HomeMy WebLinkAbout400 S Baldwin Ave - 2026 - Chow Tai FookSHEET INDEX
PROJECT SUMMARY
ADDRESSES:400 S. BALDWIN AVE., SPACE #A16, ARCADIA, CA 91007
ZONING:C-R
EXISTING OCCUPANCY:M: MERCANTILE - RETAIL
II-B, FULLY-SPRINKLEREDTYPE OF CONSTRUCTION:
EXISTING T.I. AREA TO BE REMODELED:1,274 S.F.
PROJECT CONTACT
PROJECT DESCRIPTION
EXISTING NO. OF STORY:TWO-STORY
APPLICABLE CODES
VICINITY MAP
SITE
GENERAL NOTES
ALL WORK, INCLUDING MATERIALS AND WORKMANSHIP, SHALL CONFORM
TO THE REQUIREMENTS OF LOCAL CODES, LAWS, AND ORDINANCES AND
AS SPECIFIED BY ALL GOVERNING AUTHORITIES WHERE APPLICABLE.
REFERENCE IS TO THE LATEST ACCEPTED EDITION OR REVISION. IN THE
EVENT OF CONFLICT WITH CODE REQUIREMENTS, THAT CODE
REQUIREMENT OR NOTE WHICH ESTABLISHES THE HIGHER STANDARD
SHALL TAKE PRECEDENCE.
1.
2.THE INTENTION OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL
LABOR AND MATERIALS, EQUIPMENTS, AND TRANSPORTATION
NECESSARY FOR THE COMPLETE AND PROPER EXECUTION OF THE WORK.
THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BIDDING ANY
PORTION OF THE WORK. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK. SHOULD
ANY CONDITION ARISE WHERE THE INTENT OF THE DRAWINGS IS IN
DOUBT OR WHERE THERE IS A DISCREPANCY OR TYPO BETWEEN THE
CONTRACT DOCUMENTS AND THE FIELD CONDITIONS, OR WITHIN THE
CONTRACT DOCUMENTS, THE CONTRACTOR SHALL NOTIFY THE
ARCHITECT OR DESIGNER IMMEDIATELY FOR CLARIFICATION.
3.
4.DIMENSIONS ARE FROM FACE OF STUDS OR TO CENTER OF WALL AS
INDICATED ON DRAWINGS, UNLESS NOTED OTHERWISE.
WRITTEN DIMENSIONS TAKE PRECEDENCE. DO NOT SCALE DRAWINGS.
WALLS NOTE DIMENSIONED ARE TO ALIGN WITH EXISTING WALLS OR BE
ABUTTED OR APPLIED TO EXISTING WALLS PER DRAWINGS. DOORS NOT
DIMENSIONED AND SHOWN JAMB TIGHT SHALL BE SET 3" FROM
PERPENDICULAR WALL TO OUTER EDGE OF DOOR JAMB.
5.
6.REFERENCE TO ANY DETAIL OR DRAWING IS FOR CONVENIENCE ONLY
AND DOES NOT LIMIT THE APPLICATION OF SUCH DETAILS OR DRAWINGS.
THE DESIGN, ADEQUACY AND SAFETY OF ERECTION BRACING, SHORING,
TEMPORARY SUPPORTS, ETC., IS THE SOLE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
STABILITY OF THE STRUCTURE AND PROVIDE NECESSARY BRACING
PRIOR TO THE APPLICATION OF ALL SHEAR WALLS, ROOF AND FLOOR
DIAPHRAGMS, AND FINISH MATERIALS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR INITIATING, MAINTAINING, AND SUPERVISING ALL
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.
7.
8.THE STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS,
AS WELL AS THE DRAWINGS OF OTHER CONSULTANTS, ARE
SUPPLEMENTARY TO THE ARCHITECTURAL DRAWINGS. IT SHALL BE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR TO CHECK WITH THE
ARCHITECTURAL DRAWINGS BEFORE THE INSTALLATION OF WORK SHOWN
ON THE DRAWINGS OF CONSULTANTS. THE CONTRACTOR SHALL BRING
ANY DISCREPANCY BETWEEN THE ARCHITECTURAL DRAWINGS AND THE
DRAWINGS OF THE CONSULTING ENGINEERS TO THE ATTENTION OF
DESIGNER FOR CLARIFICATION. ANY WORK INSTALLED IN CONFLICT WITH
THE ARCHITECTURAL DRAWINGS AND NOT BROUGHT TO THE DESIGNER'S
ATTENTION SHALL BE CORRECTED BY THE CONTRACTOR AT THE
CONTRACTOR'S EXPENSE AND AT NO EXPENSE TO THE OWNER OF
DESIGNER, DESIGNER, ENGINEERS AND ALL OTHER CONSULTANTS.
PRIOR TO PERFORMANCE OF WORK, THE CONTRACTOR SHALL REQUIRE
EACH SUBCONTRACTOR TO NOTIFY THE CONTRACTOR OF ANY WORK
CALLED OUT IN THE DRAWINGS FOR HIS TRADE THAT CANNOT BE FULLY
GUARANTEED.
9.
10.CONTRACTOR SHALL VERIFY THE LOCATION AND SIZE OF ALL OPENINGS
WITH ALL DRAWINGS AND MANUFACTURED ITEMS WHERE APPLICABLE.
THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND BE
SOLELY RESPONSIBLE FOR ALL CONSTRUCTION, MEANS, METHODS,
TECHNIQUES, SEQUENCES, AND PROCEDURES, AND FOR COORDINATING
ALL PORTIONS OF THE WORK.
11.
12.THE CONTRACTOR HEREIN AGREES TO REPAIR OR REPLACE ANY OR ALL
WORK, TOGETHER WITH ANY OTHER ADJACENT WORK WHICH MAY BE
DISPLACED IN CONNECTION WITH SUCH REPLACEMENT, THAT MAY
PROVE TO BE DEFECTIVE IN WORKMANSHIP OR MATERIALS WITHIN A
PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE, ORDINARY
WEAR AND UNUSUAL ABUSE OR NEGLECT EXCEPTED.
CONTRACTOR SHALL PROTEST ALL EXISTING STRUCTURES,
LANDSCAPING, MATERIALS, ETC., DURING CONSTRUCTION. CONTRACTOR
SHALL PATCH AND REPAIR ALL SURFACES DISRUPTED OR DAMAGED
DURING CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES.
13.
14.THE CONTRACTOR SHALL ON A DAILY BASIS KEEP THE PREMISES FREE
FROM ALL ACCUMULATIONS OF WASTE MATERIAL OR RUBBISH CAUSED
BY HIS EMPLOYEES, SUBCONTRACTORS, OR WORK, AND AT THE
COMPLETION OF THE WORK SHALL REMOVE ALL RUBBISH, DEBRIS,
EQUIPMENT, AND SURPLUS MATERIALS FROM IN AND ABOUT THE
BUILDING AN LEAVE THE PREMISES "BROOM CLEAN".
ANY DEVIATION FROM THE CONSTRUCTION DOCUMENTS OR
SPECIFICATIONS BY THE CONTRACTOR OR OWNER WITHOUT THE
DESIGNER'S APPROVAL RELEASES THE DESIGNER OF RESPONSIBILITY
AND LIABILITY IN CONNECTION WITH ALL WORK SO INVOLVED.
15.
16.CLARIFICATIONS ON AND/OR INCONSISTENCIES WITH THE DRAWINGS
AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
DESIGNER BY THE CONTRACTOR PRIOR TO COMMENCEMENT OF WORK.
ADDITIONAL CHARGES WILL NOT BE GRANTED BASED ON CLAIMS OF
INCOMPLETE, INACCURATE, OR INCONSISTENT DRAWINGS AND
SPECIFICATIONS.
SYMBOLSABBREVIATIONS
17.EXCESS OR WASTE CONCRETE MAY NOT BE WASHED INTO THE PUBLIC
WAY OR ANY OTHER DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE
TO RETAIN CONCRETE WASTES ON SITE UNTIL THEY CAN BE DISPOSED
OF AS SOLID WASTE.
18.SEDIMENTS AND OTHER MATERIALS MAY NOT BE TRACKED FROM THE
SITE BY VEHICLE TRAFFIC. THE CONSTRUCTION ENTRANCE ROADWAYS
MUST BE STABILIZED SO AS TO INHIBIT SEDIMENTS FROM BEING
DEPOSITED INTO THE PUBLIC WAY. ACCIDENTAL DEPOSITIONS MUST BE
SWEPT UP IMMEDIATELY AND MAY NOT BE WASHED DOWN BY RAIN OR
OTHER MEANS.
19.STOCKPILES OF EARTH AND OTHER CONSTRUCTION RELATED
MATERIALS MUST BE PROTECTED FROM BEING TRANSPORTED FROM THE
SITE BY THE FORCES OF WIND OR WATER.
20.TRASH AND CONSTRUCTION RELATED SOLID WASTES MUST BE DEPOSITED
INTO A COVERED RECEPTACLE TO PREVENT CONTAMINATION OF
RAINWATER AND DISPERSAL BY WIND.
21.FUELS, OILS, SOLVENTS AND OTHER TOXIC MATERIALS MUST BE STORED
IN ACCORDANCE WITH THEIR LISTING AND ARE NOT TO CONTAMINATE
THE SOIL AND SURFACE WATERS. ALL APPROVED STORAGE
CONTAINERS ARE TO BE PROTECTED FROM THE WEATHER. SPILLS MUST
BE CLEANED UP IMMEDIATELY AND DISPOSED OF IN A PROPER MANNER.
SPILLS MAY NOT BE WASHED INTO THE DRAINAGE SYSTEM.
22.THE ISSUANCE OF A PERMIT SHALL NOT PREVENT THE BUILDING
OFFICIAL FROM REQUIRING THE CORRECTION OF ERRORS ON THESE
PLANS OR FROM PREVENTING ANY VIOLATION OF THE CODES ADOPTED
BY THE CITY, RELEVANT LAWS, ORDINANCES, RULES AND/OR
REGULATIONS.
400 S. BALDWIN AVE, SPACE A16
ARCADIA, CA 91007
CHOW TAI FOOK
AHJ STAMPED APPROVAL
COVER SHEET, PROJECT
SUMMARY, GENERAL NOTES,
CONTACT, ABBREVIATIONS AND
SYMBOLS
T-1.0
LANDLORD:
THE SHOPS AT SANTA ANITA
400 S. BALDWIN AVE.,
ARCADIA, CA 91007
TENANT COORDINATOR
SHANNON YSAAC
TEL: (626) 462-8510
SHANNON@SHOPSATSANTAANITA.COM
MEP ENGINEER:
HYC CONSULTING ENGINEERS, INC.
660 N. DIAMOND BAR BLVD., #128
DIAMOND BAR, CA 91765
TEL: 909.396-8168
ATTN: ZHIPING FANG, P.E.
EMAIL: HYC@HYCENGINEER.COM
OCCUPANCY CALCULATION (PER 2025 CBC TABLE 1004.5)
ROOM
NUMBER ROOM NAME AREA
(S.F.)OCCUPANCY USE LOAD
FACTOR
CALCULATED
OCCUPANTS
101
103
102
(E) RESTROOM 60
(E) SALES AREA 1,049
300(E) BOH - STORAGE
18M: MERCANTILE 60 GROSS
---
TOTAL:21
---
GROSS 1
---
REMARKS
2025 CALIFORNIA BUILDING CODE - TILE 24, PART 2
2025 CALIFORNIA RESIDENTIAL CODE - TITLE 24, PART 2.5
2025 CALIFORNIA ELECTRICAL CODE - TITLE 24, PART 3
2025 CALIFORNIA MECHANICAL CODE - TITLE 24, PART 4
2025 CALIFORNIA PLUMBING CODE - TITLE 24, PART 5
2025 CALIFORNIA ENERGY CODE - TITLE 24, PART 6
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE -
TITLE 24, PART 11
2025 CALIFORNIA FIRE CODE
2026 CITY OF ARCADIA MUNICIPAL CODE
1.REMODEL OF EXISTING RETAIL STORE OF 1,503 S.F. WITH EXISTING
CEILING SYSTEM IN SALES AREA TO REMAIN.
M: STORAGE, STOCK, SHIPPING AREAS 300
1,503
SEPARATE PERMIT
SIGNAGE
FIRE SPRINKLER SYSTEM
FIRE ALARM SYSTEM
COVER SHEET, PROJECT SUMMARY, GENERAL NOTES,T-1.0
SHEET DESCRIPTION
CONTACT, ABBREVIATIONS, AND SYMBOLS
ARCHITECTURAL
A-1.0
A-2.0
T-1.1
ADA DETAILS
EXISTING FLOOR PLAN
REFLECTED CEILING PLANS
T-1.2
GREEN BUILDING CODE
T-1.3
GREEN BUILDING CODE
T-1.4
GREEN BUILDING CODE
ADA DETAILS
T-1.5
T-1.6
DOOR AND FINISH SCHEDULEA-4.0
WALL AND CEILING FINISHES
INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED
IN ACCORDANCE WITH ASTM E84 OR UL 723. SUCH INTERIOR FINISH
MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
INDIXES.
CLASS
A
B
C
FLAME SPREAD INDEX SMOKE-DEVELOPED INDEX
0-25
26-75
16-200
0-450
0-450
0-450
NOTE:
ALL WORK SHALL CONFORM TO ALL REQUIREMENTS OF STATE OF CALIFORNIA
TITLE 24 REGARDLESS OF THE INFORMATION INDICATED ON THESE PLANS. IT IS
THE RESPONSIBILITY OF THE INDIVIDUAL SUPERVISING THE CONSTRUCTION TO
ENSURE THAT THE WORK IS DONE IN ACCORDANCE WITH CODE REQUIREMENTS
PRIOR TO REQUESTING INSPECTION.
CONTRACTOR SHALL FIELD VERIFY EXISTING PATH OF TRAVEL & ACCESSIBLE
ROUTE FROM ACCESSIBLE PARKING TO EXISTING BUILDING MAIN ENTRANCE
FOR FULL COMPLIANCE WITH CURRENT CHAPTER 11B. ACCESSIBLE PATH OF
TRAVEL SHALL BE 4'-0" WIDE, MAX. 5% SLOPE AND MAX. 2.09% CROSS SLOPE.
THERE SHALL BE NO VERTICAL OFFSET GREATER THAN 1/4" ALONG THE ENTIRE
PATH OF TRAVEL FROM THE PUBLIC WAY/ACCESSIBLE PARKING STALL INTO THE
BUILDING.
TENANT:
CHOW TAI FOOK
1065 BREA MALL
SPACE 2008
BREA, CA 92821
TEL: (626) 633-6094
ATTN: GLEN SUN
EMAIL: GLEN@GEMHOORAY.COM
PROPOSED OCCUPANCY:M: MERCANTILE - RETAIL
APN:5775-031-008
NO. OF EXIT REQUIRED:ONE EXIT
NO. OF EXIT PROVIDED:ONE EXIT
TENANT IMPROVEMENT
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
2. REMODELING OF EXISTING EXTERIOR STOREFRONT.
3. NEW A/C DIFFUSERS THROUGHOUT THE SPACE. A/C UNIT TO REMAIN
EXISTING.
4. NEW ELECTRICAL LIGHTING THROUGHOUT THE SPACE AND NEW OUTLETS
IN THE RETAIL AREA.
LOCATION OF UNIT:FIRST FLOOR LEVEL
DESIGNER:
RUBY CONSULTING PARTNERS, LLC
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
ATTN: ALISON FUNG
DAN CHEN, P.E.
EMAIL: ALISON.FUNG@AOL.COM
GREEN BUILDING CODE
FRAMING PLAN AND DETAILSS-1
STRUCTURAL
NOTES & SLDE-1
ELECTRICAL
POWER PLANE-2
LIGHTING PLANE-3
CONTROL SYSTEM & PANEL SCHEDULESE-4
CERTIFICATE OF COMPLIANCEE-5
STRUCTURAL ENGINEER:
DANTAN CORPORATION
21121 E. SNOW CREED DRIVE.,
WALNUT, CA 91789
TEL: 626.329-1141
ATTN: DAN CHEN, P.E.
EMAIL:DANTANCORP@HOTMAIL.COM
NOTESM-1
MECHANICAL
HVAC FLOOR PLANM-2
A-3.0 PROPOSED FACADE ELEVATION
LEASING PLAN
T-1.7
104 (N) VIP ROOM 94 2M: MERCANTILE 60 GROSS
---
A-1.1 PROPOSED FLOOR PLAN
EMERGENCY PHOTOMETRIC PLANE-6
CEILING DETAILSA-4.1
T-1.1
SITE PLAN
SCALE: NTS
FIRST FLOOR PLAN (FOR REFERENCE ONLY)
T-1.1
1 NORTH
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
SCALE: NTS
TSD/LOD
T-1.1
2 NORTH
12"
TYP. ALL SIDES
6" HIGH RAISED
WHEELCHAIR
LOGO
5/8" RAISED
LETTERS
GRADE #2
BRAILLE
NOTE:
ARCHITECT TO SECIFY SIGN
DESIGN AND SIZE.
IN ADDITION TO THE 12" SYMBOLS @ 60" ON
RESTROOM DOORS
PROVIDE:
SIGN MOUNTED @+60" ON WALL AT LATCH
SIDE OF DOOR.
12" DIA12" DIA
RESTROOM SIGNAGE
3105 A (b) 1D
3105 A (e) 1-7
MATERIAL: ACRYLIC LAMINATE
FINISH: NON GLARE
COLOR FORMAT: PER LOMALINDA UNIVERSITY MEDICAL CNETER GRAPHIC
STANDARDS
INSTALLING: PLAQUES TO BE INSTALLED W/ DOUBLE BACK FOAM TAPE.
MEN'S FACILITY DOOR SHALL HAVE AN EQUILATERAL TRIANGLE 1/4" THICK, 12"
SIDES, AND A VERTEX POINTING UPWARD.
WOMEN'S FACILITY DOOR SHALL HAVE A 12" DIAMETER CIRCLE, 1/4" THICK.
A UNISEX FACILITY DOOR SHALL HAVE A 12" DIAMETER CIRCLE, 1/4" THICK,
AND A 1/4" THICK TRIANGLE INSCRIBED AND SUPERIMPOSED ON THE
CIRCLE.
WOMEN'S ALL-GENDER MEN'S
UNISEX
XXXXXX
RESTROOM STAFF
7"6"
UNISEXXXXXXX
1/4" ACRYLIC
LAMINATE
1'-0"
1'
-
0
"
4"
UNISEXXXXXXX
5'
-
0
"
SCALE:
11TYPICAL RESTROOM SIGN
T-1.2N.T.S.
TRANSITION BETWEEN FLOOR FINISHESA
1
THRESHOLD
2
1/
4
"
MA
X
.
LEVEL CHANGES
70 °
116°
16
°
NOTES:
DOOR CLOSERS, IF PRESENT, MUST BE SET SO
THAT IT TAKES DOOR AT LEAST 3 SECONDS TO
CLOSE FROM AN OPEN POSITION OF 70 DEGREES
TO WITHIN 3" OF THE LATCH
DOOR CLOSERS
COMPRESSED CARPET 1/4"
MAX. BELOW THRESHOLD FIN. FLOOR LEVEL
THRESHOLD
1/2" MAX.
1/4" MAX.B
C
NOTES:
1. 1/2" MAXIMUM TOTAL HEIGHT WITH 1/4" MAXIMUM VERTICAL CHANGE AT EDGE.
2. 1 : 2 SLOPED BEVEL REQUIRED IF LEVEL CHANGE IS OVER 1/4" VERITCAL LEVEL
CHANGE.
3. 1/4" MAXIMUM VERTICAL LEVEL CHANGE.
1/2" MAX.
PILE HEIGHT
SCALE:
16LEVEL CHANGE
T-1.2N.T.S.
SCALE:
13ACCESSIBILITY DOOR
T-1.2N.T.S.
30" M
I
N
.
C
L
E
A
R
19"
M
I
N
.
34
"
M
A
X
.
27
"
M
I
N
.
CLR.
27
"
MI
N
.
19"
MIN.DEPTH
ADA DINING TABLE
(SIDE VIEW)
30
"
x
4
8
"
CL
E
A
R
FL
O
O
R
SP
A
C
E
ADA DINING TABLE
(PLAN VIEW)
19"
MIN.DEPTH
SCALE:
18KNEE AND TOE CLEARANCE @ TABLE
T-1.2N.T.S.
0'-4"
SIGN TYPE 4
MAY BE OBTAINED FROM
TENANT'S SIGN VENDOR OR ONE OF
THE FOLLOWING:
SOUTHWEST SIGN COMPANY
(951) 734-6275
OR
KUTTING EDGE DESIGN
(714) 721-8795
RIGHT WINDOW VINYL DETAILS - SIGN TYPES 1, 2, 4
SCALE: 3"=1'-0"
3M SCOTCHCAL 7725-2 MATTE WHITE VINYL GRAPHICS APPLIED TO
EXTERIOR OF WINDOW GLASS PER ELEVATION LAYOUT.
SIGN TYPE 10 DETAIL
SCALE: 1"= 1"
1/16" CLEAR PHOTOPOLYMER PANEL WITH RAISED 1/32" TACTILE
COPY AND GRADE 2 BRAILLE. COPY PAINTED BLACK ON FACE.
PANEL AND BRAILLE TO REMAIN CLEAR.
AFFIXED WITH CLEAR MACTAC ADHESIVE FILM TO ENTIRE BACK OF
PLAQUE TO DUSTED CRYSTAL 7725SE-314 VINYL IN MATCHING SIZE
ON INTERIOR OF WINDOW GLASS.
PLACE ON RIGHT STOREFRONT WINDOW
0'-3"
3/8"
3/8"
3/8"
0'-2"
0'-0 5/8"
SCALE:
20 ADA EXIT DECAL
T-1.2N.T.S.
PAPER
TOWEL
DISPENSER
SANITARY
NAPKIN/
TAMPON
VENDOR
TOILET PAPER
DISPENSER,
SEAT COVER
DISPENSER
EQEQ
COAT HOOK
ON DOOR
4'
-
0
"
1'
-
0
"
MEDICAL GAS
ALARM PANEL
7'
-
0
"
F.F.L.
F.F.L.
4'
-
0
"
A
.
F
.
F
.
TIME/
ATTENDANCE
SHARP
CONTAINER
DRY ERASE BD./
TACKBOARD
NURSE
CALL
LIGHT
SWITCH
FIRE
STROBE
FIRE
EXTINGUISHER
CABINET
TOILET
SEAT
COVER
DISPENSER
PAPER
TOWEL
DISPENSER
MIRRORMIRRORSOAP
DISPENSER
CLOCK
5'
-
0
"
3'-
6
"
A.
F
.
F
.
3'
-
9
"
A
.
F
.
F
.
36x48
BOARD
3'
-
4
"
A.
F
.
F
.
CARD READER/
AUTO DOOR
PUSH PLATE
4'
-
6
"
A
.
F
.
F
.
1'-0"
3'
-
4
"
2'
-
5
"
CL
E
A
R
1'-6" U.N.O.
2'-
2
3
/
4
"
SINK, MIRROR W/
SOAP DISPENSER
44
"
17
"
D.P.
URINAL
RECESSED PAPER
TOWEL DISPENSER
AND WASTE
RECEPTACLE
DIAPER
CHANGE
STATION
FINISH FACE OF WALL
SEMI-RECESSED UNIT
FINISH FACE
OF WALL
SURFACED-
MOUNTED
UNIT
32"
20
"
33
"
7'
-
0
"
A.
F
.
F
.
NOTES:
1. GRAB BARS TO BE 1 1/4" TO 2" DIAMETER WITH 1 1/2" CLEARANCE TO FINISH WALL
SURFACE.
2. GRAB BARS SHALL HAVE BACKING AND BE DESIGNED TO SUPPORT A 250 POUND
POINT LOAD.
3. FLUSH CONTROLS SHALL BE ACCESSIBLE FROM THE WIDE SIDE OF THE TOILET.
44" MAX. HEIGHT.
SIDE ELEVATION FRONT ELEVATION
TOILET PAPER
DISPENSER
3'-6" MIN.12" MAX.
19
"
MI
N
.
33
"
17
"
M
I
N
.
19
"
M
A
X
.
17"-18"
36" MIN.6"
MAX.
33
"
24" MIN.
1
12"
MI
N
.
3'-0"MAX.
CLEAR
FLOOR
SPACE
PROVIDE LEVER HANDLE FAUCET NOT REQUIRING A GRASP TO
OPERATE. OPERATING FORCE SHALL NOT EXCEED 5 POUNDS.
74
"
M
I
N
.
MIRROR NOTE:
PROVIDE INSULATION OR OTHER
PROTECTION AT HOT WATER
SUPPLY AND DRAIN PIPES.
6" MAX.
TOE CLEARENCE8" MIN.
KNEEE
CLEARENCE
17" MIN.
DEPTH
SECTION
9"
MI
N
.
27
"
M
I
N
.
27
"
M
I
N
.
18
"
MI
N
.
17"
MIN.
30
"
M
I
N
.
8"
MAX.
48" MIN.
PLAN
34
"
M
A
X
.
40
"
M
A
X
.
NOTES:
WHERE A SINGLE COUNTER CONTAINS MORE THEN ONE TRANSACTION STATION, SUCH
AS (BUT NOT LIMITED TO) A BANK COUNTER WITH MULTIPLE TELLER WINDOWS OR
RETAIL SALES COUNTER WITH MULTIPLE CASH REGISTER STATIONS, AT LEAST 5
PERCENT (5%) BUT NEVER LESS THEN ONE, OF EACH TYPE OF STATION SHALL BE
LOCATED AT A SECTION OF COUNTER THAT IS AT LEAST 36 INCHES LONG AND NO
MORE THAN 28"-34" HIGH.
34
"
M
A
X
.
36" MIN.
46
"
M
A
X
.
54
"
M
A
X
.
W
I
T
H
N
O
OB
S
T
R
U
C
T
I
O
N
T
O
RE
A
C
H
O
V
E
R
24"
MAX.
34
"
M
A
X
.
36"MIN.
CLEAR PASSAGE
(42" PREFERRED)
34
"
M
A
X
.
TRAY SLIDE
MULTIPLE TRANSACTION STATIONS
7'
-
0
"
A.
F
.
F
.
F.F.L.
F.F.L.
TOILET SEAT
COVER
DISPENSER
48
"
M
A
X
.
GRAB BAR
W/ BACKING,
PER
GRAB BAR
W/ BACKING,
PER 14
A-4.012
-
SCALE:
15ACCESSIBLE REACH REQUIREMENTS
T-1.2N.T.S.
SCALE:
4TYP. MOUNTING HEIGHT / CLEARANCES
T-1.2N.T.S.
SCALE:
5ACCESSIBLE LAVATORY
T-1.2N.T.S.SCALE:
1ACCESSIBLE WATER CLOSET
T-1.2N.T.S.
7"-9"
12"MIN.
24" MIN.
13
1
/
2
"
M
I
N
.
URINAL
PROJECTION
SIGN TO BE PLACED AT ALL ENTRANCES AND UNDER THE ROOM
IDENTIFICATION SIGN OR RESTROOM IDENTIFICATION SIGN WHEN
ROOM IS ACCESSIBLE.
EXTERIOR PLASTIC SIGN PANEL
CORNER RADIUS 3/8" COLOR
MATCH ROOM IDENTIFICATION
SIGNS
PICTOGRAM WHITE INTERNATIONAL
SYMBOL OF ACCESSIBILITY
6"
6"
GRAB BAR BRACKET
TYPE A3 6" DEEP LEG TRACK
1 1/2" OUTSIDE DIAMETER
STAINLESS STEEL GRAB BAR
(3) 1/4" - 20 X 1 1/2" FLAT HEAD
STAINLESS STEEL SMS INTO
BACKING PLATE
NOTE:
PREDRILL HOLES THRU
CERAMIC TILE
METAL SPACERS
CERAMIC TILE THIN-SET ON WATER
RESISTANT GYPSUM BOARD,SEE
SCHEDULE FOR TYPES
WALL MEMBRANE (SHOWN DASHED)
METAL STUD
SECTION
PLAN
3 #12 MACHINE SCREWS
GRAB BAR BRACKET
1 1/2"
3"
33
"
A
B
O
V
E
FI
N
I
S
H
E
D
F
L
O
O
R
SCALE:
14ACCESSIBILITY SIGN
T-1.2N.T.S.
SCALE:
9GRAB BAR ANCHORAGE
T-1.2N.T.S.
T-1.2
SEE PLAN
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
ADA DETAILS
1'-0"
1/2" TYP.
1/
2
"
T
Y
P
.
1'
-
6
"
4
-
SCALE:
ACCESSIBLE ROUTE OF TAVEL SIGN
N.T.S
NOTES:
1.SIGN MOUNTED ON BOTH
SIDES OF POST.
2.ARROW SHALL POINT IN THE
DIRECTION OF THE PATH OF
TRAVEL.
BLACK STRIPE ON
WHITE BACKGROUND
FOR INFORMATION
NOT NOTED, SEE
2"3 1/2"2"
2"
5
1
/
2
"
10"@ EA. END, TYP.
8'-0" FOR DOUBLE
4'-0" FOR SINGLE
(2) #3 REBARS
DISABLED
PARKING
ONLY
1'-0"
2 1/2"
2
1
/
2
"
2'
-
2
"
3"
6"
3M "INTENSE BLUE" 7725-47
VINYL COPY/GRAPHICS
1/8" THICK ALUMINUM FACE
& RETURN WELDED TO SIGN
POLE FREE OF SEAMS,
JOINTS, AND WELDS
PAINTED MATTHEWS
"BRUSHED ALUMINUM"
CONTRACTOR TO PROVIDE
CONCRETE FOUNDATION
SUPPORT FOR POLE
2-1/2" DIA. ALUMINUM ROUND
TUBE WITH WELDED CAP
PAINTED MATTHEWS
"BRUSHED ALUMINUM"
SIGN PANEL RETURN WELDED
TO POLE, FREE OF SEAMS,
WELDS, OR JOINTS
FRONT VIEW
POLE MOUNT
SIDE VIEW
POLE MOUNT
6'
-
8
"
MI
N
.
VAN ACCESSIBLE SIGN
WHERE OCCURS
1
1
/
2
"DISABLED
PARKING
ONLY
6"
2'-8"
1'-0"1'-6"
8"
SIGN FACE
BLOCKING
1/
2
"
1 3/4"
FLOOR
WALL
WALL
SCALE:
ACCESSIBLE SIGN MOUNT
N.T.S
POLE MOUNTAWALL MOUNTB
FLAG MOUNTC
SCALE:
CONCRETE WHEEL STOP
N.T.S
ELEVATIONB
CONCRETE PAVING,
SEE CIVIL DWGS.
AND SITE PLAN
EPOXY BOND
#5 REBAR- 18"L
SWAGE TOP,
TYP.
EPOXY BOND
ELEVATIONA
A
-
NOTE:
1. SIGN TO BE INSTALLED PARALLEL TO
CURB, AS SINGLE-SIDED SIGN. H.C.
SYMBOL AND SIGN SHALL COMPLY
2. WITH CURRENT STATE OF CALIFORNIA
TITLE 24 REQUIREMENTS.
3. ALL NEW ADA PARKING SIGNAGE TO
CONFORM TO EXISTING SITE SIGN
PROGRAM FOR DESIGN, COLOR AND
STYLE. SEE FINAL DETAILS BY SIGN
VENDOR.
15
11
SCALE:
FEDERAL STANDARD SYMBOL
N.T.S
3'
-
0
"
3'-0"
3"
TYP.
ALIGN W/ FRONT STALL
WHITE HIGHWAY PAINT 2
COATS, 3" WIDE, TYP.
HANDICAPPED BLUE COLOR,
BACKGROUND #15090 FED.
STD. 595a OR EQUAL
NOTES:
1.ALL STROKES TO BE MIN. 3"
WIDE.
FIELD: ROYAL BLUE.
BORDER / SYMBOL: WHITE.
2.PROVIDE TWO (2) COATS OF
REFLECTIVE PAINT. LET DRY
BETWEEN COATS.
3.LOCATE SYMBOL IN FRONT OF
PARKING STALL, VISIBLE TO
TRAFFIC OFFICER AND
CENTERED AS SHOWN ON SITE
PLAN.
4.HANDICAP SYMBOL TO COMPLY
W/ CURRENT STATE, LOCAL
PUBLIC AGENCY, ETC.,
REQUIREMENTS, U.N.O.
9
42
"
48" MIN. CLR.
E DETAIL
48" MIN. CLR.
36" MIN. CLR.36" MIN. CLR.
27"
34
"
34
"
27
"
48" MIN.
48"
MIN.
48"
MIN.
48"
MIN.
60"
TYP.
48
"
MI
N
.
3/4"
1/
4
"
1/4"
48
"
MI
N
.
48"
MIN.
2.35"
2.
3
5
"
1.67"APPROX.
SCALE:
RAMP DETAIL & NOTES
N.T.S.SCALE:
TYPICAL STAIR & HANDRAIL DETAILS
N.T.S.
NOTE:
ALL RAMPS MUST MEET
HANDRAIL AND CURB
REQUIREMENTS.
VARIES (30' MAX.)
VARIES (30'
MAX.)
60" MIN.
60" MIN.
72" MIN.
WHEN DOOR SWINGS
ONTO LANDING 42" MIN.
PLUS DOOR WIDTH
60" MIN.GUARD RAIL
AND CURB
30" MAX. RISE
(TYP.)
HANDRAIL AT RAMPS
HORIZONTAL RAILING REQUIRED
WHERE INTERMEDIATE RAILS WITH
A MAXIMUM OF 4" CLEAR SPACE
BETWEEN INTERMED. RAILS ARE
NOT REQUIRED, TYPICAL.
ADJACENT HAZARD
4" MINIMUM TO
30" MAXIMUM
6" HIGH WARNING CURBS WHEN A 4"
(OR MORE) DROP OCCURS
30
"
WHEN DOOR SWINGS
ONTO LANDING 42" MIN.
PLUS DOOR WIDTH
60" MIN.
60" MIN.
VARIES
(30' MAX.)
72" MIN.
72" MIN.
30" MAX.
RISE
(TYP.)
AS REQUIRED
NOTE:
GROOVED BORDER MUST
BE ON THE LEVEL SURFACE
AT THE TOP OF THE RAMP.
1 1/2"1 1/2"
1 1/4"
TO
1 1/2"
1 1/4"
TO
1 1/2"
1 1/4"
TO
1 1/2"1 1/2"
CLR.
1 1/4" TO
1 1/2" (O.D.
1 1/2"
1 1/2"
AS REQUIRED
STREET
(TYP.)
CURB
(TYP.)
POLE
SIDEWALK SIDEWALK
NOTE: 12"x12"x2" THK. BLACK
TAC-TILE PRECAST
CONCRETE TILE, MFD. BY
INTERLOCK SAN DIEGO. TEL:
(760) 434-5586 OR EQUAL.
NOTE: SHADED AREAS OF
RAMP MUST HAVE DETECT-
ABLE WARNING SURFACE
24" MIN. OF
STRAIGHT
CURB
SEE TYPICAL
ACCESSIBILITY
NOTES SHEET
FOR MORE INFO.
NOTE: SURFACE WILL
REQUIRE 36" SECTION OF
TRUNCATED DOMES IF FLAT
TRAVEL SURFACE ADJOINS
VEHICULAR TRAFFIC WAY.
SEE DETAIL "G"
PAINT CURB
SAFETY YELLOW
(2 COATS), TYP.
LINE OF FRONT
OF REQ'D
PARKING SPACE.
1:12 SLOPE MAX.
TYP.LINE OF
OBSTRUCTION
OR EDGE OF
WALK AREA AS
OCCURS, TYP.
12" TYP.
INTERMEDIATE
TURNING
POSITION
60" MIN.
LANDING
VARIES (30' MAX.)
VARIES
(30' MAX.)
72" MIN.
60" MIN.
60" MIN.WHEN DOOR SWINGS
ONTO LANDING 42" MIN.
PLUS DOOR WIDTH
60" MIN.
72" MIN.
AS REQ'D.
30"
MAX.
RISE
(TYP.)
WALK
AREATYP.
10
TYP.1
PLTR.PLTR.
1:10 MAX. SLOPE
(TYPICAL)
CROSS SLOPE OF LANDING
AREAS SHALL NOT EXCEED
2% IN ANY DIRECTION
LINE OF OBSTRUCTION OR
EDGE OF WALK AREA, AS
OCCURS, TYP.
INTERMEDIATE
PLATFORM
TYP.
101
TY
P
.
12
1
TYP.
121
DN.DN.DN
.
2%
DN
.DN
.
G
-
HANDRAILS & GRAB BARC RAMP WITH TURNING PLATFORMC
CURB RAMP DETAILH
TRUNCATED DOMESGGROOVED WARNING BORDERF
RAMP WITH INTERMEDIATED SWITCH-BACK PLATFORMB
RAMP SECTIONDSTRAIGHT RAMP RUNA
212 T-1.3
SEE PLAN
ADA DETAILS
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
T-1.4
GREEN BUILDING CHECKLIST
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
T-1.5
GREEN BUILDING CHECKLIST
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
T-1.6
GREEN BUILDING CHECKLIST
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
T-1.7
GREEN BUILDING CHECKLIST
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
V.I.F
.(E)
C
O
L
.
V.I.F
.
(E
)
C
O
L
.
V.
I
.
F
.
(E
)
C
O
L
.
A B C D
A B C D
E
E
1
2
3
4
1
2
3
4
(E) SALES AREA
101 1,073 S.F.
(E) BOH
102 370 S.F.
(E) ALL-GENDER
103 60 S.F.
1
61'-3"
1
1
2
3
4
5
6
6
3
(CONTRACTOR TO FIELD VERIFIED)
30'-2"11'-7"12'-9"7'-6"
5'
-
5
"
19
'
-
1
1
"
12
'
-
7
"
25'-
2
"
17
'
-
5
"
(C
O
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
37
'
-
1
0
"
(C
O
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
(CO
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
A-1.0
EXISTING FLOOR PLAN KEYNOTE
SCALE: 1/4"=1'-0"
EXISTING FLOOR PLAN
A-1.0
1 NORTH
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
EXISTING FLOOR PLAN
EXISTING WALL TO REMAIN
WALL LEGEND
EXISTING WALL TO BE REMOVED.
1
2
EXISTING COLUMN TO REMAIN.
EXISTING ELECTRICAL PANEL TO REMAIN.
3
4
EXISTING STOREFRONT TO BE REPLACED.
EXISTING ADA RESTROOM TO REMAIN.
5 EXISTING INTERIOR NON-BEARING PARTITION TO BE REMOVED.
6 EXISTING DOOR TO REMAIN.
AHJ STAMP APPROVAL
V.I
.
F
.
(E
)
C
O
L
.
V.
I
.
F
.
(E
)
C
O
L
.
V.I.F.
(E) COL.
S
541 LB.
SAFE
541 LB.
SAFE 1,616 LB.
SAFECABINET
CO
U
N
T
E
R
T
O
P
(E) BOH
102 300 S.F.
(E) ALL-GENDER
103 60 S.F.
(E) SALES AREA
101 1,049 S.F.
MIN. CLEA
R
60" DIA.
A B C D
A B C D
E
E
1
2
3
4
1
2
3
4
61'-8"
(CONTRACTOR TO FIELD VERIFIED)
30'-2"
25'-
0
"
19
'
-
1
"
(C
O
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
37
'
-
1
0
"
(C
O
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
(CO
N
T
R
A
C
T
O
R
T
O
F
I
E
L
D
V
E
R
I
F
I
E
D
)
11'-4"12'-9"7'-6"
MIN. CLEA
R
60" DIA.
MIN. CLEA
R
60" DIA.
60
"
X
6
0
"
M
I
N
.
C
L
R
.
60"X60" MIN. CLR.
60
"
X
6
0
"
MI
N
.
C
L
R
.
60
"
X
6
0
"
MI
N
.
C
L
R
.
60
"
X
6
0
"
MI
N
.
C
L
R
.
48"X48" MIN. CLR.
48
"
X
4
8
"
MI
N
.
C
L
R
.
48
"
X
4
8
"
MI
N
.
C
L
R
.
48
"
X
3
0
"
M
I
N
.
C
L
R
.
48
"
X
4
8
"
M
I
N
.
C
L
R
.
48
"
X
4
8
"
M
I
N
.
C
L
R
.
1
2
2
3
4'-
0
"
4'
-
6
"
3'-4"3'-0"
3'
-
0
"
3'-0"
4'
-
5
"
5'
-
0
"
3'-3"
2'
-
6
"
7'-
0
"
3'-2"5'
-
1
"
9'-7"
20'-8"
6'
-
2
"
6'
-
9
"
7'-4"
11'-11"
11
'
-
1
0
"
2'
-
1
"
7'
-
3
"
3'
-
6
"
2'-
4
"
3'-4"2'-0"
3'-7
"
3'-7
"
2'
-
0
"
2'-
0
"
3'-7
"
2'-7
"
3'
-
5
"
10'-
7
"
3'-3
"
10'-
7
"
2'-7
"
3'-
4
"
8'-2
"
5"
3'-
6
"
11
"
3'
-
2
"
11
"
3'
-
2
"
11
"
3'
-
2
"
3'
-
2
"
P
O
T
P
O
T
POTPOTPOT
PO
T
POT POT POT POT POT POT POT POT
PO
T
POT
18
"
12
"
MIN
.
C
L
R
.
MI
N
.
C
L
R
.
18"
12"
MIN. CLR.
MIN. CLR.
18"
12"
MIN. CLR.
MIN. CLR.
4'
-
9
"
MAX. PATH OF EGRESS TRAVEL: 67'-6"
10'-6"1'-0"10'-6"
2'
-
0
"
2'-9"
1'-6
"
5'-1
1
"
1'-2
"
10
'
-
6
"
1'
-
5
"
2'
-
1
"
7'
-
3
"
1
2
3
4 5
6
7
8
9
1018
11
12 13
13
13
14
(NO WORK)
15
1
1616
17
17
17
16
16
13
1219
20
12
'
-
7
"
19
'
-
1
1
"
5'
-
5
"
21
3'-2"
3'-
8
"
(N) VIP ROOM
104 94 S.F.
MANAGER'S DESK
6
Stainless steel floor edge strip TL-01
1
8"OUTSIDE SHOP WINDOW
31.50″×31.50″×0.394″
A-1.1
1
2
3
4
5
6
NEW STOREFRONT SYSTEM.
PROVIDE "MAXIMUM OCCUPANCY 21 PERSONS" SIGN AT THIS
LOCATION. POSTED SIGNS SHALL BE OF AN APPROVED
LEGIBLE PERMANENT DESIGN AND SHALL BE MAINTAINED BY
THE OWNER OR AUTHORIZED AGENT.
PROVIDE ACCESSIBLE DECAL PER DETAIL 14/T-1.2 PER SEC.
11B-216.6. SIGNS SHALL INDICATE THE DIRECTION TO
ACCESSIBLE FACILITY ENTRANCES AND COMPLY WITH SEC.
11B-703.
PROPOSED ACCESSIBLE PATH OF TRAVEL FROM ENTRANCE TO
DESIGNATED TABLES AND SANITARY FACILITIES. ACCESSIBLE
PATH OF TRAVEL SHALL BE MINIMUM OF 44" WIDE.
NEW 28"-32" HIGH ACCESSIBLE COUNTER. SEE DETAIL 15/T-1.2
FOR COUNTER INFO.
PROVIDE EXIT SIGN AT EVERY EXIT PER DETAIL 20/T-1.2.
EXISTING 200 AMP PANEL TO REMAIN.
EXISTING TRANSFORMER TO REMAIN.
7
8
9
10
11
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
FLOOR PLANS
EXISTING WALL TO REMAIN
WALL LEGEND
PROPOSED NON-STRUCTURAL BULL-HEIGHT
PARTITION FROM FLOOR TO UNDERSIDE OF
CEILING STRUCTURE.
SCALE: 1/4"=1'-0"
PRPOSED FLOOR PLAN
A-1.1
1
PROPOSED FLOOR PLAN KEYNOTE
ENTRANCE TRANSITION, SEE DETAIL 2/A-1.1 FOR INFO.
NEW SAFE TO BE 1600 POUND, SEE STRUCTURAL DRAWING AND
CALCULATIONS FOR INFO.
NEW DISPLAY CASE BY OWNER.
12 NEW IN-WALL DISPLAY CASE BY OWNER.
13 NEW DECORATIVE PANELING BY OWNER.
14
15
EXISTING PLUMBING FIXTURES TO REMAIN.
LANDLORD'S CONSTRUCTION NOTES
TENANT SHALL BE SOLELY RESPONSIBLE FOR THE DESIGN,
INSTALLATION, AND USE OF ANY DISPLAY OR STORAGE
SYSTEM(S) WITHIN THE PREMISE INCLUDING ALL COMPLIANCE
WITH APPLICABLE BUILDING CODES, FIRE CODES AND THE
REQUIREMENTS OF ANY INSURANCE RATING BUREAUS. IF
ANYTHING DONE, OMITTED TO BE DONE OR SUFFERED TO BE
DONE BY TENANT IN, UPON OR ABOUT THE PREMISES IN REGARD
TO SUCH DISPLAY OR STORAGE SYSTEM(S) SHALL RESULT IN A
FIRE CODE VIOLATION(S) AND THE TENANT FAILS TO TAKE
CORRECTIVE ACTION AND/OR PAY THE ASSOCIATED FINE,
REGARDLESS OF WHETHER ASSESSED AGAINST TENANT OR
LANDLORD, WITHIN THE PRESCRIBED TIME PERIOD, THEN
TENANT SHALL BE LIABLE FOR ALL COSTS AND EXPENSES
RESULTING FROM SUCH VIOLATION(S) AND LANDLORD SHALL
HAVE THE RIGHT TO CORRECT ANY SUCH CONDITION(S) AT
TENANT'S EXPENSE.
1.
TENANT DISPLAY FIXTURES IN THE RETAIL SPACE AND
RACK/SHELVING/STORAGE UNITS IN THE STOCKROOM SHALL BE
DESIGNED TO PROVIDE ADEQUATE CLEARANCE FOR THE
AUTOMATIC (FIRE) SPRINKLER SYSTEM. NO DISPLAYS OR
STORAGE SHOULD EXCEED 12FT AND CEILINGS MUST BE
INSTALLED TO PROVIDE A MINIMUM OF 18" OF CLEARANCE
BETWEEN THE TOP OF THE STORAGE SYSTEM AND SPRINKLER
DEFLECTORS.
2.
TENANT DISPLAYS OR STORAGE HIGHER THAN 12'-0" ARE
CLASSIFIED AS "HIGH PILED STORAGE", WHICH REQUIRES HIGH
HAZARDOUS AUTOMATIC (FIRE) SPRINKLER PROTECTION
DESIGNED PER FM GLOBAL LOSS PREVENTION DATA SHEET AND
NFPA REQUIREMENTS FOR THE STORAGE OF "GROUP A
PLASTIC" COMMODITIES. HIGH PILED STORAGE ALSO REQUIRES
A MINIMUM 36" OF CLEARANCE BETWEEN THE TOP OF STORAGE
AND SPRINKLER DEFLECTORS.
3.
TENANT MOBILE/COMPACT STORAGE SYSTEMS SHALL BE
CONSTRUCTED OF WIRE MESH SHELVES. HOWEVER, IF
CONSTRUCTED WITH SOLID SHELVES (WOOD OR STEEL), THE
UNITS SHALL BE INSTALLED WITH A MINIMUM OF A 3" SPACER TO
PROVIDE SPACE BETWEEN UNITS AT MAXIMUM 5'-0" INTERVALS.
4.
TENANT'S ARCHITECT AND GENERAL CONTRACTOR SHALL
PROVIDE THE FOLLOWING INFORMATION TO THE MALL
REQUIRED SPRINKLER CONTRACTOR REGARDING
STOCK/STORAGE AREA.
5.
TYPE OF STORAGE SYSTEM(S). (INCLUDING DETAILS OF
THE STORAGE SYSTEM(S).
--
TYPE OF SHELVING. (WIRE MESH / SOLID WOOD / SOLID
STEEL, ETC.)
--
TYPE OF COMMODITIES. (PLASTICS, AEROSOL'S,
CLOTHING, ETC.)
--
ELEVATION OF HIGHEST SHELF / CEILING HEIGHT.--
LANDLORD STRONGLY PREFERS USE OF ENERGY STAR
PRODUCTS AND/OR EQUIPMENT WHENEVER POSSIBLE DURING
TENANT BUILD OUT, WHICH CAN REDUCE ENERGY
CONSUMPTION.
6.
DISPLAY FIXTURES, RACKS, SHELVING, AND STORAGE UNIT
REQUIREMENTS:
TENANT, TENANT'S DESIGN TEAM, AND TENANT'S CONTRACTORS
SHALL FIELD VERIFY ALL FIELD CONDITIONS PRIOR TO THE
START OF ANY CONSTRUCTION. BE ADVISED THAT ALL CHANGES
AND MODIFICATION TO THE LANDLORD'S APPROVED DRAWINGS
SHALL BE RESUBMITTED TO LANDLORD FOR RE-APPROVAL. ANY
CONSTRUCTION COMPLETED WITH OUT LANDLORD APPROVAL
SHALL BE CORRECTED AS APPROVED BY LANDLORD AT
TENANT'S EXPENSE.
1.
FIELD VERIFICATION REQUIREMENTS:
TENANT SHALL PROVIDE A FINISH SAMPLE BOARD OR SIMILAR TO
THE LANDLORD FOR APPROVAL.
1.
FINISH PLAN REQUIREMENTS:
ALL FLOORING TRANSITIONS MUST BE SMOOTH AND FLUSH. THE
USE OF PLASTIC, VINYL, OR RUBBER TRANSITIONS STRIPS IS
STRICTLY PROHIBITED. TENANTS MUST UTILIZE A HARD
SURFACE TRANSITION.
2.
NO RUBBER OR VINYL BASE IS PERMITTED IN THE SALES ARE OF
THE PREMISES.
3.
TENANT IS REQUIRED TO INSTALL A WATERPROOF MEMBRANE IN
ALL WET AREAS (RESTROOMS, KITCHENS, FOOD SERVICES,
ETC...) OF THE SPACE. TENANT SHALL USE A 30 MIL
POLYETHYLENE CLEAVAGE MEMBRANE (EQUAL TO NOBLESEAL
TS) INSTALLED PER MANUFACTURERS RECOMMENDATIONS AND
ANSI A108. MEMBRANE MUST BE EXTENDED UP THE WALL A
MINIMUM OF 6" OR EQUAL TO THE HEIGHT OF THE FLOOR BASE.
4.
ELEVATED SLABS: TENANT'S GENERAL CONTRACTOR SHALL
ADVISE THE OPERATIONS TEAM PRIOR TO ANY SLAB
MODIFICATION OR REMOVAL. IF ANY ELEVATED SLAB IS TO BE
MODIFIED IN ANYWAY (DRILLED, CORED, OR PENETRATED),
TENANT SHALL PROVIDE STAMPED AND CERTIFIED DRAWINGS
BY A LICENSED STRUCTURAL ENGINEERED CERTIFIED IN THE
LOCAL JURISDICTION. ALL PENETRATIONS SHALL BE CORE
BORED ONLY. SAW CUTTING, JACK HAMMERING, AND
TRENCHING IS STRICTLY PROHIBITED. ALL PENETRATIONS
SHALL BE SLEEVED, SEALED, FIRE STOPPED, AND
WATERPROOFED. THE PENETRATION SLEEVE SHALL EXTEND A
MINIMUM OF 4" ON EITHER SIDE OF THE SLAB AND BE LABELED
WITH THE REQUIRED NFPA RATING. TENANT GC SHALL VERIFY
THAT WORK SHALL NOT CONFLICT WITH ANY EXISTING
STRUCTURAL, UTILITY, OR OTHER UNDER-SLAB CONDITION.
(NONDESTRUCTIVE VERIFICATION MAYBE REQUIRED.) ANY
DAMAGE OR DOWNTIME CAUSED BY TENANT'S WORK SHALL BE
REPAIRED AND REIMBURSED AT TENANT'S EXPENSE.
1.
SLAB REQUIREMENTS:
NEW 6'-2" HIGH DISPLAY CASE BY OWNER.
AHJ STAMP APPROVAL
NORTH
16 EXISTING SHAFT TO REMAIN.
17 EXISTING COLUMN TO REMAIN.
18 NEW 60" HIGH RACK FOR SECURITY SYSTEM.
19 NEW 60" HIGH STORAGE RACK.
20 NEW 34" HIGH KITCHEN COUNTER WITH ACCESSIBLE KITCHEN
SINK.
21 LOCATION OF KNOX BOX FOR FIRE DEPARTMENT.
SCALE: NTS
FLOOR TRANSITION @ ENTRANCE AREA
A-1.1
2
2
L0
6
L01
L01
L01
L02
L02
L02
L02
L05
L05
L05
L0
5
L0
5
L0
5
L05
L0
5
L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05
L05
L0
5
L0
5
L05
L05
L05
L05
L05
L01
L01
L01
L03 L03
L02 L02 L02 L02 L02 L02 L02 L02
L03 L03
L02 L02
L01
L01
L02 L02
S
SL02L02L02
L03 L03
S
L02
L02
L02
L02
L02
L02
L02
L02
L02
L02
S
A/C
A/C
A/C
A/C
A/C
L05L05
(E)
E
X
I
T
(E) BULKHEAD
SOFFIT
C.H. +9'-10"
(E) STOREFRONT
SOFFIT
C.H. +9'-10"
EX
I
T
C.H. +10'-10"
(E) T-BAR CEILING
C.H. +11'-6"C.H. +10'-0"
(N) T-BAR CEILING
C.H. +9'-0"
(E) DRYWALL CEILING
A/C
A/C
A/C
A/
C
A/C
A/
C
L02L02
L02L02L02
L02L02L02
L02L02
L02L02
L02L02
C.H. +11'-6"
C.H. +10'-10"
C.H. +10'-10"
(E) T-BAR CEILING
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
C.H. +11'-6"
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
A B C D
A B C D
E
E
1
2
3
4
1
2
3
4
30'-2"
37
'
-
1
0
"
11'-4"12'-9"7'-6"
4'-5"
3'-
5
"
1'-5"1'-6"
1'
-
0
"
3'-
1
0
"
2'-5"8"
4'
-
6
"
8"
25'-8"
1'
-
6
"
3"
2'-3"21'-11"
1'-8"1'-8"2'-0"1'-8"1'-8"3'-0"1'-8"1'-8"2'-0"1'-8"1'-8"
3'
-
6
"
8"
1'
-
7
"
11'-7"3'-11"2'-7"11'-10"9"9'-8"
1'-8"
10
"
3'-0"
1'-
8
"
2'-5"4'-5"4'-5"4'-5"4'-5"4'-5"4'-5"4'-5"4'-10"
1'
-
8
"
1'-
8
"
2'-
0
"
1'
-
8
"
1'-
8
"
1'
-
0
"
8"
8"
2'-4"
2'
-
1
0
"
3'-
5
"
3'-
5
"
3'-
5
"
4'
-
7
"
5'
-
3
"
4'
-
1
"
4'
-
7
"
1'
-
8
"
1'
-
1
"
1'
-
8
"
2'
-
0
"
1'
-
8
"
11
"
3'-6"
6'-4"3'-11"
2'-
6
"
4'-7
"
4'-6
"
4'-5
"
1'-
4
"
4'-7
"
9"
4'-8
"
8"
1'-1
1
"
4'-5
"
1'-1
1
"
1'
-
1
"
1'-
9
"
4'-10"4'-5"
8'-
1
0
"
2'-
4
"
2'-
3
"
2'-8"
3'-2"11
"
2'
-
7
"
1'-8
"
4'-4"
3'-2"
1'-8
"
2'-8
"
1'-8
"
3'-
3
"
1'-
1
1
"
3'
-
5
"
2'-
1
0
"
2'-0"4"
3'
-
3
"
11
"
10
"
3'
-
2
"
4"
10
"
3'
-
3
"
11
"
2'
-
2
"
1'
-
1
1
"
8"
6'-4"
1'-8"
5'-
4
"
4'-5"2'-11"
10"
10
"
10
"
10"
8"
8"
8"8"3'
-
0
"
7'-8"6'
-
3
"
5'-3
"
8'
-
0
"
10'-
0
"
4'
-
0
"
1'-7"
2'
-
7
"
4'-0"4'-0"4'-0"4'-0"
4'
-
0
"
4'
-
0
"
4'
-
0
"
3'
-
0
"
SEE PAGE A-4.1 FOR
CEILING DETAILS.
HEAVY DUTY T-BAR GRID
SYSTEM SHALL BE USED.
A-2.0
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
EXIT PLAN &
SCALE: 1/4"=1'-0"
PROPOSED REFLECTED CEILING PLAN
A-2.0
1 NORTH
LIGHTING FIXTURE SCHEDULELANDLORD'S CONSTRUCTION NOTES
IF NOT ALREADY EXISTING, TENANT MUST PROVIDE A SEALED
PARTITION ABOVE THE STOREFRONT TO SEPARATE THE
COMMON AREA CEILING FROM THE TENANT'S SPACE. (SHALL BE
RATED IF REQUIRED BY CODE AND ALL PENETRATION SHALL
COMPLY AND BE LABELED WITH THE REQUIRED NFPA RATING.)
1.
NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED
FROM, OR PENETRATE LANDLORD'S STRUCTURE, FLOOR DECK,
OR ROOF DECK. YOU MAY ATTACH, NON-DESTRUCTIVELY, TO OR
SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE
STRUCTURAL STEEL WHICH EXISTS ABOVE THE TENANT SPACE.
WHEN ATTACHING TO LANDLORD'S STRUCTURE, DO NOT DRILL,
WELD, SCREW, OR SHOOT INTO STRUCTURE. ALTERNATIVE
METHODS OF ATTACHMENT ONLY, NOTHING TO DAMAGE
LANDLORD'S BASE BUILDING STRUCTURE. TENANT SHALL
PROVIDE SIGNED AND SEALED STRUCTURAL DRAWINGS, BY A
STRUCTURAL ENGINEER WITH LEGALLY ACTIVE REGISTRATION
AS INDICATED BY ALL JURISDICTIONAL REQUIREMENTS, FOR ALL
STRUCTURAL MODIFICATIONS FOR LANDLORD RECORDS.
2.
ANY LANDLORD EQUIPMENT, COMPONENT, AND/OR SERVICE
FEEDING OTHER TENANT(S) THAT IS EXISTING IN THE SPACE
MUST REMAIN VISIBLE AND ACCESSIBLE TO THE LANDLORD.
TENANT SHALL INSTALL ACCESS PANELS AS REQUIRED TO
MAINTAIN ACCESS. ACCESS PANELS SHALL BE LABEL TO
PROPERLY IDENTIFY SYSTEM, COORDINATE WITH MALL
OPERATIONS.
3.
SIMON REQUIRES ALL TENANTS TO USE LANDLORD'S REQUIRED
CONTRACTOR FOR ALL SPRINKLER WORK. REFER TO
SPRINKLER COMMENTS FOR FURTHER REQUIREMENTS.
4.
REFLECTED CEILING PLAN REQUIREMENTS:MANUFACTURER
& MODEL NUMBER
REMARKSDESCRIPTIONTYPEFINISHLAMP
TBD BLACK
FRAME
LED
3000K
SEE MECHANIAL DWG.LED
3000K
800L
RETURN AIR DIFFUSER LED
3000K
369L
SUPPLY AIR DIFFUSER
REFLECTED CEILING PLANS
AHJ STAMP APPROVAL
L01
L02
L03
L05
L06
LED
3000K
LED
3000K
LED
3000K
LED
3000K
WHITE
FRAME
WHITE
FRAME
WHITE
FRAME
WHITE
FRAME
24"X24" ACCESS PANEL "BEST ACCESS DOOR" BA-IVHDF
INVISA HATCH™ DRYWALL INLAY
WITH FULLY DETACHABLE HATCH
WITH MUD IN FLANGE OR EQUAL
DRYWALL FINISH TO BE
PAINTED TO MATCH
ADJACENT COLOR
SEE MECHANIAL DWG.
SEE MECHANIAL DWG.
SEE MECHANIAL DWG.
4" RECESSED LIGHT
APERTURE 75 -- BEAM ANGLE 36°
AMBIENT LIGHT, 16W
4" RECESSED LIGHT
APERTURE 75 -- BEAM ANGLE 36°
AMBIENT LIGHT, 16W
4" RECESSED LIGHT
APERTURE 75 -- BEAM ANGLE 36°
AMBIENT LIGHT, 16W
3" RECESSED DOWNLIGHT
APERTURE 75 -- ASYMETRIC LIGHT INDOOR WALL WASHER
12W
TBD
TBD
TBD
TBD
3" RECESSED SPOTLIGHT
APERTURE 75 -- BEAM ANGLE 15°
MERCHANDISE SPOTLIGHT
MANUFACTURER
& MODEL NUMBER
REMARKSDESCRIPTIONTYPEFINISHLAMP
TBDEXIT LIGHT
EMERGENCY LIGHTING TBD
TBD
TBD
TBD
TBD
3
14'-4" A.F.F.
B.O. MALL CEILING
B.O. EYEBROW
0'-0" A.F.F.
MALL FINISH FLOOR
MW10 MW10
LIGHT BOX(7000+K)
DT-84
MN10 MN10 MN10
9'-10" A.F.F.
1'
-
7
"
1'
-
4
"
1'
-
7
"
4'-10"15'-3"4'-10"1'-10"15'-3"1'-10"
1'
-
7
"
1'
-
4
"
1'
-
7
"
3'-
4
"
3'
-
8
"
3'
-
0
"
3'-0"
11"6'-8"9"2'-9"10'-9"3'-4"11'-6"
7'
-
8
"
6'-8"
4'
-
6
"
9'
-
1
1
"
14
'
-
7
"
15'-5"3'-7"
9'
-
1
1
"
4'
-
6
"
EXISTING STOREFRONT
TO REMAIN
EXISTING STOREFRONT
TO REMAIN
PROPOSED WALL WITH WINDOWS
REPLACING EXISTING STOREFRONT
(N) ALUMINUM PANEL WITH BAKED
ENAMEL COLOR--PANTONE 202C
OR EQUAL, GLOSS FINISH.
(N) ALUMINUM PANEL WITH BAKED
ENAMEL COLOR--PANTONE 202C
OR EQUAL, GLOSS FINISH.
(N) ALUMINUM PANEL WITH BAKED
ENAMEL COLOR--PANTONE 202C
OR EQUAL, GLOSS FINISH.
(N) SIGNAGE BY OTHERS.
(N) DISPLAY CASE BEHIND
STOREFRONT
(E) STOREFRONT DOOR
SYSTEM
(E) DOOR HANDLE (N) MUSHROOM GRAY 10% GLOSSY
METALLIC PAINT,
"DULUX" 40YY25/074.
(N) DISPLAY WINDOW.
(E) LED LIGHTBOX
DISPLAY
(E) STOREFRONT SYSTEM
(N) MUSHROOM GRAY 10% GLOSSY
METALLIC PAINT,
"DULUX" 40YY25/074.
(N) MUSHROOM GRAY 10% GLOSSY
METALLIC PAINT,
"DULUX" 40YY25/074.
(N) SIGNAGE BY OTHERS.
(E) BULKHEAD SOFFIT TO REMAIN (NO STRUCTURAL WORK)(E) BULKHEAD SOFFIT TO REMAIN (NO STRUCTURAL WORK)(E) BULKHEAD SOFFIT TO REMAIN (NO STRUCTURAL WORK)
A3.0
THE TENANT SPACES, THE MAIN ENTRANCES AND EXITS, PATH OF
TRAVEL, SANITARY FACILITIES, DRINKING FOUNTAINS AND PUBLIC
TELEPHONES SERVING THE TENANT SPACE SHALL BE ACCESSIBLE TO
PERSONS WITH DISABILITY. COUNTY INSPECTOR SHALL VERIFY AT
FIELD FOR COMPLIANCE PRIOR TO FINAL INSPECTION.
WHERE KEY-OPERATED LOCKING DEVICES ARE USED, POST A SIGN ON
OR ADJACENT TO THE REQUIRED MAIN EXIT DOOR WITH 1-IN.
LETTERING STATING: "THIS DOOR TO REMAIN UNLOCKED WHEN
BUILDING IS OCCUPIED."
NOTE:
1.
2.
SCALE: 1/4"=1'-0"
EXTERIOR FACADE ELEVATION
A-3.0
1
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
AHJ APPROVAL STAMP
STOREFRONT ELEVATIONS
SUSPENSION CEILING
SEE REFLECTED
CEILING PLAN
8" MAX 8" MAX
HANGER WIRE
4-WAY SEISMIC
SEPARATION JOINT
CLIP1" MIN GAP IN MAIN TEE
TEE FACE SLEEVE, CRIMP
ONE SIDE OF SPLICE
NOTE: SEISMIC CEILING JOINTS REQUIRED FOR
CEILING AREAS GREATER THAN 2500 SF (MAX 4:1
RATIO)
MA
X
T
Y
P
45
°
.
VERTICAL STRUT @ 12'-0" O.C. MAX &
6'-0" MIN FROM PERIMETER WALLS
FRO MAIN RUNNERS & 4'-0" FOR
CROSS RUNNERS. REFER TO DETAIL
ON THIS SHEET.
12 GA VERTICAL HANGER
WIRE @ 4'-0" EACH WAY W/
MIN 3 TIGHT TURNS IN 1 1/2"
BOTH ENDS OF WIRE (TYP)
12 GA. SPLAY BRACE WIRE IN
4 DIRECTIONS 90 DEG APART
@ 12'-0" X 8'-0" O.C. WITH 4
TIGHT TURNS IN 1 1/2"
NOTES:
1.2" MAX FROM BRACING WIRES TO CROSS RUNNERS.
2.SUSPENDED CEILING ATTACHMENTS IN ACCORDANCE
WITH ICC ESR #1222
MAIN RUNNERS
MAIN RUNNERS
S
E
N
W
4'-
0
"
T
Y
P
SEE N
O
T
E
1
EA
W
A
Y
SEE 3/-FOR LIGHT FIXTURE AXONOMETRIC VIEW
SEE 4/-FOR COMPRESSION STRUT
AT UNATTACHED WALLS:
PROVIDE APPROVED SEISMIC CLIPS AT
EACH T-BAR PER DETAIL ON THIS SHEET.
STANDARD 7/8" PERIMETER MOLDING TO BE PROVIDED.
UN
A
T
T
A
C
H
E
D
W
A
L
L
UNATTACHED WALL
ATTACHED WALL
ONLY WHEN EXPRESSLY APPROVED BY
THE ARCHITECT AS A DEDUCT ALTERNATE
SHALL 2" MOLDING BE PROVIDED IN LIEU
OF CLIPS. THIS ALTERNATE REQUIRES
SPREADER BARS AS INDICATED IN
DASHED LINES
AT ATTACHED WALLS:
PROVIDE APPROVED SEISMIC CLIPS AT
EACH T-BAR PER DETAIL ON THIS SHEET.
STANDARD 7/8" PERIMETER MOLDING TO BE PROVIDED.
ONLY WHEN EXPRESSLY APPROVED BY
THE ARCHITECT AS A DEDUCT ALTERNATE
SHALL POP RIVETS BE USED
GRID END CLEARANCE AT UNATTACHED
WALLS TO MEET MIN. CODE RQTS. REFER
TO TABLE ON THIS SHEET.
PERIMETER HANGER WIRES AT CROSS
AND MAIN RUNNERS, AS REQUIRED BY
CODE. REFER TO TABLE ON THIS SHEET.
VERTICAL HANGER WIRES (12GA) @ 4' O.C. MAX)
SEE 2/-FOR AXONOMETRIC VIEW
SEE 6/-FOR SEISMIC JOINT
SEE 7/-FOR ATTACHMENT DETAILS
4" X 16 GA. STEEL STUD
COMPRESSION STRUT (MAX.
LENGTH 5'-0")
ATTACH FURRING CHANNEL
W/ SADDLE TIE 16 GA. WIRE &
2 TIGHT TURNS TYP. EA
RUNNER.
MAIN RUNNERS: 1-1/2" COLD
ROLLED CHANNEL. @ 48" O.C.
MAX. PROVIDE 9GA VERTICAL
HANGER WIRES @ 36" MAX & 0-8"
MAX FROM PERIMETER WALLS &
DISCONTINUITIES, WITH SADDLE
TIE WRAPPED WITH 3 TIGHT
TURNS.
NOTCH STRUT AT MAIN
RUNNER. SECURE W/ 1-1/4"
DIA MACHINE BOLT
12 GA MIN. BRACE WIRES WHERE
REQUIRED. SPLAY IN FOUR
DIRECTIONS 90 DEG APART.
CONNET TO MAIN RUNNER AT 2"
MAX FROM CROSS RUNNER AND
TO STRUCTURE ABOVE AT 45
DEG MAX SLOPE. BRACE POINTS
TO BE AT 12'-0" INTERVALS, & 4'-0"
MAX FROM PERIMETER WALLS.
SADDLE TIE TO MAIN RUNNER W/
4 TIGHT TURNS IN 1 1/2".
MAINTAIN CLEARANCE AT ALL
CONSTRUCTION
5/8" TYPE 'X' GYP. BD.
MAIN RUNNERS: 1-1/2" COLD ROLLED
CHANNEL. @ 48" O.C. MAX. PROVIDE 9GA
VERTICAL HANGER WIRES @ 36" MAX & 8"
MAX FROM PERIMETER WALLS, WITH
SADDLE TIE WRAPPED WITH 3 TIGHT
TURNSBRACE WIRES/STRUTS: PROVIDE FOR
EACH 96 SF OF CEILING AREA.
BRACE WIRES MAY BE OMITTED FOR
CONTINUOUS LEVEL CEILING WITH
POSITIVE ATTACHMENT TO ALL
PERIMETER WALLS
96 SF
DRYWALL FURRING CHANNELS: 7/8" x 25
GA @ 16" O.C. MAX. ATTACH GYP. BD. W/ 1"
HI-LO TYPE 'S' BUGLE HEAD SCREWS @ 12"
O.C. MAX (3-1/4" MIN EDGE DISTANCE)
ATTACH MAIN RUNNERS TO PERIMETER
WALLS W/ CONTINUOUS 1.5"x1.5"x16GA
ANGLE. ATTACH TO RUNNER WITH #8 x
1/2" S.M.S.
SEE 9/-FOR AXONOMETRIC VIEW
COMPRESSION STUD OR
CHANNEL & VERTICAL
SUPPORT PER SCHEDULE
BRACE WIRES, TYP
CROSS TEE
MAIN TEE
COMPRESSION STUD OR
CHANNEL & VERTICAL
SUPPORT PER SCHEDULE
CROSS TEE
MAIN TEE
ANGLED SPLAY STUDS
(SET AT SAME ANGLE
TO GRID AND 90 DEG TO
EACH OTHER)
METAL STUD SCHEDULE
(Based on City of San Diego)
(1) 3-5/8" (25GA)-UP TO 8'-0"
(2) 1-5/8" (25GA)-UP TO 10'-0"
INSTALL PER BELOW
(2) 2-1/2" (25GA)-UP TO 15'-0"
INSTALL PER BELOW
(2) 3-5/8" (25GA) -UP TO 20'-0"
INSTALLED AS FOLLOWS:
METAL CHANNEL SCHEDULE
250T125-33 (20GA) -UP TO 6'-0"
400S137-33 (20GA) -UP TO 8'-0"
STUD/CHANNEL OPTION 1
STUD/CHANNEL OPTION 2
#8 SMS @
12" O.C.
4
5
°
.
45
°
.
M
A
X
T
Y
P
6
0
°
.
SUPPLEMENTARY HANGER WIRE, WHERE
REQ'D (REFER TO CHART ON THIS SHEET).
WIRE TO BE 12 GA WITHIN 3" OF EACH
CORNER OF LIGHT FIXTURE. SPLAY WIRES
AS SHOWN AND FASTEN TO STRUCTURE.
MIN. OF 3 WIRE TURNS EA CONNECTION
POINT.
12 GA FIXTURE SUPPORT WIRES
AT A MIN OF 2 CORNERS
LOCATED DIAGONALLY @ EA
FIXTURE. FIXTURE SUPPORT
WIRE SUPPLIED BY CEILING
CONTRACTOR.
MAIN STRUCTURAL
RUNNER 4'-0" O.C.
CROSS TEE
RECESSED FLUORESCENT
FIXTURE
THIS DETAIL APPLIES TO SEISMIC CATEGORIES
D/E/F. FOR CATEGORY C, SEE CHART ON THIS SHEET.
BEAM CONNECTION (CISCA FIG 4-A)
NON-SFRS STRUCTURAL STEEL
MEMBER. REMOVE AND REPLACE
FIREPROOFING
FOR CONNECTION OF CLIPS
0.157 DIA. X 1/2" SHOT PINS (HILTI OR
EQUAL)
MIN 3/4" WIDE X 13 GA. CLIP (HILTI OR EQUAL)
@ HANGERS
HANGER WIRE (3 TURNS MIN)
SPLAY WIRE (4 TURNS MIN)
MIN 1" WIDE x 2" LONG x 13 GA. CLIP (HILTI OR
EQUAL) @ SPLAY WIRES
3/
1
6
"
M
I
N
3/8" MAX
OPEN WEB JOISTS (CISCA FIG 4-B)
WEB MEMBERS
BOTTOM CHORD
HANGER WIRE (3 TURNS MIN)
SPLAY WIRE (4 TURNS MIN)
MIN 3" WIDE x 4" LONG x 12GA
STRAPS @ SPLAY WIRES
METAL DECKING (MIN 20 GA)
WITHOUT CONCRETE
ROOF DECKING (CISCA FIG 4-C/D)
(2) #8 x 1/2" SELF TAPPING SCREWS
#3 x 12" REBAR. TIE HANGER WIRE
TO REBAR WITH (3) WRAPS AROUND
BAR AND ONE WRAP AROUND WIRE
1" MIN
1/4" MAX
APPROVED SHOT-IN ANCHOR (HILTI
OR EQUAL). CLIP PER FIG 4A ABOVE.
SELF-TAPPING SCREWS ONLY
ALLOWED PRIOR TO CONC. POUR
STRUCTURAL CONCRETE FILL
DECK W/ CONC. FILL (CISCA FIG 5-B/C/D)
WIRE 'PIGTAIL' W/ 2" DIA LOOP & 4" TAIL
(ONLY ACCEPTABLE W/ CONC. FILL)
APPROVED SHOT-IN ANCHOR (HILTI OR
EQUAL). CLIP PER FIG 4A ABOVE.
APPROVED "RED HEAD" EYE BOLT IS
ALSO ACCEPTABLE (LOAD TEST REQ'D)
1 1/8" MIN
(3) 1 1/2"x 9GA STAPLES OR (3)
STRONGHOLD 'J' NAILS AT EACH WIRE
LOOP
1"
M
I
N
WOOD JOIST OR RAFTER, OR 2x
BLOCKING W/ 2-16d COMMON NAILS EA.
END
2"
M
I
N
1/4" DIA SCREW EYE WITH FULL THREAD
EMBEDMENT (1-1/4" MIN)
1/4" DIA. DRILLED HOLE
1/4" DIA SCREW EYE WITH FULL
THREAD EMBEDMENT (1-1/4" MIN)
WOOD JOIST OR RAFTER, TYP
3"
M
A
X
WOOD STRUCTURE (CISCA FIG 2-A/B/C/D)
1.5"x1.5"x13GAx3" ANGLE ATTACHED TO
DECK W/ APPROVED SHOT PINS (HILTI OR
EQUAL)
SLOT END OF TUBE. FASTEN TO
ANGLE W/ #10 x 2" S.M.S.
CUT METAL STUD FLANGES & BEND 90
DEGREES. ATTACH TO STRUCTURE W/
APPROVED SHOT-IN ANCHOR (HILTI OR
EQUAL).
2"
CHANNE
L STRUT
TUBE
STRUT
COMPRESSION STRUT ATTACHMENT
RUNNERS @ 4'-0" O.C.
2".
LAY-IN ACOUSTICAL CEILING PANEL
1/8" DIA STEEL POP RIVET COMPLYING WITH FI-114
STD. RUNNERS/TEES ATTACHED ON (2) ADJACENT
WALLS WITH POP RIVET OR EQUIV FASTENER.
FINISHED FACE OF WALL
8" MAX
WALL ANGLE MOLDING, HEMMED EDGE
NOTE: INSTALL SEISMIC PERIMETER CLIP. INSTALL AT MAIN AND CROSS RUNNERS AT (2) ADJ WALLS
AND ALLOW FREE MOVEMENT OF RUNNERS ON (2) OPPOSING WALLS PER ICC #ESR-1222 & 3336
HANGER WIRE
8" MAX.
WALL ANGLE
MOLDING, HEMMED
EDGE
8" MAX.
EXPANSION CLIP,
FIXED
TO PERIMETER ANGLE,
INSTALLED PER MNF
HANGER WIRE
8" MAX.
TYP. -ATTACH 7/8" ANGLE TO:
A) 18 GA. STUD W/1-1/4"
S-12 PAN HEAD SCREWS
B)18 GA. STUD W/1-1/4" HI-LO
MOD. OVAL HEAD
8" MAX.
CO
D
E
R
E
Q
'
D
G
A
P
EXPANSION CLIP, ALLOWED
TO SLIP, INSTALLED PER
MNF
DETAIL AT FIXED CONDITION DETAIL AT SLIP CONDITION
CODE REQ'D GAP
REFER TO CHART ON THIS SHEET
NOTE:
REFER TO ICC
#ESR-1222 & 3336
7/8"7/8"
SHADOW
MOLDING WHERE
APPLICABLE
MINIMUM CODE REQUIRMENTS
Design Standards
Ceiling systems (including fixtures, etc) <= 2.5 PSF
Ceiling systems (including fixtures, etc) > 2.5 PSF
Minimum intersection strength limits @ MT / CT (1)
Vertical hanger wire 12-gauge @ 4' o.c.
Connection device from vertical wire to the structure above must
sustain min 100 lbs
Main tee classifications (Minimum)
1 in 6 max plumb of vertical hanger wires
Perimeter vertical hanger wires (12-gauge) not more than 8" from
wall (or 1/4 length of tee, whichever is less)
Gap between main/cross runners and Unattached Walls
Perimeter closure (molding) width
Grid connection to perimeter attached on two adjacent walls
Perimeter tee ends tied together to prevent spreading
Horizontal restraint (splay wires or rigid bracing) within 2" of
intersection and splayed 90° apart at 45° angles
Compression posts (struts) 12' o.c. in both directions, starting 6'
from walls
Splay bracing connection strength 200 lbs or the design load,
whichever is greater
Partition attachment
Seismic separation joint or full height partition (2)
Rigid bracing for ceiling plane elevation changes
Expansion joint at intersections of corridors and at junctions of
corridors and lobbies or other similar areas
Special Inspections as required by ASCE 7-05 Sec 13.5.6.2.2 (h)
Metal panels & panels weighing > 0.5 PSF other than acoustical
tiles shall be positively attached to the ceiling suspension runners
ASTM E580
CISCA 0-2
CISCA 3-4
60 lbs
Required
Not Required
Intermediate-duty
Required
Not Required
unless molding is
less than 7/8"
Min 3/8"
Min 7/8" (or
Perimeter Wires)
Not Permitted
Required
Required (4)
Not Required
Not Required
Allowed only if
ceiling is able to
move laterally
Not Required
Not Required
Not Required
Not Required (5)
Not Required
ASTM C635,
C636, & E580
ASCE 7-13.5.6.2.1
CISCA 3-4
CISCA 3-4
180 lbs
Required
Required
Heavy-duty
Required
Required
Min 3/4"
Min2" or Approved
Seismic Clips
Required
Required
Required (4)
Required
Required
Bracing
independent of
ceiling splay
bracing
Required for
areas > 2,500 sq.
ft.
Required
Required (3)
Not Required (5)
Required (3)
Basic Connections, Perimeter, and Lateral Splay Bracing Category C Category D,E,F
BUILDING SEISMIC CATEGORY
Light fixture (all types) mechanically attached to grid NEC 410-16
(two per fixture unless independently supported)
Surface-mounted fixtures attached to grid with at least two positive
clamping devices made of min 14-gauge material each with a 12-
gauge suspension wire to structure above
Pendant-hung fixtures directly supported from structure with 9-
gauge wire (or approved alternative)
All Recessed or drop-in light fixtures
≤10 lbs –one wire to structure (may be slack)
11 to 56 lbs –two wires from housing to structure
(may be slack)
≥57 lbs –supported directly to structure by approved
Required
Not Required
Required
Required
Required
Required
Light Fixture Attachment
Required
Required (3)
Required
All directly
supported from
structure with two
12-gauge wire
located at
diagonally
opposite
corners.(3)
Heavy Duty Main Tees with cross tee rating below 16 lbs./LF:
Min. 12-gauge hanger wires must be attached to the supporting
cross tee within 3 inches of the corner of each light fixture.
Supplementary hanger wires for Heavy Duty Main Tees with
cross tee rating equal to 16 lbs./LF
Light Fixture Supplementary Hanger Wires
Required
Not Required
Air terminals
≤20 lbs –positively attached to grid
21 to 56 lbs –positively attached to grid and
two wires to structure (may be slack)
≥57 lbs –directly supported to structure
Sprinkler heads and other penetration clearance
Cable trays and electrical conduit independently supported and
braced
Service Applications
Required
Required
Required
Min 2" dia. opening
or a swing joint
Required
(1) Required for ceilings larger than 1,000 square feet.
(2) Where substantiating design calculations are not provided.
(3) Modification to ASTM E580 as required by CBC Sec 1616
(4) Ceilings under 144 SF or ceilings constructed of plaster or gyp. boards and secured at all perimeter
walls are exempt from lateral load reqts. (CISCA 3-4, pg1, Sec 2)
(5) CBC Sec 1613.1 excludes adoption of ASCE 7-05 Appendix 11A (which contains the special inspection
requirement). However, GC to verify with local jurisdiction whether special inspection will be required.
Required
Required
Required
Min 3/8" on all
sides
Not Required
SCALE:3" = 1'-0"07 CEILING -SIESMIC JOINT
SCALE:3" = 1'-0"03 CEILING -SUSPENDED ACOUSTICAL CEILING AXON
SCALE:1/4" = 1'-0"04 CEILING -SUSPENDED ACOUSTICAL CEILING PLAN
SCALE:1" = 1'-0"09 CEILING -SUSPENDED GYP BD CEILING AXON
SCALE:1/4" = 1'-0"10 CEILING -SUSPENDED GYP. BD. CEILING PLAN
SCALE:3" = 1'-0"01 CEILING -TYP COMPRESSION STRUT
SCALE:3" = 1'-0"02 CEILING -TYP LIGHT FIXTURE
SCALE:1" = 1'-0"05 CEILING ATTACHMENT DETAILS
SCALE:3" = 1'-0"08 CELING -SHADOW MOLDING @ ACT
SCALE:3" = 1'-0"06 CEILING -TYP. T-BAR GRID @ WALL
scale:
cad file:
TENANT IMPROVEMENT
page description:
job number:
seal/signature:
sheet no.:
revision date
& description:no.
project:
400 S. BALDWIN AVE.,
SPACE #A16
CHOW TAI FOOK
ARCADIA, CA 91007
JEWELRY STORE
COPYRIGHT C 2026 BY
RUBY CONSULTING PARTNERS, LLC
ALL RIGHTS RESERVED.
ruby consulting
partners, llc
710 S. MYRTLE AVE., #117
MONROVIA, CA 91016
TEL: 626.320.2815
alison.fung@aol.com
5/8/2026
LANDLORD1
6/15/2026
BUILDING DEPT.2
6/24/2026
BUILDING DEPT.3
A-4.1
CEILING DETAILS
3
NOTE:
(HEAVY DUTY T-BAR GRID SYSTEM
SHALL BE USED FOR THIS PROJECT)
3
SCALE 1/4" = 1'-0"
INTERIOR T.I. FRAMING PLAN
do not scale plan
A
A
1 1
2 2
B
B
C
C
D
D
S-1
1/4" = 1'-0"
IN
T
E
R
I
O
R
T
.
I
.
F
R
A
M
I
N
G
P
L
A
N
21
1
2
1
E
.
S
n
o
w
C
r
e
e
k
D
r
.
,
W
a
l
n
u
t
,
C
A
9
1
7
8
9
e-
m
a
i
l
:
d
a
n
t
a
n
c
o
r
p
@
h
o
t
m
a
i
l
.
c
o
m
DA
N
T
A
N
C
O
R
P
O
R
A
T
I
O
N
Of Sheets
Sheet:
Job:
Drawn:
Scale:
Date:
Revison
Jo
b
A
d
d
r
e
s
s
:
Sh
e
e
t
C
o
n
t
e
n
t
:
May 10, 2026
2026-0165
-
40
0
S
.
B
A
L
D
W
I
N
A
V
E
.
S
P
A
C
E
A
1
6
AR
C
A
D
I
A
,
C
A
.
June 12, 2026
June 23, 2026
By
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
I
N
G
&
C
O
N
S
U
L
T
A
N
T
Te
l
:
(
6
2
6
)
3
2
9
-
1
1
4
1
GENERAL NOTES AUX SYSTEM DEFERRED APPROVAL NOTES
DESIGN BUILD AUXILIARY SYSTEMS ARE UNDER SEPARATE PLAN CHECK AND
PERMIT. SYSTEMS INCLUDE BUT ARE NOT LIMITED TO LIFE SAFETY, FIRE ALARM,
INTRUSION ALARM, CCTV/CATV, TELE/DATA SYSTEMS AND ALL OTHER
REQUIRED AND OPTIONAL SYSTEMS.
1.THE AUXILIARY SYSTEMS VENDOR/CONTRACTOR/DESIGN BUILDER SHALL
PROVIDE THE APPLICATION ENGINEERING, DOCUMENTATION, AND TESTING
REQUIRED TO OBTAIN BUILDING OCCUPANCY PERMIT, LOCAL AND CALIFORNIA
STATE FIRE MARSHALL'S APPROVAL, AND SYSTEM ACCEPTANCE BY
AUTHORITIES HAVING JURISDICTION (AHJ).
2.PROVIDE EQUIPMENT AND DEVICES INDICATED HEREIN AND ON THE DRAWINGS
AND VARIOUS OTHER REQUIRED COMPONENTS.
3.VENDOR SHALL PROVIDE A SYSTEM DIAGRAM INCLUDING RISER DIAGRAMS AND
FLOOR PLANS INDICATING CONDUIT AND WIRE SIZES & QUANTITIES BETWEEN
ALL DEVICES.
4.PROVIDE ALL CONDUITS, WIRES, AND CABLES AS REQUIRED AND AS
RECOMMENDED BY THE MANUFACTURER. INSTALL AND CONNECT ALL SYSTEM
COMPONENTS IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
5.FINAL WIRING TERMINATIONS SHALL BE PERFORMED BY THE CONTRACTOR
HAVING AT LEAST 5 YEARS EXPERIENCE INSTALLING THE SYSTEMS.
6.NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72, 101. CALIFORNIA
BUILDING CODE AND CALIFORNIA FIRE CODE APPLICABLE SUBSECTIONS SHALL
APPLY TO SPECIFIED EQUIPMENT.
7.VENDOR SHALL PROVIDE ALARM DECIBEL/CANDELA CALCULATION, VOLTAGE
DROP, AND BACKUP POWER SUPPLY CAPACITY CALCULATIONS REQUIRED BY
THE AHJ.
8.VENDOR SHALL SUBMIT CATALOG CUTS, TECHNICAL DATA, CONDUCTOR TYPE,
AND DESCRIPTIVE LITERATURE FOR ALL HARDWARE COMPONENTS TO BE
FURNISHED INCLUDING CALIFORNIA STATE FIRE MARSHALL (CSFM) LISTINGS
FOR FIRE ALARM SYSTEMS.
9.VENDOR SHALL SUBMIT CALIBRATION AND TESTS PRIOR TO FINAL
ACCEPTANCE.
10.SHOULD ADDITIONAL DEVICES BE REQUIRED BY THE AHJ FOR THE FINAL
ACCEPTANCE TEST, IT SHALL BE PROVIDED BY THE
VENDOR/CONTRACTOR/DESIGN BUILDER AT NO ADDITIONAL COST.
11. VENDOR/CONTRACTOR OF AUXILIARY SYSTEMS SHALL PROVIDE A MINIMUM 1
YEAR CERTIFICATE OF GUARANTEE FOR LABOR AND MATERIALS,
INSTRUCTIONS, AND MAINTENANCE MANUAL WITH 24 HOUR FACTORY
REPRESENTATIVE SUPPORT HOTLINE. PROVIDE 8 HOURS OF INSTRUCTION
TIME TO SHOW OWNER'S REPRESENTATIVE THE FUNCTION OF THE SYSTEM.
1.METER, SERVICE, AND DISTRIBUTION SECTIONS OF MAIN SWBD TO BE 100% RATED FOR CURRENT
CARRYING AND 100% RATED FOR SHORT CIRCUIT DUTY FOR AVAILABLE FAULT FROM UTILITY. THE
SHOP DRAWING OF THE METERING AND UTILITY INCOMING SECTIONS SHALL BE REVIEWED AND
APPROVED BY THE SERVING UTILITY COMPANY.
2.PANELBOARD SHALL HAVE FLUSHED LOCKABLE DOOR KEY TO MATCH FACILITY MASTER KEY AND ALL
ELECTRICAL CABINETRIES.
3.ALL CIRCUIT BREAKERS ON PANELBOARDS SHALL HAVE PADLOCK OFF DEVICE & ALL CIRCUIT
BREAKERS FEEDING ESSENTIAL LOADS SHALL HAVE LOCK ON DEVICE INDICATED BY (*). THE CIRCUIT
BREAKERS SHALL BE BOLT-ON TYPE RATED TO WITHSTAND AVAILABLE SHORT CIRCUIT CURRENT
(ASCC) AT THE TERMINUS.
4.PROVIDE TOP CONTROL SECTION BEHIND SEPARATE LOCKABLE DOOR FOR MOUNTING TIME SWITCHES,
RELAYS, EMC CONTROL DEVICES, ETC. AS REQUIRED OR AS SHOWN. PROVIDE SHOCK MOUNT FOR ANY
MECHANICALLY HELD ELECTRONICALLY OPERATED CONTACTORS FOR SOUND AND VIBRATION
LIMITATIONS.
5.PROVIDE NAMEPLATE IDENTIFICATION TO BE MOUNTED ABOVE DOOR AND CIRCUIT DIRECTORY
HOLDER FRAMED WITH PLASTIC COVER MOUNTED BEHIND THE DOOR. ADHESIVE TYPE PLASTIC
ENVELOPE ATTACHED BEHIND THE DOOR IS NOT AN ACCEPTABLE TYPE OF DIRECTORY CARD HOLDER.
6.TRANSFORMER SHALL BE ENERGY EFFICIENT TYPE.
7.PROVIDE NEMA-3R ENCLOSURE WITH GASKET LOCKABLE DOOR FOR ALL PANELBOARDS EXPOSED TO
WEATHER. PANELBOARDS LOCATED IN SUNLIGHT SHALL HAVE AMBIENT COMPENSATED
OVERCURRENT DEVICES.
8.PANELBOARD LOCATED IN ANY DAMP LOCATION IN BUILDING SHALL HAVE GASKET DOOR.
9.CIRCUITS INDICATED BY (T) ARE TIMESWITCH & RELAY CONTROLLED.
10.BUILDING STEEL, UFER, COLD WATER PIPE, AND DRIVEN GROUNDING ROD BONDING TO BE UTILIZED
FOR COMPLETE GROUNDING ELECTRODE SYSTEM & SUPPLEMENTS PER CEC 250, GROUNDING. THE
BONDING TO BUILDING NATURAL GAS PIPING MAY BE REQUIRED BY THE AHJ.
11.FOR EXISTING PANELS WITH EXISTING BREAKERS, CONTRACTOR TO VERIFY ALL EXISTING CIRCUITS
FOR EXISTING AREAS THAT ARE TO REMAIN AND IDENTIFY IN PANEL & IN AS-BUILT. MAINTAIN CIRCUIT
CONTINUITY IF THESE CIRCUITS SERVE AREAS THAT ARE TO REMAIN.
12.NEW BREAKERS TO BE INSTALLED IN EXISTING PANEL ARE TO MATCH THE EXISTING PANELBOARD MFG.
& AIC RATING AS INDICATED OR AS REQUIRED.
13.NEW PANELBOARDS IN EXISTING FACILITY SHALL MATCH EXISTING FACILITY SERVICE, DISTRIBUTION
EQUIPMENT MANUFACTURER, AND SHORT CIRCUIT RATING.
14.NEW PANELBOARDS IN EXISTING FACILITY SHALL HAVE LOCKABLE DOOR KEY TO MATCH EXISTING
FACILITY ELECTRICAL MASTER LOCK AND KEY.
1.MAXIMUM AVAILABLE FAULT CURRENT:
SERVING UTILITY COMPANY'S LETTER OR DATA INDICATES THAT THE MAXIMUM AVAILABLE FAULT
CURRENT (MAFC) WILL NOT EXCEED THE VALUE SHOWN ON SINGLE LINE DIAGRAM. THE VALUE
SHOWN AS "MAFC" INCLUDES FACILITY MOTOR CONTRIBUTION.
2.ALL CURRENT CARRYING DEVICES SHALL BE U.L. LISTED, FULLY RATED, AND BRACED TO
WITHSTAND THE MAXIMUM AVAILABLE FAULT CURRENT AT ITS TERMINUS.
3.SERIES/COMBINATION SHORT CIRCUIT RATING MAY BE USED BY THE CONTRACTOR WHEN
OVERCURRENT DEVICE COMBINATIONS ARE LISTED UNDER U.L. 67 STANDARD. INSTALLATION
SHALL COMPLY WITH CALIFORNIA ELECTRICAL CODE (C.E.C.) ARTICLE 110-9, 110-22, AND OTHER
APPLICABLE SECTIONS.
4.APPLICABLE SERIES/COMBINATION RATED EQUIPMENT ENCLOSURES SHALL BE CLEARLY MARKED
"CAUTION - SERIES COMBINATION SYSTEM RATED __ (AS NOTED ON SINGLE LINE DIAGRAM)
AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED." IN COMPLIANCE WITH CEC
SECTION 110-22. END-USE EQUIPMENT SHALL ALSO BE MARKED WITH THE HIGHER SERIES
COMBINATION INTERRUPTING RATING AS PER CEC SECTION 240-83(c).
5.ELECTRICAL SERVICE GEAR:
VENDOR/MANUFACTURER/CONTRACTOR SHALL PROVIDE SHORT CIRCUIT STUDY AND PROTECTIVE
DEVICE COORDINATIONS AS SHOP DRAWING SUBMITTAL FOR REVIEW TO THE ENGINEER OF
RECORD PRIOR TO THE PURCHASE OF ANY ELECTRICAL GEARS FOR THE PROJECT.
THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF PROJECT AND ARE SUBJECT TO THE
APPROVAL OF THE BUILDING DEPARTMENT, FIRE MARSHAL, UTILITY COMPANY AND OTHER AGENCY
AUTHORITIES HAVING JURISDICTION (AHJ). BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK,
THE CONTRACTOR HAS REVIEWED THE PLANS THOROUGHLY, VERIFIED FIELD CONDITIONS, AND
ACCEPTED FULL RESPONSIBILITY OF PLAN CORRECTIONS, CONTINGENCY, AND ASSOCIATED EXTRA
CONSTRUCTION COSTS THAT HAVE BEEN INCLUDED IN THE CONTRACTOR'S BID.
1.ELECTRICAL DRAWINGS, SPECIFICATIONS, AND GENERAL NOTES DESCRIBE THE INTENDED SCOPE OF
WORK. DOCUMENTS SHALL BE USED FOR THE PURPOSE OF BIDDING, BUILDING DEPARTMENT REVIEW,
AND THE SECURING OF NECESSARY CONSTRUCTION PERMITS ONLY. CONTRACTOR SHALL PROVIDE
CONSTRUCTION DRAWINGS AND OBTAIN WRITTEN APPROVAL FROM ALL AUTHORITIES HAVING
JURISDICTION (AHJ) AND UTILITY COMPANIES PRIOR TO THE START OF AFFECTED WORK. ELECTRICAL
INSTALLATION SHALL COMPLY WITH CALIFORNIA ELECTRICAL CODE (LATEST VERSION) ADAPTED BY
THE JURISDICTION AND ANY LOCAL SUPPLEMENTS.
2.CONTRACTOR SHALL PROVIDE CONSTRUCTION AND SHOP DRAWINGS BASED ON THESE DRAWINGS,
SPECIFICATIONS, AND ADDITIONAL DESIGN CRITERIA FURNISHED BY OWNER AND SUBMIT TO
ARCHITECT. CONTRACTOR SHALL SUBMIT ALL DEFERRED APPROVAL CONSTRUCTION DRAWINGS TO
ALL GOVERNMENTAL AGENCIES AND UTILITY COMPANIES HAVING JURISDICTION INCLUDING POLICE
AND FIRE DEPARTMENTS FOR THEIR REVIEW AND APPROVAL OF DRAWINGS FOR CONSTRUCTION.
3.CONTRACTOR'S BID SHALL NOT BE LIMITED TO THE WORK SHOWN ON PLANS AND SPECIFICATIONS. ALL
PREMIUM OVERTIME COSTS, UTILITY CHARGES, COSTS FOR TEMPORARY UTILITY SERVICES,
ALTERATION, DEMOLITION, AND EXTENSION WORKS, PLAN CHECK/INSPECTION FEES, MISCELLANEOUS
CONTINGENCY COSTS, ETC., SHALL BE INCLUDED IN BID. (THE CONTINGENCY COST SHALL NOT BE LESS
THAN 25% OF THE OVERALL ELECTRICAL BID. CONTRACTOR SHALL IDENTIFY THE CONTINGENCY
AMOUNT IN THE BID DOCUMENT.)
4.ALL EQUIPMENT AND DEVICES SHOWN ARE NEW, CONTRACTOR FURNISHED AND INSTALLED, UNLESS
OTHERWISE NOTED. IF CONTRACTOR PROPOSES TO SUBSTITUTE SPECIFIED EQUIPMENT, HE SHALL
SUBMIT HIS REQUEST IN WRITING TO THE OWNER AND ENGINEER FOR CONSIDERATION PRIOR TO THE
BID. ALL SUBSTITUTIONS MUST BE REVIEWED BY THE ENGINEER. SUCH REVIEWS SHALL NOT RELIEVE
THE CONTRACTOR FROM COMPLYING WITH DRAWING REQUIREMENTS AND SPECIFICATIONS. THE
CONTRACTOR SHALL BE RESPONSIBLE AT HIS OWN EXPENSE FOR ANY CHANGES RESULTING FROM HIS
PROPOSED SUBSTITUTIONS WHICH AFFECT OTHER PARTS OF HIS WORK OR THE WORK OF OTHER
CONTRACTORS.
5.ELECTRICAL DRAWINGS, CONDUIT RUNS, WIRING, AND ELECTRICAL INFORMATION ARE DIAGRAMMATIC
ONLY. DO NOT SCALE THE ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR
OUTLETS. ALL RECEPTACLE AND OUTLET MOUNTING HEIGHTS AND EXACT LOCATIONS SHALL BE
COORDINATED WITH ARCHITECTURAL DRAWING ELEVATIONS PRIOR TO ROUGH-IN WORK.
6.REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF ALL LIGHTING
FIXTURES, CEILING MOUNTED OUTLETS, AND EQUIPMENT. PORTIONS OF CEILING SYSTEMS MAY BE
INACCESSIBLE. CONTRACTOR SHALL STRATEGICALLY LOCATE ACCESS BOXES, ETC., WHICH SHALL BE
READILY ACCESSIBLE IN COMPLIANCE WITH CEC ARTICLE 100. ALL LIGHTING FIXTURE WIRING,
BALLASTS, J-BOXES, ETC., SHALL BE ACCESSIBLE FROM FIXTURE OPENINGS. PROVIDE AN ADDITIONAL
JUNCTION BOX (SIZE AS REQUIRED) WHERE THE NUMBER OF CONDUCTORS EXCEEDS THE MAXIMUM
ALLOWED FOR A GIVEN JUNCTION POINT OR OUTLET.
7.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TYPES OF CEILING SYSTEMS AND TO
FURNISH APPROVED LIGHTING FIXTURES OF THE REQUIRED TYPE FOR MOUNTING IN CEILINGS.
FIXTURES SHALL BE COMPLETED WITH NECESSARY MOUNTING HARDWARE AND ACCESSORIES.
FIXTURES LOCATED IN DAMP OR WET LOCATIONS SHALL BE LABELED FOR USE IN SUCH LOCATIONS.
8.SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, FLOORS, ETC., TO MAINTAIN FIRE
RATING. FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR ALL EQUIPMENT PENETRATING INTO
FIRE RATED ENVELOPES, SPACES, ETC. ALL RECESSED LIGHTING FIXTURES, PANELBOARDS, SWITCHES,
ETC., MOUNTED IN FIRE RATED STRUCTURES SHALL BE ENCLOSED WITH AN APPROVED ENCLOSURE
CARRYING THE SAME FIRE RATING AS THAT OF THE STRUCTURE.
9.ALL WIRING AND ELECTRICAL EQUIPMENT INSTALLED FOR MECHANICAL AND PLUMBING EQUIPMENT
SHALL BE IN ACCORDANCE WITH DIVISION 15 AND ASSOCIATED DRAWINGS. CONTRACTOR SHALL
OBTAIN THE REQUIRED MECHANICAL AND PLUMBING DRAWINGS AND PROVIDE ALL EQUIPMENT,
RACEWAYS, WIRING, ETC., AS INDICATED THEREON.
10.ALL FINAL CONNECTIONS TO OWNER FURNISHED EQUIPMENT SHALL BE MADE BY THE CONTRACTOR
UNLESS OTHERWISE NOTED. VERIFY ELECTRICAL CHARACTERISTICS AND U.L. LISTINGS PRIOR TO
CONNECTION. CONTRACTOR SHALL VERIFY THE LOAD INPUT VOLTAGE OF ALL EQUIPMENT PRIOR TO
INSTALLATION. ACCEPTING ANY EQUIPMENT RESULTING IN LOAD INCREASE SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
11.ELECTRICAL OUTLETS ON OPPOSITE SIDES OF FIRE RATED WALLS AND PARTITIONS MUST BE
SEPARATED BY A DISTANCE OF 24 IN. HORIZONTALLY, IN ACCORDANCE WITH C.B.C. SEC. 714.3.2.
EXCEPTION 1.1. OPENINGS IN FIRE RATED WALLS GREATER THAN 16 SQ. IN. MUST BE FIRE STOPPED.
12.ALL CONDUCTORS AND CURRENT CARRYING DEVICES SHALL BE COPPER DUAL RATED THHN/THWN 600
VOLT 75°C MINIMUM INSULATION UNLESS OTHERWISE NOTED. ALUMINUM, WHERE NOTED, SHALL BE
DUAL RATED THHN/THWN 600 VOLT 75°C MINIMUM INSULATION. USE PROPER TEMPERATURE RATING OF
CONDUCTORS BASED ON THE AMBIENT AIR OR SOIL TEMPERATURE WHERE CONDUCTORS ARE BEING
USED. HIGHER AMPACITY CONDUCTORS AND LARGER RACEWAYS SHALL BE PROVIDED TO OFFSET THE
AMPACITY CORRECTION FACTORS AS INDICATED IN CEC TABLE 310 AND ELSEWHERE IN CODE. ALL
BUSSING SHALL BE COPPER. NMC CABLE MAY BE USED WITHIN THE DWELLING TYPE OCCUPANCY PER
CEC 334.10 IF APPROVED BY AHJ.
13.DO ALL DRILLING, CUTTING, CHANNELING AS REQUIRED TO ELECTRICAL WORK AND AS INDICATED OR
SPECIFIED HEREIN. ALL HOLES, CURBS, ETC., IN FLOORS, CEILINGS, AND WALLS SHALL BE PATCHED,
UNLESS OTHERWISE NOTED. PAINT ALL EXPOSED ELECTRICAL RACEWAYS, CABINETS, ENCLOSURES,
AND FITTINGS TO MATCH COLOR OF ADJACENT SURFACES IN FINISHED AREAS.
14.EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE PROVIDED PER C.B.C. AND SHALL BE DESIGNED TO
PROVIDE REQUIRED FOOTCANDLES AND LUMENS. PROVIDE ADDITIONAL EMERGENCY ILLUMINATION AS
REQUIRED BY INSPECTION AUTHORITIES HAVING JURISDICTION.
15.ALL ELECTRICAL EQUIPMENT SHALL BE BRACED OR ANCHORED TO RESIST A HORIZONTAL FORCE
ACTING IN ANY DIRECTION USING THE SMACNA CRITERIA.
16.BRANCH CONTROL CIRCUITING AND WIRE COUNTS MAY NOT BE INDICATED ON PLANS. CONTRACTOR IS
RESPONSIBLE FOR COMPLETING BRANCH CIRCUIT WIRING IN ACCORDANCE WITH PLAN NOTES AND AS
PERMITTED BY AHJ. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS AS PART OF RECORD TO
ARCHITECT AND AUTHORITY HAVING JURISDICTION (AHJ).
17.ALL EXISTING UTILITIES OR STRUCTURES REPORTED BY THE OWNER OR OTHERS AND THOSE SHOWN
ON THESE DRAWINGS ARE INDICATED WITH THEIR APPROXIMATE LOCATION AND EXTENT. BY
ACCEPTING THESE PLANS OR PROCEEDING WITH IMPROVEMENTS THE CONTRACTOR IS REQUIRED TO
TAKE DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OR STRUCTURES SHOWN AND ANY
OTHER UTILITIES OR STRUCTURES FOUND AT THE SITE. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO NOTIFY THE OWNERS OF THE UTILITIES OR STRUCTURES CONCERNED BEFORE
STARTING WORK.
18.COORDINATE ALL PHASES OF CONSTRUCTION AND OBTAIN APPROVAL OF WORK SCHEDULE,
SHUTDOWN, CUTOVER, OVERTIME WORK, ETC. WITH BUILDING ENGINEER OR OWNER. PROVIDE
TEMPORARY SERVICE, STANDBY GENERATOR, 24 HOURS FIRE WATCH, ETC. AS REQUIRED TO MAINTAIN
UNINTERRUPTED FACILITY OPERATION DURING CONSTRUCTION WORK.
19.THE CONTRACTOR AGREES THAT, IN ACCORDANCE WITH GENERAL CONSTRUCTION PRACTICES, THE
CONTRACTOR WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE
CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT AT ALL TIMES. CONTRACTOR
FURTHER AGREES TO DEFEND, INDEMNIFY, AND HOLD OWNER AND ENGINEER HARMLESS FROM ANY
AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH PERFORMANCE OF WORK ON THIS
PROJECT.
CODE REFERENCE
THE GOVERNING CODES FOR THIS PROJECT ARE:
2025 CALIFORNIA BUILDING CODE (CBC)
2025 CALIFORNIA ELECTRICAL CODE (CEC)
2025 CALIFORNIA MECHANICAL CODE (CMC)
2025 CALIFORNIA PLUMBING CODE (CPC)
2025 CALIFORNIA ENERGY CODE (CEES)
PANELBOARD AND SWITCHBOARD NOTES
NOTICE
SHORT CIRCUIT COMPLIANCE NOTES
CONTRIBUTION.
AVAILABLE SHORT CIRCUIT CURRENT, CALCULATED.
MAXIMUM SHORT CIRCUIT CURRENT FROM UTILITY AND INCLUDES FACILITY MOTORMAFC
ASCC
+48"
GFI
UON
E
WP.
NL
SYMBOLS
SINGLE RECEPTACLE 20A GROUNDING TYPE,115V +18" AFF OR AS NOTED.
DUPLEX RECEPTACLE 20A GROUNDING TYPE,115V +18" AFF OR AS NOTED.
1/2HOT / 1/2 SWITCHED RECEPTACLE WITH JUMPER REMOVED, +18" AFF OR AS NOTED.
DOUBLE DUPLEX RECEPTACLE 20A GROUNDING TYPE, 115V, +18" AFF OR AS NOTED.
TELEPHONE OUTLET WITH 3/4" CONDUIT TO TELEPHONE BACKBOARD, +18" AFF OR AS NOTED.
DATA OUTLET WITH 3/4" CONDUIT TO DATA TERMINAL, +18" AFF OR AS NOTED.
CONDUIT TO TEL BACKBOARD, +18" AFF OR AS NOTED.
DATA OUTLET WITH 3/4" CONDUIT TO DATA TERMINAL AND TELEPHONE OUTLET WITH 3/4"
CEILING MOUNTED DUPLEX RECEPTACLE, 20A GROUNDING TYPE
FLOOR TYPE DUPLEX RECEPTACLE 20A GROUNDING TYPE
AUTOMATIC CARBON MONOXIDE-SENSING DEVICES
CLOSED CIRCUIT TELEVISION ANTENNA OUTLET
SMOKE DETECTOR
MOTOR OR CEILING EXHAUST FAN
JUNCTION BOX TO SUIT THE FIELD CONDITIONS
TV
CO
SD
J
B NOTES:
PUSHBUTTON OPERATOR FOR ELECTRIC DOOR
DISCONNECT SWITCH WITH MAGNETIC STARTER. FUSE SIZE AS SHOWN.
DISCONNECT SWITCH, FUSE SIZE AS SHOWN.
SWITCH AND FUSES
EMERGENCY CIRCUIT. LOCK ON DEVICE FOR BREAKER SERVING
BREAKER
TRANSFORMER WITH COPPER WINDINGS
WATT/HOUR METER SOCKET
CURRENT TRANSFORMER
SWITCHBOARD WITH COPPER BUSSING
PANELBOARD WITH COPPER BUSSING
TELEPHONE CABINET WITH BACK BOARD
M
T
CONDUIT HOME RUN TO SOURCE INDICATING PANEL "A" CIRCUITS #1, 3 & 5
GARAGE GATE SWITCH
C NOTES:
A-1,3,5
HASH MARKS INDICATE QUANTITY OF CURRENT CARRYING AND NEUTRAL CONDUCTORS.
CONDUIT RUN BELOW FLOORS OR IN GRADE
CONDUIT RUN CONCEALED IN CEILING SPACE OR IN WALL
TABLE 1, CHAPTER 9 OF C.E.C. AMD TABLE 3A AND 3B SHALL DETERMINE THE CONDUIT
TELEVISION ANTENNA CABLES IN 1" CONDUIT MININUM.
DATA/COMMUNICATION CABLES IN 3/4" CONDUIT MINIMUM.
NO HASH MARK INDICATES 2 CONDUCTORS. ALL CONDUITS PROVIDED W/ GROUND WIRE.
U.O.N. (#10 INDICATES #10 AWG. CONDUCTORS) SIZE OF CONDUIT SHALL BE BASED ON
#10
20 AMP MECHANICALLY HELD (TWO WIRES CONTROL) RELAY CONTROLLING CKT.
TELEPHONE CABLES IN 3/4" CONDUIT MINIMUM.T
TV
D
D NOTES:
INDICATED WITH PROGRAMMABLE TIME SWITCH CONTROLLING COIL. ASSIGN CONTROL
CHANNEL AND DURATION.
NIGHT LIGHT CONTROLLED BY TIME SWITCH DUSK TO DAWN EXTERIOR SECURITY LIGHT
GROUND FAULT CIRCUIT INTERRUPTER, ALSO INDICATED AS GFCI
UNLESS OTHERWISE NOTED
EXISTING, ALSO INDICATED AS (E)
WEATHERPROOF
INDICATES MOUNTING HEIGHT FROM FINISHED FLOOR TO CENTER OF DEVICE
SYMBOLS AND NOTES
CIRCUIT
DESCRIPTION
GFCI CONVENIENCE OUTLET, 20A GROUNDING TYPE, 115V, +18" AFF OR AS NOTED.
AUTHORITY HAVING JURISDICTIONAHJ
C
MOTOR RATED SWITCH H.P. RATED$M
SIZES. MINIMUM CONDUIT SIZE SHALL BE 3/4", MINIMUM CONDUCTOR SIZE TO BE #12.
SINGLE RECEPTACLE, VERIFY EXACT NEMA CONFIGURATION WITH VENDOR OF EQUIPMENT.
+18" AFF OR AS NOTED.
WR.WEATHER RESISTANCE
1. ALL CONDUIT SHALL BE RIGID STEEL OR EMT. FLEXIBLE CONDUIT SHALL BE LIMITED TO
72" FOR FINAL CONNECTION TO LIGHTING FIXTURES OR MOTORS, INCLUDING GROUNDING
CONDUCTOR. P.V.C. CONDUIT MAY BE USED ONLY FOR UNDERGROUND, RE-SIZE
CONDUIT AS REQUIRED TO INCLUDE GROUNDING CONDUCTOR. MININUM CONDUIT STRAP
USE TWO (2) HOLE TYPE.
2. TELEPHONE AND TELEVISION CABLES MAY BE PREWIRED BY LOCAL TEL/COMM/CABLE T.V.
COMPANY WITHOUT CONDUIT.
1. BREAKERS, SWITCHES, FUSES, METER SOCKETS, AND CURRENT CARRYING DEVICES
SHALL BE DESIGNED TO WITHSTAND MAXIMUM AVAILABLE FAULT CURRENT (AFC)
ESTABLISHED BY SERVING UTILITY.
2. SWITCHBOARDS AND PANELBOARDS BUSSING SHALL BE TIN PLATED COPPER BRACED
TO WITH STAND MAXIMUM AVAILABLE FAULT. TRANSFORMER SHALL BE ENERGY
SAVING TYPE WITH COPPER WINDING.
1. SUBSCRIPT LETTER NEXT TO THE ABOVE SYMBOLS INDICATES DEVICE CONTROLLED.
2. DEVICES AND COVER PLATE COLOR AS SELECTED BY ARCHITECT, SEE
ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF OUTLET, UNLESS NOTED.
3. CONVENICE RECEPTACLES IN BATHROOM, LAUNDRY ROOM, AND KITCHEN WITHIN 6 FT
FROM SINK AND EXTERIOR LOCATIONS SHALL BE GROUND FAULT TYPE (GFCI)
4. TAMPER-RESISTANT RECEPTACLES SHALL BE INSTALLED IN DWELLING UNIITS, CUEST
ROOMS OF HOTELS AND MOTELS, AND CHILD CARE FACILITIES.
ALUMINUMAL
COPPERCU
(E)
100A
3P
M
(E) PNL
"HP"
(E) 480/277V 3Ø 4W MAIN
SWITCHBOARD, FIELD VERIFY.
(E)
(E)
EXISTING SINGLE LINE DIAGRAM
N.T.S.
GND
(E)
(E) PNL
"LP"
(E)
(E)
(E) 100A-3P
(E) 50A-3P
(E) 100A-3P
(FOR REFERENCE ONLY, NO CHANGE)
(E) 480V TO 208Y/120V
30KVA TRANSFORMER
JEWELRY STORE T.I. IN EXISTING MALL, PROVIDE
POWER FOR RECEPTACLES, LIGHTING, & T24.
SCOPE OF WORK
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-1
ELEC NOTES, LEGEND, SINGLE LINE
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:25 PM
V.I.F
.(E
)
C
O
L
.
V.I
.
F
.
(E
)
C
O
L
.
V.I.F.
(E) COL.
S
541 LB.
SAFE
541 LB.
SAFE 1,616 LB.
SAFECABINET
CO
U
N
T
E
R
T
O
P
POWER PLAN
SCALE:1/4"=1'-0"
(E) PNL "LP"
(E) PNL "HP"
J
+48"
+48"
+42"
(E) 480V TO 208Y/120V
30KVA TRANSFORMER
(ON PLATFORM ABOVE RESTROOM)
LP-5
(E)
CONTRACTOR TO PROVIDE LABEL ON EACH OUTLET AND DISCONNECT
MEANS INDICATING THE POWER SOURCE PANEL AND CIRCUIT
NUMBER.
GENERAL NOTES:
0.1
PROPOSED SECURITY CCTV
CAMERA CONTROLLER &
INTRUSION ALARM PNL WITH 24
HRS BATTERY BACKUP
LP-7
J$1
LP-1
2
LP-27
CONNECT TO ROLLING DOOR OPERATOR. COORDINATE WITH
MANUFACTURER RECOMMENDATIONS AND REQUIREMENTS.
OUTLET SWITCH BANK FOR RETAIL OUTLETS, INCLUDE $a, $b, $c, $d,
$e, $f
PROVIDE AUTOMATIC TIME SWITCH FOR OUTLET CONTROL, VERIFY
REQUIREMENTS WITH OWNER.
1"C UNDERGROUND CONDUITS FOR POWER AND 1"C UNDERGROUND
CONDUITS FOR TELE/DATA, CUT AND PATCH FLOOR AS REQUIRED.
CONDUITS AND WIRING RUN WITHIN CASE WORK OR LOW WALL.
COORDINATE WITH MANUFACTURER OR ARCHITECT. PROVIDE 3/4"
CONDUIT TO ACCESSIBLE CEILING SPACE FOR TEL/DATA.
EXISTING LIGHT & RECEPTACLE IN ATTIC TO REMAIN.
KEY NOTES:
1
2
3
4
LP-11 via $a
LP-13
LP-29 VIA $b
LP-17 VIA $c
LP-19 VIA $d
LP-21 VIA $e
LP-23 VIA $f
LP-8
LP-6
3
3
LP-25
3
3
3
3
4
4
5
5
6
6
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-2
POWER PLAN
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:26 PM
L0
6
L01
L01
L01
L02
L02
L02
L02
L02
L05
L05
L0
5
L05
L0
5
L0
5
L05
L0
5
L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05
L0
5
L05
L0
5
L05
L05
L05
L05
L05
L01
L01
L01
L03 L03
L02 L02 L02 L02 L02 L02 L02 L02
L03 L03
L02 L02
L01
L01
L02 L02
S
SL02L02L02
L03 L03
S
L02
L02
L02
L02
L02
L02
L02
L02
L02
L02
S
A/C
A/C
A/C
A/C
A/C
L05L05
(E)
E
X
I
T
(E) BULKHEAD
SOFFIT
C.H. +9'-10"
(E) STOREFRONT
SOFFIT
C.H. +9'-10"
EX
I
T
C.H. +10'-10"
(E) T-BAR CEILING
C.H. +11'-6"C.H. +10'-0"
(N) T-BAR CEILING
C.H. +9'-0"
(E) DRYWALL CEILING
A/C
A/C
A/C
A/C
A/C
A/C
L02L02
L02L02L02
L02L02L02
L02L02
L02L02
L02L02
C.H. +11'-6"
C.H. +10'-10"
C.H. +10'-10"
(E) T-BAR CEILING
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
C.H. +11'-6"
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
LIGHTING PLAN
SCALE:1/4"=1'-0"
(E) PNL "LP"
(E) PNL "HP"
L01
LIGHTING FIXTURE SCHEDULE
TYPE SYMBOL MANUFACTURER & MODELWATTDESCRIPTIONLAMP
TYPE NO.VOLT MOUNTING
NOTE: LIGHTING FIXTURE MANUFACTURER & MODEL IS FOR
REFERENCE ONLY. FIXTURE SHALL BE SELECTED BY ARCHITECT.
POWER AND QUALITY SHALL BE SPECIFICATION GRADE
LED 8W--3" DOWN LIGHT "ELITE LIGHTING"
RL372
CEILING
RECESSED120V
LC
$
$
$
3
4
$D
$D3
PC
OS
MS
RP
D
SINGLE POLE TOGGLE SWITCH, 36"-48" A.F.F.
THREE WAY SWITCH 20 AMP, 36"-48" A.F.F.
FOUR WAY SWITCH 20 AMP, 36"-48" A.F.F.
DIMMER SWITCH, SWITCH TYPE TO CORRESPOND WITH CONNECTED
FIXTURES, 36"-48" A.F.F.
THREE WAY DIMMER SWITCH, 36"-48" A.F.F.
0-2 HR. MANUAL BY-PASS TIMER FOR LTG.,ZONE CONTROL. PROVIDE
AS REQUIRED BY CEC FOR ELECTRIC METERED SPACE OF GREATER
THAN 5000 S.F.
OCCUPANCY SENSOR, PROVIDE DEVICES SENSING ENTIRE ENCLOSED
AREA WHERE THE DEVICES ARE LOCATED OR FIXTURES / AREA AS
SHOWN ON LIGHTING PLAN
MOTION SENSOR, PROVIDE DEVICES SENSING ENTIRE ENCLOSED
AREA WHERE THE DEVICES ARE LOCATED OR FIXTURES / AREA AS
SHOWN ON LIGHTING PLAN
PHOTOCELL / DAYLIGHT SENSOR
CONTROL RELAY PACK FOR LIGHTING / RECEPTACLES
AUTOMATIC TIME SWITCH FOR LIGHTING CONTROL.
DEMAND RESPONSE FOR LIGHTING CONTROL.
CONTROL DEVICES LEGEND:LIGHTING NOTES AND LEGENDS:
EM EMERGENCY LIGHT WITH 90 MINUTE BATTERY BACKUP OR UNIT
MOUNTED EMERGENCY INVERTER. PROVIDE UNSWITCHED HOT WIRE
AS NOTED.
THE LIGHTING PLAN IS LIMITED TO PROVIDING CODE COMPLIANCE AND
LIGHTING FIXTURE POWER SUPPLIES. CONTRACTOR TO OBTAIN
LIGHTING CONTROL LAYOUT FROM MANUFACTURER FOR ALL
REQUIRED DEVICES & WIRING. INCLUDE ALL EXTENDED WORK IN
BIDDING.
PROVIDE 6' OF FLEX METAL WIRE FROM LIGHTING FIXTURE TO J-BOX
ABOVE FIXTURE.
PROVIDE 90 MINUTES BATTERY BACKUP FOR EXIT SIGN. PROVIDE LOW
LEVEL EXIT SIGN AS REQUIRED BY FIRE DEPARTMENT OR C.B.C. 1011.6
& 1011.7
FIXTURE SHALL HAVE MINIMUM 60 LUMENS/WATT EFFICIENCY, AND
BALLAST AND LAMP SHALL BE ENERGY SAVING TYPE U.O.N.
VERIFY WITH OWNER OR ARCHITECT FOR NIGHT LIGHT REQUIREMENT.
LIGHTING SWITCH TO BE 36"-48" A.F.F. U.O.N..
RUN LIGHTING CIRCUITS THROUGH CONTROL DEVICES. PROVIDE
UNCONTROLLED HOT WIRE FOR EXIT SIGN, EMERGENCY LIGHT, AND
LIGHTING CONTROL DEVICES.
EXISTING POWER FOR SIGN TO REMAIN, FIELD VERIFY.
DISCONNECT & J-BOX FOR SIGN. PROVIDE DEDICATED NEUTRAL FOR
ALL SIGNS. FIELD VERIFY J-BOX/SIGN LOCATION AND REQUIREMENTS
WITH OWNER.
EXISTING EXHAUST FAN TO REMAIN, FIELD VERIFY. CONNECT TO
RESTROOM LIGHTING CIRCUIT.
0.1
0.2
0.3
0.4
0.5
0.6
1
2
J$
LIGHTING CONTROL PER APPLICATION
RETAIL
MA
N
U
A
L
S
W
I
T
C
H
(O
N
/
O
F
F
O
R
D
I
M
M
I
N
G
)
RE
M
O
T
E
S
W
I
T
C
H
W
I
T
H
AN
N
U
N
C
I
A
T
I
O
N
TI
M
E
C
L
O
C
K
&
OV
E
R
R
I
D
E
S
W
I
T
C
H
OC
C
U
P
A
N
C
Y
S
E
N
S
O
R
FU
L
L
O
F
F
OC
C
U
P
A
N
C
Y
S
E
N
S
O
R
PA
R
T
I
A
L
O
F
F
DA
Y
L
I
G
H
T
S
E
N
S
O
R
ON
/
O
F
F
DA
Y
L
I
G
H
T
S
E
N
S
O
R
DI
M
M
I
N
G
RE
C
E
P
T
A
C
L
E
C
O
N
T
R
O
L
TI
M
E
C
L
O
C
K
(
H
O
L
I
D
A
Y
O
F
F
)
&
O
V
E
R
R
I
D
E
S
W
I
T
C
H
PH
O
T
O
C
O
N
T
R
O
L
TI
M
E
C
L
O
C
K
AS
T
R
O
N
O
M
I
C
A
L
T
I
M
E
SW
I
T
C
H
MO
T
I
O
N
S
E
N
S
O
R
SPACE / LIGHTING TYPE CONTROL TYPE
INDOOR OUTDOOR
X X
RESTROOM X X
VA
C
A
N
C
Y
S
E
N
S
O
R
MA
N
U
A
L
S
W
I
T
C
H
(O
N
/
O
F
F
)
DE
M
A
N
D
R
E
S
P
O
N
S
E
CA
R
D
K
E
Y
C
O
N
T
R
O
L
/
AU
T
O
M
A
T
I
C
V
A
C
A
N
C
Y
O
F
F
OFFICE X X
X
L03
L02
L05
L01
L02 LED 15W--4" FIRE RATED DOWN LIGHT "ELITE LIGHTING"
FS-RL441
CEILING
RECESSED120V
L03 LED 8W--3" GIMBAL DOWN LIGHT "ELITE LIGHTING"
RL373
CEILING
RECESSED120V
L05 LED 9W--4" GIMBAL DOWN LIGHT "ELITE LIGHTING"
RL473
CEILING
RECESSED120V
J$
J$
INTERIOR SIGN X
$b
$Da
$Dc
LC
LP-9
LP-15
9a
OS
9b
9b
9a 9a 9a
9a9a9a
9a
9a9a
9a
9
9c
9c
9c
9c
15f
15f
15e 15e
15e15e
15e
15e
15e
15e 15e 15e 15e 15e 15e 15e 15e
15e 15e 15e 15e
15e15e
15e
15e
15e
15e
15e
15e
15e
15e
15e
15e
15e
15e
15g 15g 15g 15g 15g 15g 15g 15g 15g 15g 15g 15g
15g
15g
15g
15g
15g
15g
15g
15
15g
15g
15g
15g
15g
15g
15g
15g
15g
$h
15h
1
1
2
2
$De
$f
$Dg
LP-10
3
3
1
LED 5W--EXIT SIGN W/ 90 MIN.
BATTERY BACKUP SURFACE120V "LITHONIA LIGHTING"
EDG 1 R ELA
LED 5W--EMERGENCY LTG W/ 90 MIN.BATTERY BACK-UP SURFACE120V "LITHONIA LIGHTING"
EML4LB
15
9
15
9a9a
4
4
15e
15e
15e
15g
9a9a
9a
9b
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-3
LIGHTING PLAN
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:28 PM
T24 2025 COMPLIANT SEQUENCE OF OPERATION:
1. AUTOMATIC SHUTT-OFF VIA ASTRONOMICAL TIME CLOCK CONTROLS (AT THE FRESCO TOUCHSCREEN) WITH
2-HOUR BLINK WARNING .
2. MANUAL OVERRIDE OF THE LIGHTING LOAD IS PROVIDED BY THE FRESCO TOUCHSCREEN SWITCH LOCATED AT
THE BACK OF HOUSE.
SYSTEM NOTES
1. nLIGHT PHASE DIMMER CAPACITY FOR nSP5 PCD ELV 120 IS 475W@120VAC.
2. MINIMUM LOAD PER PHASE DIMMER IS 7W.
3. nLIGHT 0-10VDC nPP16 D IS FULLY RATED AT 16A @120VAC/277VAC.
3. SYSTEM STARTUP/PROGRAMMING/TRAINING SHALL BE PERFORMED BY FACTORY
AUTHORIZED TECHNICIAN/REPRESENTATIVE.
4. IF THE FRESCO SYSTEM IS CONNECTED ONLINE TO THE BUILDING LOCAL LAN, THE
AUTHORIZED USER CAN ACCESS LIGHTING CONTROL
SYSTEM DIMMING CHANNELS AND SCENES VIA FRESCO MOBILE APP INSTALLED ONTO
THEIR APPLE IPAD (PROVIDED BY OTHERS/USER).
Lights On
N.T.S.
C.E.C. MANDATORY LIGHTING/OUTLET CONTROL SYSTEM
E-4
A
AUTOMATIC SHUT OFF CONTROL:
ALL INTERIOR LIGHTS WITHOUT
OCCUPANCY SENSOR CONTROL
SHALL BE CONTROLLED BY TIMER
AND 2-HR OVERRIDE SWITCH
(SEC. 130.1(c))
LIGHTING CONTROL SUPPLIER:
SAM HIN
CONTROLS SPECIALIST
PERFORMANCE LIGHTING SYSTEM
DIRECT: 949-878-9074
EMAIL: SAMH@PERFORMANCELTG.COM
EMAIL:CONTROLS@PERFORMANCELTG.COM
NOTE:
1. LIGHTING CONTROL SYSTEM MANUFACTURER & MODEL IS FOR
REFERENCE ONLY. LIGHTING CONTROL SYSTEM SHALL BE
SELECTED BY OWNER OR ARCHITECT.
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-4
LIGHTING CONTROL, PANEL SCHEDULE
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:30 PM
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-5
ENERGY COMPLIANCE
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:33 PM
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 10, 2026
1 CITY 6/8/26
C.T.
E-6
EMERGENCY PHOTOMETRIC PLAN
0.4 0.8
0.7
1.8
2.1
1.2
1.1
2.3
4.2
2.3
1.9
0.9
1.6
2.1
4.4
1.4
2.3
2.6 3.0
1.9 2.0
0.9
0.3
0.5
0.6
0.5
0.4
3.6
1.1
0.3
0.9
1.6
0.9
0.5
2.1
1.1
0.4
1.3
3.4
1.5
0.7
1.1
0.8
0.9
2.7
1.6
1.5
1.8
1.0
1.1
1.6
4.0
2.6
1.2
0.8
1.3
1.1
0.7
0.2
0.2 0.2
4.8
4.1
A
A
A
A
AA
LUMINAIRE SCHEDULE
Symbol Label Qty File Lumens LLF WattsCatalog Number Description Lamp
A 6 ELM4L.ies 345 1.00 2.5ELM4LELM4L SP640L ONE 3.3-WATT LED
STATISTICS
Description Symbol Avg Max Min Max/Min Avg/Min
Calc Zone #1
Calc Zone #2
1.9 fc 4.8 fc 0.2 fc 24.0:1 9.5:1
1.4 fc 4.1 fc 0.2 fc 20.5:1 7.0:1
EMERGENCY PHOTOMETRIC PLAN
SCALE:1/4"=1'-0"
1
F:\PROJECTS\2026\C2026 - HYC\C26020 (Chow Tai Fook Jewelry Store Arcadia)\C26020 ELEC.dwg, 6/10/2026 4:00:37 PM
AW
M-1
MECHANICAL LEGEND, NOTE, & SCHEDULE
CONDENSATE DRAIN
SMOKE DETECTOR
OVERFLOW DRAIN
S
TYPICAL
DRAWING
DOWN
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
OUTSIDE AIR DUCT
TRANSITION - RECTANGULAR TO RECT-
TRANSITION - RECTANGULAR TO ROUND
ELBOW W/TURNING VANE
LINED DUCT, DUCT SIZE WITH L FOR
RISE IN DIRECTION OF AIRFLOW
DROP IN DIRECTION OF AIRFLOW
DUCT ENCLOSURE IN GYPSUM BOARD FOR
2 HOURS RATING
FLEXIBLE DUCT
SUPPLY AIR DUCT - SECTION
RETURN, EXHAUST, OR OUTSIDE AIR DUCT
ROUND DUCT OR STACK - SECTION
12"X 12" NECK PERFORATED CEILING
6"X 6" PERFORATED CEILING REGISTER,
DIFFUSER, 360 CFM
OAOA
T
150
CD
12X12CD
6X6R
360
150 CFM
-SECTION
THERMOSTAT WITH AUTOMATIC CHANGE-OVER
D D
R R
6X6L (L)SINGLE LINE
ANGULAR
GENERAL NOTES
SINGLE
SYMBOL
DOUBLE
RA
EAD
SA
ABBREVI-
RA
EAD
SA
ATION
LEGEND
& VENTED LOCKABLE CLEAR COVER
1.THE DRAWINGS, SPECIFICATIONS AND GENERAL NOTES DESCRIBE THE
RECOMMENDED SCOPE OF WORK AND THE DOCUMENTS SHALL BE USED FOR THE
PURPOSE OF BIDDING, BUILDINGS DEPARTMENT REVIEW, AND TO SECURE THE
NECESSARY CONSTRUCTION PERMIT ONLY. CONTRACTOR SHALL PROVIDE
CONSTRUCTION DRAWINGS AND OBTAIN WRITTEN APPROVAL OF ALL INSPECTION
AUTHORIZED GOVERNMENTAL AGENCIES AND UTILITY COMPANIES PRIOR TO START
OF AFFECTED WORK.
2.ALL MECHANICAL WORK SHALL COMPLY WITH LOCAL APPLICABLE CODE AND 2025
CALIFORNIA MECHANICAL CODE.
3.COORDINATE ALL MECHANICAL WORK W/ARCHITECTURAL, ELECTRICAL
STRUCTURAL, SUBCONTRACTOR & OTHER TRADES TO AVOID INTERFERENCES.
4.COORDINATE LOCATIONS OF OPENING THROUGH FLOOR, WALL & ROOF
W/ARCHITECTURAL, ELECTRICAL & STRUCTURAL DRAWINGS.
5.SEAL & TAPE ALL OPENINGS IN DUCTWORK AIRTIGHT AFTER TESTING.
6.ALL SIZES FOR DUCT, GRILLE, REGISTER, DIFFUSER & LOUVER SHALL BE IN INCHES.
7.CHECK & VERIFY ALL FIELD CONDITIONS & ACTUAL DIMENSIONS BEFORE PREPARING
SHOP DRAWINGS & BEGINNING INSTALLATION NOTIFY ARCHITECT IMMEDIATELLY OF
AND ALL DISCREPANCIES.
8.TEST & BALANCE ALL EXHAUST SYSTEM ACCORDING TO CFM INDICATED ON PLANS.
9.ALL APPLIANCE AND PLUMBING VENTS SHALL BE AT LEAST TEN (10) FEET IN A
HORIZONTAL DIRECTION, OR THREE (3) FEET ABOVE THE OUTSIDE-AIR INTAKES FOR
HVAC UNITS.
10.MECHANICAL MATERIAL STANDARD SHALL BE LISTED AND LABELING TO COMPLY
WITH TABLE 1701.
11.FACTORY MADE AIR DUCTS SHALL COMPLY WITH REFERENCE STANDARD CHAPTER
17. SUPPORT OF DUCTS, INSTALLER SHALL PROVIDE THE MANUFACTURER'S FIELD
FABRICATION AND INSTALLATION INSTRUCTIONS.
12.MAXIMUM LENGTH OF FLEXIBLE FUCT AND CONNECTORS SHALL NOT BE MORE THAN
5 FEET. FLEXIBLE DUCTS SHALL NOT BE USED IN LIEU OF RIGID ELBOWS.
NO.
EQUIPMENT SCHEDULE
DESCRIPTION
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 9, 2026
H.C.
UNIT APPROX. WEIGHT = 444 LBS
EXISTING SPLIT HEAT PUMP UNIT
"CARRIER" MODEL NO. 38AUQ007
66,500 BTUH ARI RATED COOLING CAPACITY, EER=11.0
66,000 BTUH HEATING CAPACITY, COP=3.3 @ 47°F
ELECTRICAL: 460V-3PH-60HZ
SHP
OUTDOOR TEMPERATURE.
MIN. CIRCUIT AMPACITY = 15.0 AMPS
MAX. OVERCURRENT PROTECTION = 20 AMPS
INSULATED, UNIT SHALL BE INCLUDE PRIMARY DRAIN ,
SECONDARY DRAIN AND MERV13 AIR FILTER.
UNIT SHALL BE HORIZONTAL WITH DRAIN PAN AND FULLY
EXISTING FAN COIL UNITFC
"CARRIER" MODEL 40RUQ007
UNIT SHALL DELIVER 2,300 CFM @ 0.5" ESP
2-1/2 HP FAN MOTOR
MIN. OSA SETTING = 500 CFM
ELECTRICAL: 460V-3Ø-60HZ
UNIT APPROX WEIGHT = 522 LBS
1
1
(EXISTING)
REFRIGERANT: R-410A
SPLIT HEAT PUMP WIRING DIAGRAM
RECOMENDATION
WIRE PER MANUFACTURE'S
AUTO CHANGE OVER
T-STATE WITH FAN &
SYSTEM OFF SWITCH
NOT TO SCALE
BY ELECTRICAL CONTRACTOR
BY MECHANICAL CONTRACTOR
BY ELECTRICAL CONTRACTOR
BY MECHANICAL CONTRACTOR
M
E
24V
SHP
M
FC
M
DISC.E
OR AS SHOWN ON DWG
460V/3Ø
DISC.E
7-DAY TIME CLOCK
E
M
120V/1Ø
POC POINT OF CONNECTION
DN.
DWG
OD
SD
TYP.
OR AS SHOWN ON DWG
460V/3Ø
HVAC FLOOR PLAN
SCALE:1/4"=1'-0"
NOTES:
EXISTING SA / RA MAIN DUCT. FIELD VERIFY EXACT SIZE, & LOCATION.
1
2
3
4
PROPOSED DUCT CONNECT TO EXISTING SA / RA MAIN DUCT. FIELD
VERIFY EXACT SIZE, & CONDITION.
5 EXISTING OSA MAIN DUCT BY LANDLORD. FIELD VERIFY EXACT SIZE, &
6 RELOCATED THERMOSTAT TO BE MOUNTED AT 45" CENTER LINE A.F.F..
EXISTING RESTROOM WITH EXISTING EXHAUST FAN TO REMAIN. FIELD
VERIFY EXACT CONDITION, REPLACE TO NEW IF NECESSARY. MIN. 75
LOCATION.
FIELD VERIFY EXACT CONDITION, REPLACE TO NEW IF NECESSARY.
CFM REQUIRED.
FC
1
SHP
1
7 EXISTING SPLIT HEAT PUMP UNIT ON ROOF TO REMAIN. FIELD VERIFY
EXACT LOCATION, CONDITION, PROVIDER SERVICES TO MAINTAIN
PROPER WORKING CONDITION.
EXISTING FAN COIL UNIT TO REMAIN. FIELD VERIFY EXACT LOCATION,
CONDITION, PROVIDER SERVICES TO MAINTAIN PROPER WORKING
CONDITION. REPLACE TO MERV13 FILTERS AFTER FINAL INSPECTION.
(ON ROOF)
EXISTING 3/4" CONDENSATE DRAIN TO REMAIN.
L0
6
L01
L01
L01
L02
L02
L02
L02
L02
L05
L05
L05
L0
5
L05
L05
L0
5
L0
5
L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05 L05
L05
L0
5
L05
L0
5
L05
L05
L05
L05
L01
L01
L01
L03 L03
L02 L02 L02 L02 L02 L02 L02 L02
L03 L03
L02 L02
L01
L01
L02 L02
S
SL02L02L02
L03 L03
S
L02
L02
L02
L02
L02
L02
L02
L02
L02
L02
S
A/C
A/C
A/C
A/C
A/C
L05L05
(E)
E
X
I
T
(E) BULKHEAD
SOFFIT
(E) STOREFRONT
SOFFIT
EX
I
T
(E) T-BAR CEILING
(N) T-BAR CEILING
(E) DRYWALL CEILING
A/C
A/C
A/C
A/
C
A/
C
A/C
L02L02
L02L02L02
L02L02L02
L02L02
L02L02
L02L02
(E) T-BAR CEILING
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
(E) T-BAR CEILING
(E) PRE-FAB DUCTWORK
200
CFM
4'-0" LINEAR SUPPLY DIFFUSER
3/4" SLOT, 2 SLOT
(TYP. FOR 11, PRICE SDS OR EQUAL)
200
CFM
200
CFM
200
CFM
200
CFM
150
CFM
8"x8" CD
200 CFM
10"x10" RR
200 CFM
200
CFM
175
CFM
175
CFM
200
CFM
200
CFM
4'-0" LINEAR RETURN DIFFUSER
3/4" SLOT, 2 SLOT
(TYP. FOR 8, PRICE SDR OR EQUAL)
200
CFM
200
CFM
200
CFM
200
CFM
150
CFM
150
CFM
150
CFM
150
CFM
200
CFM
(E)22"x14"
(E)22"x14"
P.O.C.P.O.C.
8"Ø 8"Ø 8"Ø 8"Ø 8"Ø 8"Ø
8"Ø
8"Ø
8"Ø
8"Ø
8"Ø
12"Ø14"Ø14"x14"20"x14"18"x14"22"x14"22"x14"
8"Ø
8"Ø
8"Ø
8"Ø
12"Ø12"Ø14"Ø16"x14"
20"x14"8"Ø8"Ø8"Ø
8"Ø
8"Ø
8"Ø
10"Ø
(E) OSA
(E) OSA
(E) OSA
(E)12"Ø (OSA)
1
8"Ø
2
2
3
3
5
5
6
1
7
4
AW
M-2
HVAC PLAN
AREA:
SHEET TITLE:
WESTFIELD SANTA ANITA
SPACE #A16
400 SOUTH BALDWIN AVENUE
ARCADIA, CA 91007
PROJECT NO:
SCALE:
DATE:
DRAWN BY:
REVIEWED BY:
SHEET NO:
TRAYS:
REVISION:
Tel:(909)396-8168, Fax:(909)396-8169, E-mail:hyc@hycengineer.com
660 N. Diamond Bar Blvd., #128, Diamond Bar, California 91765
HYC CONSULTING ENGINEERS, Inc.
C26020
AS SHOWN
June 9, 2026
H.C.