +34" +34"+34"+34"+34"+34"+34" +34" +34" +34"+34" 6 ID-5.03 6 ID-5.06 6 ID-5.06 6 ID-5.03 6 ID-5.06 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-2.01 FLOOR PLAN REV - -- -- -- FLOOR PLAN SCALE:3/16"=1'-0"1 SS MESH WATER FEATURE LOCATION. CONTRACTOR TO PROVIDE 2" PVC PIPE IN WALL FOR RECIRCULATION. NOTES: 1. ALL WINDOWS MARKED "MS" TO RECIEVE MANUAL MECHO SHADE INTERIOR WINDOW TREATEMENT. TBS 2. ALL WINDOWS MARKED "WF" TO RECIEVE TRANSLUCENT PRIVACY WINDOW FILM. TBS MS MS WF (ABOVE) MS MS MS MS MS MS MS MS MS WF MSMSMS MSMS MS MS MS MS MS MS MS 1 1 PROVIDE DRAPE, CEILING MOUNTED ON WHITE HOSPITAL TRACK WITH RIPPLEFOLD HEADER AND DROP TO 12" AFF 1 1 4 4 4444 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 44 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 ST A I R UP C C STORAGE RA M P U P EX I T O N L Y EX I T O N L Y SC A L E SCALE EXAM 11 EXAM 12 EXAM 13 EXAM 15 OFFICE MANAGER SURGERY SCHEDULER MEN'S RESTROOM WOMEN'S RESTROOM CONTROL ROOM PET SCANNER ROOM DEVICE CHECK STOR. / COPY / FAX ROOM NUC CAMERA 1 ME D S A M P L E S RN / NP ECHO 1 ECHO 2 ECHO 3 EXAM 1 EXAM 10EXAM 9 TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION WORK / PRINT STATION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS FAX / PRINTER FA X / PR I N T E R FAX / PRINTER EXAM 4 SINK SI N K EXIT EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE MED 8 MED 3MED 2 SINK EXAM 16 EXAM 17 EXAM 18 EXAM 14 MED 1 EX I T EXIT EXIT EXIT RR 2 STORAGE EX I T RR 1 TREADMILL 2 TREADMILL 1 EXIT MED 7 MED 6 MED 5 FA X / PR I N T E R LOCKED SHELVING OPEN SHELVING FA X / PR I N T E R 1 FA X / PR I N T E R 2 34" H CAB SINK SIN K TECH ROOM ST O R A G E C A B HOT LAB WAITING ROOM DRAW NUC CAM 66x85 NUC CAM 66x85NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET REF. REF. STAFF ROOM [28 SEATS] VENDING VENDING H20 CAB MED 4 WATER DISP. H20 CAB WATER DISP. 1 A B C D 1 BD 2 A B C D 3 A B C D 4 A B C D 5 A B C D 1 A B C D 2 A B C D 6 A B C D 3 A B C D 9 A B C 4 A B C D 5 A B C D 7 A B C D 1 A B C D 1 A C D 1 A C 1 A B C 4 A B 1 A B C D 2 A B C D3 A B C D 4 A B C D 5 A B C D 2 BC 2 BC 7 A B C D 1 A B C D 1 A B C D 2 A B C D 3 A B C D 4 AB 5 A B 5 A B 1D 2 A B C D 3 A B C D 4 A B C D 6 A B C D 5 AB 6 A B C D SIM. 4 A B C D 5 A B C D 6 A B C D SIM.6 A B C D SIM.6 A B C D SIM. 7 A B C D 7 A B C D 7 A B C D8 A B C D 8 A B C D 8 A B C D 8 A B C D 9 A B C D 1 E 1 BD SIM.SIM.SIM.SIM.SIM.SIM. 2 A BC 1 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 7 A B C D 8 A B C D 2 A B C D SIM. 8 A B C D SIM.8 A B C D SIM. 5 A B C D 3 A B C D 6 A B C D 2 A B C D 3 A B C D SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 1044 S. Fair Oaks Avenue. , CA xxxxx The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 08-31-25 MK/JC/JFS AS NOTED JFS - 1 - -- -- -- -- ID-2.02 POWER & DATA PLAN - REV -- -- -- -- POWER & DATA PLAN SCALE:3/16"=1'-0"1 ELECTRICAL SYMBOL LEGEND DATA DATA/FAX DUPLEX RECEPTACLE OUTLET QUADRUPLEX RECEPTACLE +18" (UON) W/ DATA QUADRUPLEX RECEPTACLE +18" (UON) W/ DATA & FAX DEDICATED OUTLET FOR APPLIANCES / EQUIPMENT ABOVE FINISHED FLOOR. BELOW FINISHED FLOOR. EXPLOSION PROOF. TYPICAL UNLESS OTHERWISE NOTED. WEATHER PROOF. DUCK SMOKE DETECTOR. HAND - OFF - AUTO INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR OR ABOVE GRADE TO CENTER OF DEVICE. AFF BFC EX TYP. UON WP DSD HOA +18". NOTE 1. OUTLETS THROUGHOUT CORRIDORS AND PUBLIC SPACES TO BE PLACED PER CODE BY MEP. 2. FOR ALL MEP / POWER / DATA INFORMATION IN CONTROL ROOM, PET SCAN ROOM REFER TO ELECTRICAL DRAWINGS. 3. FOR ALL SHIELDING INFORMATION IN ALL PERTINENT AREAS REFER TO ARCH DRAWINGS 1 1 1 1 1 1 1 1 1 1 4 4 20250731 1 ST A I R UP C C STORAGE RA M P U P EX I T O N L Y EX I T O N L Y CLG. HT. 12'-0"AFF CLG. HT. 12'-0"AFF CLG. HT. 9'-6"AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF B.O. FLOATING SOFFIT 8'-9" AFF B.O. SOFFIT 9'-0" AFF B.O. SOFFIT 8'-0" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF B.O. SOFFIT 8'-0" AFF B.O. SOFFIT 8'-0" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 8'-6" AFF CLG. HT. 8'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 9'-6" AFF CLG. HT. 11'-0" AFF CLG. HT. 9'-6" AFF OFFICE MANAGER MEN'S RESTROOM WOMEN'S RESTROOM STAFF ROOM CONTROL PET SCANNER ROOM DRAW WAITING DEVICE CHECK STOR. / COPY / FAX ROOM RN / NP EXAM 9 TO EXAM ROOMS WAITING FOR 35 + 2 ADA RECEPTION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS EXAM 4 VASCULAR / PROCEDURE MED 1 RR 2 RR 1 TREADMILL 2 MED 5 F9 F12 ACT-01 CLG. HT. 9'-6" AFF SURGERY SCHEDULER CLG. HT. 14'-6"AFF PT-01 PT-01 F8 F8 F8 B.O. SOFFIT 10'-3" AFF PT-01 F5F5 F5 F5 F5 F5 F5 B.O. FLOATING SOFFIT 8'-9" AFF F3 PT-01 ACT-01 F1 ACT-01 F5 F3 F5 F3 F3 F3 F5 F3 F3 F3 F3 PT-01 PT-01 ACT-01 F3 F3 F3 ACT-01 F9 ACT-01 F5 F5 B.O. SOFFIT 8'-0" AFF ACT-01 F3 F3 ACT-01 CLG. HT. 9'-6" AFF EXAM 6 ACT-01 CLG. HT. 9'-6" AFF EXAM 7 ACT-01 CLG. HT. 9'-6" AFF EXAM 8 ACT-014 5 ° F5 F3 F3 4'- 1 " F5 F5 F5 ACT-01 2'-7" F5F5F5F5F5 F12 ACT-01 CLG. HT. 9'-6" AFF EXAM 1 ACT-01 CLG. HT. 9'-6" AFF EXAM 2 F3 ACT-01 PT-01A F10 B.O. SOFFIT 9'-0" AFF B.O. SOFFIT 8'-0" AFF PT-01 F5 F5 F3 F5 F3 F5 F5 F5F5 F5 F5 F5F5 F5 PT-01A F5F5 F5F5 F5 F5 F5 F5 F5 F5 F5 F5 F5 F5 PT-01A CLG. HT. 9'-6" AFF NOTE: RCP LAYOUT IN THESE AREAS FORTHCOMING FROM CT SCANNER VENDOR / CONSULTANT. F12 F5 CLG. HT. 9'-6" AFF PT-01A F4 ACT-01 ACT-01 STUCCO (E) CLG. HT. F10 PT-01A ACT-01 CLG. HT. 9'-6" AFF ECHO 2 ACT-01 CLG. HT. 9'-6" AFF ECHO 3 ACT-01 F8 F6 F6 F6 F6 F6 F6 F6 F6 F6 F6 F6 F8F8F8 F5F5F5 F5F5F5 F5 F5 F8 F8 F8 F13F13 F3F3 F5 F9 F5 SOFFIT HT. 9'-0" AFF IT ROOM JANITOR CLOSET ELECTRICAL / TELF ROOM F9 F1 CLG. HT. 9'-6" AFF EXAM 10 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 11 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 12 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 13 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 14 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 15 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 16 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 17 ACT-01 F1 CLG. HT. 9'-6" AFF EXAM 18 ACT-01 F1 F1 CLG. HT. 9'-6" AFF EXAM 5 F1 F1 F1 F1 F1 F1 CLG. HT. 9'-6" AFF MED 2 ACT-01 F1 CLG. HT. 9'-6" AFF MED 3 ACT-01 F1 CLG. HT. 8'-6" AFF MED 4 ACT-01 F1 F5 F10 CLG. HT. 9'-6" AFF PT-01 STORAGE F1 CLG. HT. 8'-6" AFF MED 6 ACT-01 F1 CLG. HT. 8'-6" AFF MED 7 ACT-01 F1 CLG. HT. 8'-6" AFF MED 8 ACT-01 F1 F4 CLG. HT. 9'-6" AFF TREADMILL 1 ACT-01 F3 F1 CLG. HT. 9'-6" AFF NUC CAMERA 1 ACT-01 F1 CLG. HT. 9'-6" AFF NUC CAMERA 2 ACT-01 F1 ACT-01 CLG. HT. 9'-6" AFF EXAM 3 F1 ACT-01 TECH ROOM CLG. HT. 9'-6" AFF ACT-01 F10 CLG. HT. 9'-6" AFF PT-01 F10 F10F10 CLG. HT. 9'-6" AFF PT-01 F2 F1 F2 F5 F1 F1 F1 F1 CLG. HT. 9'-6" AFF ECHO 1 ACT-01 F1 F1 F1 F1CLG. HT. 9'-6" AFF F11F11F11 ACT-01 F12 F12 F12 F12 F12 F1 CLG. HT. 9'-6" AFF HOT LAB ACT-01 F12 F3 F5 F3 F12 F3 F3F3F3F3F3F3F3 F5 F5 F3 F3 F3 F3 F3 CLG. HT. 9'-6" AFF F3 F3 F3 F3 F3 F3 F3 F5 CLG. HT. 9'-6" AFF ACT-01 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 F3 PT-01 NOTE: F12 BELOW U/ SHELF/CAB F8F8F8 F8 F8 F8 B.O. SOFFIT 9'-0" AFF F5 F12 F5 F5 MOTION ACTIVATED CLG. HT. 8'-10" AFF CLG. HT. 14'-0"AFF WC-02 FACE OF SOFFIT WC-02 F.O. SOFFIT PT-01PT-01 TYP. TYP. PT-01 PT-01 TYP. TYP. PT-01 TYP. TYP. TYP. ACT-01 TYP. ACT-01 TYP. TYP. TYP. CLG. HT. 14'-6" AFF ALL SIDES OF SOFFIT PT-01 F.O. SOFFIT PT-01 TYP. PT-01 TYP. ACT-01 TYP. ACT-01 TYP. ACT-01 TYP. ACT-01 TYP. CLG. HT. 9'-6" AFF ACT-01 TYP. F.A. SOFFIT 8'-0" AFF PT-01 NOTE: WALL HEIGHT TO MATCH WINDOW SILL PT-01 PT-01 PT-01 B.O. SOFFIT 8'-0" AFF F5 F5 F12.1 F12.1 F12 F12 F12 F12 F12 F12 F12 F12 F12 F12 F12 F12 2D A-6.1 2D A-6.1 2H A-6.1 2F A-6.1 2F A-6.1 2H A-6.1 2D A-6.1 2A A-6.1 2A A-6.1 2F A-6.1 2E A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2C A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2F A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2A A-6.1 2H A-6.1 2H1 A-6.1 2H A-6.1 2H A-6.1 2H1 A-6.1 2A A-6.1 F13 OCCURS ABOVE FLOATING SOFFIT LID M1 ID-2.03 DESK BELOW M ID-2.03 2H A-6.1 2 1 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-2.03 REFLECTED CEILING PLAN - REV -- -- -- -- REFLECTED CEILING PLAN SCALE:3/16"=1'-0"1 REFLECTED CEILING NOTES 1.LIGHT FIXTURES, CEILING FIXTURES, MECHANICAL REGISTER LOCATIONS SHOWN ON THE INTERIOR DRAWINGS SHALL TAKE PRECEDENT OVER THOSE SHOWN ON MECHANICAL OR ELECTRICAL DRAWINGS. ANY CONFLICTS TO BE BROUGHT TO THE DESIGNER'S ATTENTION FOR RESOLUTION. 2.GENERAL CONTRACTOR TO COORDINATE MECHANICAL, FIRE SPRINKLER, ELECTRICAL AND STRUCTURAL SHOP DRAWINGS AND SUBMIT FOR REVIEW NOTING ANY CONFLICTS TO INSURE COORDINATION PRIOR TO FIELD WORK. 3.EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL LIGHT FIXTURES TO BE DETERMINED IN THE FIELD. 4.LOCATIONS OF ALL ACCESS PANELS NOT PREVIOUSLY EXISTING TO BE CONFIRMED WITH THE DESIGNER PRIOR TO INSTALLATION. ACCESS PANELS TO BE PAINTED TO MATCH THE ADJACENT CEILING FINISH. 5.PROVIDE A SMOOTH, NON-ABSORBANT SURFACE IN THE RESTROOMS AS REQUIRED BY THE HEALTH DEPARTMENT. 6.COMPLETE LIGHT FIXTURE SUBMITTAL TO BE SUBMITTED TO DESIGNER INCLUDING TRIMS, SWITCHPLATE AND OUTLET COVERS. 7.IN PAINTED AND FINISHED CEILINGS, ALL LIGHT TRIMS, SPEAKERS, PANELS OR OTHER TO BE PAINTED TO MATCH THE ADJACENT SURFACE. 8.BUGEYE TYPE EMERGENCY LIGHT FIXTURES ARE NOT ACCEPTABLE IN THE PUBLIC AREAS. FULLY RECESSED EMERGENCY FIXTURE BY ISOLITE OR SIMILAR TO BE USED. 9.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AN APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 10.ALL VISIBLE WALLS AND CEILING TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 2'X2' SUSPENDED CEILING GRID SYSTEM WITH 2"X2" LAY-IN ACOUSTICAL CEILING TILES TYP. 9'-6" CLG HEIGHT U.N.O. REFLECTED CEILING HATCH LIGHTING LEGEND SEE LIGHTING SCHEDULE ID-6.02 FOR FIXTURE DETAILS. 1 1 1 4 202507314 4 5 PT-01 SCALE: 1/2"=1'-0"SOFFIT - DETAILS PT-01 B. O . S O F F I T @ 8 ' - 9 " B. O . S O F F I T @ 8 ' - 9 " PT-01 PT-01 LIGHT FIXTURE LIGHT FIXTURE MM1 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 DETAIL 1 DETAIL 2 5 5 ST A I R UP C C STORAGE EXAM 11 EXAM 12 EXAM 13 EXAM 15 OFFICE MANAGER SURGERY SCHEDULER MEN'S RESTROOM WOMEN'S RESTROOM CONTROL ROOM PET SCANNER ROOM DEVICE CHECK STOR. / COPY / FAX ROOM NUC CAMERA 1 RN / NP ECHO 1 ECHO 2 ECHO 3 EXAM 1 EXAM 10EXAM 9 TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS EXAM 4 EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE MED 8 MED 3MED 2 EXAM 16 EXAM 17 EXAM 18 EXAM 14 MED 1 RR 2 STORAGE RR 1 TREADMILL 2 TREADMILL 1 MED 7 MED 6 MED 5 TECH ROOM HOT LAB WAITING ROOM DRAW NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET STAFF ROOM [28 SEATS] MED 4 LVT-01 CT-01 CT-01 LVT-01 LVT-01 LVT-01 SV-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01LVT-01 LVT-01LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 LVT-01 C-01 VCT-01 VCT-01 LVT-02 LVT-01 ST-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 VCT-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01 SV-01SV-01 SV-01 VCT-01 SV-01 SV-01 LVT-01 SV-01 SV-01 CT-01 CT-01 SV-01 SV-01 SV-01 FLOOR STRUCTURE SCHLUTER VINPRO S 30 [COLOR TBS] ADHESIVE BY LVT MFGR SPEC LVT LVT SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-2.04 FLOOR FINISH PLAN - REV #4 -- -- -- -- FLOOR FINISH PLAN SCALE:3/16"=1'-0"1 FLOORING NOTES 1.CONFIRM LOCATIONS AND EXTENT OF ALL MATERIALS AND FINISHES WITH THE INTERIOR DESIGNER PRIOR TO FABRICATION AND INSTALLATION. 2.FIELD MEASURE FOR ALL FINISHES AND MILLWORK AND NOTIFY DESIGNER OF ANY DISCREPANCIES PRIOR TO FABRICATION. 3.SUBMIT SAMPLES OF ALL TILES TO BE USED WITH TRIM PIECES. SUPPLY 10% OVERAGE FOR ATTIC STOCK. 4.ALL STONE WORK FROM APPROVED MATERIAL SAMPLES ONLY. 5.ALL FLOORING MATERIALS TO ACHIEVE A SLIP COEFFICIENT OF 0.06 AND CONFORM WITH ACTM C 1028-96 AND ANSI A137.1 SECTION 9.6.1 WET DYNAMIC COEFFICIENT OF FRICTION (DCOF). THE TILE MUST HAVE A THRESHOLD DCOF OF .42 OR GREATER. 6.ALL STONE, TILE AND GROUT TO BE SEALED - 2 COATS WITH MANUFACTURER APPROVED SEALER. 7.ALL FLOORING TO MEET IN A SMOOTH AND LEVEL FINISH WITH NO DIFFERENCE GREATER THAN 1/4". 8.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 9.ALL GUEST ACCESSIBLE AREAS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 10.REDUCER STRIPS TO BE PROVIDED AT THRESHOLD AND TRANSITIONS AS NEEDED. METAL SCHLUTER TYPE TO BE USED. FLOOR FINISH REFERENCE FLOORING LEGEND XX-XX LVT-01 VCT-01 SV-01 L-04 CT-01 LVT-02 C-01 INSTALLATION DIRECTION- SEATING AREA INSTALLATION DIRECTION- TYPICAL ST-01 A - SCALE: NTSAFLOOR TRANSITIONAL DETAIL: LVT TO LVT NOTES FOR VINYL FLOOR INSTALLATION: [ ALWAYS ADHERE TO MANUFACTURER'S STRICT SPECIFICATIONS] 1.BEGIN WITH A CLEAN CONCRETE SURFACE, FREE FROM DEBRIS AND EXISTING FLOORING MATERIALS. 2.REMOVE ANY ADHESIVES OR CONTAMINANTS THAT MAY INTERFERE WITH INSTALLATION. 3.CHECK MOISTURE LEVELS IN THE CONCRETE USING A MOISTURE METER TO PREVENT DAMAGE TO LVT. 4.IF MOISTURE LEVELS ARE TOO HIGH, APPLY A MOISTURE BARRIER PRIOR TO INSTALLATION. 5.REPAIR ANY CRACKS OR IMPERFECTIONS IN THE CONCRETE USING A SUITABLE PATCHING COMPOUND. 6.ALLOW THE PATCHING COMPOUND TO CURE PROPERLY FOR A SMOOTH INSTALLATION SURFACE. 7.CONSIDER USING AN UNDERLAYMENT FOR ADDED SOUND ABSORPTION AND CUSHIONING. 1 1 1 1 1 1 1 4 4 20250731 5 5 5 5 A B DC TO EXAM HALLWAY A B C D TO MED HALLWAY NORTH A B C D TO MED SAMPLES HALLWAY A B C D HDRTO MED HALLWAY SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.0 MATERIAL SCHEDULE - - -- -- -- -- EXAM ROOMS- TYPICAL FINISHES SCALE: 1/4"=1'-0"B 9' - 6 " 8' - 0 " TY P . 9' - 6 " 9' - 6 " 2' - 1 0 " 9' - 0 " 3' - 6 " 9' - 6 " SCALE: 1/4"=1'-0"A 1' - 6 " TY P . 2' - 1 0 " 4' - 0 " 3' - 5 " MEDICAL OFFICES- TYPICAL FINISHES SCALE: 1/4"=1'-0"C ECHO ROOMS- TYPICAL FINISHES SCALE: 1/4"=1'-0"D SMALL RESTROOMS- TYPICAL FINISHES 8' - 0 " TY P . 9' - 6 " 1' - 6 " TY P . 3' - 6 " 9' - 0 " 2' - 5 " 9' - 6 " 2' - 5 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 1' - 6 " TY P . 1' - 6 " 8' - 0 " TY P . 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . PT-03 WB-01 TYP. PT-03PT-03 PT-06 SS-01 COUNTER & BACKSPLASH PT-02 WB-01 TYP. PT-07PT-02PT-02 PT-06 ECHO 2 ECHO 1,3 2' - 1 1 " PT-02 WB-01 TYP. 2' - 1 1 " PT-02PT-02 PT-06 WB-01 TYP. PT-02PT-02 PT-02 PT-07 PT-06 EXAM ROOMS # 1,3,5,7,9,11,13,15,17 EXAM ROOMS # 2,4,6,8,10,12,14,16,18 1' - 6 " TY P . A CHECK-IN WAITING AREA TV MAIN ENTRY DOORS B OPEN CHECK-IN WAITING AREA CHECK-OUT WAITING AREA TV TO EXAM ROOMS H20 CAB WATER DISP. C E OPEN D OPEN CHECK-IN WAITING AREA OPEN OFFICE MGR. E TO HALLWAY FAX / PRINTERCHECK-OUT WAITING AREA CHECK-OUT OPEN C OPEN D A B C D OPEN TO RR VESTIBULE OPEN B TO MEN'S RESTROOM TO LABS C D OPEN TO WOMEN'S RESTROOM OFFICE MANAGER SURGERY SCHEDULER TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION WORK / PRINT STATION CHECK OUT CHECK OUT WAITING FAX /PRINTER FA X / PR I N T E R FAX / PRINTER EXAM 4 EXIT EX I T 34" H CAB H20 CAB WATER DISP. 1 A B C D 1 BD 1 E 1 BD 1 A B C D 1 BD 1 A B C D 2 A BD 1 E 1 BD 1D1 MEN'S RESTROOM WOMEN'S RESTROOM ENTER LABS EXIT LOCKED SHELVING OPEN ELECTRICAL / TELF ROOM IT ROOM REF. REF. H20CAB WATER DISP. 2 A B C D 3 A B C D 4 A B C D 5 A B C D 5 A B C D 2 A B C D 3 A B C D 4 A B C D 5 A B C D 5 A B C D A B TO EXAM ROOM HALLWAY (N) C D D1 B TO RR VESTIBULE A INTERIOR ELEVATIONS SCALE: AS NOTED ELEVATIONS - RECEPTION, WAITING AREA, CHECK-IN/CHECK-OUT SCALE: 1/4"=1'-0"1 ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER 3' - 6 " ELEVATIONS - WOMEN'S RESTROOM SCALE: 1/4"=1'-0"2 ELEVATIONS - MEN'S RESTROOM SCALE: 1/4"=1'-0"3 ELEVATIONS - HALL & RESTROOM VESTIBULE SCALE: 1/4"=1'-0"4 9' - 6 " 12 ' - 0 " 9' - 6 " 9' - 0 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 3' - 6 " ID-5.01 INTERIOR ELEVATIONS 11-10-24 - -- -- 9' - 0 " 8' - 0 " 3' - 6 " 9' - 0 " 8' - 0 " 9' - 6 " 8' - 0 " 12 ' - 0 " 8' - 9 " 9' - 0 " 8' - 0 " 6' - 6 " 9' - 6 " 2' - 5 " 3' - 6 " 9' - 0 " 12 ' - 0 " 8' - 4 " 8' - 0 " TY P . RECEPTION/WAITING AREA -KEYPLANS SCALE: NTS 12 ' - 0 " 8' - 9 " FL O A T I N G S O F F I T 10 ' - 3 " SO F F I T 3' - 6 " 8' - 9 " FL O A T I N G S O F F I T 12 ' - 0 " RESTROOM / HALLWAY / IT ROOM - KEYPLANS 1' - 6 " TY P . 6' - 8 " 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " TY P . 14 ' - 6 " 14 ' - 6 " 10 ' - 3 " SO F F I T 8' - 0 " 6' - 6 " 14 ' - 6 " 8' - 0 " ELEVATIONS - IT ROOM SCALE: 1/4"=1'-0"5 8' - 0 " 9' - 6 " 8' - 0 " TY P . WB-01 TYP. WC-01 PT-01 TACKABLE PANEL- FAB-01 WC-01WC-01WC-01 WC-01 WC-01 WC-01 WC-01 WB-01 TYP.WB-01 TYP. WC-01 WB-01 TYP. WC-01 WB-01 TYP. PT-01 WB-01 TYP. WC-01 WC-01WC-01WB-01 TYP. PT-01 WC-01WC-01 PT-02 WB-01 TYP. WC-01 WC-01 WB-01 TYP.WB-01 TYP.WB-01 TYP.WB-01 TYP. PT-02 PT-02 PT-02 MR-01 CT-06 BASE TILE, TYP. PT-01A ALL WALLS, TYP. CT-05 SURFACEBULLNOSE CT-03 TYPICAL WALLFIELD TILE CT-04 ACCENT TILE PT-01ACT-05SURFACEBULLNOSE CT-03 TYPICAL WALLFIELD TILE CT-04 ACCENT TILE MR-01 4' - 9 " WC-01WC-01 WC-01 ALL WALLS, TYP. CT-06 BASE TILE, TYP. PT-01 PT-04 WC-01 3' - 1 0 " 3' - 2 " 2' - 0 " 9' - 0 " WALL MOUNTED SS MESH WATER FEATURE, BY OTHERWC-01 4' - 9 " SS-02 COUNTERTOP AND BACKSPLASH SS-02COUNTERTOP AND BACKSPLASH 2' - 1 0 " 2' - 5 " 40 " M A X 48 " M A X 2' - 1 0 " 2' - 5 " 40 " M A X 48 " M A X DRF-01 3-FORM- EDGE MODULAR PARTITION #200.37 IN DIMENSIONS AS SHOWN- 96" TALL FAB-01 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 5 9' - 6 " 5 PT-01 FLOATING SOFFIT 1' - 1 " WC-01 1' - 1 " 5 TYPICAL ADA SINK CLEARANCE 5 A B C D TO CHECK OUT AREAFAX/PRINTER A TO CHECK OUT AREA B C D FAX/PRINTER A B C D TO EXAM HALLWAY A B TO EXAM HALLWAY C D A B C D TO EXAM HALLWAY A B C D TO EXAM HALLWAY A B DC TO EXAM HALLWAY A B C D TO EXAM HALLWAY A B TO STOR./ COPY/ FAX ROOM C FAX / PRINTER OPEN SCALE OFFICE MANAGER SURGERY SCHEDULER DEVICE CHECK EXAM 10EXAM 9 TO EXAM ROOMS CHECK OUT FAX / PRINTER FA X / PR I N T E R PRINTER EXAM 4 EXIT 34" H CAB 1 A B C D 2 A B C D 3 A B C D 7 A B C D 8 A B C D 1 BD 1 A B C D 2 A B C D 6 A B C D 3 A B C D 7 A B C D 1 A C D D 8 A B C D STOR. / COPY / FAX ROOM EXAM 1 WAITING MEDICAL ASSISTANTS SINK SIN K EXAM 5 EXAM 6 EXAM 2 EXAM 3 FA X / PR I N T E R LOCKED SHELVING OPEN SHELVING FA X / PR I N T E R 1 FA X / PR I N T E R 2 9 A B C 5 A B C D C 6 A B C D SIM. 4 A B C D 5 A B C D 6 A B C D SIM. C 9 A B C 4 A B C D 5 A B C D C 2 BC 6 A B C D SIM. 4 A B C D 5 A B C D 6 A B C D SIM. 2 A BC C 6 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.02 INTERIOR ELEVATIONS -- -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED ELEVATIONS - SURGERY SCHEDULER SCALE: 1/4"=1'-0"1 ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER ELEVATIONS - EXAM ROOM #2-3 SCALE: 1/4"=1'-0"5 8' - 0 " 4' - 6 " 9' - 6 " 3' - 6 " 9' - 0 " 9' - 6 " 8' - 0 " ELEVATIONS - OFFICE MANAGER SCALE: 1/4"=1'-0"2 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " ELEVATIONS - EXAM ROOM #1 SCALE: 1/4"=1'-0"4ELEVATIONS - DEVICE CHECK SCALE: 1/4"=1'-0"3 ELEVATIONS - EXAM ROOMS #4-8 (TYPICAL) SCALE: 1/4"=1'-0"6 8' - 0 " 3' - 6 " 9' - 0 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " 9' - 6 " 9' - 6 " 9' - 6 " 3' - 6 " 9' - 0 " 9' - 6 " 8' - 0 " TY P . 4' - 6 " 3' - 6 " 9' - 6 " 8' - 0 " 8' - 0 " TY P . 2' - 1 0 " 2' - 0 " 3' - 2 " 8' - 0 " 4' - 6 " 3' - 6 " 9' - 6 " 2' - 1 0 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 2' - 1 0 " 2' - 1 0 " 9' - 6 " 9' - 6 " 2' - 1 0 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 9' - 6 " ELEVATIONS - EXAM ROOMS #9, 11, 13, 15 (TYPICAL) SCALE: 1/4"=1'-0"7 ELEVATIONS - EXAM ROOMS #10, 12, 14, 16-18 (TYPICAL) SCALE: 1/4"=1'-0"8 9' - 6 " 8' - 0 " TY P . 9' - 6 " 9' - 6 " 2' - 1 0 " 9' - 0 " 3' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 9' - 6 " 2' - 1 0 " 9' - 0 " 3' - 6 " 9' - 6 " 8' - 0 " S O F F I T 2' - 5 " 9' - 6 " 8' - 0 " S O F F I T 9' - 6 " 8' - 0 " 2' - 5 " 8' - 0 " S O F F I T ELEVATIONS - MEDICAL ASSISTANTS STATION INT. SCALE: 1/4"=1'-0"9 9' - 6 " 2' - 0 " 3' - 6 " 8' - 0 " TY P . 3' - 6 " 2' - 5 " 2' - 5 " 2' - 0 " 3' - 6 " 2' - 0 " 3' - 6 " 1' - 6 " SCALE: NTS SURGERY SCHEDULER/OFFICE MANAGER/ DEVICE CHECK/EXAM ROOMS- KEYPLANS SCALE: NTS EXAM ROOMS & MEDICAL ASSISTANTS STATION- KEYPLANS 4' - 0 " 3' - 5 " 1' - 6 " TY P . 2' - 1 0 " 3' - 5 " 1' - 6 " TY P . 2' - 1 0 " 4' - 0 " 3' - 5 " 1' - 6 " TY P . 1' - 6 " TY P . 2' - 1 0 " 4' - 0 " 3' - 5 " 2' - 1 0 " 4' - 0 " 3' - 5 " 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " 3' - 6 " 1' - 6 " TY P . 1' - 6 " TY P . 3' - 0 " 4' - 0 " IN C A B 1' - 6 " TY P . 2' - 1 1 " PT-03 TYP. WB-01 TYP. PT-03 TYP. PT-02 WB-01 TYP. PT-06PT-02 PT-02PT-06 PT-02 WB-01 TYP. PT-02PT-02 PT-07 PT-02 WB-01 TYP. PT-06PT-02 PT-02 PT-02 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0 TACKABLE PANEL- FAB-01 PT-03PT-03 2' - 1 1 " 2' - 1 1 " FAB-01 FAB-01 9' - 6 " OPEN OPEN A TO EXAM 4 TO CHECK OUT AREA TO EXAM 5 TO EXAM 6 TO EXAM 8TO EXAM 7 MEDICAL ASSISTANTS STATION A B COPY / FAX (IN FRONT)COPY / FAX COPY / FAX TO ELEC. TELEF. ROOM C TO EXAM 15 TO EXAM 14 TO EXAM 13 TO EXAM 12 TO EXAM 11 TO EXAM 10 TO EXAM 9TO EXAM 16TO EXAM 17TO EXAM 18 SCALE A OPEN TO EXAM 3TO EXAM 2 B OPENOPEN TO JANITOR CLOSET TO CT SCANNER HALLWAY SCALE C OPEN OPEN MEDICAL ASSISTANTS TO RESTROOM HALLWAY TO EXAM 1 TO IT ROOM SC A L E SCALE STOR. / COPY / FAX ROOM NUC CAMERA 1 EXAM 1 TO EXAM ROOMS RECEPTION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS EXAM 4 SINK SIN K EXIT EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE SINK EX I T EXIT EXIT FA X / PR I N T E R LOCKED SHELVING OPENSHELVING FA X / PR I N T E R 1 FA X / PR I N T E R 2 TECH ROOM HOT LAB WAITING ROOM DRAW NUC CAM66x85 NUC CAM66x85NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET H20CAB WATER DISP. 5 A B C D 4 A B C D 1 A C D 1 A C 1 A B C 2 BC 2 BC 1D 2 A BC 3 A B C D 1 A B C D 1 BD 4 A B C D 5 A B C D 2 A B C 6 A B C D 9 A B C 4 A B C D 5 A B C D 1 A C D 1 A C 1 A B C 1 A B C D 2 A B C D3 A B C D 4 A B C D 5 A B C D 2 BC 2 BC 5 A B 1D 6 A B C D SIM. 4 A B C D 5 A B C D 6 A B C D SIM.6 A B C D SIM.6 A B C D SIM. 9 A B C D 1 E 1 BD 2 A BC 5 A B C D 3 A B C D 6 6 6 A B C TO STOR./ COPY/ FAX ROOM D A B C D TO EXAM ROOM HALLWAY (N) C TO NURSE'S STATION COPY / FAX (IN FRONT) D D OPEN TO DEVICE CHECK B TO MED HALLWAY SOUTH SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.03 INTERIOR ELEVATIONS - - -- -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED 1 ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER ELEVATIONS - EXAM ROOM HALLWAY SOUTH SCALE: 1/4"=1'-0"4 ELEVATIONS - STOR / COPY / FAX ROOM SCALE: 1/4"=1'-0" 9' - 6 " 8' - 0 " TY P . 3' - 6 " 2' - 6 " 8' - 0 " SO F F I T 2' - 1 0 " 8' - 0 " TY P . 2' - 1 0 " 8' - 0 " SO F F I T 9' - 6 " 1 ELEVATIONS - EXAM ROOM HALLWAY SOUTH (CONT.) SCALE: 1/4"=1'-0" 8' - 0 " SO F F I T 2' - 1 0 " 8' - 0 " TY P . 9' - 6 " 8' - 0 " 9' - 6 " 2 ELEVATIONS - EXAM ROOM HALLWAY NORTH SCALE: 1/4"=1'-0" 2 ELEVATIONS - EXAM ROOM HALLWAY NORTH (CONT.) SCALE: 1/4"=1'-0" SCALE: NTS EXAM ROOM HALLWAY NORTH & SOUTH - KEYPLAN 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " TY P . 9' - 6 " 9' - 6 " 1' - 6 " TY P . 8' - 0 " TY P . 8' - 0 " TY P . 2' - 1 0 " 8' - 0 " SO F F I T 3' - 6 " 9' - 6 " 1' - 6 " TY P . 2' - 1 0 " 2' - 6 " 2' - 8 " 8' - 0 " 9' - 6 " 8' - 0 " TY P . 3' - 4 " 2' - 1 0 " 1' - 8 " 3' - 6 " 3' - 4 " 1' - 4 " TY P . 9' - 6 " 9' - 6 " 8' - 0 " ELEVATIONS - ELECTRICAL/TELF ROOM SCALE: 1/4"=1'-0"5 3 ELEVATIONS - JANITOR CLOSET SCALE: 1/4"=1'-0" 9' - 6 " 1' - 6 " TY P . 8' - 0 " TY P . 8' - 0 " TY P . 9' - 6 " 1' - 3 " TY P . PT-03WC-01 WB-01 TYP. PT-03PT-03 WB-01 TYP. PT-03 WB-01 TYP. PT-03 WB-01 TYP. WC-01PT-06 WB-01 TYP. PT-06 PT-03 WB-01 TYP. PT-02 WB-01 TYP. WB-01 TYP.WB-01 TYP. WC-01 WC-01 PT-03PT-03 PT-02PT-02PT-02PT-03 WB-01 TYP. PT-03WC-01 PT-02 WB-01 TYP. PT-02PT-02PT-02 PT-02 PT-02 WB-01 TYP. PT-02 PT-02 PT-02 55 5 5 ADA KNEE CLEARANCE @ SINK SCALE: NTS6 A TO STORAGE OPENOPEN B TO MED 4 TO MED 3 TO MED 2 TO MED 1 A B C D TO MED HALLWAY SOUTH B D TO EXAM HALLWAY NORTH A C A B TO MED 8 TO MED 7 TO MED 6 TO MED 5 TO RR2 TO EXT. OPEN A B C D TO MED HALLWAY SOUTH A B C D TO MED HALLWAY NORTH NUC CAMERA 1 ME D S A M P L E S ECHO 1 ECHO 2 ECHO 3 EXAM 7 EXAM 8 VASCULAR / PROCEDURE MED 8 MED 3MED 2 SINK EXAM 18 MED 1 EXIT EXIT RR 2 STORAGE EX I T MED 7 MED 6 MED 5 SIN K TECH ROOM 66x85NUC CAMERA 2 MED 4 1 A B C D 4 A B 6 A B C D 5 AB 9 A B C D 1 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 7 A B C D 8 A B C D 1 A B C D 1 A B C 4 A B 1 A B C D 2 B C DB 2 A B C D 3 A B C D 4 AB 6 A B C D 5 AB 6 A B C D SIM.6 A B C D SIM. 8 A B C D 9 A B C D 3 A B C D SIM. 1 A B C D SIM. 2 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 6 A B C D SIM. 7 A B C D 8 A B C D 2 A B C D SIM. 6 6 A B C D TO MED HALLWAY SOUTH A B C D HDRTO MED HALLWAY A B C D TO MED HALLWAY SOUTH SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.04 INTERIOR ELEVATIONS - - -- -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED 1 ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER ELEVATIONS - MED OFFICES HALLWAY NORTH SCALE: 1/4"=1'-0"5 2 3 SCALE: 1/4"=1'-0"8 ELEVATIONS - RESTROOM 2 SCALE: 1/4"=1'-0" ELEVATIONS - MED OFFICES #1-2 (TYP.) SCALE: 1/4"=1'-0" ELEVATIONS - MED OFFICE #3 SCALE: 1/4"=1'-0" 9' - 6 " ELEVATIONS - MED OFFICES #5-8 (TYP.) SCALE: 1/4"=1'-0"6 8' - 0 " TY P . 8' - 0 " TY P . 9' - 6 " 9' - 6 " 2' - 5 " 1' - 6 " TY P . 2' - 1 1 " TY P . 9' - 6 " 9' - 6 " 2' - 5 " SCALE: NTS MED OFFICES & HALLWAY + VASCULAR / PROCEDURE - KEYPLANS 9' - 6 " 8' - 0 " TY P . ELEVATIONS - MED OFFICES HALLWAY SOUTH SCALE: 1/4"=1'-0"4 1' - 6 " TY P . 1' - 6 " TY P . 8' - 0 " TY P . 9' - 6 " 9' - 6 " 9' - 6 " 2' - 5 " 2' - 1 1 " 3' - 6 " 2' - 5 " 2' - 5 " ELEVATIONS - STORAGE SCALE: 1/4"=1'-0"7 SCALE: 1/4"=1'-0"9 ELEVATIONS - VASCULAR / PROCEDURE 8' - 0 " TY P . 8' - 0 " TY P . 9' - 6 " 9' - 6 " 1' - 6 " TY P . 1' - 6 " TY P . 8' - 0 " TY P . 9' - 6 " 1' - 6 " TY P . 3' - 6 " 9' - 0 " 2' - 5 " 9' - 6 " 1' - 6 " 2' - 5 " 9' - 6 " 9' - 6 " 9' - 6 " EQ . EQ . EQ . EQ . EQ . 7' - 6 " TY P . 9' - 6 " 9' - 6 " 9' - 6 " 1' - 6 " TY P . 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 7' - 0 " TY P . 4' - 5 " 3' - 6 " 1' - 6 " 2' - 1 1 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 2' - 5 " 2' - 0 " 3' - 6 " 9' - 6 " 1' - 6 " TY P . 9' - 0 " PT-02 WB-01 TYP. WB-01 TYP. PT-03 WB-01 TYP. PT-03 WB-01 TYP. PT-03 WB-01 TYP. PT-07 PT-02 WB-01 TYP. PT-02PT-02PT-02 PT-02 PT-02PT-06 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0 FOR FINISHES- SEE SHEET ID-5.0FOR FINISHES- SEE SHEET ID-5.0 PT-03PT-03 PT-03 2' - 1 1 " 1' - 6 " SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 1 1' - 6 " TY P . 8' - 0 " TY P . 9' - 6 " 9' - 6 " 2' - 5 " 2' - 1 1 " 3' - 6 " ELEVATIONS - MED OFFICE #4 FOR FINISHES- SEE SHEET ID-5.0 2' - 1 1 " 9' - 6 " 8' - 0 " TY P . 8' - 0 " TY P . 9' - 6 " 9' - 6 " 2' - 1 1 " 9' - 0 " 1 1 1 A OPEN TO CT SCANNER HALLWAY WAITING AREA DRAW AREA B OPEN TO MED SAMPLES HALLWAY C TO NUC CAMERA 2 TO NUC CAMERA 1 D TO HOT LAB A B C D TO CT SCANNER HALLWAY BEFORE A TO WAITING ROOM B C D AA K-8761ESSEXFAUCETSBRASS VENDING VENDING DW OPEN OPEN OPENOPENOPEN A B C D TO PET SCANNER ROOM TO PET SCANNER HALLWAY SC A L E CONTROL ROOM PET SCANNER ROOM NUC CAMERA 1 EXAM 2 EXAM 3 TECH ROOM ST O R A G E C A B HOT LAB WAITING ROOM DRAW NUC CAM66x85 NUC CAM66x85NUC CAMERA 2IT ROOM JANITOR CLOSET REF. REF. STAFF ROOM [28 SEATS] VENDING VENDING H20 CAB WATERDISP. 1 A B C D 2 A B C D3 A B C D 4 A B C D 6 A B C D 7 A B C D 5 A B C D 5 A BD 1 A B C D 2 A B C D3 A B C D 4 A B C D B 6 A B C D 2 BC 7 A B C D 1 A C D 4 AB 5 A B 4 A B 5 A BD 5 A B C D 3 A B C D A B TO WAITING ROOM C D BRASSFAUCETSESSEXK-8761 A TO WAITING ROOM B C D B BOTTLE STORAGE TO CT SCANNER HALLWAY DC TV PLACEMENT OPEN OPEN SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.05 INTERIOR ELEVATIONS - - -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED 1 ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER ELEVATIONS - WAITING ROOM SCALE: 1/4"=1'-0"5 SCALE: 1/4"=1'-0" ELEVATIONS - TECH ROOM ELEVATIONS - CONTROL ROOM SCALE: 1/4"=1'-0"7 9' - 6 " 2 SCALE: 1/4"=1'-0" ELEVATIONS - NUC CAMERA 2 8' - 0 " TY P . 9' - 6 " 6 SCALE: 1/4"=1'-0" ELEVATIONS - STAFF ROOM 7' - 2 " 9' - 6 " 9' - 6 " 9' - 0 " SO F F I T SCALE: NTS ID 5.05 - KEYPLANS 8' - 0 " TY P . 1' - 6 " TY P . 4' - 5 " 3' - 6 " 4' - 5 " 3' - 6 " 1' - 7 " 9' - 6 " 4' - 5 " 3' - 6 " 1' - 6 " TY P . 9' - 6 " 8' - 0 " 2' - 1 1 " 9' - 6 " 4 SCALE: 1/4"=1'-0" ELEVATIONS - HOT LAB 8' - 0 " 9' - 6 " 2' - 1 0 " 8' - 0 " 9' - 6 " 2' - 1 0 " 1' - 8 " 3' - 6 " 3 SCALE: 1/4"=1'-0" ELEVATIONS - NUC CAMERA 1 8' - 0 " TY P . 9' - 6 " 1' - 6 " TY P . 3' - 4 " TY P . 9' - 6 " 7' - 1 1 " 2' - 1 1 " 3' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . 1' - 6 " TY P . 2' - 1 0 " 2' - 0 " 11 ' - 0 " 1' - 6 " TY P . 1' - 5 " TY P . 8' - 0 " TY P . 14 ' - 6 " 2' - 1 0 " 3' - 6 " 8' - 0 " TY P . 9' - 6 " 8' - 0 " 1' - 6 " 8' - 0 " TY P . 9' - 0 " SO F F I T 14 ' - 6 " 2' - 0 " 9' - 0 " SO F F I T 6' - 6 " EQUAL EQUAL 4' - 5 " 3' - 6 " WB-01 TYP. PT-02PT-02 PT-02 PT-02 WB-01 TYP. PT-02 PT-02 PT-02 PT-02 PT-02 WB-01 TYP. PT-03 PT-03 PT-03 PT-03 WB-01 TYP. PT-02 PT-02 PT-02 PT-06 WB-01 TYP. PT-02PT-02 PT-02 PT-02 PT-02 WB-01 TYP. PT-07PT-02 PT-02 PT-02 WB-01 TYP. PT-02 PT-02PT-02PT-02 3' - 6 " 4' - 0 " 3' - 6 " 3' - 4 " 2' - 1 1 " WF 5 5 NOTE: 1.FOR ALL MEP / POWER / DATA INFORMATION IN CONTROL ROOM, PET SCAN ROOM REFER TO ELECTRICAL DRAWINGS. 2.FOR ALL SHIELDING INFORMATION IN ALL PERTINENT AREAS REFER TO ARCH DRAWINGS. 5 A B C D OPEN TO RN/NP A TO STAFF LOUNGE TO CT SCANNER CONTROL ROOM TO TREADMILL 1 TO CT SCANNER ROOM A B C D TO MED SAMPLES HALLWAY A B C DABCD TO MED SAMPLES HALLWAY A OPEN OPENOPEN TO ECHO 1TO RN/NP TO ECHO 2 TO ECHO 3 B OPEN MED SAMPLES TO TECH ROOMTO EXAM ROOM HALLWAY OPEN TO DRAW AREA STORAGE CAB SC A L E NUC CAMERA 1 ME D S A M P L E S RN / NP ECHO 1 ECHO 2 ECHO 3 SIN K EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE SINK EXIT EXIT RR 2 STORAGE EX I T TREADMILL 2 EXIT SINK SIN K TECH ROOM ST O R A G E C A B HOT LAB WAITING ROOM DRAW NUC CAM66x85 NUC CAM66x85NUC CAMERA 2IT ROOM JANITOR CLOSET 1 A B C D 2 A B C D 3 A B C D 4 AB 5 A B 5 A B 2 A B C D SIM. 5 A B C D 1 A B C 4 A B 1 A B C D 2 A B C D3 A B C D 4 A B C D B 2 BC 2 BC C D 1 A B C D 2 A B C D 3 A B C D 4 AB 5 A B 5 A B 4 A C D D 5 AB 6 A B C D SIM. 4 A B C 5 A B C D 6 A B C D SIM.6 A B C D SIM.6 A B C D SIM. A A A A 9 A B C D SIM.SIM.SIM.SIM. 2 A BC D D D 7 A B C D 8 A B C D 2 A B C D SIM. 5 A B C D 3 A B C D 6 6 6 6 B OPEN OPENTO TREADMILL 2 OPEN TO DRAW AREA SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.06 INTERIOR ELEVATIONS -- -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED 1 4 2 SCALE: 1/4"=1'-0" ELEVATIONS - RN / NP STATIONS SCALE: 1/4"=1'-0" ELEVATIONS - ECHO #1-2 (TYPICAL) ELEVATIONS - PET SCANNER ROOM HALLWAY SCALE: 1/4"=1'-0"5 3 SCALE: 1/4"=1'-0" ELEVATIONS - ECHO #3 9' - 6 " 9' - 6 " 8' - 0 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " 9' - 6 " SCALE: 1/4"=1'-0" ELEVATIONS - MED SAMPLES HALLWAY 9' - 6 " 8' - 0 " 9' - 6 " ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER 8' - 0 " TY P . SCALE: NTS ID 5.06 - KEYPLANS 1' - 6 " TY P . 1' - 6 " TY P . 8' - 0 " TY P . 1' - 6 " 1' - 6 " TY P . 8' - 0 " TY P . 2' - 1 1 " 1' - 6 " TY P . 1' - 6 " TY P . 2' - 1 1 " 8' - 0 " 1' - 6 " TY P . 1' - 6 " TY P . 1' - 6 " 8' - 0 " TY P . 9' - 6 " 8' - 6 " SO F F I T 8' - 0 " TY P . 1' - 6 " TY P . 8' - 0 " ELEVATIONS - PET SCANNERS ROOM HALLWAY CONT. SCALE: 1/4"=1'-0"5 9' - 6 " 8' - 0 " TY P . 1' - 6 " TY P . 9' - 6 " 2' - 1 0 " 8' - 0 " 8' - 0 " TY P . 8' - 6 " SO F F I T 2' - 1 0 " 8' - 0 " SO F F I T 8' - 0 " SO F F I T 1' - 6 " TY P . PT-03 WB-01 TYP. FOR FINISHES- SEE SHEET ID-5.0 PT-03 PT-03 PT-03PT-03 WC-01 WB-01 TYP. PT-03 PT-07 WB-01 TYP. PT-07PT-07 PT-03WC-01 WB-01 TYP. PT-03 PT-03 WC-01 PT-02 WB-01 TYP. PT-02PT-02PT-02PT-02 PT-02 FOR FINISHES- SEE SHEET ID-5.0 5 5 ADA KNEE CLEARANCE @ SINK SCALE: NTS6 A B C TO CT SCANNER HALLWAY D PET SCANNER ROOM RN / NP RR 1 TREADMILL 2 TREADMILL 1 EXIT SINK ST O R A G E C A B DRAW NUC CAM 66x85 1 A B C D 2 A B C D 3 A B C D 4 A B C D B 1 A B C D 1 A B C D 5 A B 2 A B C D 3 A B C D 4 A B C D A 6 A B C HDR TO CT SCANNER HALLWAY D A B C D PET SCANNER TO PET SCANNER CONTROL ROOM CABINET, 14" DEEP TO HALLWAY A B C D TO CT SCANNER HALLWAY SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 09-30-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20250930REV #5 -- -- -- 5 ID-5.07 INTERIOR ELEVATIONS - - -- -- -- -- INTERIOR ELEVATIONS SCALE: AS NOTED ELEVATION NOTES 1.CONTRACTOR RESPONSIBLE TO COORDINATE THE WORK OF ALL OF THE TRADES AND NOTIFY THE DESIGNER OF ANY CONFLICTS DUE TO THE FIELD CONDITIONS. ANY DISCREPANCIES TO BE RESOLVED PRIOR TO BEGINNING THE WORK. 2.INSTALLATION OF ALL MATERIALS, CABINETRY, MILLWORK AND FINISHES TO BE FROM APPROVED SUBMITTALS ONLY. 3.CONFIRM ALL FINISHES IN THE FIELD WITH THE DESIGNER PRIOR TO INSTALLATION. 4.EXACT HEIGHT OF MIRRORS AND ARTWORK TO BE CONFIRMED WITH DESIGNER PRIOR TO INSTALLATION. 5.ALL WORK TO BE CONSTRUCTED IN ACCORDANCE WITH THE GOVERNING BUILDING CODES. 6.ALL VISIBLE WALLS, FLOORS AND CEILINGS TO RECEIVE A FINISH. CONTRACTOR TO NOTIFY DESIGNER OF ANY CONFLICT OR AREA WHERE THE FINISH MATERIAL CALL OUT IS UNCLEAR. 7.MATERIAL SUBSTITUTIONS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY SUBMITTED AND APPROVED BY DESIGNER IN ADVANCE OF THE WORK. 8.ALL INTERIOR WALLS TO BE SMOOTH, LEVEL 4 FINISH TO RECEIVE WALLCOVERING OR PAINT AS SPECIFIED. 9.LONG LEADTIME ITEMS TO BE ORDERED IN A TIMELY MANNER. DESIGNER FEES FOR RE-SELECTIONS, DUE TO DELAYED ORDERING, TO BE COVERED BY GC. 10.ALL FURNITURE SHOWN BY OWNER 2 ELEVATIONS - TREADMILL ROOM 1 SCALE: 1/4"=1'-0" SCALE: NTS ID 5.07 - KEYPLANS 3 ELEVATIONS - RESTROOM 1 SCALE: 1/4"=1'-0" 4 ELEVATIONS - TREADMILL ROOM 2 SCALE: 1/4"=1'-0" 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 8' - 0 " TY P . SCALE: 1/4"=1'-0"1 ELEVATIONS - PET SCANNER ROOM 3' - 0 " 7' - 2 " 9' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 1' - 6 " TY P . 8' - 0 " TY P . 3' - 6 " 9' - 0 " 9' - 6 " 1' - 6 " TY P . 5' - 6 " 9' - 6 " 9' - 6 " 9' - 6 " 1' - 6 " 1' - 6 " TY P . 1' - 6 " TY P . 9' - 6 " 9' - 6 " 1' - 6 " 3' - 6 " 5' - 6 " 9' - 0 " 3' - 0 " 1' - 6 " TY P . 8' - 0 " TY P . 9' - 6 " 8' - 0 " TY P . FOR FINISHES- SEE SHEET ID-5.0 PT-02 WB-01 TYP. PT-02PT-02PT-02 WB-01 TYP. PT-02PT-02 PT-02 PT-07 WB-01 TYP. PT-02 PT-02 PT-06 PT-02 3' - 0 " 4 20250731 5 NOTE: 1.FOR ALL MEP / POWER / DATA INFORMATION IN CONTROL ROOM, PET SCAN ROOM REFER TO ELECTRICAL DRAWINGS. 2.FOR ALL SHIELDING INFORMATION IN ALL PERTINENT AREAS REFER TO ARCH DRAWINGS. SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-6.02 LIGHTING SCHEDULE - - -- -- -- -- LIGHTING SCHEDULE SCALE:NTS 1 FAX / PRINTER FAX / PRINTER34" H CAB OPENOPEN FAX / PRINTER FAX / PRINTER CHECK-OUT SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.01 CASEWORK AS NOTED JFS - - -- -- -- -- RECEPTION CHECK-IN AND CHECK-OUT - PLAN WORK/PRINT STATION - ELEV. RECEPTION CHECK-IN AND CHECK-OUT - ELEV. RECEPTION CHECK-IN AND CHECK-OUT - ELEV. 1A - 1D - 1B - 1C - 1J - 1E - RECEPTION CHECK-IN AND CHECK-OUT - ELEV. 1I - RECEPTION - SECTION 4' - 0 " 6" 4' - 0 " 6" 4' - 0 " 1F - 1G - 1H - RECEPTION - SECTION 1K - WORK/PRINT STATION - SECTION 10 " 7' - 1 1 " 2' - 0 " 1' - 4 " 3' - 6 " 19'-11"4'-1" 4' - 3 " 7' - 0 " 10 " 12 ' - 1 1 " 10 " 3'-2"4'-0"6'-8" 1'-3"10" 12 ' - 0 " 3' - 6 " 2' - 5 " 2' - 1 0 " 3' - 1 1 " 3'-3"1'-8" 3'-3"1'-8" 2' - 0 " 1'-0"18'-11"3'-5" 2'-7"1'-8"6'-9"3" 3' - 6 " 2' - 5 " 1'-4"3'-4"1'-4"3'-4"1'-4"6'-8"1'-4" 1' - 0 " 2" FILLERFILLER 3' - 2 " 4" 3' - 6 " 2' - 5 " 2' - 5 " 2'-0"4"1'-9" 2'-0"4"2'-0"11"10" 2' - 5 " 2'-0" 1'-6" 3' - 6 " 5" 8" 4'-1" 2' - 3 " CL E A R MI N . 2' - 5 " 2' - 3 " CL E A R MI N . 8" 4" 3' - 6 " 8" 27 " CL E A R MI N . 27 " CL E A R MI N . +44" +29" +29" 2'-0" 2'-0"1'-8" +44" +29" 1' - 0 " O/ H A N G 8" O / H A N G 8" O/HANG 2' - 7 " 2' - 3 " CL E A R MI N . UNDERSIDE OF TOP TO BE SS CONT. LED STRIP LIGHT CONCEALED CANTILEVER BRACE UNDERSIDE OF TOP TO BE SS CONCEALED CANTILEVER BRACE CONT. LED STRIP LIGHT DESK BEYOND CONT. LED STRIP LIGHT 2' - 1 0 " 2' - 0 " 3' - 6 " 2'-4" RECEPTION - SECTIONRECEPTION - SECTION 2' - 5 " 5'-8"1'-4" SS-02 SS-02 PL-02SS-02 PL-02 PL-01 SS-02 PL-02PL-01 SS-02 PL-01 SS-02 SS-02 SS-02 SS-02 PL-02 PL-01SS-02 SS-02 SS-02 SS-02 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 SURGERY SCHEDULER FAX / PRINTER OFFICE MANAGER FA X / PR I N T E R FAX/PRINTER B C D FAX/PRINTER DEVICE CHECK D A SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.02 CASEWORK - - -- -- -- -- SURGERY SCHEDULER ROOM - ELEV. OFFICE MANAGER ROOM - PLANDEVICE CHECK ROOM - PLANSURGERY SCHEDULER ROOM - PLAN 1A - 1B - OFFICE MANAGER ROOM - ELEV. 1B - 1C - 1D - OFFICE MANAGER ROOM - ELEV. 3' - 6 " 1'-9" 2' - 0 " 2' - 5 " 3'-3"3'-3"1'-9" 1'-5"3'-4"2'-8"2'-8" 3' - 6 " 2' - 0 " 2' - 5 " 1'-0" 2' - 5 " 2'-6"2'-6"1'-4"2'-1" DEVICE CHECK ROOM - ELEV. DEVICE CHECK ROOM - SECTION 3' - 7 " 2' - 0 " 2' - 5 " 1'-5"5'-2" 3'-4"3'-4"6'-0" 12 ' - 7 " 2'-0" 2A - 2B - 8' - 0 " 3' - 7 " 2' - 0 " 2' - 5 " 1'-2" 11 ' - 5 " 8'-4"4'-11"2'-0" 6' - 4 " 5' - 2 " 2' - 0 " 10'-0" 2' - 5 " 3'-2"3'-2" 2' - 5 " 2'-0"1'-1" 1'-10"3'-6"3'-0" OFFICE MANAGER ROOM - ELEV. SURGERY SCHEDULER ROOM - SECTION 2' - 5 " 1A - OFFICE MANAGER ROOM - ELEV. 3" FILLER WIRE TRAY MODESTY PANEL 2'-6" 2'-0" 2'-0" 5'-4" 2' - 0 " 1'-10" 2' - 5 " 1'-4"3'-10" 2'-0" 2' - 5 " FILLER 2" 1E - SUPPORT LOCKABLE LATERAL FILES LOCKABLE LATERAL FILES PL-02 PL-02 PL-02 PL-02 PL-02 PL-01 PL-01 TYP. PL-02PL-01 TYP. 27 " C L R . MI N . 5 27 " C L R . MI N . 527 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 MEDICAL ASSISTANTS SINK SI N K FA X / PR I N T E R C C TO STOR./ COPY/ FAX ROOM OPEN B OPEN C FAX / PRINTER AA SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.03 CASEWORK - - - -- -- MEDICAL ASSISTANT - PLAN 1A - 1E - 1C - 1H - 1D - 1B - STATION DESK - ELEV. M.A. STATION DESK - SECTION AND ELEV. M.A. STATION DESK - ELEV. M.A. STATION DESK - ELEV.M.A. STATION DESK - SECTION 1G - 1I - 3' - 6 " 2'-10" 2' - 0 " 2'-10" 4'-5"1'-4"4'-5"1'-4"4'-0" 2'-10"2'-10"FILLER 1F - M.A. STATION DESK - ELEV. 2' - 5 " M.A. STATION DESK - SECTION 18'-7" 3' - 8 " 4' - 1 1 " 2' - 0 " 7' - 7 " 2' - 4 " 1' - 5 " 2' - 9 " 3' - 1 0 " 11 ' - 7 " 1'-6" 4'-0"1'-0" 3' - 6 " 2'-10" 2' - 0 " 2' - 5 " 3'-3" 1'-5"2'-10"1'-5"2'-10"2'-10" FILLER 4'-0" 2' - 5 " 1'-4"4'-2"1'-4"4'-2"1'-4"4'-2"1'-4"5" FILLER3' - 6 " 3' - 6 " 2' - 0 " 2' - 5 " 1'-3" 1'-4"3'-3"1'-4"3'-3"1'-4"3'-3"1'-4" 1'-5"1'-5"1'-5" SUPPORT 3' - 6 " 1'-0"1'-0" 3' - 6 " 2' - 5 " 3' - 6 " 2' - 0 " 2' - 5 " 1'-3" LED STRIP LIGHT LED STRIP LIGHT 2' - 3 " CL E A R M I N . 2' - 3 " CL E A R M I N . M.A. STATION DESK - ELEV.M.A. STATION DESK - SECTION 3' - 6 " ANGLES 4'-0" 5" 1'-0" 1'-6" 2'-4" 2' - 5 " 2' - 3 " CL E A R M I N . 3' - 6 " 5" 1'-0" 1'-6" 2' - 5 " 2'-9" 1'-0" O/HANG 5" 1' - 0 " O/ H A N G 5" 1'-7" 3' - 6 " 1J - 3" WALL BELOW 3' - 6 " 3" 1'-6" ANGLES 1'-0" 3" WALL PL-01 PL-03TYP. SS-02 PL-01 SS-02 PL-01 PL-01 PL-03TYP.PL-01TYP.TYP. TYP. 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 3' - 0 " 2'-0" 5 EXAM 1 C TO NURSE'S STATION COPY / FAX (IN FRONT) A COPY / FAX (IN FRONT) TO ELEC. TELEF. ROOM STOR. / COPY / FAX ROOM LOCKED SHELVING OPEN SHELVING FA X / PR I N T E R 1 FA X / PR I N T E R 2 B COPY / FAX COPY / FAX STORAGESI N K B A SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.04 CASEWORK - - -- -- -- -- STORAGE / COPY/ FAX ROOM - PLAN STORAGE / COPY/ FAX ROOM - SECTION STORAGE / COPY/ FAX ROOM - ELEV. 1B - 1A - STORAGE / COPY/ FAX ROOM - ELEV. 1C - TYPICAL EXAM ROOM - PLAN TYPICAL EXAM ROOM - SECTION AND ELEV. 2'-11"2'-11"2'-11" DOOR LOCKS 3'-9" 12'-8" 4" 3' - 6 " 2'-8"2'-8" 1' - 8 " 2' - 1 0 " 3'-0"3'-0" 11'-7" 2'-5" 2'-5"3'-0"3'-0"3'-0" 3'-8"9'-0" 11'-7" 2' - 0 " 1' - 8 " 2' - 1 0 " 4" 2' - 1 0 " 4" 1'-8"4'-8" 4' - 8 " 1'-8" 3A - 3B - 3' - 5 " 1' - 8 " 2' - 1 0 " 1'-2" 2'-0" FILLER STORAGE - PLAN STORAGE - SECTION AND ELEV. 2A - 2B - 2C - STORAGE - ELEV. STORAGE - ELEV. STORAGE - PLAN 3' - 7 " 7'-8" 6' - 7 " 1' - 6 " 1'-6" 8' - 1 " 8' - 1 " 8' - 1 " 3'-4" 1'-6" 1'-6" 1'-6"2'-0" 8' - 0 " 7' - 7 " 1'-6" KNAPE AND VOGT 16" HEAVY DUTY SHELF BRACKET WHITE MELAMINE SHELVING KNAPE AND VOGT 1" HEAVY DUTY WALL STANDARD PL-01SS-01 TYP. PL-01 TYP. PL-01 SS-01 3' - 0 " 2'-0" 5 1'-8" AA NUC CAMERA 1 NUC CAM 66x85 NUC CAM 66x85NUC CAMERA 2 C TECH ROOM SC A L E HOT LAB C A D BRASSFAUCETSESSEXK-8761 ME D S A M P L E S VASCULAR / PROCEDURE MED SAMPLES C SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.05 CASEWORK - - -- -- -- -- HOT LAB ROOM - PLAN NUC CAMERA ROOMS - ELEVATIONS TECH ROOM - ELEV. TECH ROOM - PLAN NUC CAMERA ROOMS - PLAN HOT LAB ROOM - SECTION AND ELEV. 2A - 2B - 1A - 3' - 4 " 2' - 0 " 2' - 5 " 14'-8" 2' - 0 " 5'-11" 1' - 1 0 " 2' - 0 " 2' - 0 " 5'-11" 5A - 5B - 5C - 3' - 6 " 1' - 8 " 2' - 1 0 " 4" 2'-1"2'-1" 1'-2"1'-10"4" 3' - 2 " 4" 3' - 2 " 1'-5"2'-8"1'-2"1'-2" 3' - 6 " 1' - 8 " 2' - 1 0 " 4" 2'-0" 2'-0" 1'-0"2'-0"2'-7" 3' - 6 " 1' - 8 " 2' - 1 0 " 1'-10" 3'-2"2'-9" 4'-5" 1'-0" 1'-0" 3' - 6 " 1' - 8 " 2' - 1 0 " 4" 2'-8"2'-8" 2'-10"2'-10" 4" 3' - 2 " 2'-0" 1'-0"1'-4" HOT LAB ROOM - SECTION AND ELEV. HOT LAB ROOM - SECTION AND ELEV. 6'-6" 2' - 0 " 6'-6" 2' - 0 " 3' - 6 " 2' - 5 " 3'-1" 2' - 0 " 1'-4"3'-8"1'-4" 3'-1" 6'-4" 3' - 6 " 2' - 5 " 3'-1" 2' - 0 " 1'-4"3'-5"1'-4" 3'-1" 6'-4" 4"4" 11"3'-0"1'-6"3'-0"1'-6"3'-0"1'-6" 4'-7" 4" 1'-4"3'-0"1'-4"3'-0"1'-4" U/ CAB LIGHTING TYP. TYPICAL DESK / CABINET DETAIL 3' - 6 " 1'-3" 2' - 5 " 2' - 0 " 2'-0" 4" 1'-4" 2' - 5 " 1" 1" 4" U/ CAB LIGHTING TYP. FILLER FILLER ADJ. SHELV ES TYP. U/ CAB LIGHTING TYP. ADJ. SHELV ES TYP. 27 " CL E A R M I N . VASCULAR / PROCEDURE ROOM - PLAN VASC. / PROCEDURE RM. - ELEV. 4'-0"1'-4" 4'-0"6'-9"3'-11" 2' - 0 " 3' - 6 " 2' - 0 " 2' - 5 " 1'-4" 2'-4"FILLER2'-4" 4 - 3A - 3B - 8' - 0 " 1'-9"3'-6"3'-6" 9'-0" 4 - 4 - MED SAMPLES - ELEV. SS-01 PL-01TYP. PL-03TYP. SS-01 PL-01TYP. PL-03TYP. SS-01 PL-01TYP. PL-03TYP. SS-01 PL-01 TYP. PL-03 TYP.PL-01 SS-01 PL-01 TYP. PL-03 TYP. 1'-6" 3'-3"5 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 27 " C L R . MI N . 5 AA K-8761ESSEXFAUCETSBRASS VENDING VENDING DW OPEN OPEN OPENOPENOPEN OPEN A CABINET, 14" DEEP PET SCANNER ROOM REF. REF. STAFF ROOM [28 SEATS] VENDING VENDING H20 CAB WATER DISP. PET SCANNER TO HALLWAY REF. SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.06 CASEWORK - - -- -- -- -- STAFF ROOM - ELEV. STAFF ROOM - PLAN STAFF ROOM - ELEV AND SECTION 1A - 1B - 1C - 2B - PET SCANNER ROOM - ELEV 2'-3" 5'-3"2'-9"2'-2"1'-6"1'-6"1'-6"1'-6" 2' - 0 " 4'-0" 3' - 8 " 4' - 2 " 3'-10"3'-10"3'-5" 16'-3" 16'-3" 2' - 1 0 " 4" 2' - 9 " 2'-7" 2'-10" 1'-1" 2'-10"6'-7" 16'-3" 1D - 1'-1" 3'-8" 1' - 2 " 5'-6" 1' - 2 " 5'-6" 2A - PET SCANNER ROOM - PLAN PET SCANNER ROOM - ELEV 1'-9" 7' - 0 " 3'-6" 1'-9" 7' - 0 " 3'-6" 7' - 0 " 1'-2" 2'-4"5'-9" 10'-4" 2'-0" 5' - 9 " 4' - 7 " 1'-10"3'-5"1'-1" 1' - 2 " 2' - 6 " 1' - 2 " 2'-3" 1'-6" 1'-1" 1' - 1 " 6' - 0 " 3' - 0 " 1'-5" 3' - 4 " 2' - 1 0 " 2' - 9 " 4" 2' - 0 " 4' - 2 " 2' - 1 0 " 2' - 9 " 4" 2' - 1 0 " 2' - 4 " 2'-0" WATER DISP. - SECTION SS-01PL-01TYP. PL-03TYP. SS-01 PL-01 PL-03TYP. PL-01 PL-01 STAFF ROOM - ELEV. 1E - 5 RN / NP SINK ST O R A G E C A B A C B ECHO 1 A TREADMILL 1 C TO CT SCANNER HALLWAY STORAGE CAB DOCTOR OFFICES 5 & 8DOCTOR OFFICES 6 & 7 B C MED 2 AB SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 12-26-25 MK/JC/JFS AS NOTED JFS 20250516BID RFI #2 1 4 - 20250731REV #4 20251226REV #5 -- -- -- 5 ID-9.07 CASEWORK - - -- -- -- -- RN / NP ROOM - ELEV. RN / NP ROOM - PLAN 1B - 1A - 1C - RN / NP ROOM - ELEV. TYP. ECHO ROOM - PLAN 3A - TYP. ECHO ROOM - PLAN TYP. TREADMILL RM - PLAN TYP. TREADMILL RM - ELEV. 1'-5" 4'-8" 14'-0" 9' - 9 " 2' - 0 " 2' - 0 " 2'-0"15'-7"5'-0" 5'-0" 2' - 0 " 2' - 5 " 1'-4"3'-7" 2' - 5 " 1'-4"3'-4"1'-4"3'-6"2'-0"2'-0" 1'-4"3'-1"3'-1"1'-4"3'-0"1'-4"2'-5"2'-0" 2'-11" 5'-6" 2'-11"1'-5" 2'-11" 3'-0" 2' - 5 " 2'-11" 3'-0" 1'-4" 2' - 5 " 2' - 5 " 3'-0"1'-4"3'-0"3'-0"1'-4" 2' - 0 " 3' - 6 " FILLER 2' - 5 " 2' - 0 " 3' - 6 " 2' - 5 " 2' - 0 " 3' - 6 " 2' - 0 " 2' - 5 " 1'-4"3'-7" 1D - 8' - 0 " 3'-7" RN / NP ROOM - ELEV. STORAGE CAB - ELEV. 5" FILLER DOCTOR OFFICES - PLAN 2' - 0 " 5'-0" 1' - 6 " 2'-10" 2' - 0 " 5'-0" 1' - 6 " 2'-10" 2' - 0 " 2C - 2A -2A - 2B - DOCTOR OFFICES - ELEV. 2'-10"2'-10" 1'-3" FILLER 3A - 1'-4" 2' - 5 " 2' - 5 " 2' - 5 " 2' - 5 " 2'-0" 1'-4" 2' - 5 " 2' - 5 " 5B - 5A - 5' - 0 " 6'-4"2'-0" 2' - 0 " 2'-6" TYP. MEDICAL ROOM TYP. MEDICAL ROOM 1'-6" LAT. FILE 2'-8" VARIES STEPPED WALL BEYOND. VERIFY DEPTH STEPPED WALL BEYOND. VERIFY DEPTH NOTE: VERIFY SPACE CONDITIONS BEFORE COMMENCING ANY WORK NOTE: VERIFY SPACE CONDITIONS BEFORE COMMENCING ANY WORK NOTE: VERIFY SPACE CONDITIONS BEFORE COMMENCING ANY WORK PL-01 PL-02 PL-01 PL-02 PL-01 PL-02 SS-01 PL-01 TYP. PL-03 TYP. SS-01 PL-01 TYP. PL-03 TYP. PL-01 1 27 " C L R . MI N . 27 " C L R . MI N . 27 " C L R . MI N . 27 " C L R . MI N . 27 " C L R . MI N . 27 " C L R . MI N . 27 " C L R . MI N . 5 5 5 5 55 5 S1 GENERAL NOTES JFA Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 ALL WORKMANSHIP, MATERIAL, AND TESTING SHALL CONFORM TO THE REQUIREMENTS OF THE 2022 CALIFORNIA BUILDING CODE. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY ALL DIMENSIONS, TO VERIFY CONDITIONS AT THE JOB SITE AND TO CROSSCHECK DETAILS AND DIMENSIONS ON THE STRUCTURAL DRAWINGS WITH RELATED REQUIREMENTS ON ALL OTHER PERTINENT DRAWINGS BEFORE PROCEEDING WITH CONSTRUCTION. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH CONSTRUCTION. WHERE CONFLICTS OCCUR BETWEEN VARIOUS ELEMENTS OF THE WORKING DRAWINGS, THE MORE STRINGENT REQUIREMENTS SHALL APPLY. DETAILS MARKED TYPICAL SHALL APPLY IN ALL CASES, UNLESS SPECIFICALLY DETAILED OTHERWISE. WHERE NO DETAIL IS SHOWN, CONSTRUCTION SHALL BE AS SHOWN FOR OTHER SIMILAR WORK. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, AND SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, TECHNIQUES, SEQUENCES AND PROCEDURES, INCLUDING BRACING, SHORING, AND LAYDOWN OF CONSTRUCTION MATERIALS, ETC. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE DESIGN AND INSTALLATION OF TEMPORARY SHORING AND BRACING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. UNLESS OTHERWISE STATED IN WRITING, SITE VISITS BY REPRESENTATIVES OF THE STRUCTURAL ENGINEER: A.DO NOT INCLUDE INSPECTION OF PROTECTIVE OR TEMPORARY CONSTRUCTION. B.ARE GENERAL IN NATURE AND ARE NOT CONTINUOUS OR DETAILED. C.DO NOT GUARANTEE CONTRACTOR'S PERFORMANCE. D SHALL NOT BE CONSTRUED AS SUPERVISION OF CONSTRUCTION. DIMENSIONS SHALL GOVERN OVER SCALES SHOWN ON DRAWINGS. PRIOR TO DRILLING FOR NEW ANCHORS OR CORING FOR NEW OPENINGS, CONTRACTOR SHALL SCAN THE EXISTING STRUCTURE TO LOCATE REBAR TO AVOID DAMAGING THE EXISTING REBAR. ALL CONDUIT, DUCTWORK, CEILING AND OTHER MISCELLANEOUS ITEMS AND THEIR SUPPORTING CONNECTIONS SHALL BE RELOCATED OR REMOVED AND RECONNECTED IN KIND AS REQUIRED TO PERFORM THE STRUCTURAL WORK. 1. 2. 3. 4. 5. 6. 7. 8. 9. GENERAL RISK CATEGORY = II IMPORTANCE FACTOR I = 1.00 MAPPED ACCELERATION PARAMETERS: SS = 1.948 S1 = 0.707 SITE CLASS = D DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS: SDS = 1.299 SD1 = 0.801 SEISMIC DESIGN CATEGORY = D 1. 2. 3. 4. 5. 6. SEISMIC DESIGN DATA BASIC WIND SPEED (3 SECOND GUST) = 110 MPH RISK CATEGORY = II WIND EXPOSURE = B 1. 2. 3. WIND DESIGN DATA ALL FOUNDATION AND SOIL WORK SHALL CONFORM TO THE GEOTECHNICAL REPORT BY BYER GEOTECHNICAL, INC. (REPORT # BG23866, DATED APRIL 17, 2024) ALL FOOTINGS SHALL BE ESTABLISHED IN ACCORDANCE WITH THE SOILS REPORT. FOUNDATION DEPTHS INDICATED ON THESE DRAWINGS REPRESENT MINIMUM STRUCTURAL REQUIREMENTS. DEEPER FOUNDATIONS MAY BE REQUIRED BY THE SOILS ENGINEER. REFER TO THE SOILS REPORT. ALL FOUNDATION BEARING AND FILL MATERIALS SHALL BE INSPECTED BY THE INSPECTOR AND CONTINUOUSLY INSPECTED AND APPROVED BY THE SOILS ENGINEER PRIOR TO PLACING CONCRETE. ALLOWABLE SOIL BEARING PRESSURE: A.ISOLATED FOOTINGS = 2,000 PSF. B.CONTINUOUS FOOTINGS = 2,000 PSF. C.CONTINUOUS FOOTING SHALL BE MINIMUM OF 12" IN WIDTH AND PAD FOOTINGS SHOULD BE A MINIMUM OF 24" SQUARE. D.THE ALLOWABLE BEARING MAY BE INCREASED BY 400 PSF FOR EACH ADDITIONAL 12" OF WIDTH OR DEPTH BEYOND THE MINIMUM UP TO MAXIMUM OF 4,000 PSF E.ONE-THIRD INCREASE IN ABOVE BEARING VALUES MAY BE USED WHEN CONSIDERING WIND OR SEISMIC LOADS. LATERAL SOIL RESISTANCE: A.COEFFICIENT OF FRICTION = 0.38. B.PASSIVE RESISTANCE = 200 PCF C.PASSIVE RESISTANCE MAY BE COMBINED WITH FRICTIONAL RESISTANCE WITH A 13 REDUCTION. AT NEW SLAB ON GRADES, CONCRETE PADS ON GRADE OR FOUNDATIONS, THE SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH RECOMMENDATIONS IN THE SOIL REPORT. AT INTERIOR SLABS ON GRADE PROVIDE 2" SAND LAYER OVER NEW 10 MIL MINIMUM VAPOR RETARDER OVER 2" SAND LAYER UNLESS NOTED OTHERWISE IN SOIL REPORT. PROVIDE MINIMUM 12" LAP BETWEEN VAPOR RETARDER JOINTS UNLESS NOTED OTHERWISE BY MANUFACTURER RECOMMENDATIONS. 1. 2. 3. 4. 5. 6. 7. 8. FOUNDATIONS CONCRETE SHALL BE AS FOLLOWS: ALL CONCRETE SHALL BE NORMAL WEIGHT CONCRETE CONFORMING TO ASTM C-33. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C-150 AND SHALL BE TESTED. ALL REINFORCING BARS, DOWELS, ANCHOR BOLTS AND OTHER INSERTS SHALL BE SECURED IN POSITION PRIOR TO PLACING OF CONCRETE. CONTINUOUS INSPECTION IS REQUIRED DURING PLACING OF CONCRETE. ALL EXISTING CONCRETE SURFACES TO RECEIVE NEW CONCRETE SHALL BE ROUGHENED TO 14" AMPLITUDE AND CLEANED PRIOR TO POURING NEW CONCRETE. PROVIDE 34" CHAMFER AT ALL EXPOSED CORNERS U.N.O. LOCATION MIN. COMPRESSIVE STRENGTH, f'c @ 28 DAYS (PSI) CEMENT TYPE AGGREGATE TYPE MAXIMUM SIZE AGGREGATE (IN.) MAXIMUM SLUMP (IN.) MAXIMUM WATER/CEMENT RATIO (w/c) FOUNDATIONS SLABS ON GRADE 1" 4"OTHER 3,000 II/V HARDROCK 0.45 0.50 4" 5" 3,000 3,000 II/V II/V HARDROCK HARDROCK 1" 112" 0.50 1. 2. 3. 4. 5. 6. 7. CONCRETE ALL REINFORCING SHALL BE PLACED AND SUPPORTED IN CONFORMANCE WITH "THE MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION" LATEST EDITION, PUBLISHED BY C.R.S.I. ALL REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A-615 GRADE 60. TIE WIRE SHALL BE 16 GAGE, FULLY ANNEALED, CONFORMING TO ASTM A-1064. ALL REINFORCING STEEL SHALL HAVE THE FOLLOWING MINIMUM CONCRETE COVERAGE, UNLESS NOTED OTHERWISE: A.CONCRETE PLACED AGAINST EARTH =3" B.CONCRETE WITH FORMED SURFACES IN CONTACT WITH EARTH =2" C.CONCRETE EXPOSED TO WEATHER, #5 BAR AND SMALLER =112" 1. 2. 3. 4. REINFORCING STEEL DRYPACK MIX SHALL BE ONE PART CEMENT AND 112 PARTS FINE AGGREGATE WITH A MINIMUM OF WATER. SIKAGROUT 212 NON-SHRINK CEMENTITIOUS GROUT SHALL BE USED WHERE "GROUT" IS SPECIFIED ON DRAWINGS. COMPLY WITH ALL PERTINENT RECOMMENDATIONS BY SIKA CORP. FOR THE USE OF SIKAGROUT 212. CONTINUOUS INSPECTION BY A REGISTERED DEPUTY INSPECTOR IS REQUIRED FOR ALL GROUTING PROCEDURES. 1. 2. 3. 4. GROUT PRODUCTS ALL CONCRETE BLOCK AND CLAY BRICK MASONRY SHALL BE REINFORCED AND OPEN CELL UNITS THAT ARE GROUTED SOLID AND CONSIST OF MATERIALS AND CONSTRUCTION AS DEFINED IN THE CALIFORNIA BUILDING CODE. CONCRETE BLOCK MASONRY SHALL BE MEDIUM WEIGHT UNITS CONFORMING TO ASTM C90 WITH MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1,900 PSI. CLAY BRICK MASONRY SHALL BE ATLAS STRUCTURAL BRICK OR APPROVED EQUAL CONFORMING TO ASTM C652 WITH MINIMUM NET AREA COMPRESSIVE STRENGTH OF 2,000 PSI. ALL MASONRY SHALL HAVE A RUNNING BOND PATTERN. OPEN END BLOCKS ARE REQUIRED THROUGHOUT. AGGREGATE SHALL CONFORM TO ASTM C144 FOR MORTAR AND ASTM C404 FOR GROUT. MORTAR SHALL BE TYPE S IN ACCORDANCE WITH WITH TABLE SC-1, TYPE M OF THE TMS 602-16 AND ACHIEVE A COMPRESSIVE STRENGTH OF 1,800 PSI. USE CALIBRATED MEASURING DEVICES. FINE GROUT AND COARSE GROUT SHALL BE IN ACCORDANCE WITH SECTION 2103A.12 OF THE CBC AND ACHIEVE A COMPRESSIVE STRENGTH OF 2,000 PSI. USE SIKA CHEMICAL CORPORATION "GROUT AID". GROUTING METHOD SHALL BE IN ACCORDANCE WITH THE CALIFORNIA CODE OF REGULATIONS AND AS FOLLOWS: A.8" BLOCK WALLS SHALL BE CONSTRUCTED USING THE "LOW-LIFT"METHOD (4'-0" MAXIMUM LIFTS, NO EXCEPTIONS). B.12" BLOCK WALLS MAY BE CONSTRUCTED USING THE "HIGH-LIFT" METHOD. PROVIDE MECHANICAL VIBRATION FOR ALL GROUT. CONTINUOUS INSPECTION BY A MASONRY INSPECTOR APPROVED BY THE BUILDING DEPARTMENT IS REQUIRED. USE FULL HEIGHT VERTICAL REINFORCING BARS WITHOUT SPLICES, UNLESS NOTED OTHERWISE. BRACE BARS PER CBC REQUIREMENTS BEFORE GROUTING. ALL BOLTS EMBEDDED IN MASONRY SHALL BE GROUTED IN PLACE WITH NOT LESS THAN 1" OF GROUT BETWEEN THE BOLT AND THE MASONRY UNIT. THE FOLLOWING HOT WEATHER REQUIREMENTS SHALL BE FOLLOWED: A.PREPARATION (PRIOR TO CONDUCTING MASONRY WORK) 1.IF AMBIENT TEMPERATURE EXCEEDS 100°F OR EXCEEDS 90°F WITH A WIND VELOCITY GREATER THAN 8 MPH, a.MAINTAIN SAND PILES IN A DAMP, COOL, LOOSE CONDITION. PROVIDE NECESSARY CONDITIONS AND EQUIPMENT TO PRODUCE MORTAR HAVING A TEMPERATURE BELOW 90°F. B.DURING CONSTRUCTION (WHILE MASONRY WORK IS IN PROGRESS) 1.IF AMBIENT TEMPERATURE EXCEEDS 100°F OR EXCEEDS 90°F WITH A WIND VELOCITY GREATER THAN 8 MPH, a.MAINTAIN TEMPERATURE OF MORTAR AND GROUT BELOW 90°F. b.FLUSH MIXER, MORTAR TRANSPORT CONTAINER, AND MORTAR BOARDS WITH COOL WATER BEFORE THEY COME INTO CONTACT WITH MORTAR INGREDIENTS OR MORTAR. c.MAINTAIN MORTAR CONSISTENCY BY RETEMPERING WITH COOL WATER.d. USE MORTAR WITHIN 2 HOURS OF INITIAL MIXING. 2.IF AMBIENT TEMPERATURE EXCEEDS 115°F OR EXCEEDS 105°F WITH A WIND VELOCITY GREATER THAN 8 MPH. IN ADDITION TO THE REQUIREMENTS ABOVE, PROVIDE THE FOLLOWING: a.USE COOL MIXING WATER FOR MORTAR AND GROUT. ICE IS PERMITTED IN MIXING WATER PRIOR TO USE. DO NOT PERMIT ICE IN MIXING WATER WHEN ADDED TO OTHER MORTAR AND GROUT.b. SHADE PUMP HOSES. C.PROTECTION (WHILE MASONRY WORK IS CURING) 1.IF AMBIENT TEMPERATURE EXCEEDS 100°F OR EXCEEDS 90°F WITH WIND VELOCITY GREATER THAN 8 MPH; THEN FOG SPRAY ALL NEW COMPLETED MASONRY WORK UNTIL DAMP AT LEAST THREE (3) TIMES A DAY UNTIL MASONRY WORK IS THREE (3) DAYS OLD. VERIFY MASONRY STRENGTH BY PRISM TEST METHOD. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. MASONRY STEEL STUDS SHALL BE IN ACCORDANCE WITH THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) SPECIFICATIONS AND ICC ESR-3064P, CONFORMING TO ASTM A653SS OR A1011SS, MINIMUM YIELD = 33.0 KSI U.N.O., AND GALVANIZED CONFORMING TO ASTM A525, G90, HAVING THE MINIMUM VALUES IN ACCORDANCE WITH THE CHART BELOW. REFER TO ARCHITECTURAL DRAWINGS FOR STUDS AND DETAILS NOT SHOWN. REFER TO ARCHITECTURAL DRAWINGS FOR INTERIOR STUD SIZES, OTHER THAN THOSE INDICATED. STUD TRACKS SHALL BE SAME GAGE AS STUDS WITH 112" FLANGES, U.N.O. STUD TO TRACK CONNECTION SHALL BE 1-#8 SCREW AT EACH FLANGE U.N.O. SCREW PENETRATION THROUGH JOINED MATERIAL SHALL NOT BE LESS THAN THREE EXPOSED THREADS. SCREWS FOR COLD-FORMED METAL FRAMING SHALL BE GALVANIZED THREAD-FORMING OR THREAD-CUTTING PAN HEAD SCREWS, WITH A SELF DRILLING POINT. SCREWS SHALL BE INSTALLED AND TIGHTENED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. SIZE DESIGNATION GAGE AREA (IN )2 Ix (IN )4 Sx (IN )3 REMARKS 4" 6" 400S162-54 600S162-54 16 16 0.443 0.556 1.098 2.860 0.549 0.953 1. 2. 3. 4. 5. 6. 7. COLD-FORMED METAL FRAMING STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE FABRICATED IN ACCORDANCE WITH THE A.I.S.C. "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS". STRUCTURAL AND MISCELLANEOUS STEEL SHALL CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS. A.WIDE FLANGES: A992 B.PLATES: A36 C.STEEL TUBES: A500, GRADE C D.STEEL PIPES: A53, GRADE B E.CHANNELS AND ANGLES: A36 TYP. BOLTS SHALL CONFORM TO ASTM A307 UNLESS NOTED OTHERWISE. SHOP DRAWINGS FOR STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE REVIEWED PRIOR TO FABRICATION. ALL WELDING SHALL CONFORM TO A.W.S. A5.1, A.W.S. D1.1 AND A.W.S. D1.8 OF THE STRUCTURAL WELDING CODE. ALL WELDING SHALL BE DONE BY AWS CERTIFIED OPERATORS QUALIFIED BY AN INSPECTOR APPROVED BY THE BUILDING DEPARTMENT FOR THE TYPE OF OPERATION INVOLVED. E-70XX ELECTRODES SHALL BE USED. SPECIAL INSPECTION IS REQUIRED FOR ALL SHOP AND FIELD WELDING BY A SPECIAL WELDING INSPECTOR APPROVED BY THE BUILDING DEPARTMENT. TYPE OF WELD (SHOP OR FIELD) SHALL BE DETERMINED BY CONTRACTOR. MINIMUM SIZE OF FILLET WELDS SHALL BE IN ACCORDANCE WITH AISC WHERE SMALLER WELDS ARE INDICATED OR WHERE NO SIZE IS INDICATED. ALL EXTERIOR OR EXPOSED STEEL SHALL CONFORM TO AISC "ARCHITECTURALLY EXPOSED STRUCTURAL STEEL" (AESS) STANDARDS AND BE HOT-DIPPED GALVANIZED U.N.O. ALL STEEL FASTENERS THAT ARE EXTERIOR OR EXPOSED OR AT EXTERIOR WALLS SHALL BE GALVANIZED OR STAINLESS STEEL U.N.O. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. STRUCTURAL STEEL LUMBER SHALL BE DOUGLAS FIR-LARCH GRADED IN ACCORDANCE WITH THE LATEST WEST COAST LUMBERMANS INSPECTION BOARD GRADING RULES. MAXIMUM MOISTURE CONTENT = 19% ALL LUMBER SHALL BE S4S AND GRADE STAMPED AS FOLLOWS, UNLESS NOTED OTHERWISE: A.JOISTS, BEAMS, POSTS, ETC.: NO.1 B.PLATES, BLOCKING, STUDS: NO.1 ALL PLYWOOD DESIGNATED ON THE STRUCTURAL DRAWINGS SHALL BE DOUGLAS FIR, CONFORMING TO THE LATEST NATIONAL BUREAU OF STANDARDS "U.S. PRODUCT STANDARD PS-1". PLYWOOD SHALL BE 5-LAYER, 5-PLY, GRADE STAMPED "STRUCTURAL I" WITH EXTERIOR GLUE AND PANEL INDEX 32/16 FOR 12" PLYWOOD UNLESS NOTED OTHERWISE. ALL WOOD CONNECTORS SHALL BE MANUFACTURED BY SIMPSON STRONG-TIE COMPANY. UNLESS OTHERWISE SHOWN, ALL NAIL HOLES IN WOOD CONNECTORS SHALL BE FILLED WITH A NAIL OF THE LARGEST SIZE RECOMMENDED BY THE MANUFACTURER. ALL WOOD IN CONTACT WITH CONCRETE WITHIN 4'-0" OF GRADE SHALL BE PRESSURE TREATED PER AWPA - U1 AND M4. NO WOOD MEMBER SHALL BE CUT, NOTCHED OR BORED, EXCEPT AS DETAILED. PLATES HAVING HOLES OR NOTCHES LARGER THAN 114" IN 2x4 OR 134" IN 2x6 AND 2x8 SHALL BE REINFORCED ON EACH SIDE WITH A 112"x18" STEEL STRAP NAILED WITH 4-16d NAILS EACH SIDE OF HOLE OR NOTCH. DOUBLE TOP PLATES IN SHEAR WALLS SHALL NOT HAVE HOLES OR NOTCHES LARGER THAN 11 4" AND SHALL BE LOCATED ON CENTERLINE PLATE. BOLT HOLES IN WOOD SHALL BE 132" TO 116" LARGER THAN THE BOLT. USE STANDARD CUT WASHERS UNDER HEAD AND NUT OF BOLTS. LAG SCREWS AND WOOD SCREWS SHALL BE SCREWED INTO PLACE (NOT DRIVEN). LEAD HOLES SHALL BE PREBORED AS FOLLOWS: A.THE LEAD HOLE FOR THE SHANK SHALL HAVE THE SAME DIAMETER AS THE SHANK AND THE SAME DEPTH AS THE LENGTH OF THE UNTHREADED SHANK. B.THE LEAD HOLE FOR THE THREADED PORTION SHALL HAVE A DIAMETER EQUAL TO 40% TO 70% OF THE SHANK DIAMETER AND A LENGTH EQUAL TO AT LEAST THE LENGTH OF THE THREADED PORTION.THE LARGER FIGURE IN EACH RANGE SHALL APPLY TO LAG SCREWS OF GREATER DIAMETERS. ALL NAILS SHALL BE COMMON WIRE NAILS. SPECIAL NAILS OF THE SAME DIAMETER AND PENETRATING INTO THE SUPPORT 12 OF THE LENGTH OF THE NAIL CALLED FOR MAY BE USED FOR "SIMPSON" METAL ACCESSORIES. WHERE NOT INDICATED, NAILING SHALL MEET THE MINIMUM NAILING REQUIREMENTS IN THE "TYPICAL NAILING SCHEDULE." WHERE NAILS CANNOT BE DRIVEN WITHOUT DANGER OF SPLITTING, SUB-DRILL NAIL HOLES HAVING A DIAMETER EQUAL TO 50% TO 75% OF THE NAIL DIAMETER. PLYWOOD EDGE NAILS SHALL HAVE A 38" MINIMUM EDGE DISTANCE. PLYWOOD NAILS SHALL BE NAILED SO THAT THE NAIL HEADS ARE FLUSH WITH THE FACE OF PLYWOOD; SINKING NAIL HEADS IS PROHIBITED. ALL STEEL ELEMENTS IN CONTACT WITH TREATED LUMBER SHALL BE GALVANIZED (G185) 1.85 OZ. OF ZINC PER SQUARE FOOT OF SURFACE AREA, OR STAINLESS STEEL. ALL STEEL FASTENERS THAT ARE EXTERIOR OR EXPOSED SHALL BE GALVANIZED OR STAINLESS STEEL U.N.O. FASTENERS USED IN EXTERIOR WALLS SHALL BE HOT-DIPPED ZINC-COATED STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER. THE COATING WEIGHTS FOR HOT-DIPPED ZINC-COATED FASTENERS SHALL BE IN ACCORDANCE WITH ASTM A153. THE COATING WEIGHTS FOR MECHANICALLY DEPOSITED ZINC COATED FASTENERS SHALL BE IN ACCORDANCE WITH ASTM B695, CLASS 55 MINIMUM. ALL EXPOSED OR EXTERIOR WOOD FRAMING SHALL BE PAINTED, NATURALLY DURABLE OR PRESSURE TREATED U.N.O. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. WOOD USE THE FOLLOWING NAILING SCHEDULE, UNLESS DETAILED OTHERWISE: CONNECTION NAILING JOIST OR RAFTERS TO SIDES OF STUDS 8-INCH JOIST OR LESS FOR EACH ADDITIONAL 4 INCHES IN DEPTH OF JOIST 1. 16d AT 16"o.c. 2-16d PER 16" BRIDGING TO JOIST, TOENAIL EACH END a.BLOCKING BETWEEN JOISTS OR RAFTERS - TO JOIST OR RAFTERS - TOENAILS EACH SIDE, EACH END b.BLOCKING BETWEEN STUDS, EACH END 2.3-8d 3-10d 2-10d TOENAILS OR 2-16d SOLE PLATE TO JOIST OR BLOCKING, TYPICAL FACE NAIL SOLE PLATE TO JOIST OR BLOCKING, AT BRACED WALL PANELS 3. 3-16d AT 2x8 STUDS 2-16d AT 2x6 STUDS 4.TOP PLATE TO STUD, END NAIL 4-8d, TOENAIL OR 3-16d, END NAIL AT 2x8 STUDS 4-8d, TOENAIL OR 2-16d, END NAIL AT 2x6 STUDS 5.STUD TO SOLE PLATE 16d AT 24"o.c.6.DOUBLE STUDS, FACE NAIL 16d AT 8"o.c.DOUBLE TOP PLATES, TYPICAL FACE NAIL U.N.O7. 3-8d8.BLOCKING BETWEEN JOISTS OR RAFTERS TO TOP PLATE, TOENAIL 8d AT 6"o.c.9.RIM JOIST TO TOP PLATE, TOENAIL 2-16d10.TOP PLATES, LAPS AND INTERSECTIONS, FACE NAIL 16d AT 16"o.c. ALONG EACH EDGE11.CONTINUOUS HEADER, TWO PIECES 12.CEILING JOISTS TO PLATE, TOENAIL 13.CONTINUOUS HEADER TO STUD, TOENAIL 14.CEILING JOISTS, LAPS OVER PARTITIONS, FACE NAIL 15.CEILING JOISTS TO PARALLEL RAFTERS, FACE NAIL 16.JOIST OR RAFTERS AT ALL BEARINGS - TOENAILS, EACH SIDE 17.1" BRACE TO EACH STUD AND PLATE, FACE NAIL 18.BUILT-UP CORNER STUDS 3-8d 4-8d 3-16d 3-16d 2-10d 2-8d 16d AT 16"o.c. 3-16d 1-16d TYPICAL NAILING SCHEDULE ALL EXPANSION ANCHORS SHALL BE KB-TZ2 CONCRETE ANCHORS MANUFACTURED BY HILTI, INC. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC ESR-4266. COMPLY WITH ALL MANUFACTURER'S RECOMMENDATIONS. CONTINUOUS INSPECTION IS REQUIRED FOR ANCHOR INSTALLATION. ALL ANCHOR EMBEDMENTS SHOWN ON THE STRUCTURAL DRAWINGS ARE NOMINAL EMBEDMENTS U.N.O. ANCHORS SHALL BE STAINLESS STEEL AT EXTERIOR OR EXPOSED FASTENERS OR AT EXTERIOR WALL. DO NOT CUT OR DAMAGE EXISTING REBAR FOR ANCHOR INSTALLATION. REBAR SHOULD BE LOCATED PRIOR TO ANCHOR INSTALLATION BY NONDESTRUCTIVE METHODS. 1. 2. 3. 4. 5. 6. 7. EXPANSION ANCHORS IN CONCRETE ALL ADHESIVE ANCHORS SHALL CONSIST OF SET-3G ADHESIVE MANUFACTURED BY SIMPSON STRONG-TIE, INC ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC ESR-4057. COMPLY WITH ALL MANUFACTURER'S RECOMMENDATIONS. CONTINUOUS INSPECTION IS REQUIRED FOR ANCHOR INSTALLATION. ANCHORS SHALL BE STAINLESS STEEL OR HOT-DIP GALVANIZED AT EXTERIOR OR EXPOSED ANCHORS OR AT EXTERIOR WALLS. DO NOT CUT OR DAMAGE EXISTING REBAR FOR ANCHOR INSTALLATION. REBAR SHOULD BE LOCATED PRIOR TO ANCHOR INSTALLATION BY NONDESTRUCTIVE METHODS. 1. 2. 3. 4. 5. 6. ADHESIVE ANCHORS IN CONCRETE GENERAL NOTES ALL ADHESIVE ANCHORS SHALL CONSIST OF HIT-HY 200 V3 ADHESIVE MANUFACTURED BY HILTI, INC. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC ESR-4378. COMPLY WITH ALL MANUFACTURER'S RECOMMENDATIONS. CONTINUOUS INSPECTION IS REQUIRED FOR ANCHOR INSTALLATION. ANCHORS SHALL BE STAINLESS STEEL OR HOT-DIP GALVANIZED AT EXTERIOR OR EXPOSED ANCHORS OR AT EXTERIOR WALLS. DO NOT CUT OR DAMAGE EXISTING REBAR FOR ANCHOR INSTALLATION. REBAR SHOULD BE LOCATED PRIOR TO ANCHOR INSTALLATION BY NONDESTRUCTIVE METHODS.TAINLESS STEEL ANCHORS AT EXPOSED AREAS. 1. 2. 3. 4. 5. 6. ADHESIVE ANCHORS IN MASONRY MED 8 MED 3MED 2 EXIT EX I T MED 7 MED 6 MED 5 MED 4 EXAM 11 EXAM 12 EXAM 13 EXAM 15 OFFICE MANAGER SURGERY SCHEDULER MEN'S RESTROOM WOMEN'S RESTROOM CONTROL ROOM PET SCANNER ROOM DEVICE CHECK STOR. / COPY / FAX ROOM NUC CAMERA 1 RN / NP ECHO 1 ECHO 2 ECHO 3 EXAM 1 EXAM 10EXAM 9 TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS EXAM 4 EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE MED 2 EXAM 16 EXAM 17 EXAM 18EXAM 14 MED 1 RR 2 STORAGE RR 1 TREADMILL 2 TREADMILL 1 MED 6 TECH ROOM HOT LAB WAITING ROOM DRAW NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET STAFF ROOM [30 SEATS] MED 4 (GARAGE) GROUND LEVEL COVERED PARKING RA M P U P 1 9 B A B A 1 9 10 S419 S4 18 S4 14 S4 15 S4 10 S419 S4 TYP. 14 S4 TYP. 17E S4 TYP. AT RESTROOM WALLS 17E S4 TYP. AT RESTROOM WALLS 17E S4 TYP. AT RESTROOM WALLS 25 S4 CONCRETE INFILL OF (E) WINDOW OPENING, SEE 22 S4 CONCRETE INFILL OF (E) WINDOW OPENING, SEE 22 S4 CONCRETE INFILL OF (E) WINDOW OPENING, SEE 22 S4 25 S4 7' - 1 12" HS S 4 x 4 x 5 16 HS S 4 x 4 x 5 16 13 S4 TYP. TYP. 13 S4 TYP. PROVIDE NEW DEPRESSED SLAB ON GRADE AT RESTROOMS PER 17 S4 NOTES: 1. 2. 3. 4. 5. 6. 7. 8. NEW HSS COLUMNS SHALL BE AT CENTERLINE WALL TYP. U.N.O. INDICATES NEW 6"x16 GAGE STEEL STUDS @ 16"o.c. PARTITION WALL TYP. U.N.O. FOR TOP OF WALL CONNECTION, SEE OR . FOR HEADER AND JAMB STUD AT INTERIOR STEEL STUD PARTITION WALL OPENINGS, SEE . SEE ARCHITECTURAL DRAWINGS AND TYPICAL DETAILS FOR INFORMATION NOT SHOWN. DEMOLISH EXISTING FOUNDATIONS AS REQUIRED FOR INSTALLATION OF NEW FOUNDATIONS U.N.O. DIMENSIONS SHOWN SHALL BE FIELD VERIFIED PRIOR TO CONSTRUCTION. REPLACEMENT OF EXISTING ROOF SHEATHING AND OUT-OF-PLANE ANCHORAGE AT TOP OF WALL OF BUILDING IS A VOLUNTARY SEISMIC RETROFIT. NEW CMU SHEAR WALLS AT PARKING GARAGE IS A VOLUNTARY SEISMIC RETROFIT. FOR CONDUITS UNDER FOUNDATION, PROVIDE CONCRETE ENCASEMENT PER FOR WALL CONDUIT PENETRATIONS SEE . 1P S5 1B S5 1G S5 TYP. U.N.O. 1Q S5 5' - 0 " 5' - 0 " HSS4x4x 3 8 HSS4x4x 1 4 HSS4x4x 3 8 19 S4 15A S4 TYP. 3' - 0 " TYP. HSS6x4x 3 8 HSS6x4x 3 8 HSS6x4x 3 8 HSS6x4x 3 8 HS S 6 x 4 x 3 8 HS S 6 x 4 x 3 8 HS S 6 x 4 x 3 8 HS S 4 x 4 x 3 8 (8) HSS ALONG THIS LINE, SEE 22 S6 2'-10"4'-0"4'-0"4'-0" 1'-4" 4'-0"4'-0"4'-0" 8 S4 TYP. U.N.O. HS S 4 x 4 x 1 4 HS S 4 x 4 x 1 4 HS S 4 x 4 x 1 4 HS S 4 x 4 x 1 4 1'-0" HSS4x4x 1 4 H S S 4 x 4 x 1 4 HSS4x4x 1 4 3'-0"6'-0"2'-0"12'-8"6'-0" 1'-112"1'-4"2'-0" 2'-4"2'-4" HS S 4 x 4 x 3 8 HSS8x4x 3 8 HS S 6 x 4 x 3 8 HS S 4 x 4 x 3 8 HSS8x4x 3 8 HS S 4 x 4 x 3 8 HS S 6 x 4 x 3 8 HS S 6 x 4 x 3 8 HSS4x4x 3 8 (11) HSS ALONG THIS LINE, SEE 22 S6 10 S4 3' - 0 " 19 S4 TYP. 10 S4 HS S 4 x 4 x 3 8 4' - 0 " 31 ' - 9 " 19 S4 TYP.15A S4 TYP.10 S4 8A S4 8A S4 4' - 0 " 15A S4 TYP. 19 S4 TYP. HSS8x4x 3 8 HS S 8 x 4 x 3 8 2'-1012" HS S 4 x 4 x 3 8HSS 4 x 4 x 3 8 22 S6 10 S4 3'-0" 22 S7 22 S7 HS S 4 x 4 x 1 4 3'-0" 22 S7 3'-0"22 S7 H S S 4 x 4 x 1 4 3'-0" 22 S7 3- 0 " HSS8x4x 3 8 23 S4 HSS 6 x 4 x 3 8 HS S 8 x 4 x 3 8 HSS 6 x 4 x 3 8 4' - 0 " 3' - 0 " 7' - 0 " 22 S6 22 S6 22 S6 5' - 0 " 19 S4 TYP. 10A S4 23 S7 TYP. 23 S7 5' - 0 " 10 S4 TYP. 13 S4 TYP.15 S4 18 S4 19 S4 TYP. TYP. TY P . TYP. (E) BRICK WALL OPENING SEE ARCH. DWGS. 4" DIA. CORE AT EACH CORNER, SAWCUT CORNER TO CORNER AND DO NOT OVERCUT, CHIP AWAY REMAINDER 3 S4 (E) FOOTING TYP. ELECTRICAL EQUIPMENT (MAX. WEIGHT 1619#) SEE FOR FLOOR MOUNTED OR FOR WALL MOUNTED 1 S9 3 S9 2 S4 CABINET, SEE 25 S9 POWER DISTRIBUTION UNIT, SEE 25 S9 CT GANTRY, SEE 25 S9 PATIENT TABLE EQUIP., SEE 25 S9 25 S4 25 S4 25 S4 25 S4 7'-0" S2 FLOOR AND FOUNDATION PLAN GS FLOOR AND FOUNDATION PLAN 11/8" = 1'-0" Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 EQUIP ROOM ROOF 1 9 B A B A 1 9 (E ) B O W E D W O O D T R U S S (E ) B O W E D W O O D T R U S S (E ) B O W E D W O O D T R U S S (E ) B O W E D W O O D T R U S S (E ) B O W E D W O O D T R U S S (E) 2x8 @ 16"o.c. (E) 2x6 @ 16"o.c. (E) 2x6 @ 16"o.c. (E) 2x12 @ 16"o.c. 21 S4 21 S4 NOTES: 1. 2. 3. INDICATES REPLACE EXISTING STRAIGHT SHEATHING WITH 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT ALL UNSUPPORTED PANEL EDGES. SISTER ALL (E) 2x MEMBERS AT PLYWOOD PANEL JOINTS PER . FOR PANEL LAYOUT SEE . CONTRACTOR TO SHORE EXISTING STRUCTURE AS REQUIRED FOR INSTALLATION OF NEW FRAMING. DO NOT REMOVE SHORING UNTIL NEW BEAMS, COLUMNS AND FOUNDATIONS HAVE BEEN INSTALLED. REPLACEMENT OF EXISTING ROOF SHEATHING AND OUT-OF-PLANE ANCHORAGE AT TOP OF WALL OF BUILDING IS A VOLUNTARY SEISMIC RETROFIT. NEW CMU SHEAR WALLS AT PARKING GARAGE IS A VOLUNTARY SEISMIC RETROFIT. 18 S8 10 S6 10 S6 10 S6 19 S6 5 S6 17 S6 17 S6 TYP. 4 S4 12 S7 11 S7 4 S4 W18x35 W1 4 x 2 2 W1 4 x 2 2 W1 4 x 2 2 W1 4 x 2 2 W1 4 x 2 2 W1 4 x 2 2 W1 4 x 2 2 HSS7x5x14 (E) 10WF21 (ABOVE) (E ) 1 0 W F 2 1 (A B O V E ) (E ) 1 0 W F 2 1 ( A B O V E ) (E ) 1 0 W F 2 1 ( A B O V E ) (E ) 1 0 W F 2 1 ( A B O V E ) (E ) 1 0 W F 2 1 ( A B O V E ) W14x22 (BELOW) W1 4 x 2 2 (B E L O W ) W1 4 x 2 2 ( B E L O W ) W1 4 x 2 2 ( B E L O W ) W1 4 x 2 2 ( B E L O W ) W1 4 x 2 2 ( B E L O W ) W8x10 18 S7 18 S7 23 S6 16 S7TYP. 21 S6 W14x22 20 S6 4 S4 21 S6 15 S6 21 S6 21 S6 31 ' - 9 " 10 S6 10 S6 4 S4 TYP. 15 S7TYP. W8x10 12 S8 14 S8 19 S7 19 S7 12 S8 AT LOW ROOF AT HIGH ROOF 20 S7 BOTH SIDES WALL 20 S7 14 S8 AT LOW ROOF AT HIGH ROOF 20 S7 17 S8 12 S8 1' - 0 " TY P . 21 S7 TYP. HSS7x5x14 5 S4 19 S8 24 S7 20 S8 17 S7 TYP. 1 1 1 1 1 1 1 1 1 1 1 1 MECH. EQPT. ( MAX. WT. = 1274#) SEE 25 S6 EXHAUST FAN ( MAX. WT. = 41#) SEE 25 S7 ROOF ACCESS, SEE 24 S4 HEAT PUMP (MAX. WT. = 72#) SEE 25 S7 MECH. EQPT. ( MAX. WT. = 1274#) SEE 25 S6 MECH. EQPT. ( MAX. WT. = 1264#) SEE 25 S6 (E) MECH. EQPT. ( MAX. WT. = 893#) REINSTALL SEE 25 S6 (E)MECH. EQPT. ( MAX. WT. = 455#) REINSTALL SEE 25 S6 (E) MECH. EQPT. ( MAX. WT. = 455#) REINSTALL SEE 25 S6 SOLAR PANELS BY OTHERS TYP. (MAX. WEIGHT = 3PSF) 1 MECH. EQPT. ( MAX. WT. = 493#) SEE 25 S6 13 S7 TYP.14 S7 TYP. (E) CONCRETE SLAB OPENING, SEE ARCH. DWGS. CORE DRILL 1" DIA. HOLE AT CORNERS PRIOR TO SAWCUTTING. SAWCUT CORNER TO CORNER. DO NOT OVERCUT. CHIP AWAY REMAINDER REMOVE (E) CONCRETE SLAB AFTER INSTALLING NEW BRICK WALL BELOW S3 ROOF FRAMING PLAN GS ROOF FRAMING PLAN 11/8" = 1'-0" Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 L4x4x14x0'-4" EACH SIDE HSS TYP. WITH 12" DIA. x6" EMBED. EPOXY ANCHORS @ 24"o.c. AND 6" FROM ENDS HSS PER PLAN WITH SHORT SIDE AGAINST WALL. HSS TO REST ON SLAB ON GRADE AND TOP OF HSS TO BE AT UNDERSIDE OF (E) LEDGER, (E) ROOF SHEATHING OR NEW STEEL BEAM (E) BRICK WALL PLAN TYP.2-48 14 SIMPSON U HGRS. TYPICAL (N) 2x FULL DEPTH JOIST (N) 2-2x FULL DEPTH JOIST OPENING SISTER (N) 2x FULL DEPTH JOIST ONE SIDE EXTENDING FULL LENGTH OF (E) JOIST TYP. WITH 2 ROWS OF #12x3" WOOD SCREWS @ 12"o.c. STAGGERED (ROWS 2" FROM TOP AND BOTTOM OF JOIST) 4' - 0 " MA X . 10d @ 2"o.c. AROUND OPENING TYP. (3) 8d EACH BOARD @ (E) DIAGONAL SHEATHING TYP. 4'-0" MAX.SIMPSON ST12 EA. CORNER 2' - 0 " MA X . 2' - 0 " MA X . SISTER (N) 2x FULL DEPTH JOIST ONE SIDE EXTENDING FULL LENGTH OF (E) JOIST TYP. 2 ROWS OF #12x3" WOOD SCREWS @ 12"o.c. STAGGERED (ROWS 2" FROM TOP AND BOTTOM OF JOIST) (E) JOIST TYP. (E) JOIST TYP. (E) JOIST TYP. 12 " TYP.516 TYP. BOTTOM OF (E) LOWER ROOF OR (E) LEDGER NEW OPENING SEE ARCH. DWGS. 4" DIA. CORE AT EACH CORNER, SAWCUT CORNER TO CORNER AND DO NOT OVERCUT, CHIP AWAY REMAINDER NE W O P E N I N G SE E A R C H . D W G S . HSS PER PLAN BEHIND WALL WITH SHORT SIDE AGAINST WALL WITH 12" DIA. x6" EMBED. WITH EPOXY ADHESIVE @ 24"o.c. AND 6" FROM ENDS. LOCATE HSS AT WALL, SEE PLAN HSS 4" WIDE, DEPTH AND THICKNESS TO MATCH VERTICAL STUDS BEHIND WALL WITH 12" DIA. x6" EMBED. WITH EPOXY ADHESIVE @ 24"o.c. AND 6" FROM ENDS c HSS PER PLAN BEHIND WALL WITH SHORT SIDE AGAINST WALL WITH 12" DIA. x6" EMBED. WITH EPOXY ADHESIVE @ 24"o.c. AND 6" FROM ENDS. LOCATE HSS AT WALL, SEE PLAN 8" CMU WITH #4V @ 16"o.c. AT WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c#4x2'-8" WITH 8" EMBEDMENT WITH EPOXY ADHESIVE @ 8"o.c. EACH FACE (E) CONCRETE SLAB 2"CLR. TYP. "H " #4x LESSER OF "W" OR 2'-6" WITH 15" EMBED. WITH EPOXY ADHESIVE @ 6"o.c. "W"(E) BRICK WALL CONCRETE INFILL WITH THICKNESS EQUAL TO EXISTING WALL THICKNESS AND #4 @ 6"o.c. EACH WAY @ CENTERLINE OF WALL #4x LESSER OF "H" OR 2'-6" WITH 15" EMBED. WITH EPOXY ADHESIVE @ 6"o.c. ELEVATION 2'-0"#4x2'-6" WITH 12" EMBED. WITH EPOXY ADHESIVE @ 12"o.c. (N) FOOTING #4x3'-0" WITH 12" EMBED. WITH EPOXY ADHESIVE @ 12"o.c. (E) FOOTING (E) SLAB ON GRADE 2'-0" (E) FOOTING (E) BRICK WALL (E) SLAB ON GRADE #4x2'-6" WITH 12" EMBED. WITH EPOXY ADHESIVE @ 12"o.c. NEW FOOTING #4x3'-0" WITH 12" EMBED. WITH EPOXY ADHESIVE @ 12"o.c. 8" CMU OR BRICK WITH #4V @ 16"o.c. AT WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c 5' - 0 " (E) SLAB ON GRADE #7 @ 8"o.c. WITH 18" EMBED. WITH EPOXY (E) CONCRETE FOOTING 3" C L R . 24 " SEE PLAN 8" CMU OR BRICK WITH #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL 3' - 0 " #4x2'-6" @ 8"o.c. WITH 12" EMBED. WITH EPOXY TYP. AROUND PERIMETER OF FOOTING #5 @ 8"o.c. (E) SLAB ON GRADE CONCRETE FOOTING WITH CONT. #4 @ 12" o.c. TOP & BOTTOM #4V @ 16"o.c. @ DETAIL 10 #4V @ 8"o.c. @ DETAIL 10A PLAN #6x3'-4" @ 8"o.c. WITH 6" EMBEDMENT WITH EPOXY (E) BRICK WALL (2) #4 REBAR WITH (2) #4x4'-6" DOWEL AT BOTTOM OF WALL WITH 18" EMBEDMENT WITH EPOXY AT DETAIL 15 AND 8" EMBED. WITH EPOXY AT DETAIL 15A 8" CMU OR BRICK WALL 8" CMU WALL WITH #4V @ 16"o.c. AT WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c PLAN #6x3'-4" @ 8"o.c. WITH 6" EMBEDMENT WITH EPOXY (E) CONCRETE COLUMN (2) #4 REBAR WITH (2) #4x4'-6" DOWEL AT BOTTOM OF WALL WITH 18" EMBEDMENT WITH EPOXY JOISTS-SEE PLAN FOR SIZE AND SPACING PLYWOOD SHEATHING TYP. 10d @ 12"o.c. AT INTERIOR OF PANEL CONTINUOUS PANEL EDGE 10d @ 2"o.c. STAGGER PLYWOOD EDGES AS SHOWN PLYWOOD PANEL SHALL BE CONT. OVER TWO SPANS AND HAVE A 4'-0" MIN. LENGTH AND A MIN. WIDTH OF 1'-4". NOTE: AT EDGES OF PANEL PROVIDE 2x4 FLAT BLOCKING AT ALL UNSUPPORTED PLYWOOD PANEL EDGES D PREFORMED PLASTIC JOINT STRIP OR SAWCUT AT NON-EXPOSED INTERIOR SLABS ON GRADE REBAR SHALL RUN THRU JOINT & HAVE A 2'-0" LAP FIRST POUR SECOND POURD/418"FOR SIZE, LOCATION AND EXTENT OF CURBS AND DEPRESSIONS SEE ARCH'L. DWGS.#3 @ 8" o.c. 1' - 6 " MI N . 1'-0" #4 CONT. 10"10"2-#4 ACONTROL JOINT BCONSTRUCTION JOINT CEDGE OF SLAB DCURBS & DEPRESSIONS (E) SLAB ON GRADE CONT. TRACK AND ANCHORAGE, PER TYP. METAL STUD DETAILS LEVEL SLOPES 2'-0" #4x2'-4" WITH 4"EMBED. WITH SIMPSON SET 3G EPOXY @ 16"o.c. SLAB ON GRADE SLOPES WHERE OCCURS FINISH FLOOR #4 CONT. (E) SLAB ON GRADE SLAB ON GRADE. SLOPES WHERE OCCURS, #4x2'-4" WITH 4" EMBED. WITH SIMPSON SET 3G EPOXY @ 16"o.c. (N) 5" CONCRETE SLAB ON GRADE WITH #4 @ 16"o.c. LONG WAY (2 BARS MIN.) JOIN FLUSH WITH (E) SLAB (E) SLAB W SAWCUT (E) SLAB (N) #4x(W-1") @ 16"o.c. WITH 4"EMBED. WITH SIMPSON SET 3G EPOXY (E) SLAB ON GRADE CONT. TRACK WITH GALVANIZED 12"DIA. A36 THREADED ROD WITH 234" EMBED. WITH SIMPSON SET 3G EPOXY @ 16"o.c. STEEL STUDS @ 16"o.c. (N) CONCRETE CURB #4 CONT. 6" FINISH FLOOR WHERE OCCURS CONSTRUCTION OR CONTROL JOINTS AT 20'-0"o.c. MAXIMUM. SLAB ON GRADE SHALL BE 5" THICK WITH #4 @ 16"o.c. EACH WAY AT SLAB U.N.O. ROUGHEN EXISTING CONCRETE SURFACES TO RECEIVE NEW CONCRETE TO 14" AMPLITUDE AND CLEAN PRIOR TO POURING NEW CONCRETE. 1. 2. 3. NOTES: c 6" (N) CONCRETE CURB (E) SLAB ON GRADE SAWCUT LEVEL SLOPES 8" 2'-0" #4 CONT. 2'-0" SLAB ON GRADE SLOPES WHERE OCCURS FINISH FLOOR WHERE OCCURS (E) CONCRETE WALL OR STEM WALL FINISH FLOOR ENEW DEPRESSED SLAB TO EXISTING SLAB GTRENCH REPAIR DETAILFNEW SLAB TO EXISTING SLAB HNEW CURB AT (E) SLAB #4x2'-4" WITH 4"EMBED. WITH SIMPSON SET 3G EPOXY @ 16"o.c. SLAB ON GRADE SLOPES WHERE OCCURS JNEW DEPRESSED SLAB TO EXISTING SLAB KNEW DEPRESSED SLAB TO EXISTING SLAB #4x2'-4" WITH 4"EMBED. WITH SIMPSON SET 3G EPOXY @ 16"o.c. 4" C L R . 516 112" TYP. 1"x12"SQ. BASE PLATE WITH (4) 1"DIA. A. BOLTS TYP. 112"GROUT #3 WITH LENGTH EQUAL TO FOOTING WIDTH -1" @ 16"o.c. AROUND PERIMETER WITH 4" EMBEDMENT WITH EPOXY ADHESIVE HEAVY SANDBLAST AT CONTACT SURFACE TYP. (E) SLAB 4" COVER TYP. 3" C L R . 1' - 0 " STEEL TUBE SEE PLAN #3 @ 16"o.c. EACH WAY 18 " @ D E T A I L 1 8 24 " @ D E T A I L 1 8 A 4'-0" SQUARE AT DETAIL 8 6'-0" SQUARE AT DETAIL 8A CONCRETE FOOTING WITH #4 @ 12"o.c. EACH WAY (N) 2x JOIST WITH DEPTH TO MATCH (E) JOIST EXTENDING FULL LENGTH OF (E) JOIST TYP. 1" 1" (E) 2x JOIST #12x3" WOOD SCREW STAGGERED @ 12"o.c. TYP. AND 6"o.c. WITHIN 24" OF END OF (N) 2x JOIST TYP. CONDITION TYP. END CONDITION 14" STIFF. PLATE EACH SIDE TYP. 112" TYP. 3"3"3" STEEL COLUMN 12" PLATE WITH (4)-58"DIA. BOLTS 316 516 516 12" PLATE WITH (2)-58"DIA. BOLTS NOTES: 1. 2. 3. 4. WHERE INTERSECTING BEAM OCCURS REPLACE STIFF. PLATE WITH FULL DEPTH CONN. PLATE. SEE BEAM CONN. DETAILS FOR CONN. PLATE REQUIREMENTS. SKEW COLUMN PLATE TO ALIGN WITH BEAM WHERE SKEWED BEAM OCCURS. SLOPE COLUMN PLATE TO MATCH BEAM WHERE SLOPED BEAM OCCURS. COLUMN CAP PLATE SHALL BE COLUMN WIDTH PLUS 34" (BEAM FLANGE WIDTH MINIMUM). TYP. CONC. FILL PLACE CONCRETE FILL AROUND SLEEVES BEFORE POURING FOOTING PAD. FILL SHALL BE SAME WIDTH AS FOOTING AND FULL WIDTH OF PIPE TRENCH. 1. NOTES: 2 1 NO EXCAVATION BELOW THIS LINE 1'-6" MIN. 2" MI N . 6" M I N . FOOTING POUR JOINT 9" 1'-6" MIN. PROVIDE METAL SLEEVE 2" GREATER THAN THE O.D. OF THE PIPE REFERENCE: TITLE 24, 1809A.142. NO PIPE SHALL PASS THROUGH THE FOOTING PAD.3. LOCATE PIPE TRENCH SO THAT FOOTING WILL NOT BE UNDERMINED.4. 4" M I N . BACKFILL EXCAVATION PER GENERAL NOTES .5. PLAN OR ELEVATION CORE DRILLED HOLE OR SLEEVE TYP. 14" DIAMETER MAXIMUM TYP. L L NOTES: 1.L = 3 TIMES THE DIAMETER OF THE LARGEST ADJACENT HOLE OR SLEEVE, 3 INCHES MINIMUM. 2.LOCATE REBAR PRIOR TO CORE DRILLING OPENING. REBAR MAY NOT BE CUT OR INTERRUPTED. 6db 45°6db 3"M I N . 3" M I N . BEAM STIRRUP COLUMN TIE db T Y P . D 1 6 BAR LAP OFFSET COLUMN TIE db TYP. 6db 3"MIN . 6"MIN. OVERLAP 30db CONCRETE (2'-0"MIN.) UNLESS NOTED OTHERWISE D=6db FOR #8 OR SMALLER BARS D=8db FOR #9 OR LARGER BARS ALTERNATE:PLACE BARS IN CONTACT AND WIRE TOGETHER. 112 db CLR.12 d b O R 90° HOOK AT ALL BENT BARS TYP. U.N.O. S4 SHEET DESCIPTION JFA 1 2 3 4 5 8 9 SECTION 10 SECTION 13 PLAN DETAIL 14 PLAN DETAIL 15 17 DETAIL 18 19 SECTION 21 ELEVATION 22 23 24 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 TYP. REBAR DETAIL TYP. CORING DETAIL FOR CONCRETE OR MASONRY WALLS TYP. PIPE TRENCH/DUCT BANK AT FTG.TYP. DETAIL DETAILTYP. DETAIL TYP. CONCRETE SLAB DETAILS TYP. PLYWOOD SHEATHING PANEL LAYOUT DETAIL 15A ELEVATION 8A TYP. LARGE ROOFING OPENING 10A PLAN DETAIL A C D E F SECTION ELEVATION NOTES: INSTALL BRIDGING @ 48"o.c. WHERE WALL FINISH DOES NOT OCCUR OR IS DISCONTINUOUS ON ONE OR BOTH SIDES OF WALL. 1. 112"x16 GAGE COLD-ROLLED CHANNEL BRIDGING THRU PRE-ALIGNED STUD PUNCHOUTS L112"x112"x16 GAGE x (STUD DEPTH - 12") WITH 2-#10 SCREWS @ EACH STUD 2-#10 SCREWS EACH ANGLE 2-#10 SCREWS @ 12"o.c. DOUBLE STUDS AND TRACK L2x2x14 GAGE x STUD SIZE MINUS 12" WITH 2-#10 SCREWS EACH LEG TRACK TYP. 1" 1" NOTES: TYPICAL BACKING FOR ANY ARCHITECTURAL ITEM ATTACHED TO WALL. 1. STEEL STUDS TYP. 6"x14 GAGE TRACK WITH 112" FLANGES CUT AND BENT AT STUDS AS SHOWN 4-#10 SCREWS EACH STUD TYP. SCREWS 80% ICC ALLOW. TENSION 80% ICC ALLOW. SHEAR 4-#10 438#1184# STEEL STUDS TYP. #10 SCREW @ 24"o.c. TYP. STEEL STUDS TYP. #10 SCREW @ 24"o.c. TYP. NOTES: WHERE OPENINGS ARE SPACED 4'-0" OR LESS FROM EACH OTHER, PROVIDE STRAPPING PER . 1. B #10 SCREW @ 16"o.c. TYP. 6 PLACES AS SHOWN CONT. STEEL STUDS SAME SIZE AS WALL STUDS, COPE FLANGES AT ENDS AND LAP WEBS WITH JAMB STUDS AND FASTEN WITH 2-#10 SCREWS EACH STUD CONCRETE SLAB 38"DIA. HILTI KH-EZ WITH 212" EMBEDMENT (ICC ESR 3027) 6" B1 B1 DOUBLE STUDS AT OPENINGS LESS THAN 8'-0" WIDE. TRIPLE STUDS AT OPENINGS 8'-0" WIDE AND GREATER CONT. TRACK L2x2x14 GAGE x STUD SIZE MINUS 12" WITH 2-#10 SCREWS EACH LEG TRACK AT NESTED STUD #10 SCREW EACH LEG @ 12"o.c. #10 SCREW @ 12"o.c. TRIPLE JAMB STUD WHERE OCCURS H NOTES: 1.WHERE TRACK IS SPLICED PROVIDE AN ANCHOR WITHIN 6" OF END OF EACH TRACK. CONT. TRACK WITH 0.157" DIA. HILTI X-U SHOTPINS @ 16"o.c. (1" EMBEDMENT) (E) SLAB ON GRADE 6"x16 GAGE 600S162-54 STEEL STUDS @ 16"o.c. WITH MAXIMUM HEIGHT OF 29'-0" G NOTES: PROVIDE STRAPS EACH FACE OF WALL.1. STUDS TYP.SILL TYP. HEADER TYP. PROVIDE PLYWOOD OR DRYWALL EDGE SCREWS TO EACH STRAP BETWEEN OPENINGS CS20 WITH (8)-#10 SCREWS EACH END TO HEADER OR SILL JAMB STUDS TYP. OPENING TYP. H J L2x2x14 GAGE x STUD SIZE MINUS 12" WITH 2-#10 SCREWS TO CEILING JOIST AND (2) #10 SCREWS TO TRACK OR 12" DIA. x318" EMBED. EPOXY ANCHOR @ 48"o.c. AT BRICK WALLS OR (3) 14x212" SDS WOOD SCREWS TO BOTTOM CHORD OF EXISTING TRUSS NOTES: TRACK SAME GAGE AS JOIST.1. CONT. TRACK WITH 2-#10 SCREWS EACH WALL STUD @ STEEL STUDS, 12" DIA. x318" EMBED. EPOXY ANCHOR @ 48"o.c. AT BRICK WALLS CEILING JOISTS, SEE SCHEDULE FOR SIZE, AND BRACE PER CEILING JOIST SPAN TABLE JOIST SPACING MAX SPAN 400S162-54 16"o.c.10'-0" 600S162-54 16"o.c.16'-0" K K JOISTCONT. 18 GAGE BLOCKING CONT. 6"x18 GAGE TRACK AT MID-SPAN WITH 2-#8 SCREWS EACH JOIST AND BLOCK WALL STUD WITH 12"DIA. x318" EMBED. EPOXY ANCHOR @ 48"o.c.WALL STUD PER PLAN (E) BRICK WALL PLAN L 2'-8" MAX. #10 @ 4"o.c. AROUND PERIMETER OF OPENING 400T150-43 FLAT TRACK BLOCKING (TYP. OF 2) #10 @ 4"o.c. AROUND PERIMETER OF OPENING DOUBLE BACK TO BACK JOIST BOTH SIDES OF OPENING WITH 2 ROWS #10 SCREWS @ 16"o.c. WITH L2x2x0'-6"x14 GAGE WITH 2-#10 SCREWS EACH LEG AT EA. END L2x2x0'-6"x14 GAGE WITH 2-#10 SCREWS EACH LEG TYP. 400T150-43 FLAT TRACK BLOCKING (TYP. OF 4) REQ'D. UNDER STRAP DOUBLE BACK TO BACK JOIST BOTH SIDE OF OPENING WITH 2 ROWS #10 SCREWS @ 16"o.c. SIMPSON S/MST27 FULLY SCREWED AT EACH CORNER OF OPENING GREATER THAN 1'-6" SQUARE (4 TOTAL PER OPENING) O P E NO P E N SMALL OPENINGLARGE OPENING M 16 GAGE CONT. TRACK STEEL STUDS 1 1 MAX. 4-#10 SHEET METAL SCREWS (E) ROOF JOIST 4-#10x3" WOOD SCREWS 4x4 BLOCKING (3 BAYS) WITH A34 EACH SIDE EACH END 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4'-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" 6"x18 GAGE x8" TRACK WITH 3-#10 SCREWS TO TRACK 4-#10x112" WOOD SCREWS BRACE PARALLEL TO (E) JOISTSBRACE PERPENDICULAR TO (E) JOISTS 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4'-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" N 6" CEILING. (E) CEILING @ +16'-0" V.I.F. MI N . 6" (E) ROOF JOIST (E) ROOF JOISTS TYP. 18 GAGE SLIPTRACK (E) ROOF 4x BLOCKING @ 48"o.c. (3 BAYS AS SHOWN) WITH 4-8d TOENAILS EACH END 1" C L R . #10x3" WOOD SCREWS AT EACH 4x BLOCKING P NOTES: 1.AS AN ALTERNATE TO THIS DETAIL, PROVIDE KICKER BRACES PER DETAIL , ORN #10x3" WOOD SCREWS AT EACH (E) ROOF JOISTS (E) ROOF (E) ROOF JOISTS 18 GAGE SLIPTRACK 1" C L R . Q NOTES: R S 1.AS AN ALTERNATE TO THIS DETAIL, PROVIDE KICKER BRACES PER DETAIL , ORNR S #10x3" WOOD SCREWS AT EACH (E) ROOF JOISTS (E) CEILING JOISTS 18 GAGE SLIPTRACK STEEL STUDS 1" C L R . R NOTES: 1.FOR BRACE TO ROOF CONNECTION SEE .N 1 1 MAX. 4-#10x112" WOOD SCREWS 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4"-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" 4-#10x3" WOOD SCREWS AT EACH BLOCKING (E) CEILING JOISTS 18 GAGE SLIPTRACK STEEL STUDS 1" C L R . S NOTES: 1.FOR BRACE TO ROOF CONNECTION SEE .N 1 1 MAX. 4-#10x3" WOOD SCREWS 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4"-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" 4x FULL-DEPTH BLOCKING @ EACH BRACE (E) CEILING JOISTS WITH NEW SISTERED JOIST PER SIM. 6"x18 GAGE MIN. STEEL STUD HANGER @ EACH (E) CEILING JOIST OR 6"x18 GAGE STEELS STUD BRACE @ 48"o.c. MAX. T NOTES: 1.FOR BRACE TO ROOF CONNECTION SEE .N 1 1 MAX. 4-#10x112" WOOD SCREWS 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4"-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" 6"x18 GAGE MIN. STEEL STUD HANGER @ 16"o.c. OR 6"x18 GAGE STEELS STUD BRACE @ 48"o.c. MAX. U NOTES: 1.FOR BRACE TO ROOF CONNECTION SEE .N 1 1 MAX. 4-#10x3" WOOD SCREWS 6"x18 GAGE ALTERNATING STEEL STUD BRACING @ 4"-0"o.c. BRACING IS NOT REQUIRED TO ALTERNATE DIRECTIONS WHERE BRACE LENGTH IS LESS THAN 6'-0" 4x FULL-DEPTH BLOCKING WITH SIMPSON A35 EACH SIDE EACH FACE @ EACH BRACE 4-#10x112" WOOD SCREWS 4-#10x112" WOOD SCREWS 13 ' - 1 " M A X . FI E L D V E R I F Y 6"x16 GAGE 600S162-54 STEEL STUDS @ 16"o.c. WITH MAXIMUM HEIGHT OF 29'-0" 6"x16 GAGE 600S162-54 STEEL STUDS @ 16"o.c. WITH MAXIMUM HEIGHT OF 29'-0" +16'-0" FIELD VERIFY 13 ' - 1 " M A X . T O R O O F S H E A T H I N G FI E L D V E R I F Y +16'-0" FIELD VERIFY 13 ' - 1 " M A X . T O R O O F S H E A T H I N G FI E L D V E R I F Y 18 S8 (E) CEILING JOISTS WITH NEW SISTERED JOIST PER SIM.18 S8 S5 SHEET DESCIPTION JFA 1 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 TYP. INTERIOR STUD DETAIL SISTER JOIST PER EACH (E) JOIST SUPPORTING MECH. EQUIPMENT 1" 1" (N) 4x6 BLOCKING WITH A34 EACH SIDE EACH END (E) 2x ROOF JOIST TYP. #12x3" WOOD SCREWS @ 12"o.c. TYP. AND 6"o.c. WITHIN 24" OF END OF (N) 2x JOIST 8" M I N . ROOF SHEATHING ROOFING LEVEL MECH. EQUIPMENT (WT . = 1274# MAX.) SIMPSON ST12 STRAP AT EACH CORNER TYP. 4x CURB WITH COUNTERSUNK 12"DIA. LAG BOLTS (3 MIN. PER SIDE, 8 MIN. TOTAL) 38"DIA .x4" LAG BOLTS (3 MIN. PER SIDE, 8 MIN. TOTAL) SIMPSON A35 AT EACH CORNER TYP. 4" T Y P . 4" M I N . SISTER JOIST TYP. WHERE EXISTING ROOF JOIST IS REQUIRED TO BE CUT TO MAKE A NEW ROOF OPENING PER 24 S4 TY P . NOTES: 1. 2. LAG SCREWS SHALL HAVE MINIMUM 2" EDGE DISTANCE AT END OF 4x. LAG SCREWS FROM EQUIPMENT SHALL HAVE MINIMUM SPACING OF 4" BETWEEN LAG BOLTS IN 4x. 9 S4 SECTION USE SAME SECTION AT SIDES AND BOTTOM OF OPENING. SIDE BARS SHALL EXTEND TO FOUNDATION AT ALL FIRST FLOOR WALLS AND SHALL BE LAPPED ACCORDING TO GENERAL NOTES SHEET S1 IN CONCRETE AND (48db IN MASONRY, 2'-0"MIN.) WITH DOWELS TO FOUNDATION AT ALL FIRST FLOOR WALL OPENINGS, U.N.O. NOTES: 1. 2. ELEVATION 8" MASONRY 90° HOOK IF EMBEDMENT NOT POSSIBLE TYP. 2-#5 TYP. U.N.O. 180° HOOK IN GROUT SPACE 3" C L R . 2' - 0 " M I N . 48 d b I N M A S O N R Y T Y P . SIMPSON MSTA49 STRAP @ 48"o.c. CENTERED ON (E) BOWED TRUSS 10d @ 2"o.c. CONT. 4x8 BLOCKING WITH SIMPSON A34 EACH SIDE @ 16"o.c. (E) BOWED TRUSS (E) ROOF JOISTS. SISTER WITH 2x8 FULL LENGTH @ 48"o.c. WITH #10x3" WOOD SCREWS @ 24"o.c. TOP AND BOTTOM 12 PLYWOOD (E) 10WF21W14x22 2-4814 14 2-48 (E) ROOF JOISTS. SISTER WITH 2x8 FULL LENGTH WITH #10x3" WOOD SCREWS @ 24"o.c. TOP AND BOTTOM 3x FULL DEPTH BLOCKING WITH #10x5" WOOD SCREW @ 3"o.c. EACH SIDE SIMPSON MSTA49 STRAP @ 48"o.c. CENTERED ON (E) ROOF JOISTS 10d @ 2"o.c. (E) BLOCKING L4x4x1 4x0'-4" EACH SIDE HSS TYP. WITH 12" DIA. 6" EMBED. EPOXY ANCHORS @ 24"o.c. AND 6" FROM ENDS HSS PER PLAN WITH LONG SIDE AGAINST WALL. HSS TO REST ON SLAB ON GRADE AND TOP OF HSS TO BE AT UNDERSIDE OF (E) LEDGER, (E) ROOF SHEATHING OR NEW STEEL BEAM (E) BRICK WALL PLAN TYP.2-48 2-48 (E) ROOF JOIST 4" 4x FULL DEPTH BLOCKING (5 BAYS) EACH SIDE @ 48"o.c. 8" CMU WITH #4V @ 16"o.c. AT WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c 4x6 FULL LENGTH OF (E) 2x6 JOISTS WITH 12" DIA. x6" EMBED. EPOXY ANCHOR @ 6"o.c. 12" PLYWOOD 10d @ 2"o.c. TO 4x BLOCKING TYP. (2) CONT. #4 SIMPSON CS14 @ 48"o.c. FOR LENGTH OF NEW 4x BLOCKING WITH 10d NAILS IN ALL NAIL HOLES IN STRAP 10d @ 2"o.c. TO LEDGER STAGGERED 10d @ 2"o.c. TO LEDGER STAGGERED 112" 112" 3" 3" 2" 3"2"12" (E) BRICK WALL STEEL BEAM 12" PLATE WITH (3) 1"DIA. A307 BOLTS 11 " 112" 112" 6"112"112" 14"x9"x12" PLATE WITH (4) 34" DIA. THRU-BOLTS WITH 4"SQ. x38" THICK PLATE WASHERS TYP. 8"x8"x1 4" BENT PLATE WITH 58" DIA. THRU-BOLTS @ 48"o.c. W14x22 14 2-48 2-48 234" (E) BRICKWALL (E) LEDGER 12" PLYWOOD 4x FULL DEPTH BLOCKING ( 5 BAYS) @ 48"o.c. (E) ROOF JOISTS SIMPSON CS14 @ 48"o.c. FOR LENGTH OF NEW 4x BLOCKING WITH 10d NAILS IN ALL NAIL HOLES IN STRAP SIMPSON HDU5 @ 48"o.c. WITH (14) 14"DIA.x212" SIMPSON SDS SCREWS 10d @ 2"o.c. (E) 3x BLOCKING (E) 2x BLOCKING WITH #10x3" WOOD SCREW @ 6"o.c. 4x6 NAILER WITH COUNTERSUNK 12"DIA. WELDED STUD NAILER @ 48"o.c. (E) ROOF JOISTS. SISTER WITH 2x8 FULL LENGTH WITH #10x3" WOOD SCREWS @ 24"o.c. TOP AND BOTTOM 12" PLYWOOD 10d @ 2"o.c. WF BEAM SIMPSON A34 @ 24"o.c. SIMPSON LTP4 @ 24"o.c. SIMPSON MSTA49 STRAP @ 48"o.c. CENTERED ON (E) ROOF JOISTS 12" PLYWOOD 10d @ 2"o.c. (E) MANSARD FRAMING 10d @ 2"o.c. PLYWOOD SHEATHING TO END ON EACH SIDE OF (E) MANSARD SILL PLATE FRAMING TO ALLOW FOR (E) MANSARD FRAMING TO REMAIN IN PLACE. 4" SQUARE x38" PLATE WASHER TYP. SIMPSON HDU8 @ 48"o.c. WITH (14) 14" DIA. x112" SIMPSON SDS SCREWS AND 34" DIA. THROUGH-BOLT SISTER (E) 2x8 RAFTER WITH NEW 2x8 FULL LENGTH @ 48"o.c. WITH #10x3" WOOD SCREW @ 24"o.c. TOP AND BOTTOM CONT. 4x10 FLAT BLOCKING (E) BRICK WALL (E) MANSARD FRAMING REMOVE AND REINSTALL FRAMING AS REQUIRED TO INSTALL NEW WORK. 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. SIMPSON CMST12 @ 48"o.c. FOR LENGTH OF NEW 4x BLOCKING WITH 10d NAILS IN ALL NAIL HOLES IN STRAP 4x FULL DEPTH BLOCKING ( 7 BAYS) AT 48"o.c. (E) MANSARD FRAMING REMOVE AND REINSTALL FRAMING AS REQUIRED TO INSTALL NEW WORK. (E) BRICK WALL 4" SQUARE x38" PLATE WASHER TYP. SIMPSON HDU8 @ 48"o.c. WITH (14) 14" DIA. x212" SIMPSON SDS SCREWS AND 34" DIA. THROUGH-BOLT 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. 10d @ 2"o.c. (E) ROOF JOISTS 10d @ 2"o.c. (E) 1" HORIZONTAL SHEATHING TO REMAIN AT THIS PORTION TO ALLOW FOR (E) MANSARD FRAMING TO REMAIN IN PLACE 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. S6 SHEET DESCIPTION JFA SECTION 5 SECTION 10 SECTION 15 SECTION 17 SECTION 19 SECTION 20 SECTION 21 PLAN DETAIL 22 SECTION 23 TYP. WALL OPENING 24 DETAIL 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 PLAN #4x2'-6" @ 16"o.c. WITH 2" EMBEDMENT WITH EPOXY (E) BRICK WALL (2) -#4 REBAR WITH 8" EMBED. WITH ADHESIVE EPOXY TO (E) CONCRETE SLAB BELOW 4"FULLY GROUTED HOLLOW CELL CLAY BRICK BLOCK WALL #4x2'-8" WITH 8" EMBEDMENT WITH EPOXY ADHESIVE @ 8"o.c. (E) CONCRETE SLAB 2"CLR. TYP. 4" FULLY GROUTED HOLLOW CELL CLAY BRICK BLOCK WALL WITH #4V @ 16"o.c. @ WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c3' - 6 " MA X . (N) 4" THICK CONCRETE TO MATCH (E) CONCRETE SLAB THICKNESS #3 @ 12"o.c. WITH 180° HOOK AROUND CONT. #4 WITH 12" EMBED. WITH EPOXY ADHESIVE 2' - 8 " 8" FULLY GROUTED HOLLOW CELL CLAY BRICK BLOCK WALL WITH #4V @ 16"o.c. @ WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c NOTES: 1.ROUGHEN EXISTING CONCRETE SURFACES TO RECEIVE NEW CONCRETE TO 14" AMPLITUDE AND CLEAN PRIOR TO POURING NEW CONCRETE. SIMPSON ST12 STRAP AT EACH CORNER TYP. 4x SHAPED CURB WITH COUNTERSUNK 12"DIA. LAG BOLTS (2 MIN. PER SIDE, 4 SIDES) SIMPSON A35 AT EACH CORNER TYP. 4" T Y P . 4" M I N . TY P . MECH. EQUIPMENT (WT. = 100# MAX.) ROOF SHEATHING ROOFING LEVEL 8" M I N . 14 " M A X . (N) 4x6 BLOCKING WITH A34 EACH SIDE EACH END SISTER AS REQUIRED WHERE OPENING PER IS REQUIRED 12"DIA.x4" LAG BOLTS (1 ANCHOR AT EACH CORNER, 4 TOTAL) 24 S4 SISTER JOIST TYP. WHERE EXISTING ROOF JOIST IS REQUIRED TO BE CUT TO MAKE A NEW ROOF OPENING PER 9 S4 (E) 2x JOIST TYP. NOTES: 1. 2. LAG SCREWS SHALL HAVE MINIMUM 2" EDGE DISTANCE AT END OF 4x. LAG SCREWS FROM EQUIPMENT SHALL HAVE MINIMUM SPACING OF 4" BETWEEN LAG BOLTS IN 4x. (E) ROOF JOISTS (E) 3x BLOCKING (E) 2x BLOCKING WITH #10x3" WOOD SCREW @ 6"o.c. 4x6 NAILER WITH COUNTERSUNK 12"DIA. WELDED STUD NAILER @ 48"o.c. (E) ROOF JOISTS (E) DIAGONAL SHEATHING WF BEAM SIMPSON A34 @ 24"o.c. SIMPSON LTP4 @ 24"o.c. (E) DIAGONAL SHEATHING 8" CMU WITH #4V @ 8"o.c. AT WALL AND #4H @ 16"o.c. WITH 180° HOOK AT ENDS OF WALL c #4x2'-6" @ 8"o.c. WITH 16"EMBEDMENT WITH EPOXY (E) BRICK WALL1 12"2" c FOR BOLTS SEE 1 12" 3" 3" 4"12"MAX. FOR PLATE SEE 4 SIDES 516 NOTES: 1.BENT CONNECTION PLATE WHERE BEAMS ARE SKEWED. TY P . TY P . 15 S7 15 S7 12 " 2" C L R . 3" C L R . (E) ASPHALT OR SIDE WALK (E) FOOTING (E) SLAB ON GRADE WHERE OCCURS (E) BRICK MASONRY WALL #4 @ 12"o.c. WITH 4" EMBED. WITH SIMPSON SET-3G EPOXY ICC-ESR-4057 TYP. NOTES: 1.ROUGHEN EXISTING CONCRETE SURFACES TO RECEIVE NEW CONCRETE TO 14" AMPLITUDE AND CLEAN PRIOR TO POURING NEW CONCRETE. 1'-6"1'-6" MI N . TY P . CONCRETE FOOTING EACH SIDE EXISTING FOOTING WITH OVERALL WIDTH CENTERED ON POST AND (9) CONT. #4 AS SHOWN HSS POST TYP. WITH 14" CAP PLATE SHAPED TO MATCH HSS TOP AND BOTTOM WITH BUTT WELD ALL AROUND TYP. (E) ROOF JOISTS (E) STUDS WITH A34 TO NAILER EACH STUD 4x6 NAILER WITH COUNTERSUNK 12"DIA. WELDED STUD NAILER @ 48"o.c. WF BEAM 12" PLYWOOD (E) STUDS10d @ 2"o.c. (3) 8d EACH BOARD (E) DIAGONAL SHEATHING 4x6 WITH #10x6" WOOD SCREW STAGGERED @ 16"o.c. (E) ROOF JOISTS (E) STUDS SIMPSON A35 @ 24"o.c. WITH #6x12" SCREWS TO ROOF SHEATHING AND #8 SHEET METAL SCREWS TO HSS 4x6 WITH 34" STUD BOLTS @ 24"o.c. (E) DIAGONAL SHEATHING 14 HSS7x5x14 12" PLYWOOD 10d @ 2"o.c. (3) 8d EACH BOARD (E) JOISTS SIMPSON HDU5 AT EACH JOIST WITH (14) 14" DIA. 112" SIMPSON SDS SCREWS AND 58"DIA. x6" EMBED. EPOXY ANCHOR (E) BRICK WALL 12" PLYWOOD 10d @ 2"o.c. EXTEND PLATE FULL DEPTH AS FOLLOWS: 1. 2. 3. WHERE BEAM OCCURS ON ONE SIDE ONLY. WHERE DBL. ROW OF BOLT OCCURS. WHERE SHEAR PLATE IS SKEWED. DOUBLE ROW WHERE REQ'D. BOLTS SEE SCHEDULE SEE SCHEDULE WHERE SHEAR PLATE IS SKEWED c 3"3" 3" 3" 3" 1 12" BEAM 516 516 516 516 2-1"DIA. 3-1"DIA. 4-1"DIA. REMARKSBEAMPLATE THICKNESS FILLET WELD A307 BOLTS W8-W10 W12-W14 W16 38 38 516 5-1"DIA.W18 38 PLATE THICKNESS, SEE SCHEDULE (E) ROOF JOISTS (E) 3x BLOCKING (E) 2x BLOCKING WITH #10x3" WOOD SCREW @ 6"o.c. 4x6 NAILER WITH COUNTERSUNK 12"DIA. WELDED STUD NAILER @ 48"o.c. HSS7x5x14 12" PLYWOOD10d @ 2"o.c. WF BEAM SIMPSON A34 @ 24"o.c. SIMPSON LTP4 @ 24"o.c. L3x314x0'-3" EACH SIDE HSS7x5 BEAM WITH 34" DIA. THROUGH-BOLT TO HSS AND 12" DIA. x3" LAG SCREW TO (E) TOP PLATES 12" PLYWOOD 10d @ 2"o.c. CONT. 4x8 BLOCKING WITH SIMPSON A34 EACH SIDE @ 16"o.c. (E) BOWED TRUSS (E) ROOF JOIST L3x314x0'-3" EACH SIDE HSS7x5 BEAM WITH 34" DIA. THROUGH-BOLT TO HSS AND 12" DIA. x3" LAG SCREW TO (E) BOWED TRUSS TOP CHORD HSS7x5x14 1 1 TO 2 12" PLYWOOD (3) 10d EACH BLOCK (E) ROOF JOISTS 4x FULL BLOCKING WITH A34 EACH SIDE EACH END W18x35 14" STIFFENER PLATE EACH SIDE WEB AT EACH L4x4 BRACE L4x4x14 BRACE @ 4'-0"o.c. AND AT EACH END OF W18x35 WITH 1"DIA. A307 BOLT EACH END 6"SQ. x12" PLATE 516 14 TYP. (E) BOWED WOOD TRUSS 1112"x4"x34"x0'-8" BENT PLATE EACH SIDE WITH (2) 34"DIA. THROUGH- BOLTS 14" STIFFINER PLATE EACH SIDE WEB WF BEAM TYP.14 TYP.14 TYP.14 1 1 MAX. c F G H 1 MAX. 1 1 MAX. 1 J B C D E ANGLE OR UNISTRUT BRACE/HANGER 112" 12" BOLT JOIST OR BEAM OR 4x FULL DEPTH BLOCKING BETWEEN JOISTS WITH A34 EACH SIDE EACH END 12" BOLT THREADED ROD HANGER WITH DOUBLE NUTS L3x3x38"x0'-3" LLV 1" 12" BOLT 12 GA. x2" BENT PLATE CABLE BRACE SEE 2x BLOCKING WITH A35 ONE SIDE EACH END (2 TOTAL) CABLE BRACE SEE 12 GA. x2" BENT PLATE 14"x4" LAG BOLT 2x BLOCKING WITH A35 EACH SIDE EACH END (2 TOTAL) 4x BLOCKING WITH A35 EACH SIDE EACH END (4 TOTAL) COPE ONE LEG AND BEND OTHER LEG AT END FOR CONNECTION. NOTES: 1. 2x BLOCKING WITH A35 ONE SIDE EACH END (2 TOTAL) 4x BLOCKING WITH A35 EACH SIDE EACH END (4 TOTAL) UNISTRUT OR ANGLE BRACE UNISTRUT P1843 ADJUSTABLE HINGE WITH 12" BOLT AND 12"x4" LAG BOLT ANGLE BRACE WITH 14"x4 LAG BOLT 4x BLOCKING WITH A35 EACH SIDE EACH END (4 TOTAL) THREADED ROD EQUIPMENT STRUT CHANNEL VERTICAL LIMIT STOP L M A X . S M A X . S M A X . 6 " MA X . 6 " MA X . THIS DETAIL USED FOR ROD STIFFENER REQUIREMENTS FOR EQUIPMENT CABLE BRACING. SEE TABLE 1 FOR MAXIMUM LENGTH OF 38" THRU 78" DIAMETER RODS WITHOUT ROD STIFFENER. SEE TABLE 2 FOR MAXIMUM LENGTH OF 38" THRU 78" DIAMETER RODS WITH ROD STIFFENER. SEE TABLE 3 TO DETERMINE NUMBER OF ROD STIFFENER CLIPS REQUIRED. NOTES: 1. 2. 3. 4. ROD DIA. L MAX. TABLE 1. (L MAX. WITHOUT ROD STIFFENER) 15"21"26"32"38" 38"12"58"34"78" ROD DIA. 15"21"26"32"38" 38"12"58"34"78" S MAX. TABLE 3. (S MAX. WITH ROD STIFFENER) TABLE 2. (L MAX. WITH ROD STIFFENER) ROD STIFFENER L MAX.116" 12GA. x158"x158" STRUT CHANNEL STRUCTURE 112" 12" BOLT SHEET STEEL STRAP HANGER OR BRACE 1 MAX. 1 2x BLOCKING WITH A35 ONE SIDE EACH END (2 TOTAL) 4x BLOCKING WITH A35 EACH SIDE EACH END (4 TOTAL) SHEET STEEL STRAP BRACE WITH 14"x4 LAG BOLT K K CABLE BRACE SEE K A K THIS DETAIL USED FOR END OF CABLE BRACES. NOTES: 1. 2-WIRE ROPE CLIPS SIZED AS REQUIRED BY CABLE CABLE LOOP WITH THIMBLE SIZED AS REQUIRED CABLE BRACE 3" c JOIST OR BEAM OR 4x FULL DEPTH BLOCKING BETWEEN JOISTS WITH A34 EACH SIDE EACH END c JOIST OR BEAM OR 4x FULL DEPTH BLOCKING BETWEEN JOISTS WITH A34 EACH SIDE EACH END c JOIST OR BEAM OR 4x FULL DEPTH BLOCKING BETWEEN JOISTS WITH A34 EACH SIDE EACH END S7 SHEET DESCIPTION JFA 10 SECTION 11 SECTION 12 SECTION 13 SECTION 14 TYP. DETAIL 15 DETAIL 16 SECTION 17 SECTION 18 SECTION 19 SECTION 20 21 DETAIL 22 23 SECTION 24 DETAIL 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 TYP. MECHANICAL CONNECTION DETAILS TYP. DETAIL DETAIL 1 (N) 2x JOIST WITH DEPTH TO MATCH (E) JOIST EXTENDING FULL LENGTH OF (E) JOIST TYP. 1" 1" (E) 2x JOIST #12x3" WOOD SCREW STAGGERED @ 12"o.c. TYP. AND 6"o.c. WITHIN 24" OF END OF (N) 2x JOIST 10d @ 2"o.c.10d @ 2"o.c. 12" PLYWOOD JOINT 10d @ 2"o.c. CONT. 4x8 BLOCKING WITH SIMPSON A34 EACH SIDE @ 16"o.c. (E) BOWED TRUSS (E) ROOF JOISTS. SISTER WITH 2x8 FULL LENGTH WITH #10x3" WOOD SCREWS @ 24"o.c. TOP AND BOTTOM (E) DIAGONAL SHEATHING12" PLYWOOD (3) 8d EACH BOARD 12 PLYWOOD (E) 10WF21 W14x22 2-4814 14 2-48 (E) ROOF JOISTS (E) ROOF JOISTS 3x FULL DEPTH BLOCKING WITH #10x5" WOOD SCREW @ 6"o.c. 10d @ 2"o.c. (E) BLOCKING (3) 8d EACH BOARD (E) ROOF SHEATHING (E) STUDS 4x FULL DEPTH BLOCKING ( 5 BAYS) AT 24"o.c. SIMPSON HDU5 @ 48"o.c. WITH (14) 14" DIA. x212" SIMPSON SDS SCREWS AND 58"DIA. x6" EMBED. EPOXY ANCHOR (E) ROOF JOISTS (E) BRICK WALL 12" PLYWOOD SIMPSON CS14 @ 48"o.c. FOR LENGTH OF NEW 4x BLOCKING WITH 10d NAILS IN ALL NAIL HOLES IN STRAP10d @ 2"o.c. 4x FULL DEPTH BLOCKING ( 8 BAYS) AT 16"o.c. (E) MANSARD FRAMING REMOVE AND REINSTALL FRAMING AS REQUIRED TO INSTALL NEW WORK. SIMPSON HDU8 @ 16"o.c. WITH (14) 14" DIA. x212" SIMPSON SDS SCREWS AND 34"DIA. THROUGH-BOLTS (E) ROOF JOISTS (E) BRICK WALL SIMPSON CS14 @ 16"o.c. FOR LENGTH OF NEW 4x BLOCKING WITH 10d NAILS IN ALL NAIL HOLES IN STRAP 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES. 10d @ 2"o.c. (E) 1" HORIZONTAL SHEATHING TO REMAIN AT THIS PORTION TO ALLOW FOR (E) MANSARD FRAMING TO REMAIN IN PLACE. 10d @ 2"o.c. 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES (E) MANSARD FRAMING 4" SQUARE x38" PLATE WASHER TYP. SIMPSON HDU8 @ 48"o.c. WITH (14) 1 4" DIA. x112" SIMPSON SDS SCREWS AND 34" DIA. THROUGH-BOLT SISTER (E) 2x6 RAFTER WITH NEW 2x6 FULL LENGTH @ 48"o.c. WITH #10x3" WOOD SCREW @ 24"o.c. TOP AND BOTTOM (E) MANSARD FRAMING REMOVE AND REINSTALL FRAMING AS REQUIRED TO INSTALL NEW WORK. (E) BRICK WALL 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES 10d @ 2"o.c. PLYWOOD SHEATHING TO END ON EACH SIDE OF (E) MANSARD SILL PLATE FRAMING TO ALLOW FOR (E) MANSARD FRAMING TO REMAIN IN PLACE 12" PLYWOOD WITH 10d @ 2"o.c. EDGES AND 12"o.c. FIELD. PROVIDE 2x4 FLAT BLOCKING AT UNSUPPORTED PLYWOOD PANEL EDGES 10d @ 2"o.c. CONT. 4x10 FLAT BLOCKING S8 DETAILS AN SECTIONS GS 5 10 SECTION 12 SECTION 14 15 SECTION 17 SECTION 18 SECTION 19 SECTION 20 21 22 23 24 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 ELECTRICAL EQUIPMENT (MAX. WEIGHT = 1619#) 8" FULLY GROUTED HOLLOW CELL CLAY BRICK BLOCK WALL 12" DIA. THRU-BOLTS WITH 2" SQ. x38" THICK PLATE WASHER TYP. AT EACH MOUNTING HOLE, 4 BOLTS MIN. 30" MAX. A C.G. OF CT GANTRY (Y = 39.96") C.G. OF PET GANTRY (Y = 22.69") ELEVATION PLAN AT BASE 0. 5 2 " C.G. WT. = 4,079 LBS 12 . 4 " 12 . 4 " 36.87"36.87" PLAN AT BASE 12 . 7 " 12 . 7 " 15.67"14.33" 0. 2 " 16.81" 28.47"1.97" 6. 1 " 6. 1 " C.G. WT. = 4,631 LBS C.G. WT. = 2,304 LBS (INCLUDES 500# PATIENT) (Y = 21.3") 8. 5 " 8. 5 " 39.8"39.8" PLAN AT BASE ELEVATION C.G. WT. = 2,304 LBS (INCLUDES 500# PATIENT) 15.3"15.3" 19 . 4 " 41 . 8 " C.G. WT. = 800 LBS 5.6"8.6" 4. 9 " FRONT ELEVATION SIDE ELEVATION PLAN VIEW CT/PET GANTRY     CONCRETE SLAB AND ANCHORAGE, SEE 1 S9 BCT/PET GANTRY     CCT/PET GANTRY    DPATIENT TABLE     EUPS OR POWER DISTRIBUTION UNIT       CONCRETE SLAB AND ANCHORAGE, SEE 1 S9 CONCRETE SLAB AND ANCHORAGE, SEE 2 S9 FRONT ELEVATION SIDE ELEVATION C.G. 13 . 6 " 44.7"10" 1.7" C.G. WT. = 547 LBS SIDE ELEVATIONFRONT ELEVATION H 19.5" 21 " 19.5" C.G. WT. = 350 LBS 6"6" C.G. J 19.4"19.4" 27 . 6 6 " C.G. WT. = 700 LBS 1.85" DETAIL "A" .2 5 " 4. 2 3 " 2" WIDE Z BRACKET MOUNTING BRACKET (SEE DETAIL "A") SIDE ELEVATIONFRONT ELEVATION 4.67"4.67" C.G. SIDE ELEVATIONFRONT ELEVATION TOP VIEW L3x3x14 x 14" BRACKET MOUNTED TO CABINET FRAME WITH (4) #12 S.M. SCREWS (EACH SIDE) WALL CLEARANCE 378" 1'-118" 2'-518" 11 78"2' - 1 1 4" 1'-612" 1038" 11 78"2' - 1 1 4" 2' - 5 18" 1'-612" 1038" 1' - 1 18" FOPERATOR'S CONSOLE      CONCRETE SLAB AND ANCHORAGE, SEE 2 S9 CONCRETE SLAB AND ANCHORAGE, SEE 2 S9 GTIO OPERATOR'S CONSOLE      CONCRETE SLAB AND ANCHORAGE, SEE 2 S9 STORAGE CABINET    PARC EQUIPMENT     CONCRETE SLAB AND ANCHORAGE, SEE 2 S9 6" 12"DIA. x2-12" EMBEDMENT STAINLESS STEEL HILTI KB-TZ2 ICC-ESR-4266 AT EACH MOUNTING HOLE #4x2'-4" WITH 4" EMBED. WITH ADHESIVE @ 12"o.c. TYP. ALL SIDES MECH. EQPT. (MAX. WEIGHT = 800#) (E) SLAB ON GRADE TYP. #4 @ 12"o.c. E.W. T&B 6" MIN. TYP. NOTES: 1.WHERE UNITS ARE ADJACENT TO EACH OTHER, ACCEPTABLE TO MERGE CONCRETE PADS. 2" CL R . 3" CL R . 12 " 12"DIA. x3-34" EMBEDMENT STAINLESS STEEL HILTI KB-TZ2 ICC-ESR-4266 AT EACH MOUNTING HOLE (MINIMUM 6 ANCHORS FOR PET GANTRY, 4 ANCHORS FOR ALL OTHERS) #4x2'-4" WITH 4" EMBED. WITH ADHESIVE @ 12"o.c. TYP. ALL SIDES MECH. EQPT. (MAX. WEIGHT = 4,631#) (E) SLAB ON GRADE TYP. #4 @ 12"o.c. E.W. T&B 12" MIN. TYP. NOTES: 1.WHERE UNITS ARE ADJACENT TO EACH OTHER, ACCEPTABLE TO MERGE CONCRETE PADS. S9 SHEET DESCIPTION JFA LARGE EQUIPMENT ANCHORAGE 1 2 SECTION 3 SECTION 4 SECTION 5 PET ROOM EQUIPMENT ANCHORAGE ROOM DETAILS 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 SMALL EQUIPMENT ANCHORAGE EXAM 11 EXAM 12 EXAM 13 EXAM 15 OFFICE MANAGER SURGERY SCHEDULER MEN'S RESTROOM WOMEN'S RESTROOM CONTROL ROOM DEVICE CHECK STOR. / COPY / FAX ROOM NUC CAMERA 1 RN / NP ECHO 1 ECHO 2 ECHO 3 EXAM 1 EXAM 10EXAM 9 TO EXAM ROOMS WAITING FOR 34 + 2 ADA RECEPTION WORK / PRINT STATION CHECK OUT CHECK OUT WAITING MEDICAL ASSISTANTS ENTER LABS EXAM 4 EXAM 5 EXAM 6 EXAM 7 EXAM 8 EXAM 2 EXAM 3 VASCULAR / PROCEDURE MED 8 MED 3MED 2 EXAM 16 EXAM 17 EXAM 18EXAM 14 MED 1 UNISEX #2 STORAGE UNISEX #1 TREADMILL 2 TREADMILL 1 MED 7 MED 6 MED 5 TECH ROOM HOT LAB WAITING ROOM DRAW NUC CAMERA 2 ELECTRICAL / TELF ROOM IT ROOM JANITOR CLOSET STAFF ROOM MED 4 VOID SPACE C O R R I D O R # 7 C O R R I D O R # 7 C O R R I D O R # 6 C O R R I D O R # 1 C O R R I D O R # 3 C O R R I D O R # 2 C O R R I D O R # 4 C O R R I D O R # 5 C O R R I D O R # 2 C O R R I D O R # 2 PET/CT ROOM 98.587654321 98.587654321 B A A.1 B A 6" CJ @ 16"o.c. 19 S12 6" CJ @ 16"o.c. 22 S11 25 S11 1J S56" CJ @ 16"o.c. 21 S11 22 S11 20 S11 6" CJ @ 16"o.c. 18 S11 9 S12 22 S11 25 S11 18 S12 4" CJ @ 16"o.c. 17 S11 4" C J @ 1 6 " o . c . 4" C J @ 1 6 " o . c . 5 S12 6" CJ @ 16"o.c. 6" CJ @ 16"o.c. 9 S118 S11 10 S11 22 S11 19 S11 7 S11 16 S11 14'-0" 14'-6" 10'-3" 12'-0" 9'-6" 12'-0" 12'-0" 14'- 0" 9'-6" 9'-6" 11'-0" 14'-6" 9'-6" 8'-10" 14 ' - 0 " 12 ' - 0 " 12 ' - 0 " 9' - 0 " 11 ' - 0 " 12 ' - 0 " 10 ' - 3 " 10 ' - 3 " 12 ' - 0 " 9'-6" 9' - 6 " 12 ' - 0 " 9' - 6 " 6" CJ @ 16"o.c. 21 S11 6" CJ @ 16"o.c.6" CJ @ 16"o.c. 21 S11 1J S5 6" CJ @ 16"o.c. 6" CJ @ 16"o.c. 21 S11 21 S116" CJ @ 16"o.c. 1J S5 10 S12 1J S5 1J S5 4" CJ @ 16"o.c. 1J S5 4" CJ @ 16"o.c. 1J S5 4" C J @ 1 6 " o . c . 6" CJ @ 16"o.c. 4" CJ @ 16"o.c.4" CJ @ 16"o.c. 4" CJ @ 16"o.c. 23 S11 1J S5 1J S5 4" CJ @ 16"o.c. WITH 9'-0" AFF CEILING 4" C J @ 1 6 " o . c . 1J S5 1J S5 4" CJ @ 16"o.c. WITH 9'-0" AFF CEILING 1J S5 1J S5 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 9'-6" 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 9' - 6 " 6 S11 1J S5 1J S5 4" CJ @ 16"o.c. 1J S5 TYP. 4" CJ @ 16"o.c. 1J S5 TYP. DOUBLE BACK TO BACK 6"x16GA. JOISTS DOUBLE BACK TO BACK 6"x16GA. JOISTS 1J S5 1J S51J S5 1J S5 6" CJ @ 16"o.c. 1J S5 1J S5 4" C J @ 1 6 " o . c . 1J S5 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 9' - 6 " 6 S11 6 S11 9' - 6 " 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 4" CJ @ 16"o.c. 7 S11 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 1J S5 4" C J @ 1 6 " o . c . 1J S5 1J S5 1J S5 4" C J @ 1 6 " o . c . 4" C J @ 1 6 " o . c . 1J S5 1J S5 6 S11 9' - 6 " 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 1J S5 1J S5 4" CJ @ 16"o.c. 9'-6" 7 S11 4" CJ @ 16"o.c. WITH 8'-0" AFF CEILING 2E A-6.2 NOTES: 1. 2. 3. 4. 5. 6. INDICATES SPAN DIRECTION OF CEILING JOISTS. INDICATES CEILING HEIGHT ABOVE FINISH FLOOR. 4" CJ INDICATES 4"x16 GA. CEILING JOISTS TYP. U.N.O. 6" CJ INDICATES 6"x16 GA. CEILING JOISTS TYP. U.N.O INDICATES STEEL STUD HANGER & SISTER EXISTING CEILING JOISTS PER OR TYP. U.N.O. SEE ARCH. DWGS AND TYP. DETAILS FOR INFORMATION NOT SHOWN. SEE FOR TYP. DETAIL FOR CEILING JOIST PARALLEL TO WALL OR HANGER. SEE FOR TYP. DETAIL FOR CEILING JOIST PERPENDICULAR TO WALL OR HANGER. X'-X" 1U S5 1T S5 4" CJ @ 16" o.c. 1J S5 4" CJ @ 16" o.c. 21 S11 21 S11 1J S5 1J S5 1J S5 1J S5 1J S5 10'-3" 12'-0" 1J S5 1J S5 4" CJ @ 16" o.c. 24 S11 1J S5 4" CJ @ 16"o.c. S10 CELING JOIST PLAN XX CEILING JOIST PLAN 13/16" = 1'-0" Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 CEILING JOISTS CONT. TRACK 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 6" TY P . 1U S51U S5 (E) CEILING JOISTS CEILING JOISTS 24 S11 24 S11 4"x18 GA. STEEL STUD @ 48" o.c. WITH (4) #10 SCREWS TO HANGER STUD (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD AND BRACING PER TYP.1U S5 OMIT BRACE WHERE HANGER STUD BRACE AND DIAGONAL BRACE OCCUR AT SAME LINE OF BLOCKING SIM. (E) CEILING JOIST. SISTER(E) CEILING JOIST AT HANGING STUD PER 1T S5 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1T S5 1T S5 CONT. TRACK CEILING JOISTS 1J S5 6" TY P . 24 S11 CEILING JOISTS 4"x18 GA. STEEL STUD @ 48" o.c. WITH (4) #10 SCREWS TO HANGER STUD SIM. OMIT BRACE WHERE HANGER STUD BRACE AND DIAGONAL BRACE OCCUR AT SAME (E) CEILING JOISTS (E) CEILING JOIST. SISTER(E) CEILING JOIST AT HANGING STUD PER 1T S5 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1T S5 1T S5 CONT. TRACK CEILING JOISTS 6" TY P . 1J S5 1J S5 OMIT BRACE WHERE HANGER STUD BRACE AND DIAGONAL BRACE OCCUR AT SAME (E) CEILING JOISTS SIM. 4"x18 GA. STEEL STUD @ 48" o.c. WITH (4) #10 SCREWS TO HANGER STUD CEILING JOISTS (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER 1T S5 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1T S5 1T S5 CONT. TRACK CEILING JOISTS 6" TY P . 1J S5 1J S5 4"x18 GA. STEEL STUD @ 48" o.c. WITH (4) #10 SCREWS TO HANGER STUD CEILING JOISTS SIM. OMIT BRACE WHERE HANGER STUD BRACE AND DIAGONAL BRACE OCCUR AT SAME (E) CEILING JOISTS CEILING JOISTS CEILING JOISTS WITH (2) #10 SCREWS EACH STUD @ STEEL STUDS, 12" DIA. x318" EMBED. EPOXY ANCHOR @ 48"o.c. AT BRICK WALLS (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER TYP.1U S5 SEE ARCH. DWGS. CEILING JOISTS (E) CEILING 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACK CONT. TRACK 1U S5 1U S5 OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 4" TY P . 6" TY P . 4"x18 GA. STEEL STUD @ 48"o.c. WITH (4) #10 SCREWS EACH END 24 S11 24 S11 CEILING JOIST 24 S11 24 S11 CEILING JOIST 6" x 18 GA. STEEL STUD HANGER @ 16" o.c. (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER TYP.1U S5 SEE ARCH. DWGS. CEILING JOISTS 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACK CONT. TRACK 1J S5CEILING JOIST CEILING JOIST 1J S5 4" TY P . 4" TY P . 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1U S5 1U S5 OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 4" TY P . 6" TY P . 4"x18 GA. STEEL STUD @ 48"o.c. WITH (4) #10 SCREWS EACH END 24 S11 (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD AND BRACING PER TYP.1U S5 6"x18 GAGE STEEL STUD HANGER @ 16" o.c. (E) CEILING 6"x18 GA. STEEL STUD HANGER @ 16"o.c. 1U S5 CONT. TRACK CEILING JOISTS SEE ARCH. DWGS. 1U S5 OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 1J S5 1U S5 SIM. 6"x18 GAGE STEEL STUD BRACE @ 48" o.c. WITH (4) #10 SCREWS TO HANGING STUD 6" TY P . 24 S11 (E) CEILING (E) CEILING JOIST 4"x16 GAGE CEILING JOISTS WITH (2) #10 SCREWS EACH STUD TYP. SEE ARCH. DWGS. 1S S5 CEILING JOISTS STEEL STUD WALL 6"x16 GAGE CEILING JOISTS WITH (2) #10 SCREWS EACH STUD SE E A R C H . DW G S . 4"x16 GAGE CEILING JOISTS 6"x18 GAGE MIN. STEEL STUD HANGER @ 16"o.c. (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER STEEL STUD WALL CEILING JOISTS CONT. TRACK SEE ARCH. DWGS. 1R S5 1T S5 1J S5 1J S5 OMIT BRACE WHERE WALL STUD BRACE AND HANGER STUD BRACE OCCUR AT SAME (E) CEILING JOISTS 1T S5 (E) CEILING CEILING JOIST 1J S5 SEE ARCH. DWGS. CEILING JOISTS SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACK CONT. TRACK 1J S5 SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME (E) CEILING JOIST(E) CEILING JOIST. SISTER(E) CEILING JOIST AT HANGING STUD PER 1T S5 4" TY P . 1T S5 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1T S5 4" TY P . 4" TY P . 6" TY P . 4"x18 GA. STEEL STUD @ 48"o.c. WITH (4) #10 SCREWS EACH END (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER TYP.1U S5 SEE ARCH. DWGS. CEILING JOISTS SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACKCONT. TRACK 1J S5 CEILING JOIST OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 4" TY P . 4" TY P . 4" TY P . 6" TY P . 4"x18 GA. STEEL STUD @ 48"o.c. WITH (4) #10 SCREWS EACH END 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1U S5 1U S5 24 S11 6"x18 GAGE MIN. STEEL STUD HANGER @ 16"o.c. (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER STEEL STUD WALL CEILING JOISTS CONT. TRACK SEE ARCH. DWGS. 1R S5 1T S5 1J S5 1J S5 OMIT BRACE WHERE WALL STUD BRACE AND HANGER STUD BRACE OCCUR AT SAME (E) CEILING JOISTS 1T S5 (E) CEILING SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER TYP.1U S5 SEE ARCH. DWGS. CEILING JOISTS SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACK CONT. TRACK 1J S5 1U S5 SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. 1U S5 OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 4" TY P . 4" TY P . 4" TY P . 6" TY P . 4"x18 GA. STEEL STUD @ 48"o.c. WITH (4) #10 SCREWS EACH END 6"x18 GAGE MIN. STEEL STUD HANGER @ 16"o.c. (E) CEILING (E) CEILING JOIST STEEL STUD WALL CEILING JOISTS CONT. TRACK SEE ARCH. DWGS. 1S S5 1U S5 1J S5 1J S5 (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER 1U S5 OMIT BRACE WHERE WALL STUD BRACE AND HANGER STUD BRACE OCCUR AT SAME LINE OF BLOCKING SUSPENDED T-BAR CEILING, SEE ARCH. DWGS. S11 SHEET DESCIPTION JFA SECTION 6 SECTION 7 SECTION 8 SECTION 9 SECTION 10 SECTION 16 SECTION 17 SECTION 18 SECTION 19 SECTION 20 SECTION 21 SECTION 22 SECTION 23 TYP. DETAIL 24 SECTION 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD PER TYP.1U S5 SEE ARCH. DWGS. CEILING JOISTS (E) CEILING 6"x18 GA. STEEL STUD HANGER @ 16"o.c. CONT. TRACK CONT. TRACK 1U S5 1U S5 OMIT BRACE WHERE HANGER STUD BRACE ON EACH SIDE OCCUR AT SAME LINE OF BLOCKING 1J S5 CEILING JOIST 24 S11 24 S11 CEILING JOIST 6" x 18 GA. STEEL STUD HANGER @ 16" o.c. 1J S5 1" W18x35 CEILING JOISTS CONT. TRACK 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 6" TY P . 1U S5 1U S5 (E) CEILING JOISTS CEILING JOISTS 24 S11 24 S11 4"x18 GA. STEEL STUD @ 48" o.c. WITH (4) #10 SCREWS TO HANGER STUD (E) CEILING JOIST. SISTER (E) CEILING JOIST AT HANGING STUD AND BRACING PER TYP.1U S5 OMIT BRACE WHERE HANGER STUD BRACE AND DIAGONAL BRACE OCCUR AT SAME LINE OF BLOCKING SIM. 6" x 18 GA. BLOCKING @ 16"o.c. STOREFRONT, SEE ARCH. DWGS. 1J S5 CEILING JOISTS BOXED HEADER WITH 8"x18 GA. STUDS AND JAMB STUDS PER SIM.1B S5 34" PLYWOOD WITH #10 SCREWS @ 6"o.c. EDGES AND 12"o.c. FIELD BACK-TO-BACK 6"x16 GA. JOISTS WITH (2) #10 SCREWS @ 24"o.c. CONT. TRACK NESTED WITH BACK-TO-BACK JOISTS WITH #10 SCREW TOP & BOTTOM @ 24"o.c. SIM. (E) CEILING JOIST. SISTER(E) CEILING JOIST AT HANGING STUD PER 1T S5 6"x18 GAGE STEEL STUD HANGER @ 16"o.c. (E) CEILING 1T S5 CONT. TRACK SEE ARCH. DWGS. SE E A R C H . D W G S . WALL BEYOND WITH CONT. TOP TRACK WITH (2) #10 SCREWS TO EACH CEILING JOIST ABOVE AND #10 SCREW AT 16"o.c. TO BLOCKING 1T S56"x18 GAGE STEEL STUD HANGER @ 16"o.c.1J S5CEILING JOISTS CEILING JOISTS 1J S5 CEILING JOISTS CONT. TRACK1J S5 1J S5 6"x18 GA. CEILING JOISTS @ 16"o.c. WITH #10 SCREW EACH CEILING JOIST BELOWCONT. TRACK WITH #10 SCREW EACH FLANGE TO EACH CEILING JOIST 6"x16 GA. CEILING JOISTS @ 16"o.c. CONT. 6"x18 GA. STUD BLOCKING (E) CEILING JOIST 1S S5 (E) CEILING JOIST 1S S5 1S S5 1S S5 24 S11 CEILING JOISTS 24 S11 24 S11 24 S11CONT. 6"x18 GA. STUD BLOCKING 6"x18 GA. CEILING JOISTS @ 16" o.c. WITH #10 SCREW EACH CEILING JOIST BELOW STEEL STUD WALL 1J S5 CONT. TRACK WITH (2) #10 SCREWS TO EACH CEILING JOIST ABOVE AND #10 SCREW @ 16"o.c. TO BLOCKING 6"x16 GA. CEILING JOISTS @ 16"o.c. STEEL STUD WALL CONT. TRACK WITH (2) #10 SCREWS TO EACH CEILING JOIST ABOVE AND #10 SCREW @16"o.c. TO BLOCKING 1J S5 STEEL STUD WALL S12 SHEET DESCIPTION JFA SECTION 5 SECTION 9 SECTION 10 15 SECTION 18 SECTION 19 20 21 22 23 24 25 Foothill Cardiology Medical Group, Inc. 2910 West Broadway Los Angeles, California 90041 Telephone (323) 255-1008 30 SOUTH 1st AVENUE ARCADIA, CA 91006 BUILDING SHELL, TENANT & SITE IMPROVEMENT 24142 12-18-24 STRUCTURAL ENGINEERS GLENDALE, CALIFORNIA 91203 529 HAHN AVENUE, SUITE #200 FAX (818) 507-1556 E-MAIL ENGINEERS@GROSSMANSPEER.COM (818) 507-1020 GROSSMAN & SPEER ASSOCIATES, INC. DM #24142 07/11/2025 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 ELECTRICAL SCHEDULES,NOTES & DETAILS NONE ELECTRICAL SCHEDULES, NOTES & DETAILS SCALE: NONE E001 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 PANEL SCHEDULES & 1-LINE NONE PANEL SCHEDULES & 1-LINE SCALE: NONE E002 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 PANEL SCHEDULES NONE PANEL SCHEDULES SCALE: NONE E003 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 TITLE-24 LTS, PART 1 NONE TITLE-24 LTS, PART 1 SCALE: NONE E004 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 TITLE-24 LTS, PART 2 NONE TITLE-24 LTS, PART 2 SCALE: NONE E005 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 TITLE-24 LTS, OUTDOOR NONE TITLE-24 LTS, OUTDOOR SCALE: NONE E006 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 PET-CT SCANNER CUT SHEET-1 NONE PET-CT SCANNER CUT SHEET-1 SCALE: NONE E007 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 PET-CT SCANNER CUT SHEET-2 NONE PET-CT SCANNER CUT SHEET-2 SCALE: NONE E008 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 PET-CT SCANNER CUT SHEET-3 NONE PET-CT SCANNER CUT SHEET-3 SCALE: NONE E009 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 SWITCHBOARD SUBMITTAL NONE SWITCHBOARD SUBMITTAL SCALE: NONE E010 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 TRANSFORMER CUTSHEETS NONE TRANSFORMER CUTSHEETS SCALE: NONE E011 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 LIGHTING PLAN 1/8"=1'-0" LIGHTING PLAN SCALE: 1/8"=1'-0" E101 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 LIGHTING PLAN - PART 1 1/4"=1'-0" LIGHTING PLAN - PART 1 SCALE: 1/4"=1'-0" E101-1 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 LIGHTING PLAN - PART 2 1/4"=1'-0" LIGHTING PLAN - PART 2 SCALE: 1/4"=1'-0" E101-2 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 LIGHTING PLAN - PART 3 1/4"=1'-0" LIGHTING PLAN - PART 3 SCALE: 1/4"=1'-0" E101-3 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 LIGHTING PLAN - PART 4 1/4"=1'-0" LIGHTING PLAN - PART 4 SCALE: 1/4"=1'-0" E101-4 A B 91 A.1 8.5871 · · · · · · · · · · · · · · SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 POWER PLAN 1/8"=1'-0" POWER PLAN SCALE: 1/8"=1'-0" E102 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 POWER PLAN - PART 1 1/4"=1'-0" POWER PLAN - PART 1 SCALE: 1/4"=1'-0" E102-1 A 9 A.1 8.587 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 POWER PLAN - PART 2 1/4"=1'-0" POWER PLAN - PART 2 SCALE: 1/4"=1'-0" E102-2 B SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 POWER PLAN - PART 3 1/4"=1'-0" POWER PLAN - PART 3 SCALE: 1/4"=1'-0" E102-3 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 POWER PLAN - PART 4 1/4"=1'-0" POWER PLAN - PART 4 SCALE: 1/4"=1'-0" E102-4 A B 91 A.1 8.5871 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 EQUIPMENT PLAN 1/8"=1'-0" EQUIPMENT PLAN SCALE: 1/8"=1'-0" E103 “” A.1 A 1 9 B A B 9 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 ELECTRICAL ROOF PLAN 1/8"=1'-0" ELECTRICAL ROOF PLAN SCALE: 1/8"=1'-0" E104 · · · SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 01062026 03132026 UTILITY TRANSFORMERLOCATION 1/8"=1'-0" UTILITY TRANSFORMER LOCATION SCALE: 1/8"=1'-0" E201 – SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 MECHANICAL SCHEDULES &NOTES M001 SCALE: NONE MECHANICAL SCHEDULES & NOTES SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 MECHANICAL DETAILS M002 SCALE: NONE MECHANICAL DETAILS NONE 2 2 × × × ³ SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 MECHANICAL FLOOR PLAN M101 SCALE: 1/8"=1'-0" MECHANICAL FLOOR PLAN 1/8"=1'-0" A.1 A 1 9 B A B 9 2 2 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 MECHANICAL ROOF PLAN M102 SCALE: 1/8"=1'-0" MECHANICAL ROOF PLAN 1/8"=1'-0" 2 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 TITLE-24, MECH PART 1 MT01 SCALE: NONE TITLE-24, MECH PART 1 NONE SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 TITLE-24, MECH PART 2 MT02 SCALE: NONE TITLE-24, MECH PART 2 NONE GW GW GW 2022 NON-RESIDENTIAL MANDATORY MEASURES TABLE 5.303.2.3 FIXTURE FLOW RATE FIXTURE TYPE MAXIMUM FLOW RATE AT 20 PERCENT REDUCTION Shower heads 1.8 gpm @ 80 psi Lavatory faucets-nonresidential 0.5 gpm @ 60 psi Kitchen faucets 1.8 gpm @ 60 psi Wash fountains 1.8 [rim space (in.)/20 gpm @ 60 psi] Metering faucets 0.2 gallons/cycle Metering faucets for wash fountains 0.20 [rim space (in.)/20 gpm @60 psi] Gravity tank type water closets 1.28 gallons/flush ( See note 1) Flushometer tank water closets 1.28 gallons/flush ( See note 1) Flushometer valve water closets 1.28 gallons/flush ( See note 1) Electromechanical lydraulic water closets 1.28 gallons/flush ( See note 1) Wall Mounted Urinals .125 gallons/flush Floor Mounted Urinals .5 gallons/flush 1. includes single and dual flush water closets with an effective flush of 1.28 gallons or less: Single Flush toilets-The effective flush volume shall not exceed 1.25 gallons (4.8 liters). The effective flush volume is the average flush volume when tested in accordance with ASME A 112.19.233.2. Dual flush toilets- the effective flush volume shall not exceed 1.28 gallons (4.8 liters). The effective flush volume is defined as the composite, average flush volume of two reduced flushes and one full flush. Flush volumes will be tested in accordance with ASME A 112.19.2 and ASME A 112.19.14 · · · · · · ESOWESOW EWEWEW PLUMBING WASTE & VENT SIZE CHART PIPE SIZING PER CPC 2022, 703.2 PIPE SIZE MAX. UNIT (WASTE)MAX. UNIT (VENT) 1 1/2"1 8 2"8 24 3"35 84 4"216 256 CLEANOUT SIZING PER CPC 2022, TABLE 707.1 PIPE SIZE SIZE OF CLEANOUT THREADS PER INCH 1 1/2"1 1/2"11 1/2" 2"1 1/2"11 1/2" 3"2 1/2"8 4" & LARGER 3 1/2"8 F SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 PLUMBING SCHEDULES &NOTES P001 SCALE: NONE PLUMBING SCHEDULES & NOTES NONE FINISHED FLOOR TRAP PRIMER VALVE PRECISION PLUMBING PRODUCTS INC. MODEL P2-500. WITH VACUUM BREAKER AND CHECK VALVEWH-1 CW TO WATER HEATERS HW TO FIXTURES HWR FROM FURTHEST FIXTURE TO WATER HEATER. SET @110°F. AQUASTAT EXPANSION TANK TEMPERING VALVE D AIR RELEASE VALVE WITHIN 4" OF THE PUMP P-1 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 PLUMBING DETAILS P002 SCALE: NONE PLUMBING DETAILS NONE SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 PLUMBING DETAILS P003 SCALE: NONE PLUMBING DETAILS NONE SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 WATER HEATER ENERGYCOMPLIANCE - PART 1 P004 SCALE: NONE WATER HEATER ENERGY COMPLIANCE - PART 1 NONE SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 WATER HEATER ENERGYCOMPLIANCE - PART 2 P005 SCALE: NONE WATER HEATER ENERGY COMPLIANCE - PART 2 NONE 1 2 3 4 5 6 978 B A B 91 AA A.1 8.5 8.587 A 1 1 1 2 2 3 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 WASTE & VENT PLAN P101 SCALE: 1/8"=1'-0" WASTE & VENT PLAN 1/8"=1'-0" 1 2 3 4 5 6 978 B A B 91 AA A.1 8.5 8.587 A 1 1 1 2 2 1 1 1 1 1 3 3 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 HW & CW PLAN P102 SCALE: 1/8"=1'-0" HW & CW PLAN 1/8"=1'-0" A.1 A 1 9 B A B 9 1 2 3 B SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 GAS PLAN P103 SCALE: 1/8"=1'-0" GAS PLAN 1/8"=1'-0" 1 1 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 PLUMBING ROOF PLAN P104 SCALE: 1/8"=1'-0" PLUMBING ROOF PLAN 1/8"=1'-0" SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 WASTE & VENT ISOMETRIC P201 SCALE: NONE WASTE & VENT ISOMETRIC NONE 1 1 SHEET TITLE: REVISIONS SHEET NO.: DESCRIPTION:DATE: 30 South 1st Avenue Arcadia, CA 91006 The Design Studio, Interior Design, Inc. 466 Foothill Blvd. Suite 403 La Cañada, CA 91011 tel: (818) 567-6444 www.thedesignstudio.biz theTDS contract & residential interior design Studio Foothill Cardiology 06112025 09092025 09242025 10152025 11192025 12052025 HW & CW ISOMETRIC P202 SCALE: NONE HW & CW ISOMETRIC NONE GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: 24142 PROJECT:FOR:BY:DATE: Foothill Cardiology Arcadia Tenant Improvement Nakaishi LR 12/15/2025 STRUCTURAL CALCULATIONS TABLE OF CONTENTS DESCRIPTION PAGE NO. MAIN BUILDING GRAVITY Roof Beam Calculations MB1-MB15 Roof Beams Posts and Foundations MB16-MB45 Interior Wall Studs Headers, and Jamb Studs MB46-MB54 LATERAL Seismic Load Coefficients MB55 (E) Shear Wall With New Openings In-Plane MB56-MB69 (N) CMU Shear Wallls- In-Plane MB70-MB90 Wall Out-of Plane MB91-MB103 Freestanding Wall, Grid A Wall Infill MB104 PARKING STRUCTURE GRAVITY (E) Concrete Slab Bending with New Solar Panel Loads P1-P12 (E) Columns Punching Shear P13 LATERAL (N) CMU Shear Wallls- In-Plane, (Voluntary Retrofit)P14-P22 New Solar Panels Loads, 10% Seismic Mass Check P23 ADDED/REVISED CALCULATIONS Roof Mechanical Equipment Anchorage PC1-PC7 Roof Mechanical Equipment Supporting Beams PC8-PC19 Ceiling Joists, Detail 1J/S5 PC20-PC23 Ladder Platform PC24-PC29 10% Seismic Mass and 5% Gravity Check PC30 Parking Structure 10% Shear Wall Strength Reduction PC31 Parking Structure Gravity Strength around new opening PC32-PC34 Parking Structure Electric Panel Anchorage PC35-PC42 Miscellaneous PC43-PC51    Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Steel Beams Supporting Walls of Equipment Room Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingUniform Load : D = 0.0150 ksf, Tributary Width = 12.0 ft, (equipment room wall weight) Uniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 11.167 ft, (equipment room roof weight) Uniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 1.333 ft, (roof weight and live load) Design OKDESIGN SUMMARYMaximum Bending Stress Ratio =0.771: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 4.602 kMn / Omega : Allowable 21.870k-ft Vn/Omega : Allowable W8x10Section used for this span Span # where maximum occurs Location of maximum on span Span # 1 Load Combination +D+Lr 26.826 k Section used for this span W8x10Ma : Applied Maximum Shear Stress Ratio =0.172 : 1 14.667 ft 16.873k-ft Va : Applied 0 <360 240Ratio =0 <180 Maximum DeflectionMax Downward Transient Deflection 0.292 in 601Ratio = >=360 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.735 in Ratio = >=180Max Upward Total Deflection 0.000 in Span: 1 : Lr Only Span: 1 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D Only Dsgn. L = 14.67 ft 1 0.464 0.103 10.15 10.15 36.52 21.87 1.00 1.00 2.77 40.24 26.83+D+LrDsgn. L = 14.67 ft 1 0.771 0.172 16.87 16.87 36.52 21.87 1.00 1.00 4.60 40.24 26.83 +D+0.750LrDsgn. L = 14.67 ft 1 0.695 0.154 15.19 15.19 36.52 21.87 1.00 1.00 4.14 40.24 26.83+0.60D Dsgn. L = 14.67 ft 1 0.278 0.062 6.09 6.09 36.52 21.87 1.00 1.00 1.66 40.24 26.83 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.7348 7.375 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 4.602 4.602 Max Upward from Load Combinations 4.602 4.602 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Steel Beams Supporting Walls of Equipment Room Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Cases 2.768 2.768 D Only 2.768 2.768+D+Lr 4.602 4.602+D+0.750Lr 4.143 4.143+0.60D 1.661 1.661 Lr Only 1.833 1.833 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Steel Beams Supporting Walls of Equipment Room 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingLoad for Span Number 1Varying Uniform Load : D= 0.0150->0.0150 ksf, Extent = 0.0 -->> 16.0 ft, Trib Width = 0.0->12.0 ft, (equipment room wallweight) Uniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 11.167 ft, (equipment room roof weight) Uniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 1.333 ft, (roof weight and live load) Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.626: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 4.612 k Mn / Omega : Allowable 27.944k-ft Vn/Omega : Allowable HSS6x6x1/4Section used for this span Span # where maximum occurs Location of maximum on span Span # 1 Load Combination +D+Lr 44.376 k Section used for this span HSS6x6x1/4Ma : Applied Maximum Shear Stress Ratio =0.104 : 1 16.000 ft 17.502k-ft Va : Applied 0 <360197Ratio =0 <180 Maximum DeflectionMax Downward Transient Deflection 0.446 in 430Ratio = >=360 Max Upward Transient Deflection 0.000 in Ratio =Max Downward Total Deflection 0.976 in Ratio = >=180Max Upward Total Deflection 0.000 in Span: 1 : Lr OnlySpan: 1 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D OnlyDsgn. L = 16.00 ft 1 0.340 0.059 9.51 9.51 46.67 27.94 1.00 1.00 2.61 74.11 44.38+D+Lr Dsgn. L = 16.00 ft 1 0.626 0.104 17.50 17.50 46.67 27.94 1.00 1.00 4.61 74.11 44.38+D+0.750LrDsgn. L = 16.00 ft 1 0.555 0.093 15.50 15.50 46.67 27.94 1.00 1.00 4.11 74.11 44.38 +0.60D Dsgn. L = 16.00 ft 1 0.204 0.035 5.71 5.71 46.67 27.94 1.00 1.00 1.57 74.11 44.38 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.9761 8.091 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 4.132 4.612 3.351 2.414 2.814 3.352 0.005 5.411 2.014 HSS7x5x1/4 also acceptable 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Steel Beams Supporting Walls of Equipment Room 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Combinations 4.132 4.612 3.351 2.414 2.814 3.352 0.005 5.411 2.014 Max Upward from Load Cases 2.132 2.612 3.351 2.414 2.814 3.352 0.005 5.411 2.014Max Downward from all Load Conditions (Resis 3.351 2.414 2.814 3.352 0.005 5.411 2.014Max Downward from Load Combinations (Resis 3.351 2.414 2.814 3.352 0.005 5.411 2.014Max Downward from Load Cases (Resisting Up 3.351 2.414 2.814 3.352 0.005 5.411 2.014 D Only 2.132 2.612 3.351 2.414 2.814 3.352 0.005 5.411 2.014+D+Lr 4.132 4.612 3.351 2.414 2.814 3.352 0.005 5.411 2.014+D+0.750Lr 3.632 4.112 3.351 2.414 2.814 3.352 0.005 5.411 2.014 +0.60D 1.279 1.567 3.351 2.414 2.814 3.352 0.005 5.411 2.014Lr Only 2.000 2.000 3.351 2.414 2.814 3.352 0.005 5.411 2.014 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingLoads on all spans...Uniform Load on ALL spans : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 15.333 ft Load(s) for Span Number 2Point Load : D = 3.450 k @ 0.50 ft, (wall weight (15 psf * 15 ft tall * 15.333 trib)) Load(s) for Span Number 3Point Load : D = 1.0 k @ 0.9167 ft, (mech equipment weight) Load(s) for Span Number 4Point Load : D = 2.768, Lr = 1.833 k @ 0.3333 ft, (steel beam supporting equipment room 1 support 1) Point Load : D = 2.612, Lr = 2.0 k @ 0.3333 ft, (steel beam supporting equipment room 2 support 2) Load(s) for Span Number 5Point Load : D = 2.768, Lr = 1.833 k @ 5.417 ft, (steel beam supporting equipment room 1 support 1) Point Load : D = 2.612, Lr = 2.0 k @ 5.417 ft, (steel beam supporting equipment room 2 support 2) Load(s) for Span Number 7Point Load : D = 3.450 k @ 8.167 ft, (wall weight (15 psf * 15 ft tall * 15.333 trib)) Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.277: 1 Load Combination +D+Lr Span # where maximum occurs Span # 7 13.472 kMn / Omega : Allowable 82.834k-ft Vn/Omega : Allowable W14x22Section used for this span Span # where maximum occursLocation of maximum on span Span # 3 Load Combination +D+Lr 63.020 k Section used for this span W14x22 Ma : Applied Maximum Shear Stress Ratio =0.214 : 1 11.450 ft 22.912k-ft Va : Applied 27,885 >=360 1280Ratio =5497 >=180 Maximum DeflectionMax Downward Transient Deflection 0.048 in 4,061Ratio = >=360Max Upward Transient Deflection -0.006 in Ratio = Max Downward Total Deflection 0.153 in Ratio = >=180Max Upward Total Deflection -0.029 in Span: 7 : Lr OnlySpan: 7 : Lr Only Span: 7 : +D+LrSpan: 7 : +D+Lr 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D OnlyDsgn. L = 9.62 ft 1 0.037 0.072 1.59 -3.06 3.06 138.33 82.83 1.00 1.00 4.53 94.53 63.02 Dsgn. L = 9.27 ft 2 0.037 0.072 0.96 -3.06 3.06 138.33 82.83 1.00 1.00 4.53 94.53 63.02Dsgn. L = 11.45 ft 3 0.063 0.114 1.10 -5.26 5.26 138.33 82.83 1.00 1.00 7.21 94.53 63.02Dsgn. L = 17.25 ft 4 0.113 0.114 3.19 -9.37 9.37 138.33 82.83 1.00 1.00 7.21 94.53 63.02Dsgn. L = 10.62 ft 5 0.134 0.071 11.13 -9.37 11.13 138.33 82.83 1.00 1.00 4.48 94.53 63.02 Dsgn. L = 13.30 ft 6 0.145 0.072 -0.00 -12.05 12.05 138.33 82.83 1.00 1.00 4.52 94.53 63.02Dsgn. L = 16.33 ft 7 0.199 0.072 16.46 -12.05 16.46 138.33 82.83 1.00 1.00 4.52 94.53 63.02+D+Lr Dsgn. L = 9.62 ft 1 0.073 0.096 3.79 -6.04 6.04 138.33 82.83 1.00 1.00 6.08 94.53 63.02Dsgn. L = 9.27 ft 2 0.073 0.096 1.86 -6.04 6.04 138.33 82.83 1.00 1.00 6.08 94.53 63.02Dsgn. L = 11.45 ft 3 0.142 0.214 2.25 -11.80 11.80 138.33 82.83 1.00 1.00 13.47 94.53 63.02Dsgn. L = 17.25 ft 4 0.222 0.214 7.50 -18.38 18.38 138.33 82.83 1.00 1.00 13.47 94.53 63.02 Dsgn. L = 10.62 ft 5 0.225 0.133 18.62 -18.38 18.62 138.33 82.83 1.00 1.00 8.36 94.53 63.02Dsgn. L = 13.30 ft 6 0.237 0.119 -0.00 -19.61 19.61 138.33 82.83 1.00 1.00 7.49 94.53 63.02Dsgn. L = 16.33 ft 7 0.277 0.119 22.91 -19.61 22.91 138.33 82.83 1.00 1.00 7.49 94.53 63.02 +D+0.750LrDsgn. L = 9.62 ft 1 0.064 0.090 3.24 -5.30 5.30 138.33 82.83 1.00 1.00 5.69 94.53 63.02Dsgn. L = 9.27 ft 2 0.064 0.090 1.63 -5.30 5.30 138.33 82.83 1.00 1.00 5.69 94.53 63.02Dsgn. L = 11.45 ft 3 0.123 0.189 1.97 -10.17 10.17 138.33 82.83 1.00 1.00 11.91 94.53 63.02 Dsgn. L = 17.25 ft 4 0.195 0.189 6.42 -16.13 16.13 138.33 82.83 1.00 1.00 11.91 94.53 63.02Dsgn. L = 10.62 ft 5 0.202 0.117 16.74 -16.13 16.74 138.33 82.83 1.00 1.00 7.39 94.53 63.02Dsgn. L = 13.30 ft 6 0.214 0.107 -0.00 -17.72 17.72 138.33 82.83 1.00 1.00 6.75 94.53 63.02 Dsgn. L = 16.33 ft 7 0.257 0.107 21.30 -17.72 21.30 138.33 82.83 1.00 1.00 6.75 94.53 63.02+0.60DDsgn. L = 9.62 ft 1 0.022 0.043 0.95 -1.83 1.83 138.33 82.83 1.00 1.00 2.72 94.53 63.02Dsgn. L = 9.27 ft 2 0.022 0.043 0.58 -1.83 1.83 138.33 82.83 1.00 1.00 2.72 94.53 63.02 Dsgn. L = 11.45 ft 3 0.038 0.069 0.66 -3.15 3.15 138.33 82.83 1.00 1.00 4.33 94.53 63.02Dsgn. L = 17.25 ft 4 0.068 0.069 1.91 -5.62 5.62 138.33 82.83 1.00 1.00 4.33 94.53 63.02Dsgn. L = 10.62 ft 5 0.081 0.043 6.68 -5.62 6.68 138.33 82.83 1.00 1.00 2.69 94.53 63.02 Dsgn. L = 13.30 ft 6 0.087 0.043 -0.00 -7.23 7.23 138.33 82.83 1.00 1.00 2.71 94.53 63.02Dsgn. L = 16.33 ft 7 0.119 0.043 9.88 -7.23 9.88 138.33 82.83 1.00 1.00 2.71 94.53 63.02 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.0086 4.169 0.0000 0.000Lr Only+D+Lr 2 0.0027 4.790 -0.0002 0.618 +D+Lr+D+Lr 3 0.0023 3.817 -0.0039 9.637D Only+D+Lr 4 0.0432 7.763 -0.0015 16.100+D+Lr 5 0.0390 5.664 0.0000 16.100+D+Lr6 0.0000 5.664 -0.0290 8.645 +D+Lr 7 0.1531 8.847 0.0000 8.645 Load Combination Support 1 Support 2 Support 3 Support 4 Support 5 Support 6 Support 7 Support 8 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 2.059 9.393 5.985 17.435 13.739 9.705 11.998 5.087 2.051 Max Upward from Load Combinations 2.059 9.393 5.985 17.435 13.739 9.705 11.998 5.087 2.051Max Upward from Load Cases 1.164 6.055 3.355 9.002 6.992 5.052 6.799 3.045 2.051Max Downward from all Load Conditions (Resis 2.051 Max Downward from Load Combinations (Resis 2.051 Max Downward from Load Cases (Resisting Up 2.051D Only 0.895 6.055 3.355 9.002 6.992 4.652 6.799 3.045 2.051+D+Lr 2.059 9.393 5.985 17.435 13.739 9.705 11.998 5.087 2.051 +D+0.750Lr 1.768 8.558 5.327 15.327 12.052 8.442 10.699 4.576 2.051+0.60D 0.537 3.633 2.013 5.401 4.195 2.791 4.080 1.827 2.051Lr Only 1.164 3.338 2.630 8.433 6.747 5.052 5.199 2.042 2.051 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingLoads on all spans...Uniform Load on ALL spans : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 14.083 ft Uniform Load on ALL spans : D = 0.0210 k/ft Load(s) for Span Number 1Point Load : D = 3.169 k @ 10.830 ft, (wall weight (15 psf * 15 ft tall * 14.083 trib)) Load(s) for Span Number 2Point Load : D = 1.0 k @ 3.50 ft, (mech equipment) Point Load : D = 1.0 k @ 2.333 ft, (mech equipment) Point Load : D = 0.7605 k @ 4.167 ft, (wall weight (15 psf * 15 ft tall * 3.38 trib)) Uniform Load : D = 0.2250 k/ft, Extent = 4.167 -->> 7.20 ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall )) Load(s) for Span Number 3Point Load : D = 2.768, Lr = 1.833 k @ 8.833 ft, (steel beam supporting equipment room 1 support 1) Point Load : D = 1.0 k @ 4.583 ft, (mech equipment) Uniform Load : D = 0.2250 k/ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall )) Load for Span Number 4Uniform Load : D = 0.2250 k/ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall )) Load(s) for Span Number 5Point Load : D = 2.768, Lr = 1.833 k @ 1.50 ft, (steel beam supporting equipment room 1 support 1) Uniform Load : D = 0.2250 k/ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall)) Load(s) for Span Number 6Point Load : D = 2.424, Lr = 1.833 k @ 8.167 ft, (wall weight (15 psf * 15 ft tall * 10.773 trib)) 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Service loads entered. Load Factors will be applied for calculations.Applied Loads Point Load : D = 1.0 k @ 5.0 ft, (mech equipment) Uniform Load : D = 0.2250 k/ft, Extent = 0.0 -->> 8.167 ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall)) Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.409: 1 Load Combination +D+Lr Span # where maximum occurs Span # 5 11.520 kMn / Omega : Allowable 82.834k-ft Vn/Omega : Allowable W14x22Section used for this span Span # where maximum occurs Location of maximum on span Span # 4 Load Combination +D+Lr 63.020 k Section used for this span W14x22Ma : Applied Maximum Shear Stress Ratio =0.183 : 1 19.750 ft 33.911k-ft Va : Applied 25,111 >=3601093Ratio =10131 >=180 Maximum DeflectionMax Downward Transient Deflection 0.081 in 2,544Ratio = >=360Max Upward Transient Deflection -0.003 in Ratio =Max Downward Total Deflection 0.188 in Ratio = >=180Max Upward Total Deflection -0.009 in Span: 6 : Lr OnlySpan: 6 : Lr OnlySpan: 6 : +D+LrSpan: 6 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D OnlyDsgn. L = 15.43 ft 1 0.154 0.080 8.52 -12.72 12.72 138.33 82.83 1.00 1.00 5.01 94.53 63.02 Dsgn. L = 7.20 ft 2 0.154 0.066 0.02 -12.72 12.72 138.33 82.83 1.00 1.00 4.16 94.53 63.02Dsgn. L = 9.89 ft 3 0.158 0.103 2.94 -13.05 13.05 138.33 82.83 1.00 1.00 6.50 94.53 63.02Dsgn. L = 19.75 ft 4 0.206 0.114 8.35 -17.06 17.06 138.33 82.83 1.00 1.00 7.17 94.53 63.02Dsgn. L = 20.00 ft 5 0.251 0.114 7.29 -20.76 20.76 138.33 82.83 1.00 1.00 7.17 94.53 63.02 Dsgn. L = 17.12 ft 6 0.251 0.107 15.27 -20.76 20.76 138.33 82.83 1.00 1.00 6.76 94.53 63.02+D+LrDsgn. L = 15.43 ft 1 0.230 0.120 13.79 -19.05 19.05 138.33 82.83 1.00 1.00 7.59 94.53 63.02 Dsgn. L = 7.20 ft 2 0.230 0.096 -0.00 -19.05 19.05 138.33 82.83 1.00 1.00 6.08 94.53 63.02 Dsgn. L = 9.89 ft 3 0.249 0.164 4.13 -20.62 20.62 138.33 82.83 1.00 1.00 10.31 94.53 63.02Dsgn. L = 19.75 ft 4 0.326 0.183 13.35 -27.01 27.01 138.33 82.83 1.00 1.00 11.52 94.53 63.02Dsgn. L = 20.00 ft 5 0.409 0.183 11.34 -33.91 33.91 138.33 82.83 1.00 1.00 11.52 94.53 63.02 Dsgn. L = 17.12 ft 6 0.409 0.173 26.51 -33.91 33.91 138.33 82.83 1.00 1.00 10.90 94.53 63.02+D+0.750LrDsgn. L = 15.43 ft 1 0.211 0.110 12.45 -17.47 17.47 138.33 82.83 1.00 1.00 6.95 94.53 63.02 Dsgn. L = 7.20 ft 2 0.211 0.089 -0.00 -17.47 17.47 138.33 82.83 1.00 1.00 5.60 94.53 63.02 Dsgn. L = 9.89 ft 3 0.226 0.148 3.82 -18.73 18.73 138.33 82.83 1.00 1.00 9.36 94.53 63.02Dsgn. L = 19.75 ft 4 0.296 0.166 12.10 -24.53 24.53 138.33 82.83 1.00 1.00 10.43 94.53 63.02Dsgn. L = 20.00 ft 5 0.370 0.166 10.33 -30.62 30.62 138.33 82.83 1.00 1.00 10.43 94.53 63.02 Dsgn. L = 17.12 ft 6 0.370 0.157 23.70 -30.62 30.62 138.33 82.83 1.00 1.00 9.87 94.53 63.02+0.60DDsgn. L = 15.43 ft 1 0.092 0.048 5.11 -7.63 7.63 138.33 82.83 1.00 1.00 3.01 94.53 63.02 Dsgn. L = 7.20 ft 2 0.092 0.040 0.01 -7.63 7.63 138.33 82.83 1.00 1.00 2.50 94.53 63.02 Dsgn. L = 9.89 ft 3 0.095 0.062 1.77 -7.83 7.83 138.33 82.83 1.00 1.00 3.90 94.53 63.02Dsgn. L = 19.75 ft 4 0.124 0.068 5.01 -10.24 10.24 138.33 82.83 1.00 1.00 4.30 94.53 63.02Dsgn. L = 20.00 ft 5 0.150 0.068 4.37 -12.46 12.46 138.33 82.83 1.00 1.00 4.30 94.53 63.02 Dsgn. L = 17.12 ft 6 0.150 0.064 9.16 -12.46 12.46 138.33 82.83 1.00 1.00 4.06 94.53 63.02 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.0925 7.329 0.0000 0.000+D+Lr2 0.0000 7.329 -0.0085 2.340+D+Lr+D+Lr 3 0.0051 3.379 -0.0034 8.489 +D+Lr 4 0.1045 9.546 0.0000 8.489+D+Lr+D+Lr 5 0.0716 9.000 -0.0077 18.667+D+Lr 6 0.1880 9.273 0.0000 18.667 Load Combination Support 1 Support 2 Support 3 Support 4 Support 5 Support 6 Support 7 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 3.845 13.674 4.035 17.502 19.358 19.201 5.368 2.042 2.051 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Load Combination Support 1 Support 2 Support 3 Support 4 Support 5 Support 6 Support 7 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Combinations 3.845 13.674 4.035 17.502 19.358 19.201 5.368 2.042 2.051 Max Upward from Load Cases 2.082 9.169 3.126 11.026 12.103 11.949 2.850 2.042 2.051Max Downward from all Load Conditions (Resis 2.042 2.051Max Downward from Load Combinations (Resis 2.042 2.051Max Downward from Load Cases (Resisting Up 2.042 2.051 D Only 2.082 9.169 3.126 11.026 12.103 11.949 2.850 2.042 2.051+D+Lr 3.845 13.674 4.035 17.502 19.358 19.201 5.368 2.042 2.051+D+0.750Lr 3.404 12.548 3.808 15.883 17.544 17.388 4.738 2.042 2.051 +0.60D 1.249 5.501 1.876 6.616 7.262 7.169 1.710 2.042 2.051Lr Only 1.763 4.505 0.909 6.476 7.254 7.252 2.517 2.042 2.051 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Existing Truss Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam bracing is defined as a set spacing over all spansAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Unbraced Lengths First Brace starts at 4.0 ft from Left-Most supportRegular spacing of lateral supports on length of beam = 4.0 ft Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingLoad(s) for Span Number 1Point Load : D = 10.604, Lr = 11.366 k @ 7.090 ft, (long truss 1 support 2 reaction) Point Load : D = 0.8050, Lr = 0.870 k @ 7.090 ft, (short truss 1 support 1 reaction) Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.720: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 17.002 k Mn / Omega : Allowable 165.918k-ft Vn/Omega : Allowable W18x35Section used for this span Span # where maximum occurs Location of maximum on span Span # 1 Load Combination +D+Lr 106.20 k Section used for this span W18x35Ma : Applied Maximum Shear Stress Ratio =0.160 : 1 0.000 ft 119.423k-ft Va : Applied 0 <360448Ratio =0 <180 Maximum DeflectionMax Downward Transient Deflection 0.320 in 889Ratio = >=360 Max Upward Transient Deflection 0.000 in Ratio =Max Downward Total Deflection 0.636 in Ratio = >=180Max Upward Total Deflection 0.000 in Span: 1 : Lr OnlySpan: 1 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D OnlyDsgn. L = 3.94 ft 1 0.198 0.079 32.86 32.86 277.08 165.92 1.67 1.00 8.42 159.30 106.20Dsgn. L = 4.00 ft 1 0.354 0.078 58.70 32.86 58.70 277.08 165.92 1.15 1.00 8.28 159.30 106.20 Dsgn. L = 4.00 ft 1 0.338 0.032 56.05 42.68 56.05 277.08 165.92 1.10 1.00 3.41 159.30 106.20Dsgn. L = 4.00 ft 1 0.257 0.033 42.68 28.76 42.68 277.08 165.92 1.15 1.00 3.55 159.30 106.20Dsgn. L = 4.00 ft 1 0.173 0.035 28.76 14.27 28.76 277.08 165.92 1.24 1.00 3.69 159.30 106.20 Dsgn. L = 3.80 ft 1 0.086 0.036 14.27 14.27 277.08 165.92 1.66 1.00 3.82 159.30 106.20+D+LrDsgn. L = 3.94 ft 1 0.402 0.160 66.64 66.64 277.08 165.92 1.68 1.00 17.00 159.30 106.20Dsgn. L = 4.00 ft 1 0.720 0.159 119.42 66.64 119.42 277.08 165.92 1.15 1.00 16.86 159.30 106.20 Dsgn. L = 4.00 ft 1 0.686 0.066 113.80 85.81 113.80 277.08 165.92 1.11 1.00 7.06 159.30 106.20Dsgn. L = 4.00 ft 1 0.517 0.068 85.81 57.26 85.81 277.08 165.92 1.15 1.00 7.20 159.30 106.20Dsgn. L = 4.00 ft 1 0.345 0.069 57.26 28.15 57.26 277.08 165.92 1.25 1.00 7.34 159.30 106.20 Dsgn. L = 3.80 ft 1 0.170 0.070 28.15 28.15 277.08 165.92 1.66 1.00 7.47 159.30 106.20+D+0.750Lr 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Existing Truss Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length Dsgn. L = 3.94 ft 1 0.351 0.140 58.20 58.20 277.08 165.92 1.68 1.00 14.86 159.30 106.20Dsgn. L = 4.00 ft 1 0.628 0.139 104.24 58.20 104.24 277.08 165.92 1.15 1.00 14.72 159.30 106.20 Dsgn. L = 4.00 ft 1 0.599 0.058 99.36 75.03 99.36 277.08 165.92 1.11 1.00 6.15 159.30 106.20Dsgn. L = 4.00 ft 1 0.452 0.059 75.03 50.13 75.03 277.08 165.92 1.15 1.00 6.29 159.30 106.20Dsgn. L = 4.00 ft 1 0.302 0.061 50.13 24.68 50.13 277.08 165.92 1.25 1.00 6.43 159.30 106.20Dsgn. L = 3.80 ft 1 0.149 0.062 24.68 24.68 277.08 165.92 1.66 1.00 6.56 159.30 106.20 +0.60DDsgn. L = 3.94 ft 1 0.119 0.048 19.72 19.72 277.08 165.92 1.67 1.00 5.05 159.30 106.20Dsgn. L = 4.00 ft 1 0.212 0.047 35.22 19.72 35.22 277.08 165.92 1.15 1.00 4.97 159.30 106.20 Dsgn. L = 4.00 ft 1 0.203 0.019 33.63 25.61 33.63 277.08 165.92 1.10 1.00 2.04 159.30 106.20Dsgn. L = 4.00 ft 1 0.154 0.020 25.61 17.25 25.61 277.08 165.92 1.15 1.00 2.13 159.30 106.20Dsgn. L = 4.00 ft 1 0.104 0.021 17.25 8.56 17.25 277.08 165.92 1.24 1.00 2.21 159.30 106.20Dsgn. L = 3.80 ft 1 0.052 0.022 8.56 8.56 277.08 165.92 1.66 1.00 2.29 159.30 106.20 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.6361 10.721 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 17.002 7.474 0.909 6.476 7.254 7.252 2.517 2.042 2.051 Max Upward from Load Combinations 17.002 7.474 0.909 6.476 7.254 7.252 2.517 2.042 2.051Max Upward from Load Cases 8.583 3.822 0.909 6.476 7.254 7.252 2.517 2.042 2.051Max Downward from all Load Conditions (Resis 0.909 6.476 7.254 7.252 2.517 2.042 2.051Max Downward from Load Combinations (Resis 0.909 6.476 7.254 7.252 2.517 2.042 2.051 Max Downward from Load Cases (Resisting Up 0.909 6.476 7.254 7.252 2.517 2.042 2.051D Only 8.419 3.822 0.909 6.476 7.254 7.252 2.517 2.042 2.051+D+Lr 17.002 7.474 0.909 6.476 7.254 7.252 2.517 2.042 2.051 +D+0.750Lr 14.856 6.561 0.909 6.476 7.254 7.252 2.517 2.042 2.051+0.60D 5.051 2.293 0.909 6.476 7.254 7.252 2.517 2.042 2.051Lr Only 8.583 3.653 0.909 6.476 7.254 7.252 2.517 2.042 2.051 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Joists Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingUniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 14.0 ft, (roof dead and live load) Point Load : D = 2.606 k @ 10.667 ft, (wall weight (15 psf * 15 ft tall * 11.583 trib)) Uniform Load : D = 0.2250 k/ft, Extent = 10.667 -->> 15.0 ft, Tributary Width = 1.0 ft, (wall weight (15 psf * 15 ft tall)) Design OKDESIGN SUMMARYMaximum Bending Stress Ratio =0.264: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 6.527 kMn / Omega : Allowable 82.834k-ft Vn/Omega : Allowable W14x22Section used for this span Span # where maximum occurs Location of maximum on span Span # 1 Load Combination +D+Lr 63.020 k Section used for this span W14x22Ma : Applied Maximum Shear Stress Ratio =0.104 : 1 15.000 ft 21.882k-ft Va : Applied 0 <360 1179Ratio =0 <180 Maximum DeflectionMax Downward Transient Deflection 0.056 in 3,242Ratio = >=360 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.153 in Ratio = >=180Max Upward Total Deflection 0.000 in Span: 1 : Lr Only Span: 1 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D Only Dsgn. L = 15.00 ft 1 0.180 0.070 14.89 14.89 138.33 82.83 1.00 1.00 4.43 94.53 63.02+D+LrDsgn. L = 15.00 ft 1 0.264 0.104 21.88 21.88 138.33 82.83 1.00 1.00 6.53 94.53 63.02 +D+0.750LrDsgn. L = 15.00 ft 1 0.242 0.095 20.04 20.04 138.33 82.83 1.00 1.00 6.00 94.53 63.02+0.60D Dsgn. L = 15.00 ft 1 0.108 0.042 8.93 8.93 138.33 82.83 1.00 1.00 2.66 94.53 63.02 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.1526 7.800 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 4.734 6.527 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Max Upward from Load Combinations 4.734 6.527 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Joists Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from Load Cases 2.634 4.427 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Max Downward from all Load Conditions (Resis 7.278 1.869 5.208 5.949 -0.836 5.638 2.005Max Downward from Load Combinations (Resis 7.278 1.869 5.208 5.949 -0.836 5.638 2.005Max Downward from Load Cases (Resisting Up 7.278 1.869 5.208 5.949 -0.836 5.638 2.005D Only 2.634 4.427 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 +D+Lr 4.734 6.527 7.278 1.869 5.208 5.949 -0.836 5.638 2.005+D+0.750Lr 4.209 6.002 7.278 1.869 5.208 5.949 -0.836 5.638 2.005+0.60D 1.580 2.656 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Lr Only 2.100 2.100 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Brick Wall Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: CODE REFERENCES Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16Load Combination Set : IBC 2021 Material Properties Analysis Method :ksi Bending Axis : Major Axis Bending Beam is Fully Braced against lateral-torsional bucklingAllowable Strength Design Fy : Steel Yield : 50.0 ksi Beam Bracing :E: Modulus : 29,000.0 Service loads entered. Load Factors will be applied for calculations.Applied Loads Beam self weight calculated and added to loadingUniform Load : D = 0.0150, Lr = 0.020 ksf, Tributary Width = 1.333 ft, (roof dead and live load) Uniform Load : D = 0.90 k/ft, Tributary Width = 1.0 ft, (wall weight (120 pcf * 9" brick * 10 ft tall)) Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.307: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 7.023 k Mn / Omega : Allowable 82.834k-ft Vn/Omega : Allowable W14x22Section used for this span Span # where maximum occurs Location of maximum on span Span # 1 Load Combination +D+Lr 63.020 k Section used for this span W14x22Ma : Applied Maximum Shear Stress Ratio =0.111 : 1 0.000 ft 25.457k-ft Va : Applied 0 <3601038Ratio =0 <180 Maximum DeflectionMax Downward Transient Deflection 0.005 in 37,696Ratio = >=360 Max Upward Transient Deflection 0.000 in Ratio =Max Downward Total Deflection 0.168 in Ratio = >=180Max Upward Total Deflection 0.000 in Span: 1 : Lr OnlySpan: 1 : +D+Lr Maximum Forces & Stresses for Load Combinations Span # Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios MV Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length D OnlyDsgn. L = 14.50 ft 1 0.299 0.108 24.76 24.76 138.33 82.83 1.00 1.00 6.83 94.53 63.02+D+Lr Dsgn. L = 14.50 ft 1 0.307 0.111 25.46 25.46 138.33 82.83 1.00 1.00 7.02 94.53 63.02+D+0.750LrDsgn. L = 14.50 ft 1 0.305 0.111 25.28 25.28 138.33 82.83 1.00 1.00 6.97 94.53 63.02+0.60D Dsgn. L = 14.50 ft 1 0.179 0.065 14.85 14.85 138.33 82.83 1.00 1.00 4.10 94.53 63.02 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+Lr 1 0.1677 7.291 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 7.023 7.023 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Max Upward from Load Combinations 7.023 7.023 7.278 1.869 5.208 5.949 -0.836 5.638 2.005Max Upward from Load Cases 6.829 6.829 7.278 1.869 5.208 5.949 -0.836 5.638 2.005Max Downward from all Load Conditions (Resis 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Max Downward from Load Combinations (Resis 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 0% Steel Beam LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Roof Beam Supporting Brick Wall Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Downward from Load Cases (Resisting Up 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 D Only 6.829 6.829 7.278 1.869 5.208 5.949 -0.836 5.638 2.005+D+Lr 7.023 7.023 7.278 1.869 5.208 5.949 -0.836 5.638 2.005+D+0.750Lr 6.974 6.974 7.278 1.869 5.208 5.949 -0.836 5.638 2.005+0.60D 4.098 4.098 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 Lr Only 0.193 0.193 7.278 1.869 5.208 5.949 -0.836 5.638 2.005 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 1 worst case reaction: Axial Load at 18.50 ft, D = 9.002, LR = 8.433 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.7437 Location of max.above base 0.0 ft 17.661 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.389 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.744 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.655 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.233 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 9.228+D+Lr 17.661+D+0.750Lr 15.553 +0.60D 5.537Lr Only 8.433 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 17.661Minimum" 5.537 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 9.228Minimum" 9.228MaximumReaction, Y-Y Axis Base 9.228 Minimum" 9.228MaximumReaction, X-X Axis Top 9.228Minimum" 9.228 MaximumReaction, Y-Y Axis Top 9.228 Minimum" 9.228MaximumMoment, X-X Axis Base 9.228Minimum" 9.228 MaximumMoment, Y-Y Axis Base 9.228Minimum" 9.228MaximumMoment, X-X Axis Top 9.228 Minimum" 9.228 MaximumMoment, Y-Y Axis Top 9.228Minimum" 9.228 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 17661 lbs Foundation Area = 12.25 sq.ft (3'-6" both ways) Soil Pressure = 1442 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 2 worst case reaction: Axial Load at 18.50 ft, D = 12.103, LR = 7.254 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.8247 Location of max.above base 0.0 ft 19.583 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.519 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.825 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.748 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.312 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 12.329+D+Lr 19.583+D+0.750Lr 17.769 +0.60D 7.397Lr Only 7.254 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 19.583Minimum" 7.254 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 12.329Minimum" 12.329MaximumReaction, Y-Y Axis Base 12.329 Minimum" 12.329MaximumReaction, X-X Axis Top 12.329Minimum" 12.329 MaximumReaction, Y-Y Axis Top 12.329 Minimum" 12.329MaximumMoment, X-X Axis Base 12.329Minimum" 12.329 MaximumMoment, Y-Y Axis Base 12.329Minimum" 12.329MaximumMoment, X-X Axis Top 12.329 Minimum" 12.329 MaximumMoment, Y-Y Axis Top 12.329Minimum" 12.329 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 19583 lbs Foundation Area = 13.444 sq.ft (3'-8" both ways) Soil Pressure = 1457 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 1 gridline A reaction: Axial Load at 18.50 ft, D = 0.8950, LR = 1.164 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.09622 Location of max.above base 0.0 ft 2.285 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.047 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.096 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.084 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.028 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 1.121+D+Lr 2.285+D+0.750Lr 1.994 +0.60D 0.673Lr Only 1.164 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 2.285Minimum" 0.673 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 1.121Minimum" 1.121MaximumReaction, Y-Y Axis Base 1.121 Minimum" 1.121MaximumReaction, X-X Axis Top 1.121Minimum" 1.121 MaximumReaction, Y-Y Axis Top 1.121 Minimum" 1.121MaximumMoment, X-X Axis Base 1.121Minimum" 1.121 MaximumMoment, Y-Y Axis Base 1.121Minimum" 1.121MaximumMoment, X-X Axis Top 1.121 Minimum" 1.121 MaximumMoment, Y-Y Axis Top 1.121Minimum" 1.121 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 2285 lbsBrick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 12 ft wide = 19980 lbs Total Load = 22265 lbs Foundation Area = 15 sq.ft (1'-3" wide x 12' long) Soil Pressure = 1484 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 1 gridline B: Axial Load at 18.50 ft, D = 3.045, LR = 2.042 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.2237 Location of max.above base 0.0 ft 5.313 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.138 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.224 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.202 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.083 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 3.271+D+Lr 5.313+D+0.750Lr 4.802 +0.60D 1.963Lr Only 2.042 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 5.313Minimum" 1.963 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 3.271Minimum" 3.271MaximumReaction, Y-Y Axis Base 3.271 Minimum" 3.271MaximumReaction, X-X Axis Top 3.271Minimum" 3.271 MaximumReaction, Y-Y Axis Top 3.271 Minimum" 3.271MaximumMoment, X-X Axis Base 3.271Minimum" 3.271 MaximumMoment, Y-Y Axis Base 3.271Minimum" 3.271MaximumMoment, X-X Axis Top 3.271 Minimum" 3.271 MaximumMoment, Y-Y Axis Top 3.271Minimum" 3.271 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 1 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 5313 lbs Brick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 3 ft wide = 4995 lbs Total Load = 30288 lbs Foundation Area = 9 sq.ft (3' both ways) Soil Pressure = 1145 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 2 gridline A reaction: Axial Load at 18.50 ft, D = 2.082, LR = 1.763 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.1714 Location of max.above base 0.0 ft 4.071 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.097 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.171 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.153 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.058 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 2.308+D+Lr 4.071+D+0.750Lr 3.630 +0.60D 1.385Lr Only 1.763 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 4.071Minimum" 1.385 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 2.308Minimum" 2.308MaximumReaction, Y-Y Axis Base 2.308 Minimum" 2.308MaximumReaction, X-X Axis Top 2.308Minimum" 2.308 MaximumReaction, Y-Y Axis Top 2.308 Minimum" 2.308MaximumMoment, X-X Axis Base 2.308Minimum" 2.308 MaximumMoment, Y-Y Axis Base 2.308Minimum" 2.308MaximumMoment, X-X Axis Top 2.308 Minimum" 2.308 MaximumMoment, Y-Y Axis Top 2.308Minimum" 2.308 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline A Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 4071 lbs Brick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 3 ft wide = 4995 lbs Total Load = 22265 lbs Foundation Area = 9 sq.ft (3' both ways)Soil Pressure = 1007 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam across roof 2 gridline B reactions: Axial Load at 18.50 ft, D = 2.850, LR = 2.517 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.2355 Location of max.above base 0.0 ft 5.593 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.130 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.236 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.209 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.078 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 3.076+D+Lr 5.593+D+0.750Lr 4.964 +0.60D 1.846Lr Only 2.517 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 5.593Minimum" 1.846 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 3.076Minimum" 3.076MaximumReaction, Y-Y Axis Base 3.076 Minimum" 3.076MaximumReaction, X-X Axis Top 3.076Minimum" 3.076 MaximumReaction, Y-Y Axis Top 3.076 Minimum" 3.076MaximumMoment, X-X Axis Base 3.076Minimum" 3.076 MaximumMoment, Y-Y Axis Base 3.076Minimum" 3.076MaximumMoment, X-X Axis Top 3.076 Minimum" 3.076 MaximumMoment, Y-Y Axis Top 3.076Minimum" 3.076 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beams Across Roof 2 Gridline B Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 5593 lbs Brick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 3 ft wide = 4995 lbs Total Load = 22265 lbs Foundation Area = 9 sq.ft (3' both ways) Soil Pressure = 1176 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 1 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam supporting existing truss reaction 1: Axial Load at 18.50 ft, D = 8.419, LR = 8.583 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.7255 Location of max.above base 0.0 ft 17.228 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.364 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.726 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.635 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.218 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 8.645+D+Lr 17.228+D+0.750Lr 15.082 +0.60D 5.187Lr Only 8.583 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 17.228Minimum" 5.187 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 1 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 8.645Minimum" 8.645MaximumReaction, Y-Y Axis Base 8.645 Minimum" 8.645MaximumReaction, X-X Axis Top 8.645Minimum" 8.645 MaximumReaction, Y-Y Axis Top 8.645 Minimum" 8.645MaximumMoment, X-X Axis Base 8.645Minimum" 8.645 MaximumMoment, Y-Y Axis Base 8.645Minimum" 8.645MaximumMoment, X-X Axis Top 8.645 Minimum" 8.645 MaximumMoment, Y-Y Axis Top 8.645Minimum" 8.645 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 1 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 17228 lbs Foundation Area = 12.25 sq.ft Soil Pressure = 1406 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS5x5x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 288.970 lbs * Dead Load FactorAXIAL LOADS . . .steel beam supporting existing truss reaction 2: Axial Load at 18.50 ft, D = 3.822, LR = 3.653 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.1589 Location of max.above base 0.0 ft 7.764 k 48.849 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 18.987 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 18.987 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.084 1.00 1.00 115.03 115.03+D+Lr PASS PASS0.00 0.000 0.00 ftft0.159 1.00 1.00 115.03 115.03+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.140 1.00 1.00 115.03 115.03 +0.60D PASS PASS0.00 0.000 0.00 ftft0.050 1.00 1.00 115.03 115.03 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 4.111+D+Lr 7.764+D+0.750Lr 6.851 +0.60D 2.467Lr Only 3.653 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 7.764Minimum" 2.467 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 4.111Minimum" 4.111MaximumReaction, Y-Y Axis Base 4.111 Minimum" 4.111MaximumReaction, X-X Axis Top 4.111Minimum" 4.111 MaximumReaction, Y-Y Axis Top 4.111 Minimum" 4.111MaximumMoment, X-X Axis Base 4.111Minimum" 4.111 MaximumMoment, Y-Y Axis Base 4.111Minimum" 4.111MaximumMoment, X-X Axis Top 4.111 Minimum" 4.111 MaximumMoment, Y-Y Axis Top 4.111Minimum" 4.111 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS5x5x1/4 R xx = 1.930 in Depth = 5.000 in R yy = 1.930 in J = 25.800 in^4 Width = 5.000 in Wall Thick = 0.250 in Zx = 7.610 in^3 Area = 4.300 in^2 Weight = 15.620 plf I xx = 16.00 in^4 S xx = 6.41 in^3Design Thick = 0.233 in I yy = 16.000 in^4 C = 10.500 in^3 S yy = 6.410 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Truss Post 2 Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 7764 lbs Foundation Area = 9 sq.ftSoil Pressure = 863 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Joists Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam supporting existing joists reaction: Axial Load at 18.50 ft, D = 4.427, LR = 2.10 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.2844 Location of max.above base 0.0 ft 6.753 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.196 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.284 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.262 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.118 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 4.653+D+Lr 6.753+D+0.750Lr 6.228 +0.60D 2.792Lr Only 2.100 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 6.753Minimum" 2.100 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Joists Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 4.653Minimum" 4.653MaximumReaction, Y-Y Axis Base 4.653 Minimum" 4.653MaximumReaction, X-X Axis Top 4.653Minimum" 4.653 MaximumReaction, Y-Y Axis Top 4.653 Minimum" 4.653MaximumMoment, X-X Axis Base 4.653Minimum" 4.653 MaximumMoment, Y-Y Axis Base 4.653Minimum" 4.653MaximumMoment, X-X Axis Top 4.653 Minimum" 4.653 MaximumMoment, Y-Y Axis Top 4.653Minimum" 4.653 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Existing Joists Worst Case Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 6753 lbs Brick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 3 ft wide = 4995 lbs Total Load = 11748 lbs Foundation Area = 9 sq.ft (3' both ways) Soil Pressure = 1305.33 psf < 1500 psf OK! 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Brick Wall Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Stress Grade Top & Bottom PinnedAnalysis Method :18.50Overall Column HeightTop & Bottom FixityAllowable Strength Fy : Steel Yield ksi29,000.0 ksi Steel Section Name :HSS4x4x1/4 50.0 ft E : Elastic Bending Modulus Y-Y (depth) axis : X-X (width) axis : Unbraced Length for buckling ABOUT Y-Y Axis = 18.50 ft, K = 1.0 Unbraced Length for buckling ABOUT X-X Axis = 18.50 ft, K = 1.0 Brace condition for deflection (buckling) along columns : Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 225.885 lbs * Dead Load FactorAXIAL LOADS . . .steel beam supporting brick wall reaction: Axial Load at 18.50 ft, D = 6.829, LR = 0.1930 k DESIGN SUMMARY PASS Max. Axial+Bending Stress Ratio =0.3052 Location of max.above base 0.0 ft 7.248 k 23.746 k 0.0 k-ft Load Combination +D+Lr Load Combination 0.0 11.702 k-ft Bending & Shear Check Results PASS Maximum Shear Stress Ratio 0.0 k 0.0 : 1 Location of max.above base 0.0 ftAt maximum location values are . . . : 1 At maximum location values are . . . k 11.702 k-ft 0.0 k-ft Pa : Axial Pn / Omega : Allowable Ma-x : Applied Mn-x / Omega : Allowable Ma-y : Applied Mn-y / Omega : Allowable Va : AppliedVn / Omega : Allowable Maximum Load Reactions . . Top along X-X 0.0 kBottom along X-X 0.0 k Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Maximum Load Deflections . . . Along Y-Y 0.0 in at 0.0ft above base for load combination : Along X-X 0.0 in at 0.0ft above base for load combination : 0.0 Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Location Stress Ratio Status LocationStatus Load Combination Results Cbx Cby KxLx/Ry KyLy/Rx D Only PASS PASS0.00 0.000 0.00 ftft0.297 1.00 1.00 146.05 146.05+D+Lr PASS PASS0.00 0.000 0.00 ftft0.305 1.00 1.00 146.05 146.05+D+0.750Lr PASS PASS0.00 0.000 0.00 ftft0.303 1.00 1.00 146.05 146.05 +0.60D PASS PASS0.00 0.000 0.00 ftft0.178 1.00 1.00 146.05 146.05 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments D Only 7.055+D+Lr 7.248+D+0.750Lr 7.200 +0.60D 4.233Lr Only 0.193 k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumAxial @ Base 7.248Minimum" 0.193 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Brick Wall Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: k k-ft Item X-X Axis Reaction Y-Y Axis ReactionAxial Reaction @ Base @ Top@ Base @ Base @ Top Extreme Reactions Extreme Value @ Base @ Base@ Top @ Top Mx - End Moments My - End Moments MaximumReaction, X-X Axis Base 7.055Minimum" 7.055MaximumReaction, Y-Y Axis Base 7.055 Minimum" 7.055MaximumReaction, X-X Axis Top 7.055Minimum" 7.055 MaximumReaction, Y-Y Axis Top 7.055 Minimum" 7.055MaximumMoment, X-X Axis Base 7.055Minimum" 7.055 MaximumMoment, Y-Y Axis Base 7.055Minimum" 7.055MaximumMoment, X-X Axis Top 7.055 Minimum" 7.055 MaximumMoment, Y-Y Axis Top 7.055Minimum" 7.055 Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance D Only 0.0000 0.000 0.000 ftft inin 0.000 +D+Lr 0.0000 0.000 0.000 ftft inin 0.000+D+0.750Lr 0.0000 0.000 0.000 ftft inin 0.000+0.60D 0.0000 0.000 0.000 ftft inin 0.000 Lr Only 0.0000 0.000 0.000 ftft inin 0.000 Steel Section Properties :HSS4x4x1/4 R xx = 1.520 in Depth = 4.000 in R yy = 1.520 in J = 12.800 in^4 Width = 4.000 in Wall Thick = 0.250 in Zx = 4.690 in^3 Area = 3.370 in^2 Weight = 12.210 plf I xx = 7.80 in^4 S xx = 3.90 in^3Design Thick = 0.233 in I yy = 7.800 in^4 C = 6.560 in^3 S yy = 3.900 in^3 Ycg = 0.000 in 0% Steel Column LIC# : KW-06015294, Build:20.22.12.28 GROSSMAN & SPEER ASSOCIATES, INC. (c) ENERCALC INC 1983-2022 DESCRIPTION:Steel Beam Supporting Brick Wall Post Project File: 24142 roof beams and posts.ec6 Project Title:Engineer:Project ID:Project Descr: Sketches Foundation Check: Post Load = 7248 lbs Brick Wall Load = 120 pcf * 9in/(12in/ft) * 18.5 ft tall * 3 ft wide = 4995 lbs Total Load = 12243 lbs Foundation Area = 9 sq.ft (3' both ways) Soil Pressure = 1360 psf < 1500 psf OK! 0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐ Z/ (,   LQ 2.IRU /  LQ 6 # RF ,QWHULRU:DOO6WHHO6WXG)UDPLQJ 352-(&7180%(5 352-(&7 68%-(&7  )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ &DVH6HLVPLF ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ/  LQ 2. ,QWHULRU:DOO'RRU+HDGHU6WHHO6WXG)UDPLQJ )RRW:LGH'RRU 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐ Z/ (, 3DE (,/  LQ&DVH6HLVPLF ѐ Z/ (, 3DE (,/  LQ 2.IRU /  LQ 6 VWXGV ,QWHULRU:DOO'RRU-DPE6WXG6WHHO6WXG)UDPLQJ )RRW:LGH'RRU 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ &DVH6HLVPLF ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ/  LQ 2. ,QWHULRU:DOO'RRU+HDGHU6WHHO6WXG)UDPLQJ )RRW,QFK:LGH'RRU 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐ Z/ (, 3DE (,/  LQ&DVH6HLVPLF ѐ Z/ (, 3DE (,/  LQ 2.IRU /  LQ 6 VWXGV ,QWHULRU:DOO'RRU-DPE6WXG6WHHO6WXG)UDPLQJ )RRW,QFK:LGH'RRU 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡)$;   HPDLOHQJLQHHUV#JURVVPDQVSHHUFRP )25 3$*( 1DNDLVKL %< '$7( 96 &RQGLWLRQ ,QWHULRU:LQGRZ+HDGHU )RRW,QFK:LGH 660$6WXG'HVLQJDWLRQ6:DOO:HLJKW 660$7UDFN'HVLQJDWLRQ76WHHO6WXGV SVI<LHOG6WUHQJWK  NVL  *\SVXP%RDUG%RWK6LGHV SVI 6WXG6SDFLQJ   RF 0LVFDQG,QVXODWLRQ SVI 6WXG6SDQ  IW 7RWDO SVI 2SHQLQJZLGWK  IW2SHQLQJKHLJKW  IW +HLJKWRIZDOODERYHRSHQLQJ  IW +HLJKWRIERWWRPRIRSHQLQJ  IW %R[HG+HDGHU&RPSRVHGRI WUDFNV &ULWHULD EDVHGRQ86*6ZHEVLWHDQG$6&( VWXGV6'6  DS  $6&(7DEOH 5S  $6&(7DEOH ,S  $6&(6HFWLRQ ] IW +HLJKWRISRLQWRIVXSSRUWRIWRSRIZDOO K IW %XLOGLQJKHLJKW +HDGHU6HFWLRQ 6HLVPLF&RHIILFLHQW $6&(6HFWLRQ )S  DS 6'6 :S  ]K  5S,S  :S)SPD[  6'6 ,S :S :S)SPLQ  6'6 ,S :S :S *RYHUQV ZYHUW)S :S 6HLVPLF&RHIILFLHQWVLQ$6'&RQWUROOLQJ&RPELQDWLRQ 6'6 '( )S$6' :S)S$6' SVI ,QWHULRU:DOO/RDGLQ$6')LQWZDOO SVI +HDGHU/RDGLQJ ZKRUL] &DVH,QWHULRU:DOO/RDGZKRUL] SOI ZYHUW SOI 0PD[KRUL] LQN 0PD[YHUW LQN0DOORZKRUL] LQN 0DOORZYHUW LQN0PD[KRUL]0DOORZKRUL]0PD[YHUW0DOORZYHUW  &DVH6HLVPLFZKRUL] SOI ZYHUW SOI 0PD[KRUL] LQN 0PD[YHUW LQN0DOORZKRUL] LQN 0DOORZYHUW LQN 0PD[KRUL]0DOORZKRUL]0PD[YHUW0DOORZYHUW 2. 6WXG'HIOHFWLRQ XQIDFWRUHGORDGV ,KRUL] LQ,YHUW LQ &DVH,QWHULRU:DOO/RDG ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ &DVH6HLVPLF ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ/  LQ 2. ,QWHULRU:DOO:LQGRZ+HDGHU6WHHO6WXG)UDPLQJ )RRW,QFK:LGH 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐ Z/ (, 3DE (,/  LQ &DVH6HLVPLF ѐ Z/ (, 3DE (,/  LQ 2.IRU /  LQ 6 VWXGV ,QWHULRU:DOO:LQGRZ-DPE6WXGV6WHHO6WXG)UDPLQJ )RRW,QFK:LGH 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ &DVH6HLVPLF ѐKRUL] ZKRUL]/ (,KRUL]  LQ ѐYHUW ZYHUW/ (,YHUW  LQ/  LQ 2. ,QWHULRU:DOO:LQGRZ+HDGHU6WHHO6WXG)UDPLQJ )RRW,QFK:LGH 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% *52660$1 63((5$662&,$7(6,1&6758&785$/(1*,1((56 +$+1$9(18(68,7(*/(1'$/(&$/,)251,$  ‡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ѐ Z/ (, 3DE (,/  LQ &DVH6HLVPLF ѐ Z/ (, 3DE (,/  LQ 2.IRU /  LQ 6 VWXGV ,QWHULRU:DOO:LQGRZ-DPE6WXGV6WHHO6WXG)UDPLQJ )RRW,QFK:LGH 352-(&7180%(5  352-(&7 )RRWKLOO&DUGLRORJ\$UFDGLD7HQDQW,PSURYHPHQW 68%-(&7  0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR Seismic Load Coefficient Special Reinforced Masonry Shear Walls SDS = 1.299 R = 5 Ω = 2.5 Cd = 3.5 Ie = 1 CS = SDS / (R / Ie) = 0.26Wp Diaphragm Coefficient Fpx = 0.2SDSIeWp = 0.26Wp 24142 Seismic Load Coefficient 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 Seismic Load (E) Shear Wall With New Openings 0% new openings (E) Shear Wall With New Openings Comp. Model 0% RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Clay Matl 1050 420 0.25 0.6 Custom 1.5 40 40 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Clay Matl 8 Typical 24 Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Distributed 1 DL DL -1 2 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Yes Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Yes Y DL 0.9 Sds*DL -0.2 EL -1 Wall Panel Distributed Loads (BLC 1 : DL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(0ft)Y -312 -312 0 75 2 WP1(18.5ft)Y -280 -280 0 75 Wall Panel Distributed Loads (BLC 2 : EL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(18.5ft)X 1051 1051 0 %100 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@24" oc (ctr)1-#4 2 R2 Not Reqd.#4@24" oc (ctr)1-#4 3 R3 Not Reqd.#4@24" oc (ctr)1-#4 4 R4 Not Reqd.#4@24" oc (ctr)1-#4 5 R5 Not Reqd.#4@24" oc (ctr)1-#4 6 R6 Not Reqd.#4@24" oc (ctr)1-#4 7 R7 Not Reqd.#4@24" oc (ctr)1-#4 8 R8 Not Reqd.#4@24" oc (ctr)1-#4 9 R9 Not Reqd.#4@24" oc (ctr)1-#4 10 R10 Not Reqd.#4@24" oc (ctr)1-#4 11 R11 Not Reqd.#4@24" oc (ctr)1-#4 (E) Shear Wall With New Openings Comp. Model 0% RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 2 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.1749 2 0.4763 3 0.1339 3 133.1491 23.7288 22.3516 2 R2 Typical 0.0246 2 0.1444 3 0.1213 3 202.1935 21.6082 32.717 3 R3 Typical 0.0974 2 0.9514 3 0.1997 4 445.0986 118.651 110.2737 4 R4 Typical 0.0164 2 0.1804 4 0.2046 4 202.1935 22.6426 34.7183 5 R5 Typical 0.0805 1 0.6773 4 0.2171 4 798.8949 362.0152 218.1694 6 R6 Typical 0.0166 2 0.2251 4 0.1664 2 303.2902 34.781 52.6096 7 R7 Typical 0.1042 2 0.6114 3 0.2189 3 155.9747 39.6369 28.6921 8 R8 Typical 0.0161 1 0.2494 3 0.1672 1 334.883 38.6252 58.3562 9 R9 Typical 0.0966 1 0.9119 4 0.2288 1 437.49 141.6298 112.3407 10 R10 Typical 0.0242 1 0.1598 4 0.1324 4 202.1935 21.6082 32.6992 11 R11 Typical 0.178 1 0.5247 4 0.1404 1 133.1491 23.7288 27.0659 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 172.9408 2 104.1783 1 0 4 0 4 1763.3114 2 2 0 min 75.8437 3 -104.1781 2 0 1 0 1 -1684.9485 3 (E) Shear Wall With New Openings Comp. Model 0% Detail Report: WP1 Masonry Wall R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11L1 L2 L3 L4 L5 N1 N13 N15 N26 18 . 5 f t 75 ft CRITERIA Code:TMS 402-16: Strength Special Insp:No Design Rule:Typical Seismic Design Rule:None Wall Area:NCMA Transfer In?:No Transfer Out?:No K:1 Use Cracked?:Yes In Icr Factor:0.5 Out Icr Factor:0.5 Custom Regions:No MATERIALS Material Type:Masonry Material Set:Clay Matl Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Mortar Type:Type M or S Cement Type:Portland, Lime/Mortar GEOMETRY Total Height (ft):18.5 Total Length (ft):75 Total Lintel Depth (in):16 Block Nom Width:8" Block Grouting:Fully Grouted 1.5 Shear Factor:No REGION RESULTS Region UC Max In Plane LC UC Shear In Plane LC UC Max Out Plane LC UC Shear Out Plane LC R1 0.4763 3 0.1339 3 0.1576 2 NC NC R2 0.1444 3 0.1213 3 0.0222 2 NC NC R3 0.9514 3 0.1997 4 0.0878 2 NC NC R4 0.1804 4 0.2046 4 0.0148 2 NC NC R5 0.6773 4 0.2171 4 0.0725 1 NC NC R6 0.2251 4 0.1664 2 0.0149 2 NC NC R7 0.6114 3 0.2189 3 0.0939 2 NC NC R8 0.2494 3 0.1672 1 0.0145 1 NC NC R9 0.9119 4 0.2288 1 0.0871 1 NC NC R10 0.1598 4 0.1324 4 0.0218 1 NC NC R11 0.5247 4 0.1404 1 0.1604 1 NC NC REINFORCEMENT RESULTS Region Vertical Reinforcement Horizontal Reinforcement Boundary Reinforcement R1 #4@24" oc ctr Not Reqd.1-#4 ctr R2 #4@24" oc ctr Not Reqd.1-#4 ctr R3 #4@24" oc ctr Not Reqd.1-#4 ctr R4 #4@24" oc ctr Not Reqd.1-#4 ctr R5 #4@24" oc ctr Not Reqd.1-#4 ctr R6 #4@24" oc ctr Not Reqd.1-#4 ctr R7 #4@24" oc ctr Not Reqd.1-#4 ctr R8 #4@24" oc ctr Not Reqd.1-#4 ctr R9 #4@24" oc ctr Not Reqd.1-#4 ctr R10 #4@24" oc ctr Not Reqd.1-#4 ctr R11 #4@24" oc ctr Not Reqd.1-#4 ctr LINTEL REINFORCEMENT RESULTS Lintel Flexural Reinforcement Shear Reinforcement L1 1-#4 Not Reqd. L2 1-#4 Not Reqd. L3 1-#4 Not Reqd. L4 1-#4 Not Reqd. L5 1-#4 Not Reqd. RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1Masonry Wall R1R2R3R4R5R6R7R8R9R10R11L1L2L3L4L5N1 N13 N15 N26 18.5 ft 75 ftCRITERIACode:TMS 402-16: StrengthSpecial Insp:NoDesign Rule:TypicalSeismic Design Rule:NoneWall Area:NCMATransfer In?:NoTransfer Out?:NoK:1Use Cracked?:YesIn Icr Factor:0.5Out Icr Factor:0.5Custom Regions:No MATERIALSMaterial Type:MasonryMaterial Set:Clay MatlMasonry f'm (ksi):1.5Masonry Em (ksi):1050Steel fy (ksi):40Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfMortar Type:Type M or SCement Type:Portland, Lime/MortarGEOMETRYTotal Height (ft):18.5Total Length (ft):75Total Lintel Depth (in):16Block Nom Width:8"Block Grouting:Fully Grouted1.5 Shear Factor:NoREGION RESULTSRegionUC Max In Plane LC UC Shear In Plane LC UC Max Out Plane LC UC Shear Out Plane LCR10.4763 3 0.1339 3 0.1576 2 NC NCR20.1444 3 0.1213 3 0.0222 2 NC NCR30.9514 3 0.1997 4 0.0878 2 NC NCR40.1804 4 0.2046 4 0.0148 2 NC NCR50.6773 4 0.2171 4 0.0725 1 NC NCR60.2251 4 0.1664 2 0.0149 2 NC NCR70.6114 3 0.2189 3 0.0939 2 NC NCR80.2494 3 0.1672 1 0.0145 1 NC NCR90.9119 4 0.2288 1 0.0871 1 NC NCR100.1598 4 0.1324 4 0.0218 1 NC NCR110.5247 4 0.1404 1 0.1604 1 NC NCREINFORCEMENT RESULTSRegion Vertical Reinforcement Horizontal Reinforcement Boundary Reinforcement R1 #4@24" oc ctr Not Reqd.1-#4 ctr R2 #4@24" oc ctr Not Reqd.1-#4 ctr R3 #4@24" oc ctr Not Reqd.1-#4 ctr R4 #4@24" oc ctr Not Reqd.1-#4 ctr R5 #4@24" oc ctr Not Reqd.1-#4 ctr R6 #4@24" oc ctr Not Reqd.1-#4 ctr R7 #4@24" oc ctr Not Reqd.1-#4 ctr R8 #4@24" oc ctr Not Reqd.1-#4 ctr R9 #4@24" oc ctr Not Reqd.1-#4 ctr R10 #4@24" oc ctr Not Reqd.1-#4 ctr R11 #4@24" oc ctr Not Reqd.1-#4 ctr LINTEL REINFORCEMENT RESULTS Lintel Flexural Reinforcement Shear Reinforcement L1 1-#4 Not Reqd. L2 1-#4 Not Reqd. L3 1-#4 Not Reqd. L4 1-#4 Not Reqd. L5 1-#4 Not Reqd. RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 2 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):42 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):3.5 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 23.2848 at 0 ft Min: -8.0381 at 6.475 ft P k Max: 2.9934 at 18.5 ft Min: -3.4792 at 0 ft V k Max: 14.1873 at 0 ft Min: -11.3017 at 0 ft M k-ft WARNINGProgram does not design masonry wall for axial tension. AXIAL DETAILS P/(Pn*Φ):0.175 P (k):23.285 Pn (k):147.943 Φ:0.9 Location (ft):0 Load Comb:2 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.476 Mu (k-ft):11.302 Mn (k-ft):26.365 Φ:0.9 Location (ft):0 Load Comb:3 a (in):1.717 c (in):2.146 d (in):42 SHEAR SUMMARY Vu/(Vn*Φ):0.134 Vu (k):2.993 Vn (k):27.94 Φ:0.8 Location (ft):18.5 Load Comb:3 Corresponding M (k- ft): 14.187 Corresponding P (k):0.129 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% 0Q  $V I\ GD                Detail Report: WP1 (In-Plane, Region R1)CRITERIACode:TMS 402-16: StrengthSpecial Insp:NoWall Area:NCMAHor Bar Size:#4Vert Bar Size:#4No. Tens Bars:1Effective Depth (in):42 MATERIALSMasonry f'm (ksi):1.5Masonry Em (ksi):1050Steel fy (ksi):40Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfWall Dead Wt (psf):78GEOMETRYTotal Height (ft):18.5Total Length (ft):3.5Block Grouting:Fully GroutedGrout Spacing:24"Block Nom Width:8"1.5 Shear Factor:NoENVELOPE DIAGRAMSMax: 23.2848 at 0 ftMin: -8.0381 at 6.475 ftPk Max: 2.9934 at 18.5 ftMin: -3.4792 at 0 ftVk Max: 14.1873 at 0 ftMin: -11.3017 at 0 ftMk-ftWARNINGProgram does not design masonry wall for axial tension.AXIAL DETAILSP/(Pn*Φ):0.175P (k):23.285Pn (k):147.943 Φ:0.9Location (ft):0Load Comb:2 Rad gyration r (in):2.2h'/r:100.909Red Factor R:0.481BENDING SUMMARYMu/(Mn*Φ):0.476 Mu (k-ft):11.302 Mn (k-ft):26.365 Φ:0.9 Location (ft):0 Load Comb:3 a (in):1.717 c (in):2.146 d (in):42 SHEAR SUMMARY Vu/(Vn*Φ):0.134 Vu (k):2.993 Vn (k):27.94 Φ:0.8 Location (ft):18.5 Load Comb:3 Corresponding M (k- ft): 14.187 Corresponding P (k):0.129 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 2 (E) Shear Wall With New Openings Comp. Results 0% 9Q   0X 9 G $QY VTUW I P  3X       VTUW   Detail Report: WP1 (In-Plane, Region R3) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):140.4 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):11.7 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 43.3695 at 0 ft Min: 4.8162 at 18.5 ft P k Max: 21.1152 at 0 ft Min: -22.6012 at 0 ft V k Max: 123.5712 at 0 ft Min: -112.881 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.097 P (k):43.369 Pn (k):494.554 Φ:0.9 Location (ft):0 Load Comb:2 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.951 Mu (k-ft):112.881 Mn (k-ft):131.834 Φ:0.9 Location (ft):0 Load Comb:3 a (in):2.281 c (in):2.852 d (in):140.4 SHEAR SUMMARY Vu/(Vn*Φ):0.2 Vu (k):22.021 Vn (k):137.842 Φ:0.8 Location (ft):0 Load Comb:4 Corresponding M (k- ft): 123.571 Corresponding P (k):23.601 M / (V*d):0.467 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R5) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):252 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):21 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 64.2741 at 0 ft Min: 8.6297 at 18.5 ft P k Max: 46.2524 at 0 ft Min: -48.0673 at 0 ft V k Max: 245.2051 at 0 ft Min: -262.1564 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.08 P (k):64.274 Pn (k):887.661 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.677 Mu (k-ft):245.205 Mn (k-ft):402.239 Φ:0.9 Location (ft):0 Load Comb:4 a (in):3.338 c (in):4.172 d (in):252 SHEAR SUMMARY Vu/(Vn*Φ):0.217 Vu (k):47.357 Vn (k):272.712 Φ:0.8 Location (ft):0 Load Comb:4 Corresponding M (k- ft): 238.612 Corresponding P (k):23.279 M / (V*d):0.236 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R7) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):49.2 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):4.1 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 16.2544 at 0 ft Min: 1.6731 at 18.5 ft P k Max: 6.3216 at 0 ft Min: -6.214 at 0 ft V k Max: 23.8453 at 0 ft Min: -24.4811 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.104 P (k):16.254 Pn (k):173.305 Φ:0.9 Location (ft):0 Load Comb:2 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.611 Mu (k-ft):24.232 Mn (k-ft):44.041 Φ:0.9 Location (ft):0 Load Comb:3 a (in):2.268 c (in):2.836 d (in):49.2 SHEAR SUMMARY Vu/(Vn*Φ):0.219 Vu (k):6.279 Vn (k):35.865 Φ:0.8 Location (ft):0 Load Comb:3 Corresponding M (k- ft): 24.481 Corresponding P (k):7.055 M / (V*d):0.945 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R9) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):138 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):11.5 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 42.2808 at 0 ft Min: 4.7755 at 18.5 ft P k Max: 25.7036 at 0 ft Min: -22.6044 at 0 ft V k Max: 129.157 at 0 ft Min: -137.4301 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.097 P (k):42.281 Pn (k):486.1 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.912 Mu (k-ft):129.157 Mn (k-ft):157.366 Φ:0.9 Location (ft):0 Load Comb:4 a (in):2.582 c (in):3.227 d (in):138 SHEAR SUMMARY Vu/(Vn*Φ):0.229 Vu (k):25.704 Vn (k):140.426 Φ:0.8 Location (ft):0 Load Comb:1 Corresponding M (k- ft): 137.43 Corresponding P (k):42.281 M / (V*d):0.465 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R11) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):42 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1050 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18.5 Total Length (ft):3.5 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 23.7005 at 0 ft Min: -8.5818 at 6.475 ft P k Max: 3.7989 at 0 ft Min: -3.0031 at 18.5 ft V k Max: 12.4508 at 0 ft Min: -15.6207 at 0 ft M k-ft WARNINGProgram does not design masonry wall for axial tension. AXIAL DETAILS P/(Pn*Φ):0.178 P (k):23.701 Pn (k):147.943 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:100.909 Red Factor R:0.481 BENDING SUMMARY Mu/(Mn*Φ):0.525 Mu (k-ft):12.451 Mn (k-ft):26.365 Φ:0.9 Location (ft):0 Load Comb:4 a (in):1.717 c (in):2.146 d (in):42 SHEAR SUMMARY Vu/(Vn*Φ):0.14 Vu (k):3.799 Vn (k):33.832 Φ:0.8 Location (ft):0 Load Comb:1 Corresponding M (k- ft): 15.621 Corresponding P (k):23.701 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 1 (E) Shear Wall With New Openings Comp. Results 0% Detail Report: WP1 (In-Plane, Region R11)CRITERIACode:TMS 402-16: StrengthSpecial Insp:NoWall Area:NCMAHor Bar Size:#4Vert Bar Size:#4No. Tens Bars:1Effective Depth (in):42 MATERIALSMasonry f'm (ksi):1.5Masonry Em (ksi):1050Steel fy (ksi):40Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfWall Dead Wt (psf):78GEOMETRYTotal Height (ft):18.5Total Length (ft):3.5Block Grouting:Fully GroutedGrout Spacing:24"Block Nom Width:8"1.5 Shear Factor:NoENVELOPE DIAGRAMSMax: 23.7005 at 0 ftMin: -8.5818 at 6.475 ftPk Max: 3.7989 at 0 ftMin: -3.0031 at 18.5 ftVk Max: 12.4508 at 0 ftMin: -15.6207 at 0 ftMk-ftWARNINGProgram does not design masonry wall for axial tension.AXIAL DETAILSP/(Pn*Φ):0.178P (k):23.701Pn (k):147.943 Φ:0.9Location (ft):0Load Comb:1 Rad gyration r (in):2.2h'/r:100.909Red Factor R:0.481BENDING SUMMARYMu/(Mn*Φ):0.525 Mu (k-ft):12.451 Mn (k-ft):26.365 Φ:0.9 Location (ft):0 Load Comb:4 a (in):1.717 c (in):2.146 d (in):42 SHEAR SUMMARY Vu/(Vn*Φ):0.14 Vu (k):3.799 Vn (k):33.832 Φ:0.8 Location (ft):0 Load Comb:1 Corresponding M (k- ft): 15.621 Corresponding P (k):23.701 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(5).r3d ]Page 2 (E) Shear Wall With New Openings Comp. Results 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 (N) CMU Shear Wall Loads and diaphragm (High Roof) 0% (N) CMU Shear Wall Comp. Model (High Roof)0% RISA-3D Version 22 [ 24142 in-plane(11).r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Concrete Matl 1350 540 0.25 0.6 Custom 2 60 60 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Concrete Matl 8 Typical 16 2 WP2 N31 N20 N1 N21 Concrete Conc3000NW 48 Typical N/A Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Distributed 1 DL DL -1 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Y DL 0.9 Sds*DL -0.2 EL -1 Wall Panel Distributed Loads (BLC 2 : EL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(18ft)X 688 688 0 8.58 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@16" oc (ctr)1-#4 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.0383 1 0.8792 2 0.1355 1 459.5984 152.9836 66.714 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 17.5852 2 9.0377 1 0 2 0 2 134.4998 2 2 0 min 17.5852 1 -9.0385 2 0 1 0 1 -134.4853 1 (N) CMU Shear Wall Comp. Model (High Roof)0% Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):102.96 MATERIALS Masonry f'm (ksi):2 Masonry Em (ksi):1350 Steel fy (ksi):60 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):18 Total Length (ft):8.58 Block Grouting:Fully Grouted Grout Spacing:16" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 17.5852 at 0 ft Min: 0 at 18 ft P k Max: 9.0377 at 0 ft Min: -9.0385 at 0 ft V k Max: 134.4998 at 0 ft Min: -134.4853 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.038 P (k):17.585 Pn (k):510.665 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:98.182 Red Factor R:0.508 BENDING SUMMARY Mu/(Mn*Φ):0.879 Mu (k-ft):134.5 Mn (k-ft):169.982 Φ:0.9 Location (ft):0 Load Comb:2 a (in):2.649 c (in):3.311 d (in):102.96 SHEAR SUMMARY Vu/(Vn*Φ):0.135 Vu (k):9.038 Vn (k):83.392 Φ:0.8 Location (ft):0 Load Comb:1 Corresponding M (k- ft): 134.5 Corresponding P (k):17.585 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(11).r3d ]Page 1 (N) CMU Shear Wall Comp. Results (High Roof)0% Detail Report: WP1 (In-Plane, Region R1)CRITERIACode:TMS 402-16: StrengthSpecial Insp:NoWall Area:NCMAHor Bar Size:#4Vert Bar Size:#4No. Tens Bars:1Effective Depth (in):102.96 MATERIALSMasonry f'm (ksi):2Masonry Em (ksi):1350Steel fy (ksi):60Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfWall Dead Wt (psf):78GEOMETRYTotal Height (ft):18Total Length (ft):8.58Block Grouting:Fully GroutedGrout Spacing:16"Block Nom Width:8"1.5 Shear Factor:NoENVELOPE DIAGRAMSMax: 17.5852 at 0 ftMin: 0 at 18 ft Pk Max: 9.0377 at 0 ftMin: -9.0385 at 0 ftVk Max: 134.4998 at 0 ftMin: -134.4853 at 0 ftMk-ftAXIAL DETAILSP/(Pn*Φ):0.038P (k):17.585Pn (k):510.665 Φ:0.9Location (ft):0Load Comb:1 Rad gyration r (in):2.2h'/r:98.182Red Factor R:0.508BENDING SUMMARYMu/(Mn*Φ):0.879Mu (k-ft):134.5Mn (k-ft):169.982 Φ:0.9Location (ft):0Load Comb:2 a (in):2.649c (in):3.311d (in):102.96SHEAR SUMMARYVu/(Vn*Φ):0.135Vu (k):9.038 Vn (k):83.392 Φ:0.8 Location (ft):0Load Comb:1 Corresponding M (k- ft): 134.5 Corresponding P (k):17.585 M / (V*d):1Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(11).r3d ]Page 2 (N) CMU Shear Wall Comp. Results (High Roof)0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 (N) CMU Shear Wall Loads and diaphragm (Low Roof, Short Wall) 0% (N) CMU Shear Wall Comp. Model (Low Roof, Short Wall)0% RISA-3D Version 22 [ 24142 in-plane(9).r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Concrete Matl 1350 540 0.25 0.6 Custom 2 60 60 2 Clay Matl 1050 420 0.25 0.6 Custom 2 60 60 3 Gen Masonry 1050 420 0.25 0.6 79.999 2 60 60 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Clay Matl 8 Typical 24 2 WP2 N31 N20 N1 N21 Concrete Conc3000NW 36 Typical N/A Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Distributed 1 DL DL -1 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Y DL 0.9 Sds*DL -0.2 EL -1 Wall Panel Distributed Loads (BLC 2 : EL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(10ft)X 630 630 0 8.83 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@24" oc (ctr)1-#4 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.0127 1 0.4991 1 0.1092 1 789.4679 129.4114 67.3239 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 10.0542 2 7.3543 1 0 2 0 2 64.5866 2 2 0 min 10.0542 1 -7.3544 2 0 1 0 1 -64.5854 1 (N) CMU Shear Wall Comp. Model (Low Roof, Short Wall)0% Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):105.96 MATERIALS Masonry f'm (ksi):2 Masonry Em (ksi):1050 Steel fy (ksi):60 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):10 Total Length (ft):8.83 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 10.0542 at 0 ft Min: 0 at 10 ft P k Max: 7.3543 at 0 ft Min: -7.3544 at 0 ft V k Max: 64.5866 at 0 ft Min: -64.5854 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.013 P (k):10.054 Pn (k):877.187 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:54.545 Red Factor R:0.848 BENDING SUMMARY Mu/(Mn*Φ):0.499 Mu (k-ft):64.585 Mn (k-ft):143.79 Φ:0.9 Location (ft):0 Load Comb:1 a (in):2.269 c (in):2.835 d (in):105.96 SHEAR SUMMARY Vu/(Vn*Φ):0.109 Vu (k):7.354 Vn (k):84.155 Φ:0.8 Location (ft):0 Load Comb:1 Corresponding M (k- ft): 64.587 Corresponding P (k):10.054 M / (V*d):0.995 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(9).r3d ]Page 1 (N) CMU Shear Wall Comp. Results (Low Roof, Short Wall)0% Detail Report: WP1 (In-Plane, Region R1)CRITERIACode:TMS 402-16: StrengthSpecial Insp:NoWall Area:NCMAHor Bar Size:#4Vert Bar Size:#4No. Tens Bars:1Effective Depth (in):105.96 MATERIALSMasonry f'm (ksi):2Masonry Em (ksi):1050Steel fy (ksi):60Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfWall Dead Wt (psf):78GEOMETRYTotal Height (ft):10Total Length (ft):8.83Block Grouting:Fully GroutedGrout Spacing:24"Block Nom Width:8"1.5 Shear Factor:NoENVELOPE DIAGRAMSMax: 10.0542 at 0 ftMin: 0 at 10 ft Pk Max: 7.3543 at 0 ftMin: -7.3544 at 0 ftVk Max: 64.5866 at 0 ftMin: -64.5854 at 0 ftMk-ftAXIAL DETAILSP/(Pn*Φ):0.013P (k):10.054Pn (k):877.187 Φ:0.9Location (ft):0Load Comb:1 Rad gyration r (in):2.2h'/r:54.545Red Factor R:0.848BENDING SUMMARYMu/(Mn*Φ):0.499Mu (k-ft):64.585Mn (k-ft):143.79 Φ:0.9Location (ft):0Load Comb:1 a (in):2.269c (in):2.835d (in):105.96SHEAR SUMMARYVu/(Vn*Φ):0.109Vu (k):7.354 Vn (k):84.155 Φ:0.8 Location (ft):0Load Comb:1 Corresponding M (k- ft): 64.587 Corresponding P (k):10.054 M / (V*d):0.995Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(9).r3d ]Page 2 (N) CMU Shear Wall Comp. Results (Low Roof, Short Wall)0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 (N) CMU Shear Wall Loads and diaphragm (Low Roof, Long Wall) 0% (N) CMU Shear Wall Comp. Model (Low Roof, Long Wall)0% RISA-3D Version 22 [ 24142 in-plane(8).r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Concrete Matl 1350 540 0.25 0.6 Custom 2 60 60 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Concrete Matl 8 Typical 16 2 WP2 N27 N29 N33 N31 Masonry Concrete Matl 8 Typical 16 3 WP3 N28 N30 N34 N32 Masonry Concrete Matl 8 Typical 16 Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Distributed 1 DL DL -1 1 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Yes Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Yes Y DL 0.9 Sds*DL -0.2 EL -1 Wall Panel Distributed Loads (BLC 1 : DL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(0ft)Y -900 -900 0 13.83 Wall Panel Distributed Loads (BLC 2 : EL) Wall Label Direction Start Magnitude [lb/ft, F]End Magnitude [lb/ft, F]Start Location [(ft, %)]End Location [(ft, %)] 1 WP1(10ft)X 889 889 0 %100 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@16" oc (ctr)1-#4 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.0115 2 0.2827 3 0.1005 3 1236.5052 144.708 169.9627 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 14.2369 2 16.8338 1 0 3 0 3 40.7241 4 2 0 min -0.8089 3 -16.8379 2 0 2 0 1 -40.904 3 (N) CMU Shear Wall Comp. Model (Low Roof, Long Wall)0% Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:1 Effective Depth (in):165.96 MATERIALS Masonry f'm (ksi):2 Masonry Em (ksi):1350 Steel fy (ksi):60 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):10 Total Length (ft):13.83 Block Grouting:Fully Grouted Grout Spacing:16" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 14.2369 at 0 ft Min: -1.0071 at 1.5 ft P k Max: 17.2762 at 1 ft Min: -17.2548 at 1 ft V k Max: 40.7241 at 0 ft Min: -40.904 at 0 ft M k-ft WARNINGProgram does not design masonry wall for axial tension. AXIAL DETAILS P/(Pn*Φ):0.012 P (k):14.237 Pn (k):1373.895 Φ:0.9 Location (ft):0 Load Comb:2 Rad gyration r (in):2.2 h'/r:54.545 Red Factor R:0.848 BENDING SUMMARY Mu/(Mn*Φ):0.283 Mu (k-ft):40.904 Mn (k-ft):160.787 Φ:0.9 Location (ft):0 Load Comb:3 a (in):1.834 c (in):2.293 d (in):165.96 SHEAR SUMMARY Vu/(Vn*Φ):0.101 Vu (k):17.088 Vn (k):212.453 Φ:0.8 Location (ft):1 Load Comb:3 Corresponding M (k- ft): 33.573 Corresponding P (k):0 M / (V*d):0.141 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(8).r3d ]Page 1 (N) CMU Shear Wall Comp. Results (Low Roof, Long Wall)0% Detail Report: WP1 (In-Plane, Region R1)CRITERIACode:TMS 402-16: StrengthSpecial Insp:NoWall Area:NCMAHor Bar Size:#4Vert Bar Size:#4No. Tens Bars:1Effective Depth (in):165.96 MATERIALSMasonry f'm (ksi):2Masonry Em (ksi):1350Steel fy (ksi):60Steel E (ksi):29000Block Material:Conc 115 pcfGrout Weight:140 pcfWall Dead Wt (psf):78GEOMETRYTotal Height (ft):10Total Length (ft):13.83Block Grouting:Fully GroutedGrout Spacing:16"Block Nom Width:8"1.5 Shear Factor:NoENVELOPE DIAGRAMSMax: 14.2369 at 0 ftMin: -1.0071 at 1.5 ftPk Max: 17.2762 at 1 ftMin: -17.2548 at 1 ftVk Max: 40.7241 at 0 ftMin: -40.904 at 0 ftMk-ftWARNINGProgram does not design masonry wall for axial tension.AXIAL DETAILSP/(Pn*Φ):0.012P (k):14.237Pn (k):1373.895 Φ:0.9Location (ft):0Load Comb:2 Rad gyration r (in):2.2h'/r:54.545Red Factor R:0.848BENDING SUMMARYMu/(Mn*Φ):0.283 Mu (k-ft):40.904 Mn (k-ft):160.787 Φ:0.9 Location (ft):0 Load Comb:3 a (in):1.834 c (in):2.293 d (in):165.96 SHEAR SUMMARY Vu/(Vn*Φ):0.101 Vu (k):17.088 Vn (k):212.453 Φ:0.8 Location (ft):1 Load Comb:3 Corresponding M (k- ft): 33.573 Corresponding P (k):0 M / (V*d):0.141 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(8).r3d ]Page 2 (N) CMU Shear Wall Comp. Results (Low Roof, Long Wall)0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 1 2/10/2025 Specifier's comments: 1 Input data Anchor type and diameter: HY 270 + HAS-R 304/316 SS 1/2 Item number: 2045004 HAS-R 316 SS 1/2"x8" (element) / 2194247 HIT-HY 270 (adhesive) Specification text: Hilti Æ 1/2 HY 270 + HAS-R 304/316 SS with 6 in nominal embedment depth per ICC-ES ESR-4143 , Hammer drilled installation per MPII Effective embedment depth: hef = 6.000 in. Material: ASTM F 593 Evaluation Service Report: ESR-4143 Issued I Valid: 11/1/2023 | 1/1/2025 Proof: Design Method LRFD (AC58) Masonry + ACI 318-19 Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.400 in. Anchor plateR : lx x ly x t = 12.000 in. x 8.000 in. x 0.400 in.; (Recommended plate thickness: not calculated) Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x 4.000 in. x 0.250 in. Base material: cracked Grout-filled CMU, f=2000, f = 1,999 psi, L x W x H: 16.000 in. x 8.000 in. x 8.000 in.; Solid Head Joint: no; open ended unit: no Temp. short/long: 32 °F / 32 °F Joints: vertical: 0.375 in.; horizontal: 0.375 in. Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d)) Shear load: yes (17.10.6.3 (c)) R - The anchor calculation is based on a rigid anchor plate assumption. (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 2 2/10/2025 Geometry [in.] (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 3 2/10/2025 Geometry [in.] & Loading [lb, in.lb] 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 0; Vx = 2,396; Vy = 0; Mx = 0; My = 0; Mz = 0; Nsus = 0; Mx,sus = 0; My,sus = 0; yes 80 1 x y 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 0 2,396 2,396 0 Max. concrete compressive strain: 0.00 [‰] Max. concrete compressive stress: 0 [psi] Resulting tension force in (x/y)=(-/-): 0 [lb] Resulting compression force in (x/y)=(-/-): 0 [lb] Anchor forces are calculated based on the assumption of a rigid anchor plate. (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 4 2/10/2025 3 Shear load Load [lb]Capacity [lb]Utilization bV [%]Status Steel 2,396 3,576 67 OK Pryout bond 2,396 3,445 70 OK Masonry crushing strength 2,396 3,591 67 OK Masonry breakout in direction x+2,396 3,010 80 OK 3.1 Steel strength Vsa = ESR value refer to ICC-ES ESR-4143 f Vsa ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 Vsa,seismic [lb]f f seismic f Vsa [lb]Vua [lb] 5,960 0.600 1.000 3,576 2,396 3.2 Pryout strength (Bond strength controls) Vmpg =min(kcp · Nmag, kcp · Nmbg)f Vmpg ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 ANa see ACI 318-19, Section 17.6.5.1, Fig. 17.6.5.1(b) ANa0 = (2 cNa)2 ACI 318-19 Eq. (17.6.5.1.2a) cNa = 10 da √t uncr,m1100 ACI 318-19 Eq. (17.6.5.1.2b) y ec,Na = (1 1 + e' NcNa )£ 1.0 ACI 318-19 Eq. (17.6.5.3.1) y ed,Na = 0.7 + 0.3 (ca,min cac )£ 1.0 ACI 318-19 Eq. (17.6.5.4.1b) Nba,m = l a · t cr,m · p · da · hef ACI 318-19 Eq. (17.6.5.2.1) Variables kcp da [in.]hef [in.]ca,min [in.]t uncr,m [psi]t cr,m [psi] 2 0.500 6.000 3.813 435 300 asat atop aV,seis ec1,N [in.]ec2,N [in.]l a 1.000 1.000 0.870 0.000 0.000 1.000 Calculations cNa [in.]ANa [in.2]ANa0 [in.2]y ed,Na y ec1,Na y ec2,Na 3.131 39.20 39.20 1.000 1.000 1.000 y cp,Na Nba,m [lb] 1.000 2,461 Results Vmpg [lb]f f seismic f Vmpg [lb]Vua [lb] 4,921 0.700 1.000 3,445 2,396 LRFD overstrength diaph load : 671plf/0.7*2.5 (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 5 2/10/2025 3.3 Masonry crushing strength f Vmc ³ Vua AC58 Table 3.2 Vmc = 1750 · (f' m · Ase,V) 14 AC58 Eq. 3-1 Variables f' m [psi]Ase,v [in.2] 1,999 0.14 Results Vmc [lb]f f seismic f Vmc [lb]Vua [lb] 7,182 0.500 1.000 3,591 2,396 3.4 Masonry breakout strength x+ Vmb = (AVm AVm0)y ed,V,m y m,V y h,V,m y parallel,V Vb,m ACI 318-19 Eq. (17.7.2.1a) f Vmb ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 AVm see ACI 318-19 , Section 17.7.2.1, Fig. R 17.7.2.1(b) AVm0 = 4.5 c2 a1 ACI 318-19 Eq. (17.7.2.1.3) y ec,V,m = (1 1 + 2e' v3ca1 )£ 1.0 ACI 318-19 Eq. (17.7.2.3.1) y ed,V,m = 0.7 + 0.3(ca2 1.5ca1)£ 1.0 ACI 318-19 Eq. (17.7.2.4.1b) y h,V,m = √1.5ca1ha ³ 1.0 ACI 318-19 Eq. (17.7.2.6.1) Vb,m = (7 (le da)0.2 √da)l a √f' m c1.5 a1 ACI 318-19 Eq. (17.7.2.2.1a) Variables le [in.]da [in.]ca1 [in.]ca2 [in.]AVm [in.2]AVm0 [in.2]f' m [psi] 4.000 0.500 12.187 4.000 169.89 668.41 1,999 Calculations y ed,V,m y parallel,V ec,V [in.]y ec,V,m y m,V y h,V,m 0.766 1.000 0.000 1.000 1.000 1.548 Results Vb,m [lb]f f seismic f Vmbg [lb]Vua [lb] 14,270 0.700 1.000 3,010 2,396 (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | Copy - Masonry - Feb 10, 2025 Page: Specifier: E-Mail: Date: 6 2/10/2025 4 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Refer to the manufacturer's product literature for cleaning and installation instructions. • For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/ • The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG. • Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS! • Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar joints. • The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration. • If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void. • The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use provided with the product have to be followed to ensure a proper installation. • The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user. • Drilling method (hammer, rotary) to be in accordance with the approval! • Masonry needs to be built in a regular way in accordance with state-of the art guidelines! Fastening meets the design criteria! (N) CMU Shear Wall Diaphragm anchorage detail 21/S6 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 5'-0" w1 16'-6" Wall out-of plane connection detail 17/S6 & 19/S6 R=0.57k 1'-6" w1 20'-0" R=0.47k 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 1'-0" w1 10'-0" Wall out-of plane connection detail 20/S7 8'-6" R=0.47k 3'-3" w1 10'-0" R=0.36k 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRSubdiaphragm 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRWall out-of plane strongback 1'-3" w1 19'-0" R=0.44k 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRWall out-of plane strongback 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR w1 18'-6" R=0.38k Wall out-of plane bending new CMU wall w1 10'-0" R=0.2k Low roof High roof R=0.2k R=0.38k 24142 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 Wall out-of plane (N) through-bolt and (E) Truss Connection 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 1 2/3/2025 Specifier's comments: 1 Input data Anchor type and diameter: HY 200-A V3 + threaded rod 5.8 5/8 Item number: 385428 HAS 5.8 5/8"x8" (element) / 2334276 HIT-HY 200-R V3 (adhesive) Specification text: Hilti Æ 5/8 HY 200-A V3 + threaded rod 5.8 with 5.645 in nominal embedment depth per ICC-ES ESR-4878 , Hammer drilled installation per MPII Effective embedment depth: hef = 5.645 in. Material: 5.8 Evaluation Service Report: ESR-4878 Issued I Valid: 11/1/2023 | 11/1/2024 Proof: Design Method LRFD (AC58) Masonry + ACI 318-19 Stand-off installation: Profile: Base material: cracked Grout-filled CMU, f=1500, f = 1,500 psi, L x W x H: 16.000 in. x 8.000 in. x 8.000 in.; Solid Head Joint: no; open ended unit: no Temp. short/long: 32 °F / 32 °F Joints: vertical: 0.375 in.; horizontal: 0.375 in. Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d)) Shear load: yes (17.10.6.3 (c)) Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 2 2/3/2025 Geometry [in.] Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 3 2/3/2025 Geometry [in.] & Loading [lb, in.lb] 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 2,800; Vx = 0; Vy = 0; Mx = 0; My = 0; Mz = 0; Nsus = 0; Mx,sus = 0; My,sus = 0; yes 100 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 2,800 0 0 0 Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 4 2/3/2025 3 Tension load Load [lb]Capacity [lb]Utilization bN [%]Status Steel 2,800 10,650 27 OK Bond 2,800 3,101 91 OK Masonry breakout 2,800 2,804 100 OK 3.1 Steel strength Nsa = ESR value refer to ICC-ES ESR-4878 f Nsa ³ Nua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 Nsa,seismic [lb]f f seismic f Nsa [lb]Nua [lb] 16,384 0.650 1.000 10,650 2,800 3.2 Bond strength Nma = (ANaANa0) · y ec1,Na · y ec2,Na · y ed,Na · Nba,m ACI 318-19 Eq. (17.6.5.1a) f Nma ³ Nua AC58 Table 3.2 + ACI 318-19 Table D.4.1.1 ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b) ANa0 = (2 cNa)2 ACI 318-19 Eq. (17.6.5.1.2a) cNa = 10 da √t uncr,m1100 ACI 318-19 Eq. (17.6.5.1.2b) y ed,Na = 0.7 + 0.3 (ca,min cNa )£ 1.00 ACI 318-19 Eq. (17.6.5.4.1b) Nba,m = l a · t cr,m · p · da · hef ACI 318-19 Eq. (17.6.5.2.1) Variables da [in.]hef [in.]ca,min [in.]t uncr,m [psi]t cr,m [psi]asat atop 0.625 5.645 7.813 897 574 1.000 1.000 l a aN,seis 1.000 1.000 Calculations cNa [in.]ANa [in.2]ANa0 [in.2]y ed,Na 5.618 126.27 126.27 1.000 Nba,m [lb] 6,362 Results Nma [lb]f f seismic f Nma [lb]f Nua [lb] 6,362 0.650 0.750 3,101 2,800 Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 5 2/3/2025 3.3 Masonry breakout strength Nmb = ANm ANm0 · y ed,N,m · y c,N,m · Nb,m ACI 318-19 Eq. (17.6.5.1a) f Nmb ³ Nua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 ANm see ACI 318-19, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANm0 = 9 · h2 ef ACI 318-19 Eq. (17.6.2.2.1) y ed,N = 0.7 + 0.3 ca,min 1.5 · hef £ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) Nb,m = km · l a · √f' m · h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables hef [in.]ca,min [in.]y c,N,m kc 5.645 7.813 1.000 12 l a f' m [psi] 1.000 1,500 Calculations ANm [in.2]ANm0 [in.2]y ed,N,m Nb,m [lb] 270.94 286.76 0.977 6,232 Results Nmb [lb]f f seismic f Nmb [lb]Nua [lb] 5,752 0.650 0.750 2,804 2,800 Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% www.hilti.com Hilti PROFIS Engineering 3.1.10 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Feb 8, 2024 Page: Specifier: E-Mail: Date: 6 2/3/2025 4 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Refer to the manufacturer's product literature for cleaning and installation instructions. • For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/ • The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG. • Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS! • Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar joints. • The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration. • If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void. • The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use provided with the product have to be followed to ensure a proper installation. • The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user. • Drilling method (hammer, rotary) to be in accordance with the approval! • Masonry needs to be built in a regular way in accordance with state-of the art guidelines! Fastening meets the design criteria! Wall out-of plane (N) Adhesive Anchor Detail 20/S7 0% GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: Freestanding Wall, Grid A Wall Infill LR Footing Soil Values TW = 10.00 Allowable Soil Bearing =1500 psf/ft Allowable Soil Bearing EQ =2000 psf/ft Soil Density = 110 pcf Footing/Soil Friction Ratio = 0.350 8.00 ft. Seismic Force - Out of Plane SDS = 1.299 Cs = 1.039 (ASCE 7 Ch. 15) wEQ = 81.1 psf TG = 2.00 Weights Weight of Wall = 624 lbs @ x=2.50 ft.0.00 ft. Weight of Footing = 1502 lbs @ x=2.50 ft.TF = 2.00 h Weight of Soil Over Left Side = 0 lbs @ x=1.09 ft. Weight of Soil Over Right Side = 0 lbs @ x=3.92 ft.2.00 ft. ASD Alternative Load Combination: 0.9D + E/1.4 2.17 ft.0.67 ft.2.17 ft. MOT = 2779 lb-ft x Mresist = 4790 lb-ft x = 1.05 ft. Resultant not within middle third of footing p = 1214 psf OK Sliding Force = 463 lbs Sliding Resistance = 670 lbs OK Bending in Footing (LRFD) Mmax = 5756 lb-ft f'c = 3000 psi # 4 bot. bars @ 12'' o.c. As = 0.20 sq. in ϕMn = 18164 lb-ft OK Mmax = 0 lb-ft f'c = 3000 psi # 4 top bars @ 12'' o.c. As = 0.20 sq. in ϕMn = 18164 lb-ft OK Bending in Wall (LRFD) Mmax = 2594 ft-lbs f'm = 1500 psi # 4 vert. bars @ 8'' o.c. As = 0.29 sq. in ϕMn = 4240 lb-ft OK  0% Parking Slab With New Solar Panel Loads Gravity Comp. Model P1 RISA-3D Version 22 [ 24142 Parking(23) Gravity.r3d ]Page 1 Basic Load Cases BLC Description Category Y Gravity Nodal Surface(Plate/Wall) 1 DL DL -1 240 2 LL LL 12349 Load Combinations Description Solve P-Delta BLC Factor BLC Factor 1 ASCE Strength 2 (a)Y DL 1.2 LL 1.6 General Materials Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Density [lb/ft³]Plate Methodology 1 gen_Conc3NW 3155 1372 0.15 0.6 214 Isotropic 2 gen_Conc4NW 3644 1584 0.15 0.6 145 Isotropic 3 gen_Conc3LW 2085 906 0.15 0.6 109.999 Isotropic 4 gen_Conc4LW 2408 1047 0.15 0.6 109.999 Isotropic 5 gen_Alum 10100 4077 0.3 1.29 173 Isotropic 6 gen_Steel 29000 11154 0.3 0.65 490 Isotropic 7 gen_Plywood 1800 38 0 0.3 35 Isotropic 8 RIGID 1e+6 0.3 0 0 Isotropic 9 gen_Ortho 0.65 490 Orthotropic Plate Primary Data Label A Node B Node C Node D Node Material Thickness [in] 1 P10000 N7920 N7919 N7924 N7922 gen_Conc3NW 7.7 2 P10001 N7907 N7917 N7915 N7908 gen_Conc3NW 7.7 3 P10002 N7927 N7926 N7951 N7952 gen_Conc3NW 7.7 4 P10003 N7931 N7930 N7943 N7942 gen_Conc3NW 7.7 5 P10004 N7880 N7934 N7938 N7937 gen_Conc3NW 7.7 6 P10005 N7936 N7932 N7889 N7903 gen_Conc3NW 7.7 7 P10006 N7881 N7884 N7848 N7862 gen_Conc3NW 7.7 8 P10007 N7930 N7940 N7945 N7943 gen_Conc3NW 7.7 9 P10008 N7942 N7941 N7899 N7898 gen_Conc3NW 7.7 10 P10009 N7931 N7886 N7889 N7932 gen_Conc3NW 7.7 11 P10010 N7948 N7947 N7953 N7954 gen_Conc3NW 7.7 Concrete Column Design Parameters Label Shape Length [ft]y sway z sway Rebar Design Flexural Layout Rebar Design Shear Layout 1 M1 CRND12 8.5 Custom Column Layout Custom Shear Layout 2 M2 CRND12 8.5 Custom Column Layout Custom Shear Layout 3 M4 CRND12 8.5 Custom Column Layout Custom Shear Layout 4 M7 CRND12 8.5 Custom Column Layout Custom Shear Layout 5 M8 CRND12 8.5 Custom Column Layout Custom Shear Layout 6 M23 CRND12 8.5 Custom Column Layout Custom Shear Layout 7 M24 CRND12 8.5 Custom Column Layout Custom Shear Layout 8 M25 CRND12 8.5 Custom Column Layout Custom Shear Layout 9 M26 CRND12 8.5 Custom Column Layout Custom Shear Layout 10 M27 CRND12 8.5 Custom Column Layout Custom Shear Layout 11 M28 CRND12 8.5 Custom Column Layout Custom Shear Layout 12 M29 CRND12 8.5 Custom Column Layout Custom Shear Layout 13 M30 CRND12 8.5 Custom Column Layout Custom Shear Layout 14 M33 CRND12 8.5 Custom Column Layout Custom Shear Layout 15 M34 CRND12 8.5 Custom Column Layout Custom Shear Layout 16 M36 CRND12 8.5 Custom Column Layout Custom Shear Layout 17 M22 CRND12 8.5 Custom Column Layout Custom Shear Layout 7.7/12*214 =137psf = 11/12*150 = 137psf Parking Slab With New Solar Panel Loads Gravity Comp. Model P2 RISA-3D Version 22 [ 24142 Parking(23) Gravity.r3d ]Page 2 Concrete Column Design Parameters (Continued) Label Shape Length [ft]y sway z sway Rebar Design Flexural Layout Rebar Design Shear Layout 18 M37 CRND12 8.5 Custom Column Layout Custom Shear Layout Node Loads and Enforced Displacements (BLC 1 : DL) Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)] 1 N3843 L Y -0.9 2 N3519 L Y -0.9 3 N3146 L Y -0.9 4 N3229 L Y -0.9 5 N5746 L Y -0.9 6 N186 L Y -0.9 7 N5927 L Y -0.9 8 N6000 L Y -0.9 9 N7581 L Y -0.9 10 N7430 L Y -0.9 11 N350 L Y -0.9 12 N7770 L Y -0.9 13 N9392 L Y -0.9 14 N9489 L Y -0.9 15 N13019 L Y -0.9 16 N12184 L Y -0.9 17 N12739 L Y -0.9 18 N12539 L Y -0.9 19 N37 L Y -0.9 20 N36 L Y -0.9 21 N38 L Y -0.9 22 N39 L Y -0.9 23 N5295 L Y -0.9 24 N13119 L Y -0.9 25 N7199 L Y -0.9 26 N7028 L Y -0.9 27 N8387 L Y -0.9 28 N8308 L Y -0.9 29 N8153 L Y -0.9 30 N8061 L Y -0.9 31 N10451 L Y -0.9 32 N9714 L Y -0.9 33 N10892 L Y -0.9 34 N11532 L Y -0.9 Plate Surface Loads (BLC 2 : LL) Plate Label Direction Magnitude [psf, F] 1 P13306 Y -40 2 P13303 Y -40 3 P13300 Y -40 4 P13298 Y -40 5 P13296 Y -40 6 P13295 Y -40 7 P13294 Y -40 8 P13293 Y -40 9 P13292 Y -40 10 P13291 Y -40 11 P13290 Y -40 12 P13289 Y -40 13 P13288 Y -40 14 P13285 Y -40 15 P13283 Y -40 New solar panels columns 900# Parking slab live load 40 psf Parking Slab With New Solar Panel Loads Gravity Comp. Model P3 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P4 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P5 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P6 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P7 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P8 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P9 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P10 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P11 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, Conc. Slab Bending 24142 P12 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LRParking Slab With New Solar Panel Loads, (E) Columns Punching Shear 24142 P13 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR Seismic Load Coefficient Special Reinforced Masonry Shear Walls SDS = 1.299 R = 5 Ω = 2.5 Cd = 3.5 Ie = 1 CS = SDS / (R / Ie) = 0.26Wp Diaphragm Coefficient Fpx = 0.2SDSIeWp = 0.26Wp 24142 Seismic Load Coefficient, (N) CMU Shear Walls (Voluntary Retrofit) P14 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 Seismic Load, (N) CMU Shear Wall East of Grid 1 (Voluntary Retrofit) P15 (N) CMU Shear Wall East of Grid 1 (Voluntary Retrofit)P16 RISA-3D Version 23 [ 24142 in-plane(3) Parking.r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Concrete Matl 1350 540 0.25 0.6 Custom 2 60 60 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Concrete Matl 8 Typical 16 Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Nodal 1 DL DL -1 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Yes Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Yes Y DL 0.9 Sds*DL -0.2 EL -1 Node Loads and Enforced Displacements (BLC 2 : EL) Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)] 1 N26 L X 101.9 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@16" oc (ctr)5-#4 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.01 2 1.048 3 0.669 3 1454.638 837.633 156.209 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 15.002 2 104.576 1 0 4 0 4 877.485 2 2 0 min 6.579 3 -104.576 2 0 1 0 1 -877.485 1 1 &086KHDU:DOO(DVWRI*ULG 9ROXQWDU\5HWURILW P17 Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:5 Effective Depth (in):186 MATERIALS Masonry f'm (ksi):2 Masonry Em (ksi):1350 Steel fy (ksi):60 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):8.5 Total Length (ft):15.5 Block Grouting:Fully Grouted Grout Spacing:16" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 15.002 at 0 ft Min: 0 at 8.5 ft P k Max: 104.576 at 0 ft Min: -104.576 at 0 ft V k Max: 877.485 at 0 ft Min: -877.485 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.01 P (k):15.002 Pn (k):1616.264 Φ:0.9 Location (ft):0 Load Comb:2 Rad gyration r (in):2.2 h'/r:46.364 Red Factor R:0.89 BENDING SUMMARY Mu/(Mn*Φ):1.048 Mu (k-ft):877.467 Mn (k-ft):930.703 Φ:0.9 Location (ft):0 Load Comb:3 a (in):4.094 c (in):5.117 d (in):186 SHEAR SUMMARY Vu/(Vn*Φ):0.669 Vu (k):104.574 Vn (k):195.262 Φ:0.8 Location (ft):0 Load Comb:3 Corresponding M (k- ft): 877.485 Corresponding P (k):6.579 M / (V*d):0.541 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (5 ) T o t 40 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 23 [ 24142 in-plane(3) Parking.r3d ]Page 1 1 &086KHDU:DOO(DVWRI*ULG 9ROXQWDU\5HWURILW P18 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 Seismic Load, (N) CMU Shear Wall On South Side (Voluntary Retrofit) P19 (N) CMU Shear Walls South Side (Voluntary Retrofit)P20 RISA-3D Version 22 [ 24142 in-plane(2) Parking.r3d ]Page 1 Masonry Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Self Weight [lb/ft³]f'm [ksi]Flex Steel [ksi]Shear Steel [ksi] 1 Concrete Matl 1350 540 0.25 0.6 Custom 2 60 60 Wall Panel Data Label A Node B Node C Node D Node Material Type Material Set Thickness [in]Design Rule Panel/Spacing 1 WP1 N1 N15 N26 N13 Masonry Concrete Matl 8 Typical 16 Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 8"Fully Grouted Yes NCMA Basic Load Cases BLC Description Category X Gravity Y Gravity Nodal 1 DL DL -1 2 EL EL 0.26 1 Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor 1 ASCE Strength 6 (a)Yes Y DL 1.2 Sds*DL 0.2 EL 1 2 ASCE Strength 6 (b)Yes Y DL 1.2 Sds*DL 0.2 EL -1 3 ASCE Strength 7 (a)Yes Y DL 0.9 Sds*DL -0.2 EL 1 4 ASCE Strength 7 (b)Yes Y DL 0.9 Sds*DL -0.2 EL -1 Node Loads and Enforced Displacements (BLC 2 : EL) Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)] 1 N26 L X 98.5 Masonry Wall Reinforcement Wall Region Hor. Bar Size Vert. Bar Size Boundary Reinf. 1 WP1 R1 Not Reqd.#4@16" oc (ctr)4-#4 TMS 402-16: STRENGTH Wall Panel Masonry Code Checks (In-Plane) Wall Panel Region Design Rule Axial UC LC Bending UC LC Shear UC LC Pn*phi[k]Mn*phi[k-ft]Vn*phi[k] 1 WP1 R1 Typical 0.0249 2 0.8405 3 0.4692 1 1470.592 643.5581 205.0877 Envelope Wall Panel Forces Wall LabelElevation [ft]Axial [k]LC x Shear [k]LC z Shear [k]LC x-x Moment [k-ft]LC z-z Moment [k-ft]LC 1 WP1 0 max 25.164 2 102.9851 1 0 4 0 4 856.2742 2 2 0 min 11.0358 3 -102.9851 2 0 1 0 1 -856.2742 1 (N) CMU Shear Walls South Side (Voluntary Retrofit)P21 Detail Report: WP1 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#4 Vert Bar Size:#4 No. Tens Bars:4 Effective Depth (in):312 MATERIALS Masonry f'm (ksi):2 Masonry Em (ksi):1350 Steel fy (ksi):60 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):8.5 Total Length (ft):26 Block Grouting:Fully Grouted Grout Spacing:16" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 25.164 at 0 ft Min: 0 at 8.5 ft P k Max: 102.9851 at 0 ft Min: -102.9851 at 0 ft V k Max: 856.2742 at 0 ft Min: -856.2742 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.01 P (k):25.164 Pn (k):2711.153 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:46.364 Red Factor R:0.89 BENDING SUMMARY Mu/(Mn*Φ):0.709 Mu (k-ft):856.259 Mn (k-ft):1341.792 Φ:0.9 Location (ft):0 Load Comb:3 a (in):3.915 c (in):4.894 d (in):312 SHEAR SUMMARY Vu/(Vn*Φ):0.349 Vu (k):102.983 Vn (k):368.787 Φ:0.8 Location (ft):0 Load Comb:3 Corresponding M (k- ft): 856.274 Corresponding P (k):11.036 M / (V*d):0.32 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 4 e a . c e l l (4 ) T o t 32 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 22 [ 24142 in-plane(2) Parking.r3d ]Page 1 (N) CMU Shear Walls South Side (Voluntary Retrofit)P22 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 24142 Solar Panel Columns 10% Seismic Mass Increase P23 GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: RTU1 & RTU4 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 40.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 455 lbs Fp,ASD = 211 lbs h = 44.0 in. Fp,vert,ASD =84 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 2787 in-lbs T = MOT / d = 70 lbs V = Fp,ASD = 211 lbs d = 40.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.29 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C LR 24142 0DLQ%XLOGLQJ 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: RTU2 & RTU3 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 50.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 893 lbs Fp,ASD = 414 lbs h = 48.0 in. Fp,vert,ASD =166 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 3936 in-lbs T = MOT / d = 79 lbs V = Fp,ASD = 414 lbs d = 50.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.53 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C LR 24142 0DLQ%XLOGLQJ 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: RTU5 & RTU6 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 59.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 1274 lbs Fp,ASD = 591 lbs h = 50.0 in. Fp,vert,ASD =236 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 2702 in-lbs T = MOT / d = 46 lbs V = Fp,ASD = 591 lbs d = 59.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.73 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C 0DLQ%XLOGLQJ  /5 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: RTU7 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 59.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 1264 lbs Fp,ASD = 586 lbs h = 50.0 in. Fp,vert,ASD =235 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 2681 in-lbs T = MOT / d = 45 lbs V = Fp,ASD = 586 lbs d = 59.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.73 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C 0DLQ%XLOGLQJ /5  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: RTU8 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 45.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 493 lbs Fp,ASD = 229 lbs h = 60.0 in. Fp,vert,ASD =91 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 5798 in-lbs T = MOT / d = 129 lbs V = Fp,ASD = 229 lbs d = 45.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.33 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C /5  0DLQ%XLOGLQJ 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: HP1 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 11.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 71 lbs Fp,ASD = 33 lbs h = 40.0 in. Fp,vert,ASD =13 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 1044 in-lbs T = MOT / d = 95 lbs V = Fp,ASD = 33 lbs d = 11.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.08 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C LR 24142 0DLQ%XLOGLQJ 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: EF3 Roof Mechanical Equipment Anchorage Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 (Address: 30 South 1st Avenue, Arcadia Ca, 91006) ap =2.5 (ASCE 7-16 Table 13.6-1) Rp =6 (ASCE 7-16 Table 13.6-1) Ip =1 (ASCE 7-16 Section 13.1.3) z =20 (Floor height [ft.] where component is attached) hbuilding =20 (Building height [ft.]) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.650 Wp Governs Fp,max = 1.6*SDS*Ip*Wp =2.078 Wp Fp,min = 0.3*SDS*Ip*Wp =0.390 Wp Fp =0.650 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD ASD Alternative Load Combination: (0.9 - Fp,vert)D + E/1.4 Fp,ASD = 0.650 /1.4 =0.464 Wp L = 17.0 in. Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 41 lbs Fp,ASD = 19 lbs h = 22.0 in. Fp,vert,ASD =8 lbs MOT = Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 169 in-lbs T = MOT / d = 10 lbs V = Fp,ASD = 19 lbs d = 17.0 in. Use 3/8'' Dia. x 4'' Lag Screws at each corner Short Side View 2 in tension 4 in shear 2 *Tallow = 2226 lbs OK 4 *Vallow = 832 lbs OK (T / Tallow) + (V / Vallow) = 0.03 < 1.0 OK Fp Wp Fp,vert T C Wp Fp,vert T C LR 24142 0DLQ%XLOGLQJ 3& Detail Report: M2 Load Combination:LC 1: DL + RLL + OL1 Code check:0.829 (axial/bending) y z y z x Input Data Shape:3-2X8 (nominal) Member Type:Beam Length (ft):16 Material Type:Wood Design Rule:Typical Internal Sections:97 Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3 J Node:N4 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:DF Type:Solid Sawn Database:Visually Graded Species:Douglas Fir-Larch Grade:No.1 Cm:No Ci:No Emod:1 Nu:0.3 Alpha (1e F ):5o -1 0.3 Density (lb/ft ):3 35.001 Shape Properties Fb (ksi):1 Ft (ksi):0.675 Fv (ksi):0.18 Fc (ksi):1.5 E (ksi):1700 Emod:1 COVE (Table F1):0.25 Emin (ksi):621.025 b (actual) (in):4.5 d (actual) (in):7.25 # of Plies (ksi):3 Kf (ksi):0.6 Design Properties le2 (ft):1 le1 (ft):16 le-bend top:Lbyy le-bend bot (ft):16 K :y-y 1 K :z-z 1 y sway:No z sway:No C :D 1.25 R :B 2.073 C :L 1 C :r 1 C :fu 1 C :P 0.336 K :f 0.6 Max Defl Ratio:L/283 Max Defl Location:8 Span:1 M2 N3 N4 -0.6776 at 8 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.7019 at 0 ft -0.7019 at 16 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -4.0818 at 8 ft z-z Moment (k-ft) Axial Stress (ksi) 1.2425 at 8 ft Bending Compression Stress (ksi) -1.2425 at 8 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.661 ksi -- Axial Tension Analysis 0 ksi 1.013 ksi -- Flexural Analysis, Fb1'1.242 ksi 1.499 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.242 ksi 1.499 ksi -- Flexural Analysis, Fb2'0 ksi 1.5 ksi -- Bending & Axial Compression Analysis --0.829 PASS Bending & Axial Tension Analysis --0.829 PASS Shear Analysis 0.032 ksi 0.225 ksi 0.143 PASS RISA-3D Version 22 [ 24142 Beams7.r3d ]Page 1 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.829 (axial/bending)y z y zx Input DataShape:3-2X8 (nominal)Member Type:BeamLength (ft):16Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):7.25# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):16le-bend top:Lbyyle-bend bot (ft):16K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 2.073C:L 1C:r 1 C :fu 1C:P 0.336K:f 0.6Max Defl Ratio:L/283Max Defl Location:8Span:1M2N3 N4 -0.6776 at 8 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.7019 at 0 ft -0.7019 at 16 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -4.0818 at 8 ft z-z Moment (k-ft) Axial Stress (ksi) 1.2425 at 8 ft Bending Compression Stress (ksi) -1.2425 at 8 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.661 ksi -- Axial Tension Analysis 0 ksi 1.013 ksi -- Flexural Analysis, Fb1'1.242 ksi 1.499 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.242 ksi 1.499 ksi -- Flexural Analysis, Fb2'0 ksi 1.5 ksi -- Bending & Axial Compression Analysis --0.829 PASS Bending & Axial Tension Analysis --0.829 PASS Shear Analysis 0.032 ksi 0.225 ksi 0.143 PASS RISA-3D Version 22 [ 24142 Beams7.r3d ]Page 2 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.829 (axial/bending)y z y zx Input DataShape:3-2X8 (nominal)Member Type:BeamLength (ft):16Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):7.25# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):16le-bend top:Lbyyle-bend bot (ft):16K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 2.073C:L 1C:r 1 C :fu 1C:P 0.336K:f 0.6Max Defl Ratio:L/283Max Defl Location:8Span:1M2N3 N4-0.6776 at 8 fty Deflection (in)Diagrams:z Deflection (in)Axial Force (k)0.7019 at 0 ft -0.7019 at 16 fty Shear Force (k)z Shear Force (k)Torsion (k-ft)y-y Moment (k-ft)-4.0818 at 8 ftz-z Moment (k-ft)Axial Stress (ksi)1.2425 at 8 ftBending Compression Stress (ksi)-1.2425 at 8 ftBending Tension Stress (ksi)AWC NDS-18 / AWC SPDWS-21 ASD Code CheckLimit State Required Available Unity Check ResultApplied Loading -Bending/Axial ----Applied Loading -Shear + Torsion ----Axial Compression Analysis 0 ksi 0.661 ksi --Axial Tension Analysis 0 ksi 1.013 ksi --Flexural Analysis, Fb1'1.242 ksi 1.499 ksi --Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2)Strong Axis Bending Capacity Span Length of Bending MemberDepth (width) of bending memberBreadth (thickness) of rectangular bending memberNumber of PliesReference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F)Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F)Load duration factor (Table 2.3.2)Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.242 ksi 1.499 ksi -- Flexural Analysis, Fb2'0 ksi 1.5 ksi -- Bending & Axial Compression Analysis --0.829 PASS Bending & Axial Tension Analysis --0.829 PASS Shear Analysis 0.032 ksi 0.225 ksi 0.143 PASS RISA-3D Version 22 [ 24142 Beams7.r3d ]Page 3  (T  [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M2 Load Combination:LC 1: DL + RLL + OL1 Code check:0.921 (axial/bending) y z y z x Input Data Shape:3-2X6 (nominal) Member Type:Beam Length (ft):14.5 Material Type:Wood Design Rule:Typical Internal Sections:97 Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3 J Node:N4 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:DF Type:Solid Sawn Database:Visually Graded Species:Douglas Fir-Larch Grade:No.1 Cm:No Ci:No Emod:1 Nu:0.3 Alpha (1e F ):5o -1 0.3 Density (lb/ft ):3 35.001 Shape Properties Fb (ksi):1 Ft (ksi):0.675 Fv (ksi):0.18 Fc (ksi):1.5 E (ksi):1700 Emod:1 COVE (Table F1):0.25 Emin (ksi):621.025 b (actual) (in):4.5 d (actual) (in):5.5 # of Plies (ksi):3 Kf (ksi):0.6 Design Properties le2 (ft):1 le1 (ft):14.5 le-bend top:Lbyy le-bend bot (ft):14.5 K :y-y 1 K :z-z 1 y sway:No z sway:No C :D 1.25 R :B 1.805 C :L 1 C :r 1 C :fu 1 C :P 0.233 K :f 0.6 Max Defl Ratio:L/194 Max Defl Location:7.25 Span:1 M2 N3 N4 -0.894 at 7.25 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.5571 at 0 ft -0.5571 at 14.5 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.8297 at 7.25 ft z-z Moment (k-ft) Axial Stress (ksi) 1.4967 at 7.25 ft Bending Compression Stress (ksi) -1.4967 at 7.25 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.481 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.497 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.497 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.921 PASS Bending & Axial Tension Analysis --0.921 PASS Shear Analysis 0.034 ksi 0.225 ksi 0.15 PASS RISA-3D Version 22 [ 24142 Beams1.r3d ]Page 1 3-2x6 Sistered Roof Beams Supporting Mech. Eq.3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.921 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):14.5Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):14.5le-bend top:Lbyyle-bend bot (ft):14.5K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.233K:f 0.6Max Defl Ratio:L/194Max Defl Location:7.25Span:1M2N3 N4 -0.894 at 7.25 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.5571 at 0 ft -0.5571 at 14.5 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.8297 at 7.25 ft z-z Moment (k-ft) Axial Stress (ksi) 1.4967 at 7.25 ft Bending Compression Stress (ksi) -1.4967 at 7.25 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.481 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.497 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.497 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.921 PASS Bending & Axial Tension Analysis --0.921 PASS Shear Analysis 0.034 ksi 0.225 ksi 0.15 PASS RISA-3D Version 22 [ 24142 Beams1.r3d ]Page 2 3-2x6 Sistered Roof Beams Supporting Mech. Eq.3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.921 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):14.5Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):14.5le-bend top:Lbyyle-bend bot (ft):14.5K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.233K:f 0.6Max Defl Ratio:L/194Max Defl Location:7.25Span:1M2N3 N4-0.894 at 7.25 fty Deflection (in)Diagrams:z Deflection (in)Axial Force (k)0.5571 at 0 ft -0.5571 at 14.5 fty Shear Force (k)z Shear Force (k)Torsion (k-ft)y-y Moment (k-ft)-2.8297 at 7.25 ftz-z Moment (k-ft)Axial Stress (ksi)1.4967 at 7.25 ftBending Compression Stress (ksi)-1.4967 at 7.25 ftBending Tension Stress (ksi)AWC NDS-18 / AWC SPDWS-21 ASD Code CheckLimit State Required Available Unity Check ResultApplied Loading -Bending/Axial ----Applied Loading -Shear + Torsion ----Axial Compression Analysis 0 ksi 0.481 ksi --Axial Tension Analysis 0 ksi 1.097 ksi --Flexural Analysis, Fb1'1.497 ksi 1.624 ksi --Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2)Strong Axis Bending Capacity Span Length of Bending MemberDepth (width) of bending memberBreadth (thickness) of rectangular bending memberNumber of PliesReference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F)Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F)Load duration factor (Table 2.3.2)Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.497 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.921 PASS Bending & Axial Tension Analysis --0.921 PASS Shear Analysis 0.034 ksi 0.225 ksi 0.15 PASS RISA-3D Version 22 [ 24142 Beams1.r3d ]Page 3 (10+20)*16/12 Eq. = 893#/2 3-2x6 Sistered Roof Beams Supporting Mech. Eq.3& Detail Report: M2 Load Combination:LC 1: DL + RLL + OL1 Code check:0.763 (axial/bending) y z y z x Input Data Shape:3-2X6 (nominal) Member Type:Beam Length (ft):14.5 Material Type:Wood Design Rule:Typical Internal Sections:97 Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3 J Node:N4 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:DF Type:Solid Sawn Database:Visually Graded Species:Douglas Fir-Larch Grade:No.1 Cm:No Ci:No Emod:1 Nu:0.3 Alpha (1e F ):5o -1 0.3 Density (lb/ft ):3 35.001 Shape Properties Fb (ksi):1 Ft (ksi):0.675 Fv (ksi):0.18 Fc (ksi):1.5 E (ksi):1700 Emod:1 COVE (Table F1):0.25 Emin (ksi):621.025 b (actual) (in):4.5 d (actual) (in):5.5 # of Plies (ksi):3 Kf (ksi):0.6 Design Properties le2 (ft):1 le1 (ft):14.5 le-bend top:Lbyy le-bend bot (ft):14.5 K :y-y 1 K :z-z 1 y sway:No z sway:No C :D 1.25 R :B 1.805 C :L 1 C :r 1 C :fu 1 C :P 0.233 K :f 0.6 Max Defl Ratio:L/212 Max Defl Location:7.703 Span:1 M2 N3 N4 -0.8176 at 7.7 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.4644 at 0 ft -0.8349 at 14.5 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.3431 at 10.12 ft z-z Moment (k-ft) Axial Stress (ksi) 1.2393 at 10.12 ft Bending Compression Stress (ksi) -1.2393 at 10.12 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.481 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.239 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.239 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.763 PASS Bending & Axial Tension Analysis --0.763 PASS Shear Analysis 0.051 ksi 0.225 ksi 0.225 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 1 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.763 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):14.5Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):14.5le-bend top:Lbyyle-bend bot (ft):14.5K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.233K:f 0.6Max Defl Ratio:L/212Max Defl Location:7.703Span:1M2N3 N4 -0.8176 at 7.7 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.4644 at 0 ft -0.8349 at 14.5 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.3431 at 10.12 ft z-z Moment (k-ft) Axial Stress (ksi) 1.2393 at 10.12 ft Bending Compression Stress (ksi) -1.2393 at 10.12 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.481 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.239 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.239 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.763 PASS Bending & Axial Tension Analysis --0.763 PASS Shear Analysis 0.051 ksi 0.225 ksi 0.225 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 2 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M2Load Combination:LC 1: DL + RLL + OL1 Code check:0.763 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):14.5Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):14.5le-bend top:Lbyyle-bend bot (ft):14.5K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.233K:f 0.6Max Defl Ratio:L/212Max Defl Location:7.703Span:1M2N3 N4-0.8176 at 7.7 fty Deflection (in)Diagrams:z Deflection (in)Axial Force (k)0.4644 at 0 ft -0.8349 at 14.5 fty Shear Force (k)z Shear Force (k)Torsion (k-ft)y-y Moment (k-ft)-2.3431 at 10.12 ftz-z Moment (k-ft)Axial Stress (ksi)1.2393 at 10.12 ftBending Compression Stress (ksi)-1.2393 at 10.12 ftBending Tension Stress (ksi)AWC NDS-18 / AWC SPDWS-21 ASD Code CheckLimit State Required Available Unity Check ResultApplied Loading -Bending/Axial ----Applied Loading -Shear + Torsion ----Axial Compression Analysis 0 ksi 0.481 ksi --Axial Tension Analysis 0 ksi 1.097 ksi --Flexural Analysis, Fb1'1.239 ksi 1.624 ksi --Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2)Strong Axis Bending Capacity Span Length of Bending MemberDepth (width) of bending memberBreadth (thickness) of rectangular bending memberNumber of PliesReference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F)Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F)Load duration factor (Table 2.3.2)Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.239 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.763 PASS Bending & Axial Tension Analysis --0.763 PASS Shear Analysis 0.051 ksi 0.225 ksi 0.225 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 3  (T  [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M3 Load Combination:LC 1: DL + RLL + OL1 Code check:0.723 (axial/bending) y z y z x Input Data Shape:3-2X6 (nominal) Member Type:Beam Length (ft):15 Material Type:Wood Design Rule:Typical Internal Sections:97 Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N5 J Node:N6 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:DF Type:Solid Sawn Database:Visually Graded Species:Douglas Fir-Larch Grade:No.1 Cm:No Ci:No Emod:1 Nu:0.3 Alpha (1e F ):5o -1 0.3 Density (lb/ft ):3 35.001 Shape Properties Fb (ksi):1 Ft (ksi):0.675 Fv (ksi):0.18 Fc (ksi):1.5 E (ksi):1700 Emod:1 COVE (Table F1):0.25 Emin (ksi):621.025 b (actual) (in):4.5 d (actual) (in):5.5 # of Plies (ksi):3 Kf (ksi):0.6 Design Properties le2 (ft):1 le1 (ft):15 le-bend top:Lbyy le-bend bot (ft):15 K :y-y 1 K :z-z 1 y sway:No z sway:No C :D 1.25 R :B 1.805 C :L 1 C :r 1 C :fu 1 C :P 0.219 K :f 0.6 Max Defl Ratio:L/231 Max Defl Location:7.5 Span:1 M3 N5 N6 -0.7771 at 7.5 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.4686 at 0 ft -0.4686 at 15 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.2204 at 7.5 ft z-z Moment (k-ft) Axial Stress (ksi) 1.1744 at 7.5 ft Bending Compression Stress (ksi) -1.1744 at 7.5 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.451 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.174 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.174 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.723 PASS Bending & Axial Tension Analysis --0.723 PASS Shear Analysis 0.028 ksi 0.225 ksi 0.126 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 1 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M3Load Combination:LC 1: DL + RLL + OL1 Code check:0.723 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):15Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N5J Node:N6I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):15le-bend top:Lbyyle-bend bot (ft):15K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.219K:f 0.6Max Defl Ratio:L/231Max Defl Location:7.5Span:1M3N5 N6 -0.7771 at 7.5 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.4686 at 0 ft -0.4686 at 15 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -2.2204 at 7.5 ft z-z Moment (k-ft) Axial Stress (ksi) 1.1744 at 7.5 ft Bending Compression Stress (ksi) -1.1744 at 7.5 ft Bending Tension Stress (ksi) AWC NDS-18 / AWC SPDWS-21 ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Compression Analysis 0 ksi 0.451 ksi -- Axial Tension Analysis 0 ksi 1.097 ksi -- Flexural Analysis, Fb1'1.174 ksi 1.624 ksi -- Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2) Strong Axis Bending Capacity Span Length of Bending Member Depth (width) of bending member Breadth (thickness) of rectangular bending member Number of Plies Reference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F) Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F) Load duration factor (Table 2.3.2) Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.174 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.723 PASS Bending & Axial Tension Analysis --0.723 PASS Shear Analysis 0.028 ksi 0.225 ksi 0.126 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 2 [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M3Load Combination:LC 1: DL + RLL + OL1 Code check:0.723 (axial/bending)y z y zx Input DataShape:3-2X6 (nominal)Member Type:BeamLength (ft):15Material Type:WoodDesign Rule:TypicalInternal Sections:97Design Code:AWC NDS-18 / AWC SPDWS-21 ASD I Node:N5J Node:N6I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:DFType:Solid SawnDatabase:Visually GradedSpecies:Douglas Fir-Larch Grade:No.1Cm:NoCi:NoEmod:1 Nu:0.3Alpha(1e F ):5o -1 0.3Density(lb/ft ):3 35.001Shape PropertiesFb(ksi):1Ft(ksi):0.675Fv(ksi):0.18Fc(ksi):1.5 E (ksi):1700Emod:1COVE(Table F1):0.25Emin(ksi):621.025 b (actual) (in):4.5d (actual) (in):5.5# of Plies (ksi):3Kf(ksi):0.6Design Propertiesle2 (ft):1le1 (ft):15le-bend top:Lbyyle-bend bot (ft):15K:y-y 1K:z-z 1 y sway:Noz sway:NoC:D 1.25R:B 1.805C:L 1C:r 1 C :fu 1C:P 0.219K:f 0.6Max Defl Ratio:L/231Max Defl Location:7.5Span:1M3N5 N6-0.7771 at 7.5 fty Deflection (in)Diagrams:z Deflection (in)Axial Force (k)0.4686 at 0 ft -0.4686 at 15 fty Shear Force (k)z Shear Force (k)Torsion (k-ft)y-y Moment (k-ft)-2.2204 at 7.5 ftz-z Moment (k-ft)Axial Stress (ksi)1.1744 at 7.5 ftBending Compression Stress (ksi)-1.1744 at 7.5 ftBending Tension Stress (ksi)AWC NDS-18 / AWC SPDWS-21 ASD Code CheckLimit State Required Available Unity Check ResultApplied Loading -Bending/Axial ----Applied Loading -Shear + Torsion ----Axial Compression Analysis 0 ksi 0.451 ksi --Axial Tension Analysis 0 ksi 1.097 ksi --Flexural Analysis, Fb1'1.174 ksi 1.624 ksi --Actual Bending Stress due to Bending Moment (Strong Axis)(Eq. 3.3-2)Strong Axis Bending Capacity Span Length of Bending MemberDepth (width) of bending memberBreadth (thickness) of rectangular bending memberNumber of PliesReference bending design value (Table 4A, 4B, 4C, 4D, 4E, 4F)Reference modulus of elasticity (Table 4A, 4B, 4C, 4D, 4E, 4F)Load duration factor (Table 2.3.2)Temperature factor (Table 2.3.3) Wet service factor for Fb (Table 4A, 4B, 4C, 4D, 4E, 4F) Size factor for sawn lumber (Sec. 4.3.6) Incision factor for dimension lumber (Fb, Ft, Fc, Fv)(Table 4.3.8) Incision factor for dimension lumber (E, Emin)(Table 4.3.8) Repetitive member factor for dimension lumber, prefabricated wood I-joists, and structural composite lumber (Sec 4.3.9) Slenderness ratio of bending member (Eq. 3.3-5) Coefficient of variation for modulus of elasticity (Table F1, App. F) Reference modulus of elasticity for beam stability and column stability calculations (Eq. D-4, App. D) Adjusted modulus of elasticity for beam stability and column stability calculations (Table 4.3.1) Critical buckling design value for bending members (Sec. 3.3.3.8) Beam stability factor (Eq. 3.3-6) Reference bending value multiplied by all applicable adjustment factors except Cfu, Cv, and CL (Sec. 3.3.3.8) Adjusted bending design value (Table 4.3.1) Coefficient of variation for modulus of elasticity (Table F1, App. F) Flexural Analysis, Fb1'1.174 ksi 1.624 ksi -- Flexural Analysis, Fb2'0 ksi 1.625 ksi -- Bending & Axial Compression Analysis --0.723 PASS Bending & Axial Tension Analysis --0.723 PASS Shear Analysis 0.028 ksi 0.225 ksi 0.126 PASS RISA-3D Version 22 [ 24142 Beams8.r3d ]Page 3  (T  [6LVWHUHG5RRI%HDPV6XSSRUWLQJ0HFK(T3& Detail Report: M1 Load Combination:LC 2: ASCE ASD 2 Code check:0.330 (axial/bending) y z y z x Input Data Shape:400S162-54 Member Type:Beam Length (ft):10 Material Type:Cold Formed Steel Design Rule:Typical Internal Sections:97 Design Code:AISI S100-20: ASD I Node:N1 J Node:N2 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:A653 SS Gr33 E (ksi):29500 G (ksi):11346 Nu:0.3 Therm. Coeff. (/1E5 F):0.65 Density (lb/ft ):3 490 Fy (ksi):33 Fu (ksi):45 Shape Properties D (in):4 B (in):1.625 t (in):0.057 R (in):0.085 d (in):0.5 Iyy (in ):4 0.159 Izz (in ):4 1.1 Area (in ):2 0.443 J (in ):4 0.000473 Cw (in ):6 0.56 ro (in):2.09 Xc (in):0.484 m (in):0.754 j (in):2.25 rz (in):1.576 ry (in):0.599 x0 (in):-1.24 Se,z (in ):3 0.549 Set,z (in ):3 0.549 Sf,z (in ):3 0.55 Sfy,z (in ):3 0.55 Se,y (in ):3 0.143 Set,y (in ):3 0.143 Sf,y (in ):3 0.143 Sfy,y (in ):3 0.311 Design Properties Lb y-y (ft):1 Lb z-z (ft):10 L :comp top Lbyy Lcomp bot (ft):10 C :b 1 C :m y-y 0.6 C :m z-z 0.85 K :y-y 1 K :z-z 1 R:N/A y sway:No z sway:No a:N/A Function:Lateral Max Defl Ratio:L/726 Max Defl Location:5 Span:1 M1 N1 N2 -0.1653 at 5 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.1192 at 0 ft -0.1192 at 10 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -0.298 at 5 ft z-z Moment (k-ft) Axial Stress (ksi) 6.5011 at 5 ft Bending Compression Stress (ksi) -6.5011 at 5 ft Bending Tension Stress (ksi) AISI S100-20: ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Tension Analysis 0 k 8.754 k -- Axial Compression Analysis 0 k 1.744 k -- Flexural Analysis (Strong Axis)0.298 k-ft 0.904 k-ft -- Flexural Analysis (Weak Axis)0 k-ft 0.235 k-ft -- Shear Analysis (Major Axis y)0.119 k 2.603 k 0.046 PASS Shear Analysis (Minor Axis z)0 k 1.88 k 0 PASS Bending & Axial Interaction Check (UC Bending Max)--0.33 PASS RISA-3D Version 22 [ 24142 Beams5.r3d ]Page 1 400S162-54 Ceiling Joist Detail 1J/S5 3& Detail Report: M1Load Combination:LC 2: ASCE ASD 2 Code check:0.330 (axial/bending)y z y zx Input DataShape:400S162-54Member Type:BeamLength (ft):10Material Type:Cold Formed SteelDesign Rule:TypicalInternal Sections:97Design Code:AISI S100-20: ASD I Node:N1J Node:N2I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:A653 SS Gr33E (ksi):29500G (ksi):11346 Nu:0.3Therm. Coeff. (/1E5 F):0.65Density(lb/ft ):3 490 Fy (ksi):33Fu(ksi):45Shape PropertiesD (in):4B (in):1.625t (in):0.057R (in):0.085d (in):0.5Iyy(in ):4 0.159Izz(in ):4 1.1Area(in ):2 0.443J(in ):4 0.000473 Cw (in ):6 0.56ro(in):2.09Xc(in):0.484m (in):0.754j (in):2.25rz(in):1.576ry(in):0.599x0(in):-1.24Se,z (in ):3 0.549 Set,z (in ):3 0.549Sf,z (in ):3 0.55Sfy,z (in ):3 0.55Se,y (in ):3 0.143Set,y (in ):3 0.143Sf,y (in ):3 0.143Sfy,y (in ):3 0.311Design PropertiesLb y-y (ft):1Lb z-z (ft):10L:comp top LbyyLcomp bot (ft):10C:b 1C:m y-y 0.6 C :m z-z 0.85K:y-y 1K:z-z 1R:N/Ay sway:Noz sway:No a:N/AFunction:LateralMax Defl Ratio:L/726Max Defl Location:5Span:1 M1 N1 N2 -0.1653 at 5 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.1192 at 0 ft -0.1192 at 10 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -0.298 at 5 ft z-z Moment (k-ft) Axial Stress (ksi) 6.5011 at 5 ft Bending Compression Stress (ksi) -6.5011 at 5 ft Bending Tension Stress (ksi) AISI S100-20: ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Tension Analysis 0 k 8.754 k -- Axial Compression Analysis 0 k 1.744 k -- Flexural Analysis (Strong Axis)0.298 k-ft 0.904 k-ft -- Flexural Analysis (Weak Axis)0 k-ft 0.235 k-ft -- Shear Analysis (Major Axis y)0.119 k 2.603 k 0.046 PASS Shear Analysis (Minor Axis z)0 k 1.88 k 0 PASS Bending & Axial Interaction Check (UC Bending Max)--0.33 PASS RISA-3D Version 22 [ 24142 Beams5.r3d ]Page 2 (6.8+10)*16/12 400S162-54 Ceiling Joist Detail 1J/S5 3& Detail Report: M2 Load Combination:LC 2: ASCE ASD 2 Code check:0.507 (axial/bending) y z y z x Input Data Shape:600S162-54 Member Type:Beam Length (ft):16 Material Type:Cold Formed Steel Design Rule:Typical Internal Sections:97 Design Code:AISI S100-20: ASD I Node:N3 J Node:N4 I Release:Fixed J Release:Fixed I Offset:N/A J Offset:N/A T/C Only:Both Way Material Properties Material:A653 SS Gr33 E (ksi):29500 G (ksi):11346 Nu:0.3 Therm. Coeff. (/1E5 F):0.65 Density (lb/ft ):3 490 Fy (ksi):33 Fu (ksi):45 Shape Properties D (in):6 B (in):1.625 t (in):0.057 R (in):0.085 d (in):0.5 Iyy (in ):4 0.181 Izz (in ):4 2.86 Area (in ):2 0.556 J (in ):4 0.000594 Cw (in ):6 1.34 ro (in):2.56 Xc (in):0.385 m (in):0.663 j (in):3.38 rz (in):2.268 ry (in):0.571 x0 (in):-1.05 Se,z (in ):3 0.953 Set,z (in ):3 0.953 Sf,z (in ):3 0.953 Sfy,z (in ):3 0.953 Se,y (in ):3 0.149 Set,y (in ):3 0.149 Sf,y (in ):3 0.149 Sfy,y (in ):3 0.438 Design Properties Lb y-y (ft):1 Lb z-z (ft):16 L :comp top Lbyy Lcomp bot (ft):16 C :b 1 C :m y-y 0.6 C :m z-z 0.85 K :y-y 1 K :z-z 1 R:N/A y sway:No z sway:No a:N/A Function:Lateral Max Defl Ratio:L/453 Max Defl Location:8 Span:1 M2 N3 N4 -0.4233 at 8 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.1938 at 0 ft -0.1938 at 16 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -0.7751 at 8 ft z-z Moment (k-ft) Axial Stress (ksi) 9.7565 at 8 ft Bending Compression Stress (ksi) -9.7565 at 8 ft Bending Tension Stress (ksi) AISI S100-20: ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Tension Analysis 0 k 10.987 k -- Axial Compression Analysis 0 k 1.26 k -- Flexural Analysis (Strong Axis)0.775 k-ft 1.527 k-ft -- Flexural Analysis (Weak Axis)0 k-ft 0.245 k-ft -- Shear Analysis (Major Axis y)0.194 k 2.74 k 0.071 PASS Shear Analysis (Minor Axis z)0 k 1.88 k 0 PASS Bending & Axial Interaction Check (UC Bending Max)--0.507 PASS RISA-3D Version 22 [ 24142 Beams5.r3d ]Page 1 600S162-54 Ceiling Joist Detail 1J/S5 3& Detail Report: M2Load Combination:LC 2: ASCE ASD 2 Code check:0.507 (axial/bending)y z y zx Input DataShape:600S162-54Member Type:BeamLength (ft):16Material Type:Cold Formed SteelDesign Rule:TypicalInternal Sections:97Design Code:AISI S100-20: ASD I Node:N3J Node:N4I Release:FixedJ Release:FixedI Offset:N/AJ Offset:N/AT/C Only:Both WayMaterial PropertiesMaterial:A653 SS Gr33E (ksi):29500G (ksi):11346 Nu:0.3Therm. Coeff. (/1E5 F):0.65Density(lb/ft ):3 490 Fy (ksi):33Fu(ksi):45Shape PropertiesD (in):6B (in):1.625t (in):0.057R (in):0.085d (in):0.5Iyy(in ):4 0.181Izz(in ):4 2.86Area(in ):2 0.556J(in ):4 0.000594 Cw (in ):6 1.34ro(in):2.56Xc(in):0.385m (in):0.663j (in):3.38rz(in):2.268ry(in):0.571x0(in):-1.05Se,z (in ):3 0.953 Set,z (in ):3 0.953Sf,z (in ):3 0.953Sfy,z (in ):3 0.953Se,y (in ):3 0.149Set,y (in ):3 0.149Sf,y (in ):3 0.149Sfy,y (in ):3 0.438Design PropertiesLb y-y (ft):1Lb z-z (ft):16L:comp top LbyyLcomp bot (ft):16C:b 1C:m y-y 0.6 C :m z-z 0.85K:y-y 1K:z-z 1R:N/Ay sway:Noz sway:No a:N/AFunction:LateralMax Defl Ratio:L/453Max Defl Location:8Span:1 M2 N3 N4 -0.4233 at 8 ft y Deflection (in) Diagrams: z Deflection (in) Axial Force (k) 0.1938 at 0 ft -0.1938 at 16 ft y Shear Force (k)z Shear Force (k) Torsion (k-ft)y-y Moment (k-ft) -0.7751 at 8 ft z-z Moment (k-ft) Axial Stress (ksi) 9.7565 at 8 ft Bending Compression Stress (ksi) -9.7565 at 8 ft Bending Tension Stress (ksi) AISI S100-20: ASD Code Check Limit State Required Available Unity Check Result Applied Loading -Bending/Axial ---- Applied Loading -Shear + Torsion ---- Axial Tension Analysis 0 k 10.987 k -- Axial Compression Analysis 0 k 1.26 k -- Flexural Analysis (Strong Axis)0.775 k-ft 1.527 k-ft -- Flexural Analysis (Weak Axis)0 k-ft 0.245 k-ft -- Shear Analysis (Major Axis y)0.194 k 2.74 k 0.071 PASS Shear Analysis (Minor Axis z)0 k 1.88 k 0 PASS Bending & Axial Interaction Check (UC Bending Max)--0.507 PASS RISA-3D Version 22 [ 24142 Beams5.r3d ]Page 2 (6.8+10)*16/12 600S162-54 Ceiling Joist Detail 1J/S5 3& Ladder Platform 3& Ladder Platform 3& Ladder Platform 3& Ladder Platform 3& RISA-3D Version 22 [ 24142 Platform ladder.r3d ]Page 1 Cold Formed Steel Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Density [lb/ft³]Yield [ksi]Fu [ksi] 1 A653 SS Gr33 29500 11346 0.3 0.65 490 33 45 2 A653 SS Gr50/1 29500 11346 0.3 0.65 490 50 65 Member Primary Data Label I Node J Node Section/Shape Type Design List Material Design Rule 1 M1 N1 N2 2-600S162-54-BB Beam CS B-to-B A653 SS Gr33 Typical 2 M2 N3 N4 400S162-54 Beam CS A653 SS Gr33 Typical 3 M3 N5 N6 400S162-54 Beam CS A653 SS Gr33 Typical 4 M4 N7 N8 400S162-54 Beam CS A653 SS Gr33 Typical 5 M5 N9 N10 400S162-54 Beam CS A653 SS Gr33 Typical 6 M6 N11 N12 400S162-54 Beam CS A653 SS Gr33 Typical 7 M7 N13 N1 400S162-54 Beam CS A653 SS Gr33 Typical 8 M8 N13 N14 400S162-54 Beam CS A653 SS Gr33 Typical 9 M9 N14 N2 400S162-54 Beam CS A653 SS Gr33 Typical Member Area Loads (BLC 1 : DL) Node ANode BNode C Node DDirection Load Direction A Magnitude [psf]B Magnitude [psf]C Magnitude [psf]D Magnitude [psf]Exclude Braces 1 N3 N13 N1 N4 Y A-B -15 -15 -15 -15 Yes 2 N14 N5 N6 N2 Y A-B -15 -15 -15 -15 Yes 3 N8 N7 N4 N6 Y A-B -15 -15 -15 -15 Yes 4 N5 N3 N9 N10 Y A-B -15 -15 -15 -15 Yes 5 N1 N11 N12 N2 Y A-B -15 -15 -15 -15 Yes Member Area Loads (BLC 2 : RLL) Node ANode BNode C Node DDirection Load Direction A Magnitude [psf]B Magnitude [psf]C Magnitude [psf]D Magnitude [psf]Exclude Braces 1 N3 N13 N1 N4 Y A-B -40 -40 -40 -40 Yes 2 N14 N5 N6 N2 Y A-B -40 -40 -40 -40 Yes 3 N8 N7 N4 N6 Y A-B -40 -40 -40 -40 Yes 4 N5 N3 N9 N10 Y A-B -40 -40 -40 -40 Yes 5 N1 N11 N12 N2 Y A-B -40 -40 -40 -40 Yes Node Loads and Enforced Displacements (BLC 1 : DL) Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)] 1 N15 L Y -0.1 2 N16 L Y -0.1 Node Loads and Enforced Displacements (BLC 2 : RLL) Node Label L, D, M Direction Magnitude [(k, k-ft), (in, rad), (k*s²/ft, k*s²*ft)] 1 N15 L Y -0.2 2 N16 L Y -0.2 Load Combinations Description Solve P-Delta BLC Factor BLC Factor 1 DL+RLL Yes Y DL 1 RLL 1 2 RLL Yes Y RLL 1 Ladder Platform 3& RISA-3D Version 22 [ 24142 Platform ladder.r3d ]Page 2 Deflection Design Label LC Ratio LC Ratio LC Ratio 1 Typical 1 240 2 360 3 240 Envelope AISI S100-20: ASD Member Cold Formed Steel Code Checks Member Shape Code CheckLoc[ft]LCShear CheckLoc[ft]DirLCPn/Om[k]Tn/Om[k]Mnyy/Om[k-ft]Mnzz/Om[k-ft]Vny/Om[k]Vnz/Om[k]Cb Eqn 1 M1 2-600S162-54-BB 0.7488 4.0833 1 0.1861 0 y 1 5.9358 21.9737 NC 3.0547 5.4797 -0.625 1 H1.2-1 2 M2 400S162-54 0.5052 2.3216 1 0.2052 0 y 1 4.1207 8.7539 0.2267 0.8012 2.6035 1.8799 1.0932H1.2-1 3 M3 400S162-54 0.5011 2.3769 1 0.2018 0 y 1 4.1207 8.7539 0.2267 0.8012 2.6035 1.8799 1.0933H1.2-1 4 M4 400S162-54 0.0017 1.4167 1 0.0008 2.8333 y 1 4.8743 8.7539 0.2358 0.9038 2.6035 1.8799 1.1364F3.1-1 5 M5 400S162-54 0.2416 2.184 1 0.118 0 y 1 4.8743 8.7539 0.2358 0.9038 2.6035 1.8799 1.0142F3.1-1 Envelope Beam Deflection Checks Beam Design Rule Span Defl [in]Ratio LC Defl [in]Ratio LC Defl [in]Ratio LC 1 M1 Typical 1 -0.169 579 1(DL+RLL)-0.12 816 2(RLL)N/A N/A N/A 2 M2 Typical 1 -0.068 932 1(DL+RLL)-0.048 1334 2(RLL)N/A N/A N/A 3 M3 Typical 1 -0.068 939 1(DL+RLL)-0.047 1345 2(RLL)N/A N/A N/A 4 M4 Typical 1 0 NC 1(DL+RLL)0 NC 2(RLL)N/A N/A N/A 5 M5 Typical 1 -0.011 3136 1(DL+RLL)-0.007 4737 2(RLL)N/A N/A N/A Ladder Platform 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR10% Seismic Mass Check and 5% gravity check 24142 0DLQ%XLOGLQJ 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 3DUNLQJ6WUXFWXUH 10 % Shear Strength Reduction 'HPROLVKHG6KHDU:DOOIRUQHZHOHFWULFDOWUDQVIRUPHU 1HZ0DVRQU\6KHDU:DOOUHSODFHVGHPROLVKHGVKHDUZDOO  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 3DUNLQJ6WUXFWXUH Slab Strength around new opening  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 3DUNLQJ6WUXFWXUH 6ODE6WUHQJWKDURXQGQHZRSHQLQJ  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR 3DUNLQJ6WUXFWXUH 6ODE6WUHQJWKDURXQGQHZRSHQLQJ  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: Nonstructural Component Anchorage LR Seismic Loading on component shall be based on ASCE 7-16 Chapter 13 Seismic Design Requirements For Nonstructural Components. Criteria (based on USGS website and ASCE 7-16) SDS =1.299 ap =1 (ASCE 7-16 Table 13.6-1) Rp =2.5 (ASCE 7-16 Table 13.6-1) Ip =1.5 (ASCE 7-16 Section 13.1.3) z =0 (Floor height [ft.] where component is attached) hbuilding =0 (N/A because component is on grade) Seismic Coefficient (ASCE 7-16 Section 13.3.1) Fp = 0.4*ap*SDS*Wp* (1+2*(z / h)) / (Rp / Ip) =0.312 Wp Fp,max = 1.6*SDS*Ip*Wp =3.118 Wp Fp,min = 0.3*SDS*Ip*Wp =0.585 Wp Governs Fp =0.585 Wp Seismic Coefficient for Vertical Component (ASCE 7-16 Section 13.3.1.2) Fp,vert = 0.2*SDS*Wp =0.260 Wp Seismic Coefficients in ASD Per ASCE 7-16 Table 13.6-1, Overstrength Factor Ωo = 2.0 For Concrete Anchorage ASD Alternative Load Combination: (0.9 - Fp,vert)D + ΩoE/1.4 L = 30.0 in. Fp,ASD = 0.585 /1.4 =0.418 Wp Fp,vert,ASD =0.260 /1.4 =0.186 Wp Overturning Weight, Wp = 1619 lbs Fp,ASD = 676 lbs h = 45.0 in. Fp,vert,ASD =300 lbs MOT = Ωo*Fp,ASD*h + Fp,vert,ASD*(L/2) - 0.9*Wp*(L/2) = 43489 in-lbs T = MOT / d = 1450 lbs V = Ωo*Fp,ASD = 1352 lbs d = 30.0 in. Use 3/4'' Dia. x 4'' Embed. Hilti KB-TZ at each corner Short Side View 2 in tension 4 in shear T/2 725 lbs V/4 338 lbs Wp Fp,vert T C Fp 3&  3DUNLQJ6WUXFWXUH (OHFWULF3DQHO www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 1 9/4/2025 Specifier's comments: 1 Input data Anchor type and diameter: Kwik Bolt TZ2 - SS 304 1/2 (3 1/4 ) hnom3 Item number: 2210261 KB-TZ2 1/2x4 1/2 SS304 Specification text: Hilti Æ 1/2 in Kwik Bolt TZ2 - SS 304 with 3.75 in nominal embedment depth per ICC-ES ESR-4266 , Hammer drill bit installation per MPII, Effective embedment depth: hef,act = 3.250 in., hnom = 3.750 in. Material: AISI 304 Evaluation Service Report: ESR-4266 Issued I Valid: 10/1/2024 | 12/1/2025 Proof: Design Method ACI 318-19 / Mech Shear edge breakout verification: Row closest to edge (Case 3 only from ACI 318-19 Fig. R.17.7.2.1b) Stand-off installation: Profile: Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 12.000 in. Installation: Hammer drilled hole, Installation condition: Dry Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d)) Shear load: yes (17.10.6.3 (c)) 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 2 9/4/2025 Geometry [in.] & Loading [lb, in.lb] 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 3 9/4/2025 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 725; Vx = 59; Vy = 338; Mx = 0; My = 0; Mz = 0; yes 48 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 725 343 59 338 3 Tension load Load Nua [lb]Capacity f Nn [lb]Utilization bN = Nua/f Nn Status Steel Strength*725 8,906 9 OK Pullout Strength*N/A N/A N/A N/A Concrete Breakout Failure**725 1,535 48 OK * highest loaded anchor **anchor group (anchors in tension) 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 4 9/4/2025 3.1 Steel Strength Nsa = ESR value refer to ICC-ES ESR-4266 f Nsa ³ Nua ACI 318-19 Table 17.5.2 Variables Ase,N [in.2]futa [psi] 0.10 120,404 Calculations Nsa [lb] 11,875 Results Nsa [lb]f steel f Nsa [lb]Nua [lb] 11,875 0.750 8,906 725 3.2 Concrete Breakout Failure Ncb = (ANcANc0)y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1a) f Ncb ³ Nua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,min cac , 1.5hef cac )£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables hef [in.]ca,min [in.]y c,N cac [in.]kc l a f' c [psi] 3.250 3.000 1.000 7.500 17 1.000 3,000 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 62.02 95.06 0.885 1.000 5,455 Results Ncb [lb]f concrete f seismic f nonductile f Ncb [lb]Nua [lb] 3,148 0.650 0.750 1.000 1,535 725 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 5 9/4/2025 4 Shear load Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status Steel Strength*343 5,426 7 OK Steel failure (with lever arm)*N/A N/A N/A N/A Pryout Strength**343 4,408 8 OK Concrete edge failure in direction y+**343 1,075 32 OK * highest loaded anchor **anchor group (relevant anchors) 4.1 Steel Strength Vsa,eq = ESR value refer to ICC-ES ESR-4266 f Vsteel ³ Vua ACI 318-19 Table 17.5.2 Variables Ase,V [in.2]futa [psi]aV,seis 0.10 120,404 1.000 Calculations Vsa,eq [lb] 8,348 Results Vsa,eq [lb]f steel f Vsa,eq [lb]Vua [lb] 8,348 0.650 5,426 343 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 6 9/4/2025 4.2 Pryout Strength Vcp = kcp [(ANc ANc0)y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1a) f Vcp ³ Vua ACI 318-19 Table 17.5.2 ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANc0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.1.4) y ed,N = 0.7 + 0.3 (ca,min 1.5hef)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) y cp,N = MAX(ca,mincac , 1.5hefcac)£ 1.0 ACI 318-19 Eq. (17.6.2.6.1b) Nb = kc l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables kcp hef [in.]ca,min [in.]y c,N 2 3.250 3.000 1.000 cac [in.]kc l a f' c [psi] 7.500 17 1.000 3,000 Calculations ANc [in.2]ANc0 [in.2]y ed,N y cp,N Nb [lb] 62.02 95.06 0.885 1.000 5,455 Results Vcp [lb]f concrete f seismic f nonductile f Vcp [lb]Vua [lb] 6,297 0.700 1.000 1.000 4,408 343 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW www.hilti.com Hilti PROFIS Engineering 3.1.20 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7 Company: Address: Phone I Fax: Design: Fastening point: | Concrete - Aug 1, 2025 Page: Specifier: E-Mail: Date: 7 9/4/2025 4.3 Concrete edge failure in direction y+ Vcb = (AVc AVc0)y ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1a) f Vcb ³ Vua ACI 318-19 Table 17.5.2 AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)* AVc0 = 4.5 c2 a1 ACI 318-19 Eq. (17.7.2.1.3) y ed,V = 0.7 + 0.3(ca2 1.5ca1)£ 1.0 ACI 318-19 Eq. (17.7.2.4.1b) y h,V = √1.5ca1ha ³ 1.0 ACI 318-19 Eq. (17.7.2.6.1) Vb = (7 (leda)0.2 √da)l a √f' c c1.5 a1 ACI 318-19 Eq. (17.7.2.2.1a) Variables ca1 [in.]ca2 [in.]y c,V ha [in.]le [in.] 3.000 3.000 1.000 12.000 3.250 l a da [in.]f' c [psi]y parallel,V 1.000 0.500 3,000 1.000 Calculations AVc [in.2]AVc0 [in.2]y ed,V y h,V Vb [lb] 33.75 40.50 0.900 1.000 2,048 Results Vcb [lb]f concrete f seismic f nonductile f Vcb [lb]Vua [lb] 1,536 0.700 1.000 1.000 1,075 343 *Anchor row defined by: Anchor 1; Case 3 controls 5 Combined tension and shear loads, per ACI 318-19 section 17.8 bN bV z Utilization bN,V [%]Status 0.472 0.319 5/3 44 OK bNV = bz N + bz V <= 1 3& (OHFWULF3DQHO&RQFUHWH$QFKRUDJH5HSRUW Wood Beam LIC# : KW-06015294, Build:20.25.07.09 GROSSMAN & SPEER ASSOCIATES, INC.(c) ENERCALC, LLC 1982-2025 DESCRIPTION:Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Project File: ENERCALC_20 Referenced Design Standard(s) : NDS 2018 Load Combination Set : IBC 2018 Code References Governing Code : IBC 2018, CBC 2019 Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.1 1000 1000 1500 625 1700 620 180 675 31.21 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2018 2-2x8 Span = 21.0 ft 1 2 D(0.02128) Lr(0.0133) .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.010 ksf, Tributary Width = 1.330 ft .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.573: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 10.500ft 27.00 psi= = 1,725.00psi 2-2x8Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 225.00 psi== Section used for this span 2-2x8 Maximum Shear Stress Ratio 0.120 : 1 0.000 ft== 989.03psi Maximum Deflection 697 <360 235Ratio =0 <180 Max Downward Transient Deflection 0.361 in 0 Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 1.068 in Ratio =>=180Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1.00Length = 21.0 ft 1 0.527 0.110 0.90 1.200 1.151.00 1.00 1.43 654.3 1,242.0 0.26 162.01.00 17.91.00 1.00+D+Lr 1.200 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 21.0 ft 1 0.573 0.120 1.25 1.200 1.151.00 1.00 2.17 989.0 1,725.0 0.39 225.01.00 27.01.00 . LocationLoad CombinationMax.LocationLoad CombinationSpan Max. Overall Maximum Deflections "-" Defl in Span in Span"+" Defl +D+Lr1 1.0678 10.577 0.0000 0.000 3&Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Wood Beam LIC# : KW-06015294, Build:20.25.07.09 GROSSMAN & SPEER ASSOCIATES, INC.(c) ENERCALC, LLC 1982-2025 DESCRIPTION:Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Project File: ENERCALC_20 Location in SpanMax. Downward Defl Location in SpanLoad Combination Span Max. Upward Defl Maximum Deflections for Load Combinations D Only 1 0.7064 10.577 0.0000 0.000in ftinft +D+Lr 1 1.0678 10.577 0.0000 0.000in ftinft +D+0.750Lr 1 0.9775 10.577 0.0000 0.000in ftinft+0.60D 1 0.4238 10.577 0.0000 0.000in ftinft Lr Only 1 0.3614 10.577 0.0000 0.000in ftinft . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.413 0.413 Max Upward from Load Combinations 0.413 0.413 Max Upward from Load Cases 0.273 0.273 D Only 0.273 0.273 +D+Lr 0.413 0.413 +D+0.750Lr 0.378 0.378 +0.60D 0.164 0.164 Lr Only 0.140 0.140 3&Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Wood Beam LIC# : KW-06015294, Build:20.25.07.09 GROSSMAN & SPEER ASSOCIATES, INC.(c) ENERCALC, LLC 1982-2025 DESCRIPTION:Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Project File: ENERCALC_20 Referenced Design Standard(s) : NDS 2018 Load Combination Set : IBC 2018 Code References Governing Code : IBC 2018, CBC 2019 Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.1 1000 1000 1500 625 1700 620 180 675 31.21 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :IBC 2018 2-2x6 Span = 15.80 ft 1 2 D(0.02128) Lr(0.0133) .Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loading Uniform Load : D = 0.0160, Lr = 0.010 ksf, Tributary Width = 1.330 ft .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.506: 1 Load Combination +D+Lr Span # where maximum occurs Span # 1 Location of maximum on span 7.900ft 26.00 psi= = 1,868.75psi 2-2x6Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+Lr = = = 225.00 psi== Section used for this span 2-2x6 Maximum Shear Stress Ratio 0.116 : 1 15.396 ft== 944.66psi Maximum Deflection 714 <360 249Ratio =0 <180 Max Downward Transient Deflection 0.265 in 0 Ratio =>=360 Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection 0.761 in Ratio =>=180Max Upward Total Deflection 0 in fb: Actual F'b fv: Actual F'v Span: 1 : Lr Only n/a Span: 1 : +D+Lr n/a .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCMCF rt Shear ValuesMax Stress Ratios M CDV fbM fvF'b V F'vSegment Length Cfu D Only 0.0 0.00 0.00.0 1.00Length = 15.80 ft 1 0.457 0.105 0.90 1.300 1.151.00 1.00 0.78 615.4 1,345.5 0.19 162.01.00 16.91.00 1.00+D+Lr 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.01.00 1.00Length = 15.80 ft 1 0.506 0.116 1.25 1.300 1.151.00 1.00 1.19 944.7 1,868.8 0.29 225.01.00 26.01.00 . LocationLoad CombinationMax.LocationLoad CombinationSpan Max. Overall Maximum Deflections "-" Defl in Span in Span"+" Defl +D+Lr1 0.7611 7.958 0.0000 0.000 3&Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Wood Beam LIC# : KW-06015294, Build:20.25.07.09 GROSSMAN & SPEER ASSOCIATES, INC.(c) ENERCALC, LLC 1982-2025 DESCRIPTION:Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Project File: ENERCALC_20 Location in SpanMax. Downward Defl Location in SpanLoad Combination Span Max. Upward Defl Maximum Deflections for Load Combinations D Only 1 0.4958 7.958 0.0000 0.000in ftinft +D+Lr 1 0.7611 7.958 0.0000 0.000in ftinft +D+0.750Lr 1 0.6947 7.958 0.0000 0.000in ftinft+0.60D 1 0.2975 7.958 0.0000 0.000in ftinft Lr Only 1 0.2653 7.958 0.0000 0.000in ftinft . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.301 0.301 Max Upward from Load Combinations 0.301 0.301 Max Upward from Load Cases 0.196 0.196 D Only 0.196 0.196 +D+Lr 0.301 0.301 +D+0.750Lr 0.275 0.275 +0.60D 0.118 0.118 Lr Only 0.105 0.105 3&Ceiling joist Details 2F/A-6.1 and 1T, 1U of sheet S5 Company:Date:1/27/2026 Engineer:Page:1 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 1.Project information Project description: Location: Design name: Design Comment: 2. Input Data &Anchor Parameters GeneralDesign method:ACI 318-19 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: A615 Grade 60 Rebar Diameter (inch): 0.875 Effective Embedment depth,hef (inch): 17.500 Code report: ICC-ES ESR-4057 Anchor category:- Anchor ductility: Yes hmin (inch): 19.50 cac (inch): 43.56 Cmin (inch): 1.75 Smin (inch): 3.00 Base MaterialConcrete: Normal-weight Concrete thickness,h (inch): 25.00 State: Cracked Compressive strength, f’c (psi): 2500 Ψc,V:1.0 Reinforcement condition:B tension,B shear Supplemental edge reinforcement: Not applicable Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hole condition: Dry concrete Inspection: Continuous Temperature range, Short/Long: 150/110°F Reduced installation torque (for AT-3G): Not applicable Ignore 6do requirement: Not applicable Build-up grout pad: No Recommended AnchorAnchor Name: SET-3G™-SET-3G w/ #7 A615 Gr. 60 Rebar Code Report: ICC-ES ESR-4057 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:2 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 Load and GeometryLoad factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: Yes Anchors subjected to sustained tension: No Ductility section for tension: 17.10.5.2 not applicable Ductility section for shear: 17.10.6.2 not applicable Ω0 factor: not set Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]: 21631 Vuax [lb]:0 Vuay [lb]: 6574 <Figure 1> Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& N  A N 6HH&DOFSDJH3 Company:Date:1/27/2026 Engineer:Page:3 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 <Figure 2> 3. Resulting Anchor Forces Anchor Tension load, Nua (lb) Shear load x, Vuax (lb) Shear load y, Vuay (lb) Shear load combined, √(Vuax)²+(Vuay)² (lb) 1 21631.0 0.0 6574.0 6574.0 Sum 21631.0 0.0 6574.0 6574.0 Maximum concrete compression strain (‰): 0.00 Maximum concrete compression stress (psi):0 Resultant tension force (lb): 21631 Resultant compression force (lb):0 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:4 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 4. Steel Strength of Anchor in Tension (Sec. 17.6.1) Nsa (lb)Nsa (lb) 54000 0.75 40500 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.6.2) Nb = kc a f’chef1.5 (Eq. 17.6.2.2.1) kc a f’c (psi)hef (in)Nb (lb) 17.0 1.00 2500 17.500 62227 0.75 Ncb =0.75 (ANc/ ANco)ed,N c,N cp,NNb (Sec. 17.5.1.2 &Eq. 17.6.2.1a) ANc (in2)ANco (in2 ca,min (in)ed,N c,N cp,N Nb (lb)0.75 Ncb (lb) 2756.25 2756.25 -1.000 1.00 1.000 62227 0.65 30335 6. Adhesive Strength of Anchor in Tension (Sec. 17.6.5) k,cr =k,crfshort-termKsat(f’c /2,500)n N.seis k,cr (psi)fshort-term Ksat N.seis f’c (psi)n k,cr (psi) 1265 1.00 1.00 1.00 2500 0.25 1265 Nba =a cr dahef (Eq. 17.6.5.2.1) a cr (psi)da (in)hef (in)Nba (lb) 1.00 1265 0.88 17.500 60854 0.75 Na =0.75 (ANa / ANa0)ed,Na cp,NaNba (Sec. 17.5.1.2 &Eq. 17.6.5.1a) ANa (in2)ANa0 (in2)cNa (in)ca,min (in)ed,Na p,Na Na0 (lb)0.75 Na (lb) 493.90 493.90 11.11 -1.000 1.000 60854 0.65 29666 8. Steel Strength of Anchor in Shear (Sec. 17.7.1) Vsa (lb)grout V,seis grout V,seis Vsa (lb) 32400 1.0 0.65 0.60 12636 10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.7.3) Vcp =min|kcpNa ;kcpNcb| =min|kcp(ANa / ANa0)ed,Na cp,NaNba ;kcp(ANc / ANco)ed,N c,N cp,NNb|(Sec. 17.5.1.2 &Eq. 17.7.3.1a) Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:5 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 kcp ANa (in2)ANa0 (in2)ed,Na cp,Na Nba (lb)Na (lb) 2.0 493.90 493.90 1.000 1.000 60854 60854 ANc (in2)ANco (in2)ed,N c,N cp,N Nb (lb)Ncb (lb)Vcp (lb) 2756.25 2756.25 1.000 1.000 1.000 62227 62227 0.70 85195 11. Results Interaction of Tensile and Shear Forces (Sec. R17.8) Tension Factored Load,Nua (lb)Design Strength, øNn (lb)Ratio Status Steel 21631 40500 0.53 Pass Concrete breakout 21631 30335 0.71 Pass Adhesive 21631 29666 0.73 Pass (Governs) Shear Factored Load,Vua (lb)Design Strength, øVn (lb)Ratio Status Steel 6574 12636 0.52 Pass (Governs) Pryout 6574 85195 0.08 Pass Interaction check (Nua/ɸNua)5/3 (Vua/ɸVua)5/3 Utilization Ratio Permissible Status Sec. R17.8 0.59 0.34 92.7% 1.0 Pass SET-3G w/ #7 A615 Gr. 60 Rebar with hef = 17.500 inch meets the selected design criteria. 12. Warnings -Per designer input, the tensile component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor tensile force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.10.5.2 for tension need not be satisfied –designer to verify. -Per designer input, the shear component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor shear force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.10.6.2 for shear need not be satisfied –designer to verify. -Designer must exercise own judgement to determine if this design is suitable. -Refer to manufacturer’s product literature for hole cleaning and installation instructions. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Detail Report: WP16 (In-Plane, Region R1) CRITERIA Code:TMS 402-16: Strength Special Insp:No Wall Area:NCMA Hor Bar Size:#5 Vert Bar Size:#3 No. Tens Bars:1 Effective Depth (in):204 MATERIALS Masonry f'm (ksi):1.5 Masonry Em (ksi):1350 Steel fy (ksi):40 Steel E (ksi):29000 Block Material:Conc 115 pcf Grout Weight:140 pcf Wall Dead Wt (psf):78 GEOMETRY Total Height (ft):8.5 Total Length (ft):17 Block Grouting:Fully Grouted Grout Spacing:24" Block Nom Width:8" 1.5 Shear Factor:No ENVELOPE DIAGRAMS Max: 77.282 at 0 ft Min: 64.294 at 8.5 ft P k Max: 26.406 at 4.25 ft V k Max: 466.784 at 8.5 ft Min: 227.766 at 0 ft M k-ft AXIAL DETAILS P/(Pn*Φ):0.065 P (k):77.282 Pn (k):1329.508 Φ:0.9 Location (ft):0 Load Comb:1 Rad gyration r (in):2.2 h'/r:46.364 Red Factor R:0.89 BENDING SUMMARY Mu/(Mn*Φ):0.865 Mu (k-ft):466.784 Mn (k-ft):599.83 Φ:0.9 Location (ft):8.5 Load Comb:1 a (in):7.027 c (in):8.783 d (in):204 SHEAR SUMMARY Vu/(Vn*Φ):0.218 Vu (k):26.406 Vn (k):151.623 Φ:0.8 Location (ft):8.5 Load Comb:1 Corresponding M (k- ft): 466.784 Corresponding P (k):64.294 M / (V*d):1 Sh Steel Reqd:No Gammag:1 CROSS SECTION DETAILING (1 ) # 3 e a . c e l l (1 ) T o t 8 7. 6 2 5 No horizontal reinforcement required NOTE: All units are in "in." RISA-3D Version 23 [ 24142 Parking(23) Gravity.r3d ]Page 1 1HZ&08:DOO)RRWLQJ6WDELOLW\ 3DUNLQJ6WUXFWXUH 3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR /   +  6KHDU:DOO 6KHDU:DOO)RXQGDWLRQ 1 &086KHDU:DOO(DVWRI*ULG Σw 9 H 5 1HZ&08:DOO)RRWLQJ6WDELOLW\ 3DUNLQJ6WUXFWXUH  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR /   +  6KHDU:DOO 6KHDU:DOO)RXQGDWLRQ 1 &086KHDU:DOO6RXWK6LGH Σw 9 H 5 1HZ&08:DOO)RRWLQJ6WDELOLW\ 3DUNLQJ6WUXFWXUH  3& GROSSMAN & SPEER ASSOCIATES, INC.STRUCTURAL ENGINEERS 529 HAHN AVENUE, SUITE 200, GLENDALE, CALIFORNIA 91203 (818) 507-1020 • FAX (818) 507-1556 e-mail: engineers@grossmanspeer.com PROJECT NUMBER: PROJECT:FOR:PAGE: SUBJECT:BY:DATE: LR1HZ&08:DOO)RRWLQJ6WDELOLW\ 3DUNLQJ6WUXFWXUH  3& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 1 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 1 1/27/2026 Specifier's comments: 1 Input data Anchor type and diameter: HY 200-A V3 + Rebar A615 Gr.60 #6 Item number: not available (element) / 2334276 HIT-HY 200-R V3 (adhesive) Specification text: #6 HY 200-A V3 + Rebar A615 Gr.60 with 6.75 in nominal embedment depth per ICC-ES ESR-4878 , Hammer drilled installation per MPII Effective embedment depth: hef = 6.750 in. Material: ASTM A 615 GR.60 Evaluation Service Report: ESR-4878 Issued I Valid: 9/1/2025 | 11/1/2025 Proof: Design Method LRFD (AC58) Masonry + ACI 318-19 Stand-off installation: Profile: Base material: cracked Grout-filled CMU, f=1500, f = 1,500 psi, L x W x H: 16.000 in. x 8.000 in. x 8.000 in.; Solid Head Joint: yes; open ended unit: yes Temp. short/long: 32 °F / 32 °F Joints: vertical: 0.375 in.; horizontal: 0.375 in. Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry Seismic loads (cat. C, D, E, or F) Tension load: yes (17.10.5.3 (d)) Shear load: yes (17.10.6.3 (c)) $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 2 1/27/2026 Geometry [in.] $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 3 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 3 1/27/2026 Geometry [in.] & Loading [lb, in.lb] 1.1 Design results Case Description Forces [lb] / Moments [in.lb]Seismic Max. Util. Anchor [%] 1 Combination 1 N = 0; Vx = 0; Vy = 4,335; Mx = 0; My = 0; Mz = 0; Nsus = 0; Mx,sus = 0; My,sus = 0; yes 98 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force y 1 0 4,335 0 4,335     6HH&DOFSDJH3 $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 4 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 4 1/27/2026 3 Shear load Load [lb]Capacity [lb]Utilization bV [%]Status Steel 4,335 8,870 49 OK Pryout cone 4,335 11,409 38 OK Masonry crushing strength 4,335 4,435 98 OK Masonry breakout in direction y+4,335 10,831 41 OK 3.1 Steel strength Vsa = ESR value refer to ICC-ES ESR-4878 f Vsa ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 Vsa,seismic [lb]f f seismic f Vsa [lb]Vua [lb] 14,783 0.600 1.000 8,870 4,335 3.2 Pryout strength (Masonry breakout strength controls) Vmpg = kcp · Nmbgf Vmpg ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 ANm see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b) ANm0 = 9 h2 ef ACI 318-19 Eq. (17.6.2.2.1) y ec1,N,m = (1 1 + ec1,N cNa )£ 1.0 ACI 318-19 Eq. (17.6.2.3.1) y ec1,N,m = (1 1 + ec2,NcNa )£ 1.0 ACI 318-19 Eq. (17.6.2.3.1) y ed,N,m = 0.7 + 0.3 (c ccr,N)£ 1.0 ACI 318-19 Eq. (17.6.2.4.1b) Nb,m = km l a √f' c h1.5 ef ACI 318-19 Eq. (17.6.2.2.1) Variables kcp hef [in.]ec1,N [in.]ec2,N [in.]ca,min [in.]y c,N 2 6.750 0.000 0.000 26.000 1.000 km l a 12 1.000 Calculations ANm [in.2]ANm0 [in.2]y ec1,N,m y ec2,N,m y ed,N Nb,m [lb] 410.06 410.06 1.000 1.000 1.000 8,150 Results Vmpg [lb]f concrete f seismic f Vmpg [lb]Vua [lb] 16,299 0.700 1.000 11,409 4,335 $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 5 1/27/2026 3.3 Masonry crushing strength f Vmc ³ Vua AC58 Table 3.2 Vmc = 1750 · (f' m · Ase,V) 14 AC58 Eq. 3-1 Variables f' m [psi]Ase,v [in.2] 1,500 0.44 Results Vmc [lb]f f seismic f Vmc [lb]Vua [lb] 8,870 0.500 1.000 4,435 4,335 3.4 Masonry breakout strength y+ Vmb = (AVm AVm0)y m,V y h,V,m y parallel,V Vb,m ACI 318-19 Eq. (17.7.2.1a) f Vmb ³ Vua AC58 Table 3.2 + ACI 318-19 Table 17.5.2 AVm see ACI 318-19 , Section 17.7.2.1, Fig. R 17.7.2.1(b) AVm0 = 4.5 c2 a1 ACI 318-19 Eq. (17.7.2.1.3) y ed,V,m = 0.7 + 0.3(ca2 1.5ca1)£ 1.0 ACI 318-19 Eq. (17.7.2.4.1b) y h,V,m = √1.5ca1ha ³ 1.0 ACI 318-19 Eq. (17.7.2.6.1) Vb,m = (7 (le da)0.2 √da)l a √f' m c1.5 a1 ACI 318-19 Eq. (17.7.2.2.1a) Variables le [in.]da [in.]ca1 [in.]ca2 [in.]AVm [in.2]AVm0 [in.2]f' m [psi] 6.000 0.750 26.667 26.000 503.25 3,200.00 1,500 Calculations y ed,V,m y parallel,V ec,V [in.]y m,V y h,V,m 0.895 1.000 0.000 1.000 2.290 Results Vb,m [lb]f f seismic f Vmbg [lb]Vua [lb] 47,995 0.700 1.000 10,831 4,335 $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 6 1/27/2026 4 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (EN1992-4, AS5216, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • The equations presented in this report are based on imperial units. When inputs are displayed in metric units, the user should be aware that the equations remain in their imperial format. • Refer to the manufacturer's product literature for cleaning and installation instructions. • The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG. • Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS! • Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar joints. • The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration. • If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void. • The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use provided with the product have to be followed to ensure a proper installation. • The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user. • Drilling method (hammer, rotary) to be in accordance with the approval! • Masonry should be built according to industry standards. Fastening meets the design criteria! $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 7 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 7 1/27/2026 5 Installation data Anchor plate, steel: - Anchor type and diameter: HY 200-A V3 + Rebar A615 Gr.60 #6 Profile: - Item number: not available (element) / 2334276 HIT-HY 200-R V3 (adhesive) Hole diameter in the fixture: - Maximum installation torque: 1,200 in.lb Plate thickness (input): - Hole diameter in the base material: 0.875 in. Hole depth in the base material: 6.750 in. Drilling method: Drilled in hammer mode Minimum thickness of the base material: 7.625 in. Cleaning: No cleaning of the drilled hole is required #6 HY 200-A V3 + Rebar A615 Gr.60 with 6.75 in nominal embedment depth per ICC-ES ESR-4878 , Hammer drilled installation per MPII Coordinates Anchor in. Anchor x y c-x c+x c-y c+y 1 0.000 0.000 40.000 26.000 50.000 50.000 $QFKRUDJH'HWDLO63& www.hilti.com Hilti PROFIS Engineering 3.1.26 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2026 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 8 Company: Address: Phone I Fax: Design: Fastening point: | Masonry - Jan 26, 2026 Page: Specifier: E-Mail: Date: 8 1/27/2026 6 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:1 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 1.Project information Project description: Location: Design name: Design Comment: 2. Input Data &Anchor Parameters GeneralDesign method:ACI 318-19 Units: Imperial units Anchor Information: Anchor type: Bonded anchor Material: A615 Grade 60 Rebar Diameter (inch): 0.750 Effective Embedment depth,hef (inch): 6.000 Code report: ICC-ES ESR-4057 Anchor category:- Anchor ductility: Yes hmin (inch): 7.75 cac (inch): 8.77 Cmin (inch): 1.75 Smin (inch): 3.00 Base MaterialConcrete: Normal-weight Concrete thickness,h (inch): 25.00 State: Cracked Compressive strength, f’c (psi): 2500 Ψc,V:1.0 Reinforcement condition:B tension,B shear Supplemental edge reinforcement: Not applicable Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Hole condition: Dry concrete Inspection: Continuous Temperature range, Short/Long: 150/110°F Reduced installation torque (for AT-3G): Not applicable Ignore 6do requirement: Not applicable Build-up grout pad: No Recommended AnchorAnchor Name: SET-3G™-SET-3G w/ #6 A615 Gr. 60 Rebar Code Report: ICC-ES ESR-4057 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:2 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 Load and GeometryLoad factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: Yes Anchors subjected to sustained tension: No Ductility section for tension: 17.10.5.2 not applicable Ductility section for shear: 17.10.6.2 not applicable Ω0 factor: not set Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]:0 Vuax [lb]: 4335 Vuay [lb]:0 <Figure 1> Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63&     6HH&DOFSDJH3 Company:Date:1/27/2026 Engineer:Page:3 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 <Figure 2> 3. Resulting Anchor Forces Anchor Tension load, Nua (lb) Shear load x, Vuax (lb) Shear load y, Vuay (lb) Shear load combined, √(Vuax)²+(Vuay)² (lb) 1 0.0 4335.0 0.0 4335.0 Sum 0.0 4335.0 0.0 4335.0 Maximum concrete compression strain (‰): 0.00 Maximum concrete compression stress (psi):0 Resultant tension force (lb):0 Resultant compression force (lb):0 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'Vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'Vy (inch): 0.00 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& Company:Date:1/27/2026 Engineer:Page:4 Project: Address: Phone: E-mail: Anchor Designer™ for Concrete Software Version 3.3.2501.2 8. Steel Strength of Anchor in Shear (Sec. 17.7.1) Vsa (lb)grout V,seis grout V,seis Vsa (lb) 23760 1.0 0.65 0.60 9266 9. Concrete Breakout Strength of Anchor in Shear (Sec. 17.7.2) Shear parallel to edge in y-direction: Vbx =min|7(le / da)0.2 da a f’cca11.5; 9 a f’cca11.5|(Eq. 17.7.2.2.1a &Eq. 17.7.2.2.1b) le (in)da (in)a f’c (psi)ca1 (in)Vbx (lb) 6.00 0.750 1.00 2500 4.00 3600 Vcby =(2)(AVc/ AVco)ed,V c,V h,VVbx (Sec. 17.5.1.2, 17.7.2.1(c)&Eq. 17.7.2.1a) AVc (in2)AVco (in2)ed,V c,V h,V Vbx (lb)Vcby (lb) 72.00 72.00 1.000 1.000 1.000 3600 0.70 5040 10. Concrete Pryout Strength of Anchor in Shear (Sec. 17.7.3) Vcp =min|kcpNa ;kcpNcb| =min|kcp(ANa / ANa0)ed,Na cp,NaNba ;kcp(ANc / ANco)ed,N c,N cp,NNb|(Sec. 17.5.1.2 &Eq. 17.7.3.1a) kcp ANa (in2)ANa0 (in2)ed,Na cp,Na Nba (lb)Na (lb) 2.0 157.63 388.23 0.822 1.000 18520 6179 ANc (in2)ANco (in2)ed,N c,N cp,N Nb (lb)Ncb (lb)Vcp (lb) 144.00 324.00 0.833 1.000 1.000 12492 4627 0.70 6478 11. Results Interaction of Tensile and Shear Forces (Sec. 17.8) Shear Factored Load,Vua (lb)Design Strength, øVn (lb)Ratio Status Steel 4335 9266 0.47 Pass || Concrete breakout y+ 4335 5040 0.86 Pass (Governs) Pryout 4335 6478 0.67 Pass SET-3G w/ #6 A615 Gr. 60 Rebar with hef = 6.000 inch meets the selected design criteria. 12. Warnings -Per designer input, the tensile component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor tensile force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.10.5.2 for tension need not be satisfied –designer to verify. -Per designer input, the shear component of the strength-level earthquake force applied to anchors does not exceed 20 percent of the total factored anchor shear force associated with the same load combination. Therefore the ductility requirements of ACI 318 17.10.6.2 for shear need not be satisfied –designer to verify. -Designer must exercise own judgement to determine if this design is suitable. -Refer to manufacturer’s product literature for hole cleaning and installation instructions. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong-Tie Company Inc.5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com $QFKRUDJH'HWDLO63& BUILDING ENERGY ANALYSIS REPORT PROJECT: Project Designer: Report Prepared by: Job Number: Date: The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2022 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC – www.energysoft.com. Foothill Cardiology Medical Group, Inc 2712 Loker Avenue West #1063 2910 West Broadway, Suite 200 Los Angeles, CA 90041 Nakaishi Associates Architects Pro Engineering Ray Parsi (323) 255-1008 Arcadia, CA 91006 11/18/2025 24-574 Carlsbad, CA 92010 (949)-842-2199 30 South 1st Avenue TABLE OF CONTENTS 3 1 Table of Contents 2 Form NRCC/LMCC-PRF-E Certificate of Compliance Cover Page CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 1 of 17) Project Name: Foothill Cardiology Date Prepared: 2025-11-18 A. General Information 1 Project Name Foothill Cardiology 2 Run Title Title 24 Analysis 3 Project Location 30 South 1st Avenue 4 City Arcadia 5 Standards Version Compliance 2022 6 Zip code 91006 7 Compliance Software (version)EnergyPro 9.4 8 Climate Zone 9 9 Building Orientation (deg)0 10 Building Type(s)• Nonresidential 11 Weather File HOLLYWOOD-BURBANK_STYP20.epw 12 Project Scope • Existing addition and alteration 13 Number of Dwelling Units 0 14 Total Conditioned Floor Area in Scope (ft2)12206 15 Total # of hotel/motel rooms 0 16 Total Unconditioned Floor Area (ft2)0 17 Fuel Type Natural gas 18 Nonresidential Conditioned Floor Area 12206 19 Total # of Stories (Habitable Above Grade)1 20 Residential Conditioned Floor Area 0 CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 2 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 B. PROJECT SUMMARY Table B shows which building components are included in the performance calculation. If indicated as not included, the project must show compliance prescriptively if within the permit application. Building Components Complying via Performance Building Components Complying Prescriptively Envelope (See Table G)Nonres Performance Solar Thermal Water Heating (See Table I3) Performance The following building components are ONLY eligible for prescriptive compliance and should be documented on the NRCC form listed if within the scope of the permit application (i.e. compliance will not be shown on the NRCC-PRF-E).MultiFam Not Included Not Included Mechanical (See Table H) Nonres Performance Covered Process: Commercial Kitchens (see Table J) Performance Indoor Lighting (Unconditioned) 140.6 & 170.2(e) NRCC-LTI-E is required MultiFam Not Included Not Included Outdoor Lighting 140.7 & 170.2(e)NRCC-LTO-E is required Domestic Hot Water (See Table I) Nonres Performance Covered Process: Laboratory Exhaust (see Table J) Performance Sign Lighting 140.8 & 170.2(e)NRCC-LTS-E is required MultiFam Not Included Not Included Building Components Complying with Mandatory Measures Lighting (Indoor Conditioned, see Table K) Nonres Not Included Photovoltaics (see Table F) Performance Electrical power systems, commissioning, solar ready, elevator and escalator requirements are mandatory and should be documented on the NRCC form listed if applicable (i.e. compliance will not be shown on the NRCC-PRF-E.) MultiFam Not Included Not Included Electrical Power Distribution 110.11 NRCC-ELC-E is required Battery (see Table F) Performance Commissioning 120.8 NRCC-CXR-E is required Not Included Solar and Battery 110.10 NRCC-SAB-E is required CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 3 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 C1. COMPLIANCE SUMMARY COMPLIES3 Time Dependent Valuaton (TDV)Source Energy Use Efficiency1 (kBtu/ft2 - yr)Total2 (kBtu/ft2 - yr)Total2 (kBtu/ft2 - yr) Standard Design 434.24 n/a n/a Proposed Design 420.48 n/a n/a Compliance Margins 13.76 n/a n/a Pass n/a n/a 1 Efficiency measures include improvements like a better building envelope and more efficient equipment 2 Compliance Totals include efficiency, photovoltaics and batteries 3 New Construction, Complete Addition Scope: Building complies when all efficiency and total compliance margins are greater than or equal to zero and unmet load hour limits are not exceeded Existing, Addition and Alteration Scope: Building complies when efficiency compliance margin is greater than or equal to zero and unmet load hour limits are not exceeded CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 4 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 C2. TDV ENERGY COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft2 - yr) COMPLIES2 Energy Component Standard Design (TDV)Proposed Design (TDV)Compliance Margin (TDV)1 Space Heating 2.01 2.81 -0.8 Space Cooling 184.74 219.42 -34.68 Indoor Fans 175.11 131.95 43.16 Heat Rejection 0 0 0 Pumps & Misc.0 0 0 Domestic Hot Water 11.24 5.16 6.08 Indoor Lighting 61.14 61.14 0 Flexibility --------- EFFICIENCY COMPLIANCE TOTAL 434.24 420.48 13.76 (3.2%) Photovoltaics --------- Batteries --------- TOTAL COMPLIANCE 434.24 420.48 13.76 (3.2%) 1 Notes: This number in parenthesis following the Compliance Margin in column 4, represents the Percent Better than Standard. CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 5 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 C3. TDV ENERGY RESULTS FOR NON-REGULATED COMPONENTS1 Non-Regulated Energy Component Standard Design (TDV)Proposed Design (TDV)Compliance Margin (TDV)1 Receptacle 121.12 121.12 --- Process 705.23 705.23 --- Other Ltg --------- Process Motors --------- TOTAL (TOTAL COMPLIANCE + NON-REGULATED COMPONENTS)1260.59 1246.83 13.76 (1.1%) 1 Notes: This table is not used for Energy Code Compliance. C6. 'ABOVE CODE' QUALIFICATIONS This project is pursuing CalGreen Tier 1 This project is pursuing CalGreen Tier 2 CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 6 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 C7. ENERGY USE SUMMARY Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Margin (MWh) Standard Design Site (MBtu) Proposed Design Site (MBtu) Margin (MBtu) Space Heating ---0.2 ---8.5 9.5 -1 Space Cooling 69.4 86.5 -17.1 --------- Indoor Fans 72 58 14 --------- Heat Rejection ------------------ Pumps & Misc.------------------ Domestic Hot Water 3.3 ------21.8 24.7 -2.9 Indoor Lighting 29.1 29.1 0 --------- Flexibility ------------------ EFFICIENCY TOTAL 173.8 173.8 0 30.3 34.2 -3.9 Photovoltaics ------------------ Batteries ------------------ ENERGY USE SUBTOTAL 173.8 173.8 0 30.3 34.2 -3.9 Receptacle 52.7 52.7 0 55.3 55.3 0 Process 324.7 324.7 0 --------- Other Ltg ------------------ Process Motors ------------------ ENERGY USE TOTAL 551.2 551.2 0 85.6 89.5 -3.9 CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 7 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 C8. ENERGY USE INTENSITY (EUI) Standard Design (kBtu/ft2 / yr)Proposed Design (kBtu/ft2 / yr)Margin (kBtu/ft2 / yr)Margin Percentage GROSS EUI1 161.09 161.41 -0.32 -0.2 NET EUI1 161.09 161.41 -0.32 -0.2 1 Notes: Gross EUI is Energy Use Total (not including PV)/Total Building Area. Net EUI is Energy Use Total (including PV)/Total Building Area. D1. EXCEPTIONAL CONDITIONS • The project uses the Simplified Geometry Performance Modeling Approach which is not capable of modeling daylighting controls and assumes the prescriptive Secondary Daylit Control requirements are met. PRESCRIPTIVE COMPLIANCE documentation (form NRCC-LTI-02-E) for the requirements of section 140.6(d) Automatic Daylighting Controls in Secondary Daylit Zones is required. • The proposed building includes HVAC components that do not meet the mandatory efficiency requirements. • The user model includes space(s) that are designed to be served by mechanical cooling systems, but the cooling systems were not included in the simulation model. A cooling system has been modeled for both the proposed and standard cases. • The user model includes space(s) without sufficient cooling equipment. Cooling equipment has been added to the model to meet cooling loads. G1. ENVELOPE GENERAL INFORMATION (conditioned spaces only) 01 02 03 04 Opaque Surfaces & Orientation Total Gross Surface Area (ft2)Total Fenestration Area (ft2)Window to Wall Ratio (%) North-Facing1 2255 594 26.34 East-Facing2 1412 167 11.83 South-Facing3 2275 174 7.65 West-Facing4 1398 219 15.67 Notes 1North-Facing is oriented to within 45 degrees of true north, including 4500'00" east of north (NE), but excluding 4500'00" west of north (NW), 2East-Facing is oriented to within 45 degrees of true east, including 4500'00" south of east (SE), but excluding 4500'00" north of east (NE), 3South-Facing is oriented to within 45 degrees of true south, including 4500'00" west of south (SW), but excluding 4500'00" east of south (SE), 4West-Facing is oriented to within 45 degrees of true west, including 4500'00" north of west (NW), but excluding 4500'00" south of west (SW), CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 8 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 G1. ENVELOPE GENERAL INFORMATION (conditioned spaces only) 01 02 03 04 Opaque Surfaces & Orientation Total Gross Surface Area (ft2)Total Fenestration Area (ft2)Window to Wall Ratio (%) Total 7340 1154 15.72 Roof 12206 0 0 Notes 1North-Facing is oriented to within 45 degrees of true north, including 4500'00" east of north (NE), but excluding 4500'00" west of north (NW), 2East-Facing is oriented to within 45 degrees of true east, including 4500'00" south of east (SE), but excluding 4500'00" north of east (NE), 3South-Facing is oriented to within 45 degrees of true south, including 4500'00" west of south (SW), but excluding 4500'00" east of south (SE), 4West-Facing is oriented to within 45 degrees of true west, including 4500'00" north of west (NW), but excluding 4500'00" south of west (SW), G4. NONRESIDENTIAL AIR BARRIER 01 02 Building Story Name Air Barrier Com-Floor 1 No air barrier CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 9 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 G5. OPAQUE SURFACE ASSEMBLY SUMMARY 01 02 03 04 05 06 07 08 09 10 Surface Name Construction Type Area (ft2)Framing Type Cavity R-Value Continuous R-Value Units Value Description of Assembly Layers Status1 Interior Exterior Masonary Wall8 Exterior Wall 6,670 N/A 0 N/A N/A U-factor 0.2463 Concrete - Solid Grout - 125 lb/ft3 - 8 in. Brick - 48 lb/ft3 - 3 5/8 in.E Slab On Grade14 Underground Floor 12,206 N/A 0 N/A N/A F-factor 0.73 Slab Type =Unheated slab on grade Insulation Orientation =None Insulation R-Value =none E R-30 Roof with attic (Sin16 Roof 12,206 Metal 30 N/A N/A U-factor 0.0589 Single Ply Roofing - 1/4 in. Vapor permeable felt - 1/8 in. Plywood - 1/2 in. Air - Cavity - Wall Roof Ceiling - 4 in. or more Composite-1 Gypsum Board - 1/2 in. A 8 CMU Wall26 Exterior Wall 232 N/A 0 N/A N/A U-factor 0.3794 Concrete - Part Grouted and Empty - 125 lb/ft3 - 8 in.N R-21 Wall Metal Stud49 Exterior Wall 438 Metal 21 N/A N/A U-factor 0.178 Stucco - 7/8 in. Vapor permeable felt - 1/8 in. Composite-2 Gypsum Board - 1/2 in. A R-19 Wall Metal Stud65 Interior Wall 70 Metal 19 N/A N/A U-factor 0.1674 Stucco - 7/8 in. Vapor permeable felt - 1/8 in. Composite-3 Gypsum Board - 1/2 in. E 1 Status: N - New, A - Altered, E - Existing CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 10 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 G7A. FENESTRATION ASSEMBLY SUMMARY (NONRESIDENTIAL) 01 02 03 04 05 06 07 08 09 Fenestration Assembly Name Fenestration Type/ Product Type / Frame Type Certification Method1 Assembly Method Area (ft2) Overall U-factor Overall SHGC Overall VT Status2 Cooling (E) Vertical fenestration Fixed window N/A NFRC Manufactured 786 0.3 0.23 0.5 E Cooling (door)(E) Vertical fenestration Glazed door N/A NFRC Manufactured 24 0.3 0.23 0.5 E Cooling (N)(Window) Vertical fenestration Fixed window N/A NFRC Manufactured 158 0.3 0.23 0.5 N Cooling (N) Vertical fenestration Glazed door N/A NFRC Manufactured 186 0.3 0.23 0.5 N 1 Notes: Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.6-B. Center of Glass (COG) values are for the glass-only, determined by the manufacturer, and are shown for ease of verification. Site-built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis. 2 Status: N - New, A - Altered, E - Existing CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 11 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 H1. DRY SYSTEM EQUIPMENT (FURNACES, AIR HANDLING UNITS, HEAT PUMPS, VRF, ECONOMIZERS ETC.) 01 02 03 04 05 06 07 08 09 10 11 12 Equipment Name Equipment Type Qty Heating Cooling Economizer Type (if present) Status1Total Heating Output (kBtu/h) Supp Heat Output (kBtu/h) Efficiency Unit Efficiency Total Cooling Output (kBtu/h) Efficiency Unit Efficiency RTU-1 (Existing) Single Zone Air Conditioner (SZAC) Air System 1 90 0 AFUE 0 54.73 EER SEER 12.2 14 Fixed DB E RTU-2 (Existing) Single Zone Air Conditioner (SZAC) Air System 1 90 0 AFUE 0 90.25 EER 11 Fixed DB E RTU-3 (Existing) Single Zone Air Conditioner (SZAC) Air System 1 90 0 AFUE 0 90.25 EER 11 Fixed DB E RTU-4 (Existing) Single Zone Air Conditioner (SZAC) Air System 1 90 0 AFUE 0 54.73 EER SEER 12.2 14 Fixed DB E RTU-5 Single Zone Heat Pump (SZHP) Air System 1 88.53 0 COP 3.5 107.73 EER 12.1 Fixed DB N RTU-6 Single Zone Heat Pump (SZHP) Air System 1 88.53 0 COP 3.5 107.73 EER 12.1 Fixed DB N RTU-7 Single Zone Heat Pump (SZHP) Air System 1 69.78 0 COP 3.4 78.35 EER 12 Fixed DB N RTU-8 Single Zone Heat Pump (SZHP) Air System 1 36.45 0 HSPF2 7.1 35.72 EER2 SEER2 12.2 14.5 Fixed DB N 1 Status: N - New, A - Altered, E - Existing CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 12 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 H1. DRY SYSTEM EQUIPMENT (FURNACES, AIR HANDLING UNITS, HEAT PUMPS, VRF, ECONOMIZERS ETC.) 01 02 03 04 05 06 07 08 09 10 11 12 Equipment Name Equipment Type Qty Heating Cooling Economizer Type (if present) Status1Total Heating Output (kBtu/h) Supp Heat Output (kBtu/h) Efficiency Unit Efficiency Total Cooling Output (kBtu/h) Efficiency Unit Efficiency HP-1 Single Zone Heat Pump 1 12.5 0 HSPF2 10.5 11.52 EER2 SEER2 13 21 N/A N 1 Status: N - New, A - Altered, E - Existing H3. NONRESIDENTIAL / COMMON USE AREA FAN SYSTEMS SUMMARY 01 02 03 04 05 06 07 08 09 10 11 12 13 Name or Item Tag Qty Design OA CFM Supply Fan Return / Relief Fan Status1 CFM Power Power Units Control Fan Type CFM Power Power Units Control RTU-1 (Existing)1 226.2 2,000 0.2 BHP Constant Vol N/A N/A N/A N/A N/A E RTU-2 (Existing)1 327 2,900 2 BHP Constant Vol N/A N/A N/A N/A N/A E RTU-3 (Existing)1 236.4 2,900 2 BHP Constant Vol N/A N/A N/A N/A N/A E RTU-4 (Existing)1 195.75 1,750 0.2 BHP Constant Vol N/A N/A N/A N/A N/A E RTU-5 1 333.75 3,000 2.1 BHP Constant Vol N/A N/A N/A N/A N/A N RTU-6 1 318.3 3,000 2.1 BHP Constant Vol N/A N/A N/A N/A N/A N RTU-7 1 67.8 2,400 1.88 BHP Constant Vol N/A N/A N/A N/A N/A N RTU-8 1 114.75 1,200 0.86 BHP Constant Vol N/A N/A N/A N/A N/A N HP-1 1 0 400 0.03 BHP Constant Vol N/A N/A N/A N/A N/A N 1 Status: N - New, A - Altered, E - Existing CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 13 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 H8. SYSTEM SPECIAL FEATURES 01 02 03 04 System Name Equipment Type Interlocks per 140.4(n)1 Other Special Features and Controls RTU-1 (Existing)Single Zone Air Conditioner (SZAC) Air System N/A Fixed DB RTU-2 (Existing)Single Zone Air Conditioner (SZAC) Air System N/A Fixed DB RTU-3 (Existing)Single Zone Air Conditioner (SZAC) Air System N/A Fixed DB RTU-4 (Existing)Single Zone Air Conditioner (SZAC) Air System N/A Fixed DB RTU-5 Single Zone Heat Pump (SZHP) Air System N/A Zone(s) With CO2 Sensor Vent. Control Fixed DB RTU-6 Single Zone Heat Pump (SZHP) Air System N/A Fixed DB RTU-7 Single Zone Heat Pump (SZHP) Air System N/A Fixed DB RTU-8 Single Zone Heat Pump (SZHP) Air System N/A Fixed DB DHW1 - SHW Service Hot Water N/A Fixed Temperature Control Notes: This table includes controls related to the performance path only. For projects using the prescriptive path, mandatory and prescriptive controls requirements are documented on the NRCC-MCH-E. 1 Yes = interlocks are provided, No = interlocks are not provided, NA means no operable openings. H9. NONRESIDENTIAL / COMMON USE AREA & HOTEL/MOTEL VENTILATION 01 02 03 04 05 06 07 Zone Name Mechanical Ventilation Conditioned Area (sf)DCV or Occupant Sensor Controls, or BothVentilation Function # of People Supply OA CFM Exhaust CFM 1-Zone 1 Office - Office space 7.54 226.2 0 1508 N/A 2-Zone 2 Misc - All others 10.9 327 0 2180 N/A 3-Zone 3 Misc - All others 7.88 236.4 0 1576 N/A 4-Zone 4 Misc - All others 6.53 195.75 0 1305 N/A CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 14 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 H9. NONRESIDENTIAL / COMMON USE AREA & HOTEL/MOTEL VENTILATION 01 02 03 04 05 06 07 Zone Name Mechanical Ventilation Conditioned Area (sf)DCV or Occupant Sensor Controls, or BothVentilation Function # of People Supply OA CFM Exhaust CFM 5-Zone 5 Misc - All others 74.17 333.75 0 2225 DCV 6-Zone 6 Misc - All others 10.61 318.3 0 2122 N/A 7-Zone 7 Misc - All others 2.26 67.8 0 452 N/A 8-Zone 8 Misc - All others 3.83 114.75 0 765 N/A 9-Zone 9 General - Unoccupied 0.11 0 0 73 N/A H11. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY 01 02 03 04 05 06 07 08 09 10 11 12 System ID System Type Qty Rated Capacity (kBtuh)Airflow (cfm)Fan VSD Heating Cooling Design MIn.Min. Ratio Power Power Units Cycles 1-Zone 1-Trm Uncontrolled 1 N/A N/A 2,000 N/A 0 N/A N/A N/A 2-Zone 2-Trm Uncontrolled 1 N/A N/A 2,900 N/A 0 N/A N/A N/A 3-Zone 3-Trm Uncontrolled 1 N/A N/A 2,900 N/A 0 N/A N/A N/A 4-Zone 4-Trm Uncontrolled 1 N/A N/A 1,750 N/A 0 N/A N/A N/A 5-Zone 5-Trm Uncontrolled 1 N/A N/A 3,000 N/A 0 N/A N/A N/A 6-Zone 6-Trm Uncontrolled 1 N/A N/A 3,000 N/A 0 N/A N/A N/A 7-Zone 7-Trm Uncontrolled 1 N/A N/A 2,400 N/A 0 N/A N/A N/A 8-Zone 8-Trm Uncontrolled 1 N/A N/A 1,200 N/A 0 N/A N/A N/A HP-1 Single Zone Heat Pump 1 12.5 11.52 400 N/A N/A 0.03 BHP Continuous CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 15 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 I1. WATER HEATER EQUIPMENT SUMMARY 01 02 03 04 05 06 07 08 09 10 11 12 13 14 Name Heater Element Type Tank Type Qty Tank Vol (gal) Rated Input Rated Input Unit Efficiency Efficiency Unit Tank Insulation R-value Int/Ext Standby Loss Fraction 1st Hr. Rating or Flow Rate (gal) Heat Pump Type Tank Location or Ambient Condition NORITZ MODEL NCC300DV2 Natural Gas Instantaneous 1 1 300 kBtu/Hr 0.97 TE N/A 0 N/A N/A N/A L. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION Selections made by Documentation Author indicate which Certificates of Installation must be submitted for the features to be recognized for compliance. These documents must be retained and provided to the building inspector during construction and can be found online Building Component Form/Title Envelope NRCI-ENV-E - Envelope (for all buildings) Mechanical NRCI-MCH-E - For all buildings with Mechanical Systems Plumbing NRCI-PLB-E - For all buildings with Plumbing Systems M. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE Selections made by Documentation Author indicate which Certificates of Acceptance must be submitted for the features to be recognized for compliance. These documents must be provided to the building inspector during construction and must be completed through an Acceptance Test Technician Certification Provider (ATTCP). Building Component Form/Title & System Name(s) Envelope NRCA-ENV-02-F - NRFC label verification for fenestration Mechanical NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in conjunction with MCH-07-A Supply Fan VFD Acceptance (if applicable) since testing activities overlap RTU-5, RTU-6, RTU-7 and RTU-8., HP-1 Mechanical NRCA-MCH-03-A - Constant Volume Single Zone HVAC RTU-5, RTU-6, RTU-7 and RTU-8., HP-1 Mechanical NRCA-MCH-05-A - Air Economizer Controls RTU-5, RTU-6, RTU-7 and RTU-8. CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 16 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 M. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE Selections made by Documentation Author indicate which Certificates of Acceptance must be submitted for the features to be recognized for compliance. These documents must be provided to the building inspector during construction and must be completed through an Acceptance Test Technician Certification Provider (ATTCP). Building Component Form/Title & System Name(s) Mechanical NRCA-MCH-06-A Demand Control Ventilation Systems must be submitted for all systems required to employ demand controlled ventilation (refer to ) can vary outside ventilation flow rates based on maintaining interior carbon dioxide (CO2) concentration setpoints. RTU-5 Mechanical NRCA-MCH-12-A FDD for Packaged Direct Expansion Units RTU-5, RTU-6, RTU-7 and RTU-8. N. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION Selections made by Documentation Author indicate which Certificates of Verification must be submitted for the features to be recognized for compliance. These documents must be retained and provided to the building inspector during construction and can be found online There are no Certificates of Verification applicable to this project CERTIFICATE OF COMPLIANCE - NONRESIDENTIAL PERFORMANCE COMPLIANCE METHOD NRCC-PRF-E Nonresidential Performance Compliance Method (Page 17 of 17) CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220601 Report Generated: 2025-11-18 00:06:42 Compliance ID: EnergyPro-6073-1125-3137 Documentation Author's Declaration Statement 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Ray Parsi Documentation Author Signature: Signature Date:Company: Pro Engineering Address: 2712 Loker Avenue West #1063 CEA/HERS Certification Identification (if applicable): 26481 City/State/Zip: Carlsbad, CA 92010 Phone: (949)-842-2199 Responsible Person's Declaration statement I certify the following under penalty of perjury, under the laws of the State of California: 1.The information provided on this Certificate of Compliance is true and correct. 2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer) 3.The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5.I understand that a registered copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections, and I will take the necessary steps to accomplish this requirement. 6.I understand that a registered copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy, and I will take the necessary steps to accomplish these requirements. Responsible Designer Name: David Nakaishi Responsible Designer Signature: Company: Nakaishi Associates Architects Address: 2910 West Broadway, Suite 200 Date Signed: City/State/Zip: Los Angeles, CA 90041 License #: C-7727 Phone: (323) 255-1008 Title:Scope: Responsible Designer Name: Ray Parsi Responsible Designer Signature: Company: Pro Engineering Consulting Inc Address: 2712 Loker Avenue West #1063 Date Signed: City/State/Zip: Carlsbad, CA 92010 License #: 26481 Phone: (949)-842-2199 Title:Scope:   2025-11-18 2025-11-18 Date of Response: 3/9/2026 Response to Letter of Request for Short-Circuit Current Value for Panel Sizing and Protection Coordination Disclaimer: SCE provides the information contained in this letter on an “as is” basis without warranty of any kind, either express or implied. This disclaimer of liability applies to any claim or cause of action for damages or injuries occurring as a result of any error, omission, deletion or defect in the content of the information provided, including, but not limited to, negligence, breach of contract, or tort. Under no circumstances shall SCE or any of its parent or affiliate companies, employees, directors or shareholders be liable to any party for (i) any direct, indirect, special, punitive, incidental, exemplary, consequential, or any other damages arising in any way out of the availability, use or reliance on the information provided; or (ii) any claim attributable to errors, omissions or other inaccuracies in the information provided herein. The values provided below are maximum Short-Circuit values, based on current distribution system conditions. Utility distribution systems are dynamic, and the electrical characteristics of the system can vary significantly due to abnormal conditions, upgrades, modifications, and temporary or permanent reconfigurations. Therefore, the Short-Circuit values provided below are subject to change frequently and without notice. SCE does not guarantee to hold the system parameters represented in this information constant. Consequently, SCE recommends that all electrical work on the service panel main breaker should be done in a de-energized condition to eliminate arc flash hazard at this location. To: Customer: FC Arcadia Property, LLC, c/o Foothill Cardiology Medical Group Phone: 0 Address: 235 E Badillo St. Covina Fax: 0 City, ZIP: Covina, CA 91723 Email: 0 From: Southern California Edison (SCE) - Distribution Engineering Engineer: Rianne Paracuelles Phone: 0 Address: 3 Innovation Way Fax: 0 City, ZIP: Pomona, CA 91768 Email: Rianne.Paracuelles@sce.com Subject: Southern California Edison’s Contribution to Short-Circuit Current at the Point-of- Connection of SCE’s Service Conductors to the Customer’s Service Entrance Facilities (see disclaimer, above) Project: Name: FC Arcadia Property, LLC, c/o Foothill Cardiology Medical Group Address: 30 W. 1st Ave. Date of Response: 3/9/2026 City, Zip: Arcadia, CA 91006 Structure: P5816506 (1) The voltage and service configuration to be utilized for this project will be 208 Volts, 3- phase, 4-wire to serve a 1,200-Ampere main switchboard. (2) SCE’s contribution to Short-Circuit Current, at the time of calculation, is approximately 15,500 Amperes (3-phase) and 15,800 Amperes (phase-ground). The 3-phase X/R = 2.03 and the phase-ground X/R = 2.04. Service Conductors: 3 runs of 700 Size (☒ Al ☐ Cu) Distance from Transformer: 14 feet Transformer: 150 kVA, 3-phase, %Z = 2.7 ☐Existing Transformer ☒New Transformer Comments: (3) SCE’s maximum contribution to Short-Circuit Current is approximately 38,100 Amperes (3-phase), and 38,900 Amperes (phase-ground). These maximum Short-Circuit Current values are based on SCE’s largest transformer capable of serving a 1,200-Ampere main service switchboard (at 100% rating). Service Conductors: 4 runs of 700 Size (☒ Al ☐ Cu) Distance from Transformer: 14 feet Transformer: 500 kVA, 3-phase, %Z = 3.6 Comments: