HomeMy WebLinkAbout370 Campus Dr - 2025 - Solar CarportTITLE SHEET A0.0 HOLY ANGELS - SOLAR PROJECT HOLY ANGELS CATHOLIC CHURCH, ARCADIA 370 CAMPUS DRIVE, ARCADIA , CA 91007 CALL 811 DIG ALERT PRIOR TO EXCAVATING: COMPLIANCE WITH GOVERNMENT CODE 4216 IS TO BE FOLLOWED PRIOR TO ANY EXCAVATION TAKING PLACE. SCOPE OF WORK WORK CONSISTS OF INSTALLING (1) PHOTOVOLTAIC (PV) SOLAR POWER ARRAYS OVER AN EXISTING PARKING LOT. SOLAR POWER SYSTEM CONSISTS OF EQUIPMENT, LIGHTING, PV MONITORING AND METERING COMMUNICATIONS AND POWER INTERCONNECT TO THE UTILITY GRID. 2 EV CHARGING STATIONS SHARING (1) DUAL (LEVEL 2) CHARGER (6) EV CAPABLE STALLS TOTAL MODULE COUNT: 184 + 1 FALSE MODULE AT ARRAY A KILOWATTS DC: 101.20 kW TOTAL ARRAYS: 1 DEFERRED SUBMITTALS: 0 SHEET #SHEET TITLE ARCHITECTURAL DRAWINGS A0.0 TITLE SHEET A1.0 SITE & FIRE ACCESS PLAN A1.1 COLUMN PLAN 4 SHEETS ELECTRICAL DRAWINGS E000 ELECTRICAL NOTES E100 ELECTRICAL PV PLAN E200 1-LINE DIAGRAM E201 GROUNDING DIAGRAM E300 ELECTRICAL DETAILS E400 ELECTRICAL PLACARDS E500 LIGHTING PLAN E501 PHOTOMETRIC PLAN E502 TITLE 24 CALCULATIONS 12 SHEETS STRUCTURAL DRAWINGS S100 GENERAL STRUCTURAL NOTES S200 FRAMING PLAN & SCHEDULE S300 SECTION - 5X S500 STEEL DETAILS 5 SHEETS TOTAL:21 SHEETS SHEET INDEX SITE INFORMATION: PROJECT ADDRESS: 370 CAMPUS DRIVE ARCADIA, CA 91007 APN: 5778-012-001 & 2778-012-002 & 5778-012-003 JURISDICTION: CITY OF ARCADIA GOVERNING CODES: CALIFORNIA CODE OF REGULATIONS: 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC) .................... (PART 1, TITLE 24, CCR) 2022 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1, AND 2 (PART 2, TITLE 24, CCR) (2021 EDITION INTERNATIONAL BUILDING CODE WITH 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA ELECTRICAL CODE ...................................... (PART 3, TITLE 24, CCR) (2020 EDITION NATIONAL ELECTRICAL CODE WITH 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA MECHANICAL CODE (CMC) ......................... (PART 4, TITLE 24, CCR) (2021 EDITION IAPMO UNIFORM MECHANICAL CODE WITH 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA PLUMBING CODE (CPC) ........................... (PART 5, TITLE 24, CCR) (2021 EDITION IAPMO UNIFORM PLUMBING CODE WITH 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA ENERGY CODE ......................................... (PART 6, TITLE 24, CCR) (2021 EDITION CALIFORNIA ENERGY COMMISSION BUILDING ENERGY EFFICIENCY STANDARDS) 2022 CALIFORNIA FIRE CODE (CFC) ..................................... (PART 9, TITLE 24, CCR) (2021 EDITION OF INTERNATIONAL FIRE CODE WITH 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA GREEN CODE ....................................... (PART 11, TITLE 24, CCR) 2022 CALIFORNIA REFERENCED STANDARDS CODE ............... (PART 12, TITLE 24, CCR) NFPA 13 - 2022 NFPA 72 - 2022 REFERENCE CODE SECTIONS FOR APPLICABLE STANDARDS: 2022 CBC, CHAPTER 35 2022 CFC, CHAPTER 80 INSPECTIONS: SAFETY DURING CONSTRUCTION TO COMPLY WITH 2022 CFC CHAPTER 33 NOTES: 1) NOTICE TO THE APPLICANT/OWNER/OWNER'S AGENT/ARCHITECT OR ENGINEER OF RECORD: BY USING THIS PERMITTED CONSTRUCTION DRAWINGS FOR CONSTRUCTION.INSTALLATION OF THE WORK SPECIFIED HEREIN, YOU AGREE TO COMPLY WITH THE REQUIREMENTS OF THE COUNTY OF LOS ANGELES FOR SPECIAL INSPECTIONS, STRUCTURAL OBSERVATIONS, CONSTRUCTION MATERIAL TESTING AND OFF-SITE FABRICATION OF BUILDING COMPONENTS, CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS AND AS, REQUIRED BY THE CALIFORNIA CONSTRUCTION CODES. 2) LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS SHALL BE IN ACCORDANCE WITH CFC 906 AND CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19. 3) DURING CONSTRUCTION, AT LEAST ONE EXTINGUISHER SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH STAIRWAY, IN ALL STORAGE AND CONSTRUCTION SHEDS, IN LOCATIONS WHERE FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER CFC SECTION 3315.1. 4) BUILDINGS UNDERGOING CONSTRUCTION, ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC CHAPTER 33. WELDING, CUTTING, AND OTHER HOT WORK SHALL BE IN CONFORMANCE WITH CFC CHAPTER 35. 5) ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC WAY, AN APPROVED SIGN OR MEANS SHALL BE USED TO IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION SHALL CONFORM TO CBC SECTION 501.2. 6) DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5 CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS, OPENINGS OR COMBUSTIBLE ROOF EAVE LINES UNLESS PROTECTED BY AND APPROVED SPRINKLER SYSTEM OR LOCATED IN A TYPE I OR TYPE IIA STRUCTURE SEPARATED BY 10 FEET FROM OTHER STRUCTURES. CONTAINERS LARGER THAN 1 CUBIC YARD SHALL BE OF NON-LIMITED COMBUSTIBLE MATERIALS OR SIMILARLY PROTECTED OR SEPARATED. CFC 304.3. 7) EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE CABINETS, FIRE EXTINGUISHER LOCATIONS, AND STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED BY CURTAINS, MIRRORS, OR OTHER DECORATIVE MATERIAL. 8) THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS PERMITTED IN ANY EGRESS PATHS. SHEET NO.: SHEET TITLE DATE: 02.12.24 REVISION DATENO. A HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 100P 02.12.24 BACKCHECK 07.23.24 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 D100 DATA SHEETS D101 DATA SHEETS S400 FOUNDATION & ANCHORAGE DETAILS E101 ELECTRICAL EV PLAN A1.1 ACCESSIBLE PARKING STANDARDS - EV A1.1 A1.2 B REV B 01.08.25 C C REV C 06.03.25 138'-8 5/8" 37 MODULES 8'-8 3/4"40'-0 5/8"40'-0 1/16"39'-11 3/4"9'-11 1/2" 37 ' - 6 5 / 8 " 5 M O D U L E S 18 ' - 9 1 / 4 " 18 ' - 9 1 / 4 " NO PARKING NO PARKING NOPARKING EV CHA R G I N G ONL Y NO PAR K I N G A HOLY ANGELS SCHOOL HOLY ANGELS CATHOLIC CHURCH HOLY ANGELS CATHOLIC CHURCH (E) PARKING LOT FAIRVIEW AVE HOLLY AVE CAMPUS DR (E) SPORT COURTS (E) SPORTS FIELD(E) GRASS (E) AC PAVING (E) AC PAVING (E) PAVILION (E) PARKING LOT (E) SPORT COURTS PROPE R T Y L I N E PROPERTY L I N E PR O P E R T Y L I N E PR O P E R T Y L I N E 20' ASSUMED LARGE VEHICLE ACCESS 1 A1.1 3- 51 ' - 9 1 / 2 " (E) FH (E) FH 2 E100 (N) TRUNCATED DOMES PER 2/A1.2 PROPERTY L I N E PROPERTY LI N E (N) TRUNC. DOMES PER 2/A1.2 3 A1.1 4 A1.1 10 ' - 0 " M I N STEEL COLUMN SOLAR MODULES STEEL PURLINS STEEL BEAM CONCRETE FOUNDATION SITE PLAN & FIRE ACCESS PLAN A1.0 Scale: 1/16" = 1'-0" (FOR 24X36 SHEETS)2 ARRAY DIMENSIONS Scale: 1" = 40' (FOR 24X36 SHEETS)1 SITE PLAN & FIRE ACCESS PLAN N 20 40 80 Scale: 1/8" = 1'-0" (FOR 24X36 SHEETS)3 ARRAY SECTION 1684 8 16 32 SHEET NO.: SHEET TITLE DATE: 02.12.24 REVISION DATENO. A HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 100P 02.12.24 BACKCHECK 07.23.24 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 NOTE: 1. ALL PARKING IS EXISTING TO REMAIN, NO RESTRIPING IS PROPOSED AS PART OF THE SCOPE OF THE SOLAR INSTALLATION 2. EXISTING FIRE DEPARTMENT ACCESS IS EXISTING TO REMAIN AND NOT IMPEDED BY NEW SOLAR ARRAY STRUCTURE B REV B 01.08.25 C C C REV C 06.03.25 EV CH A R G I N G ON L Y NO PA R K I N G COL. #A-1 COL. #A-2 COL. #A-3 CLCL CL CL CLCL CLCL OU T L I N E O F P R O P O S E D A R R A Y A COL. #A-4 CLCL STEEL COLUMNS TO LAND ON STRIPING BETWEEN HEAD OF PARKING STALL, COLUMNS TO BE FULLY INSIDE EXISTING STRIPING AT CORNERS OF STALLS, AS SHOWN ON PLANS LINE OF FOUNDATION, FLUSH WITH (E) GRADE, SEE SECTION ON A1.0 TYP 1 2 - EV CH A R G I N G ON L Y NO PA R K I N G 7 6 4 TYP 3 TYP 2 5' - 0 " MI N . 12 ' - 0 " M I N . 7' - 1 1 " M I N . 18'-0" MIN. 7' - 1 1 " M I N . 8' - 4 1 / 2 " MI N . 1' - 1 1 / 2 " 1' - 1 1 / 2 " 1' - 1 1 / 2 " 4'-0" MIN. 5 8 22'-1" 9TYP 30"x48" MIN. CLR (N) VAN ACC. EVCS (N) STD. EVCS (N) STD. EVCS (N) STD. EVCS 3' - 0 " 7'-4 1/2"± 3'-0" 7' - 1 1 / 2 " ± COLUMN PLAN A1.1 SHEET NO.: SHEET TITLE DATE: 02.12.24 REVISION DATENO. A HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 100P 02.12.24 BACKCHECK 07.23.24 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 NOTES: 1. ALL PARKING IS EXISTING TO REMAIN, NO RESTRIPING IS PROPOSED AS PART OF THE SCOPE OF THE SOLAR INSTALLATION 2. EXISTING FIRE DEPARTMENT ACCESS IS EXISTING TO REMAIN AND NOT IMPEDED BY NEW SOLAR ARRAY STRUCTURE 3. INSPECTOR TO VERIFY THAT SLOPES AT ACCESSIBLE ROUTE DO NOT EXCEED MAXIMUM 5% RUNNING SLOPE & 2.08% CROSS SLOPE Scale: 1/8" = 1'-0" (FOR 24X36 SHEETS)1 COLUMN PLAN 1684 N Scale: 1/8" = 1'-0" (FOR 24X36 SHEETS)2 ENLARGED EV PLAN 1684 N ACCESSIBLE PARKING AND ACCESSIBLE ROUTE REQUIREMENTS: 1.(N) ACCESSIBLE ROUTE INDICATED BY DOTS: 2.(E) ACCESSIBLE ROUTE INDICATED BY DASHED LINE: 3.(N) & (E) ACCESSIBLE ROUTE REQUIRES: 5% DIRECTIONAL SLOPE MAX. 2.08% CROSS SLOPE MAXIMUM 4. FOR EV DETAILS AND ALL OTHER DIMENSIONS, REFER TO SHEET A1.2 5.EV ACCESSIBLE STALLS AND ACCESS AISLES REQUIRE: 2.08% DIRECTIONAL SLOPE 2.08% CROSS SLOPE MAX Scale: 1/8" = 1'-0" (FOR 24X36 SHEETS)3 ENLARGED PLAN 1684 Scale: 1/8" = 1'-0" (FOR 24X36 SHEETS)4 ENLARGED PLAN 1684 USING TABLE 5.106.5.6.3 EVCS ALTERNATIVE COMPLIANCE (REFER TO SHEET E200 FOR EV CALCULATIONS): TOTAL NUMBER OF ALTERED PARKING SPACES: 26 TOTAL KVA REQUIRED (EVSE & EV CAPABLE): 52.8 KVA PROPOSED NUMBER OF LEVEL 2 EVSE: 4 KVA/EVSE = 16.64 KVA B REV B 01.08.25 C C C C C C REV C 06.03.25 EV CHARGING ONLY12 " LETTERS: 12" HIGH MIN HELVETICA (GREEN OR CONTRASTING COLOR TO PAVEMENT) TYPICAL STRIPING AT ACCESSIBLE EV PARKING STALLS: 4" WIDE GREEN (OR CONTRASTING COLOR TO PAVEMENT) CL CL CL 12'-0" MIN @ EV VAN ACCESSIBLE STALLS 9'-0" MIN @ EV STD ACCESSIBLE STALLS 3' - 0 " SYMBOL: WHITE PAINT BACKGROUND AND LETTERING: GREEN PAINT 3'-0" BORDER: 4" WIDE WHITE PAINT EQ EQ CL CL TYPICAL STRIPING AT STANDARD EV PARKING STALLS: 4" WIDE GREEN (OR CONTRASTING COLOR TO PAVEMENT) SIGN AND IDENTIFICATION 1.CHARACTERS AND SYMBOLS SHALL BE WHITE ON GREEN BACKGROUND. 12" 18 " IN C I R C U L A T I O N P A T H 8 0 " U . O . N . 6" 36 " 12" DIA. TORX SCREWS (TYP.) REFLECTIVE ALUMINUM SIGN WITH BEADED TEXT MIN. 1" CHARACTERS WHEN MOUNTED LESS THAN 70" OR MIN. 2" CHARACTERS WHEN MOUNTED HIGHER THAN 70" 1 1/2" SQ. GALV. STL. UNISTRUT SET IN CONC. FTG. SLEEVED & BOLTED. 30 " NOTES: 1. FTG. CONCRETE - F'c = 2,500 PSI CONC. WALK OR AC PAVING ELECTRIC ONLY VEHICLE 60 " M I N . U . O . N . LETTERING SYMBOL AND BORDER SHALL BE REFLECTORIZED WHITE ON A GREEN BACKGROUND. 46 " M A X 15 " M I N . GROUND PLAN ELEVATION 1. PER 11B-302.1 FLOOR AND GROUND SURFACES SHALL BE STABLE, FIRM AND SLIP RESISTANT. 2. PER 11B-308.3.1 PROVIDE A CLEAR GROUND SPACE THAT ALLOWS A PARALLEL APPROACH TO THE EV CHARGER WITH THE SIDE REACH IS UNOBSTRUCTED.. 2' - 6 " 4'-0" PER 11B-309.4 OPERATION OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. EXCEPTION: ELECTRIC VEHICLE CONNECTORS SHALL NOT BE REQUIRED TO PROVIDE OPERABLE PARTS THAT HAVE AN ACTIVATING FORCE OF 5 POUNDS (22.2 N) MAXIMUM. PER 11B-812.4 VEHICLE SPACES, ACCESS AISLES SERVING THEM, AND VEHICULAR ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES (2489 MM) MIN. WHERE PROVIDED, OVERHEAD CABLE MANAGEMENT SYSTEMS SHALL NOT OBSTRUCT REQUIRED VERTICAL CLEARANCE. PER 11B-707.7.2 CHARACTERS DISPLAYED ON THE SCREEN SHALL BE IN A SANS SERIF FONT. CHARACTERS SHALL BE 3/ 16 INCH (4.8 MM) HIGH MIN. BASED ON THE UPPERCASE LETTER "I". CHARACTERS SHALL CONTRAST WITH THEIR BACKGROUND WITH EITHER LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. EV CHARGING * POINT-OF-SALE SYSTEMS PER 11B-707.9.1.1 A TACTILELY DISCERNIBLE NUMERICAL KEYPAD SIMILAR TO A TELEPHONE KEYPAD CONTAINING A RAISED DOT WITH A DOT BASE DIAMETER BETWEEN 1.5 MM AND 1.6 MM AND A HEIGHT BETWEEN 0.6 MM AND 0.9 MM ON THE NUMBER 5 KEY THAT ENABLES A VISUALLY IMPAIRED PERSON TO ENTER HIS OR HER OWN PERSONAL IDENTIFICATION NUMBER OR ANY OTHER PERSONAL INFORMATION NECESSARY TO PROCESS THE TRANSACTION IN A MANNER THAT PROVIDES THE OPPORTUNITY FOR THE SAME DEGREE OF PRIVACY INPUT AND OUTPUT AVAILABLE TO ALL INDIVIDUALS. PER 11B-707.9.1.2 OTHER TECHNOLOGY OTHER TECHNOLOGY, SUCH AS A RADIO FREQUENCY IDENTIFICATION DEVICE, FINGERPRINT BIOMETRICS OR SOME OTHER MECHANISM THAT ENABLES A VISUALLY IMPAIRED PERSON TO ACCESS THE VIDEO TOUCH SCREEN DEVICE WITH HIS OR HER PERSONAL IDENTIFIER AND TO PROCESS HIS OR HER TRANSACTION IN A MANNER THAT PROVIDES THE OPPORTUNITY FOR THE SAME DEGREE OF PRIVACY INPUT AND OUTPUT AVAILABLE TO ALL INDIVIDUALS. WHERE A VIDEO SCREEN OVERLAY IS PROVIDED IT SHALL BE EQUIPPED WITH A TACTILELY DISCERNIBLE NUMERICAL KEYPAD COMPLYING WITH SECTION 11B-707.9.1.1. *POINT-OF-SALE SYSTEMS - SEE BELOW PER 11B-308.3.2 OBSTRUCTED HIGH SIDE REACH WHERE THE REACH DEPTH EXCEEDS 10 INCHES, THE HIGH SIDE REACH SHALL BE 46 INCHES MAX. FOR A REACH DEPTH OF 24 INCHES MAX. 46 " M A X . 10 " - 2 4 " MA X . BOLLARDS (WHERE OCCUR) Po w e r C h a r g e EV CHARGER (PLAN VIEW) BOLLARDS (WHERE OCCUR) 48 " M A X NO PARKING 8" LETTERS: 12" HIGH MIN. HELVETICA MEDIUM WHITE (NO STRIPE OVER TEXT) STRIPING: 4" WIDE GREEN (OR CONTRASTING COLOR TO PAVEMENT) TYPICAL STRIPING AT EV ACCESS AISLES: 4" WIDE BORDER ALL SIDES, GREEN (OR CONTRASTING COLOR TO PAVEMENT) AT DIAGONAL PARKING, EXTEND BORDER STRIPING & HATCHED LINES PER PLAN PER PLAN 5'-0" MIN @ EV AT DIAGONAL PARKING, EXTEND STRIPING & HATCHED LINES PER PLAN CLCL FOR AREA BEYOND ACCESS AISLE AND SITE SPECIFIC ACCESSIBLE PATH OF TRAVEL, FLUSH TRANSITIONS OR CURB RAMPS, SEE ENLARGED SITE PLANS ON ARCHITECTURAL SHEETS PE R P L A N 18 ' - 0 " M I N 2. 3 " - 2 . 4 " SECTION A-A 0. 2 " H T . A .45"-.47" .9 " - . 9 2 " 36 " A T B A S E IN D I R E C T I O N O F T R A V E L DI R E C T I O N O F T R A V E L A 0. 2 " H T . FLUSH TRANSITION AT CURB RAMPS TOP DIAMETER=.45" - .47" BOTTOM DIAMETER= .90" - .92" PER CBC SECTION 11B-705.1 MAINTAIN 2.3" - 2.4" DISTANCE AT BREAK TO COMPLY WITH SECTION A-A CL 0.65" TAPERED EDGES WHERE EXPOSED, MAX DEPTH WITH SLOPE NOT STEEPER THAN 1:2 2.3"-2.4" VARIES PER PLAN NOTES: 1. YELLOW COLOR IS REQUIRED FOR NEW INSTALLATIONS YELLOW COLOR #33538 SAE AMS-STD-595A SECTION A-A 1'-0"1'-0" 4'-0"7 1/2" 5 1 / 2 " 2 1 / 2 " TY P (2) #3 BARS SECTIONELEVATION 5 1 / 2 " FINISHED GRADE NOTES: 1. PREFABRICATED P.C. CONCRETE - F'c = 3,500 PSI 3 4" DIA. STEEL PIN, 21" LONG 6" PROJECTION TYP. PLAN 1'-0" TYP 2' - 0 " T Y P CL CL CL CL ACCESSIBLE PARKING SIGNAGE IN FRONT OF EACH ACCESSIBLE STALL, SEE 1/- 1" DIA. HOLE (TYP.) ACCESSIBLE PARKING STANDARDS - EV Scale: 1/2" = 1'4 STANDARD (NON-ACCESS) PARKING STRIPING - EV Scale: 1" = 1'1 PARKING SIGN - EV Scale: 1/2" = 1'3 ACCESSIBLE PARKING STRIPING - EV SHEET NO.: SHEET TITLE DATE: 02.12.24 REVISION DATENO. A HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 100P 02.12.24 BACKCHECK 07.23.24 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 A1.2 Scale: 1" = 1'6 ACCESSIBLE EV CHARGER DETAIL Scale: 1/2" = 1'5 ACCESSIBLE ACCESS AISLE STRIPING - EV Scale: 1" = 1'2 TRUNCATED DOMES Scale: 1/2" = 1'7 CONCRETE WHEEL STOP B REV B 01.08.25 C REV C 06.03.25 SHEET LIST TABLE SHEET NUMBER SHEET TITLE SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 ELECTRICAL NOTES A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 A AMPERE AC ALTERNATING CURRENT AF AMP FRAME, AMP FUSED AFF ABOVE FINISH FLOOR AIC AMPS INTERRUPTING CURRENT AMB AMBIENT ANSI AMERICAN NATIONAL STANDARDS INSTITUTE APPROX APPROXIMATE AT AMP TRIP AVG AVERAGE AWG AMERICAN WIRE GAUGE BLDG BUILDING BOS BALANCE OF SYSTEM C CONDUIT CAT CATALOG CB CIRCUIT BREAKER CEC CALIFORNIA ELECTRICAL CODE CIR,CKT CIRCUIT CLR CLEARS CMB COMBINER BOX CONT CONTINUOUS, CONTINUED CTRL CONTROL CU COPPER DC DIRECT CURRENT DEG DEGREE DISC DISCONNECT E EXISTING EAEACH EMT ELECTRIC METALLIC TUBING ENC ENCLOSURE EQ EQUAL EST ESTIMATED FAFIRE ALARM FLA FULL LOAD AMPS G GROUND GEC GROUNDING ELECTRODE CONDUCTOR GFCI GROUND FAULT CURRENT INTERRUPTER GFI GROUND FAULT INTERRUPTER HP HORSE POWER HZHERTZ J-BOX JUNCTION BOX KATHOUSAND AMPS KAIC THOUSAND AMPS INTERRUPT CURRENT KCMIL THOUSAND CIRCULAR MILS KVTHOUSAND VOLTS KV BIL BASIC IMPULSE LEVEL (KV) KVA THOUSAND VOLT-AMPS KW KILOWATTS LB(S)POUND(S) LCL LONG TIME CONTINUOUS LOAD M METER MAN MANUAL MAX MAXIMUM MB MAIN BREAKER MCA MINIMUM CURRENT AMPS MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MM METER MAIN MOCP MAXIMUM OVER CURRENT PROTECTION MTG MOUNTING NEC NATIONAL ELECTRICAL CODE NEU NEUTRAL NF NON-FUSED NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NO.NUMBER NOM NOMINAL NRTL NATIONALLY RECOGNIZED TESTING LABORATORY NTS NOT TO SCALE O.C.ON CENTER P PLUG, POLE, PUMP AS APPROPRIATE PB PULL BOX PH, Ø PHASE PNL PANEL POC POINT OF CONNECTION PV PHOTOVOLTAIC PVC POLYVINYL CHLORIDE REF REFERENCE RGS RIGID STEEL CONDUIT RM ROOM SCE SOUTHERN CALIFORNIA EDISON S/N SOLID NEUTRAL SN SERIAL NUMBER SQ SQUARE SS SAFETY SWITCH STD STANDARD STRUCT STRUCTURAL SWBD SWITCHBOARD SWGR SWITCHGEAR T, TEMP TEMPERATURE TID TURLOCK IRRIGATION DISTRICT TYP TYPICAL U.O.N.UNLESS OTHERWISE NOTED UGPS UNDERGROUND PULL SECTION UL UNDERWRITER'S LABORATORY V VOLTS VA VOLT-AMPS VAC VOLTS ALTERNATING CURRENT VDC VOLTS DIRECT CURRENT W WATTS, WIRE AS APPROPRIATE WP WEATHERPROOF XFMR TRANSFORMER Y WYE #NUMBER %PERCENT &AND (E)EXISTING 'FEET "INCHES +PLUS =EQUAL °C DEGREE CENTIGRADE 1.DRAWINGS ARE NECESSARILY DIAGRAMMATIC BY THEIR NATURE AND ARE NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL OR WORK, MATERIALS AND EQUIPMENT SHALL COMPLY WITH THE RULES AND REGULATIONS SPECIFIED IN THE EDITION OF NATIONAL FIRE ASSOCIATION (NFPA) ADOPTED BY THE JURISDICTION OF THE PROJECT. 2.EVERY PIPE OR CONDUIT IN ITS EXACT LOCATION. CAREFULLY INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AND COORDINATE THE WORK. ORGANIZE AND LAY OUT WORK SO THAT IT WILL BE CONCEALED IN FURRED CHASES AND SUSPENDED CEILINGS, ETC., IN FINISHED PORTIONS OF THE BUILDING, UNLESS SPECIFICALLY NOTED TO BE EXPOSED. INSTALL ALL WORK PARALLEL OR PERPENDICULAR TO BUILDING LINES UNLESS OTHERWISE NOTED. 3.ALL EQUIPMENT AND MATERIALS SHALL BE DELIVERED TO THE PROJECT SITE CLEAN AND SEALED FOR PROTECTION, TAKE SUCH PRECAUTIONS AS ARE NECESSARY TO PROTECT APPARATUS AND MATERIALS FROM DAMAGE. PROTECT FACTORY FINISH FROM DAMAGE DURING CONSTRUCTION ACCEPTANCE OF THE PROJECT. 4.PROVIDE NEW PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN PRODUCTION OF SUCH EQUIPMENT. PROVIDE THE MANUFACTURER'S LATEST STANDARD DESIGN FOR THE TYPE OF PRODUCT SPECIFIED. 5.PRODUCTS SHALL CONFORM TO REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE. WHERE UNDERWRITERS' LABORATORIES HAVE SET STANDARDS, LISTED PRODUCTS AND ISSUED LABELS, PRODUCTS USED SHALL BE LISTED AND LABELED TO THOSE STANDARDS BY UL OR ANOTHER AGENCY ACCEPTABLE BY THE AUTHORITY HAVING JURISDICTION. PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE LISTING OF THE EQUIPMENT. 6.SUPPLY SIDE CONNECTIONS AS PERMITTED BY THE CEC ARTICLE 705.12 SHALL BE MADE IN ACCORDANCE WITH CEC ARTICLE 230. 7.DESIGNATIONS: EXTERNALLY MARK ALL EQUIPMENT, DEVICES, FEEDERS, BRANCH CIRCUITS AND SIMILAR ITEMS WITH NAMEPLATES AS INDICATED ELSEWHERE IN THESE DRAWINGS AND SPECIFICATIONS. 8.COORDINATE THE SCHEDULING OF ALL WORK REQUIRING ELECTRICAL SHUTDOWNS WITH THE OWNER. THIS MAY REQUIRE PERFORMING THE WORK OUTSIDE OF NORMAL WORKING HOURS AND/OR PROVIDING TEMPORARY POWER WITH A PORTABLE GENERATOR OR BY OTHER APPROVED MEANS. COORDINATE TEMPORARY POWER REQUIREMENTS AND POSSIBLE ALTERNATE POWER SERVICES WITH THE OWNER. 9.EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH THE RESPECTIVE EQUIPMENT MANUFACTURER'S PUBLISHED RECOMMENDATIONS. 10.OBSERVE ALL CLEARANCES REQUIRED BY CEC 110.26 AND 110.34. 11.EQUIPMENT SHALL BE SET LEVEL AND PLUMB. 12.SEAL OPENINGS INTO EQUIPMENT TO PREVENT ENTRANCE OF ANIMALS, BIRDS, WEATHER, AND INSECTS. 13.ALL UNUSED OPENINGS SUCH AS, BUT NOT LIMITED TO, KNOCKOUTS ON PANELS AND BOXES, SURFACE WIREWAY OPENINGS, AND CIRCUIT BREAKER EMPTY SLOTS SHALL BE COVERED WITH APPROVED COVER PLATES. 14.COOPERATE WITH TRADES OF ADJACENT, RELATED OR AFFECTED MATERIALS OR OPERATIONS, AND WITH TRADES PERFORMING CONTINUATIONS OF THIS WORK IN ORDER TO AFFECT TIMELY AND ACCURATE PLACING OF WORK AND TO COORDINATE, IN PROPER AND CORRECT SEQUENCE, THE WORK OF SUCH TRADES. 15.WORK SHALL BE PERFORMED BY THE COMPETENT WORKERS SKILLED IN THEIR TRADE. 16.THIS INSTALLATION SHALL BE COMPLETE AND FUNCTIONAL. 17.MODULES ARE NEVER TO BE WALKED, KNEELED, OR SAT UPON, NOR TRANSPORTED ON YOUR HEAD OR IN SUCH A FASHION THAT PUTS PRESSURE ON ANY AREA OF THE MODULE OTHER THAN THE FRAME. 18.MODULES MUST BE SECURED AT ALL TIMES, REFER TO THE MODULE MANUAL FOR MORE DETAILS ON RIGGING, UNPACKING, HANDLING, SUPPORTING, AND INSTALLATION. 19.ALL EXISTING PANEL-BOARDS MODIFIED BY THIS PROJECT SHALL BE UPDATED WITH NEW TYPE WRITTEN DIRECTORIES. 20.MODULES SHALL NOT BE STORED IN ANY WAY THAT EXPOSES THE UNDERSIDE OF THE MODULE TO SUNLIGHT, ALLOWS MOISTURE (RAIN, SNOW ETC.) TO ACCUMULATE ON THE UNDERSIDE OF THE MODULE, OR MAY EXPOSE THE UNDERSIDE OF THE MODULE TO RISK OF PHYSICAL DAMAGE FROM ANOTHER OBJECT. 21.REFER TO STRUCTURAL SHEETS FOR EQUIPMENT ANCHORING TECHNIQUES. 22.CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY AND LIABILITY FOR COMPLIANCE WITH REGULATIONS PER FEDERAL OSHA, CAL/OSHA AND LOCAL REGULATIONS PERTAINING TO WORK PRACTICES, PROTECTION OF WORKERS AND VISITORS TO THE SITE. 23.CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AT SITE BEFORE COMMENCING WORK. 24.WORK REQUIRED UNDER THIS CONTRACT INCLUDES ALL LABOR AND MATERIALS, EQUIPMENT ETC. NECESSARY AND REASONABLY INCIDENTAL TO COMPLETE THE PROJECT. ALL MATERIALS SHALL BE IN NEW AND UNUSED CONDITION AND OF HIGH QUALITY IN EVERY RESPECT. 25.MANUFACTURER'S MATERIAL, EQUIPMENT, ETC. SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. 26.THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL UTILITY AS-BUILT PLANS AND THE LOCATIONS OF ALL EXISTING UTILITIES AND STRUCTURES. 27.ALL WORK SHALL BE INSTALLED IN CONFORMANCE WITH ALL APPLICABLE LOCAL CODES AND ORDINANCES BY EXPERIENCED WORKERS AND A LICENSED CONTRACTOR WHO SHALL OBTAIN ALL NECESSARY PERMITS AND PAY ALL REQUIRED FEES. 28.GOOD HOUSEKEEPING IS EXPECTED. TRASH SHALL BE REMOVED AS FREQUENTLY AS NEEDED TO ENSURE A TIDY AND SAFE WORK ENVIRONMENT. 29.ALL WORK SHALL BE INSTALLED IN CONFORMANCE WITH CONSTRUCTION SPECIFICATIONS. 30.ALL PV SYSTEM COMPONENTS SHALL BE LISTED BY A RECOGNIZED TESTING AGENCY. 31.PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING MATERIALS SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE DURING CONSTRUCTION DATA ACQUISITION SYSTEM GENERAL ELECTRICAL NOTES ABBREVIATIONS POWER LEGEND PHOTOVOLTAIC ARRAY PANELBOARD NEW CONDUIT RUN, UNDERGROUND NEW CONDUIT RUN, EXPOSED ON ROOF OR WALL EARTH GROUND DC-AC INVERTER TRANSFORMER FUSE FUSED SWITCH DISCONNECT SWITCH CIRCUIT BREAKER OR MOTOR CIRCUIT PROTECTOR GROUND WIRING KILOWATTHOUR/DEMAND METER (FURNISHED BY UTILITY COMPANY) PHOTOVOLTAIC MODULE E000 ELECTRICAL SHEET INDEX APPLICABLE CODES ALL WORK SHALL CONFORM TO ALL PERTINENT CODES, REGULATIONS, LAWS, AND ORDINANCES AS REQUIRED BY THE STATE OF CALIFORNIA. 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC) (PART 1, TITLE 24, CCR) 2022 CALIFORNIA BUILDING CODE (CBC), VOL. 1 & 2 (PART 2, TITLE 24, CCR) 2022 CALIFORNIA ELECTRICAL CODE (PART 3, TITLE 24, CCR) 2022 CALIFORNIA MECHANICAL CODE (CMC) (PART 4, TITLE 24, CCR) 2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24, CCR) 2022 CALIFORNIA FIRE CODE (CFC) (PART 9, TITLE 24, CCR) 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (PART 11, TITLE 24, CCR) 2022 CALIFORNIA REFERENCED STANDARDS CODE (PART 12, TITLE 24, CCR) SOLAR PHOTOVOLTAIC EQUIPMENT SHALL COMPLY WITH UL 508, 854, AND UL 1703, 1741, 4703, 6703, 61730-1 (FOR CONSTRUCTION, 61730-2 (FOR TESTING) REQUIREMENTS. NOPARKING NOPARKING NOPARKING EV CH A R G I N G ONL Y NO PA R K I N G 'INV1' PNL 'SP' & DAS STRUCTURE 'A' PROPOSED UNDERGROUND TRENCH OR BORE. REFERENCE DETAILS 1 & 2/E300 (TYP) 2 E100 ENLARGED SERVICE EQUIPMENT LAYOUT 'INV2' 'T-SP' (PROVIDE 6" MIN. VENTILATION CLEARANCE) SPARE MODULE NOT ELECTRICALLY CONNECTED PROPOSED 24"x24" UNDERGROUND PULL BOX (2) 2 1/2"C - PV AC PWR (1) 2"C - PV AC PWR (2) 2 1/2"C - PV AC PWR (1) 2"C - PV AC PWR PROPOSED EXPOSED RACEWAYS MOUNTED TO UNDERSIDE OF STRUCTURE PURLINS (TYP) AC DISCO. 'ULD': MANUAL, VISIBLY OPEN & LOCKABLE OPEN, 24HR ACCESSIBLE. 36" CLEARANCE (TYP) (E) 'MSB' & SCE METER #359150-007450 SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 ELECTRICAL PV PLAN A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 SCALE: 1"= 40' ELECTRICAL PV PLAN1 0'10'20'40' E100 SCALE: 1"= 5' ENLARGED SERVICE EQUIPMENT LAYOUT2 0'2.5'5' GENERAL NOTES: 1.COORDINATE EXACT STRUCTURE COLUMN LOCATIONS WITH STRUCTURAL. 2.PROVIDE PVC SCHED. 40 CONDUIT BELOW GRADE, RMC/IMC WHERE SUBJECT TO PHYSICAL DAMAGE AND UP TO A HEIGHT OF 8' ABOVE GRADE, EMT CONDUIT WITH RAINTIGHT COMPRESSION FITTINGS ELSEWHERE. 3.UNDERGROUND RACEWAYS SHALL BE INSTALLED A MINIMUM OF 24" BELOW GRADE TO TOP OF RACEWAY. 4.CONTACT DIGALERT PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATIONS. 5.COORDINATE UNDERGROUND INSTALLATIONS WITH AS-BUILTS AND OTHER TRADES. 6.MAINTAIN CODE REQUIRED CLEARANCES BETWEEN NEW UNDERGROUND RACEWAYS AND EXISTING UTILITIES AS REQUIRED. WHERE EXISTING UTILITIES ARE IN CONFLICT, A TRENCH DEEPER THAN 24" SHALL BE REQUIRED. OF SOUTHERN CALIFORNIA UNDERGROUND SERVICE ALERT DIG ALERT NO PARKING NO PARKING EV CH A R G I N G ON L Y NO PA R K I N G STRUCTURE 'A' PROPOSED UNDERGROUND TRENCH OR BORE. REFERENCE DETAILS 1 & 2/E300 (TYP) 2 E100 ENLARGED SERVICE EQUIPMENT LAYOUT PROPOSED 24"x24" UNDERGROUND PULL BOX 3 1/2"C - EV AC PWR EVCS3/4 EVCS1/2 PROPOSED PERMANENT BOLLARD PER STRUCTURAL (TYP) PNL EV 36" CLEARANCE (TYP) SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 ELECTRICAL EV PLAN A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 SCALE: 1"= 15' ELECTRICAL EV PLAN1 0'15' E101 GENERAL NOTES: 1.COORDINATE EXACT STRUCTURE COLUMN LOCATIONS WITH STRUCTURAL. 2.PROVIDE PVC SCHED. 40 CONDUIT BELOW GRADE, RMC/IMC WHERE SUBJECT TO PHYSICAL DAMAGE AND UP TO A HEIGHT OF 8' ABOVE GRADE, EMT CONDUIT WITH RAINTIGHT COMPRESSION FITTINGS ELSEWHERE. 3.UNDERGROUND RACEWAYS SHALL BE INSTALLED A MINIMUM OF 24" BELOW GRADE TO TOP OF RACEWAY. 4.CONTACT DIGALERT PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATIONS. 5.COORDINATE UNDERGROUND INSTALLATIONS WITH AS-BUILTS AND OTHER TRADES. 6.MAINTAIN CODE REQUIRED CLEARANCES BETWEEN NEW UNDERGROUND RACEWAYS AND EXISTING UTILITIES AS REQUIRED. WHERE EXISTING UTILITIES ARE IN CONFLICT, A TRENCH DEEPER THAN 24" SHALL BE REQUIRED. OF SOUTHERN CALIFORNIA UNDERGROUND SERVICE ALERT DIG ALERT SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 1-LINE DIAGRAM A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E200 SYSTEM SUMMARY SYSTEM SIZE: 101.2KW (DC-STC), 91KVA (AC), 92.803KW (CEC-AC) MODULES: (184) ZNSHINE PV-TECH CO., LTD. ZXM7-SHLDD144-550/M INVERTERS: (1) CHINT POWER SYSTEMS AMERICA CPS SCA50KTL-DO/US-480 [480V] (1) CHINT POWER SYSTEMS AMERICA CPS SCA36KTL-DO/US-480 [480V] FROM (E) SCE XFR (E) (E) LOADS (E) LOADS (E) GROUNDING SYSTEM (E) MAIN SERVICE BOARD "MSB": 1,600A, 208Y/120V, 3ɸ, 4W, NEMA 3R, 65KAIC ......... (E) LOADS (E) LOADS (E) (E) LOADS (E) LOADS (E) G N SCE 359150-007450 (E) 1600A 3P STRINGING TABLE: SUPPLY SIDE CONNECTION. SEE GENERAL NOTES FOR ADDITIONAL REQUIREMENTS L = 2 1 0 F T V. D . = 1 . 0 5 % (2) 2 1/2"C - 3 #250 THWN-2 AL, #1 AL GND 400A 3CL A S S R G AC DISC. 'ULD', 400A, 240V, 3P, 4W, NEMA 3R, 200KAIC, MANUAL, VISIBLY OPEN & LOCKABLE OPEN. 24HR ACCESSIBLE. RATED FOR SERVICE ENTRANCE. SQUARE D H325NR OR EQUAL N #1/0 AWG CU MAIN BONDING JUMPER 3 1/2"C - 3 #600 THWN-2 CU, #1/0 CU NEU, #1/0 CU SSBJ #1/0 AWG BARE CU GEC L = 2 5 F T V. D . = 0 . 1 2 % 1"C - SEE ALSOENERGY DRAWINGS FOR EXACT REQUIREMENTS COM M CO M M COM M DAS FACTORY CABLE 15A 1P 15A 3P 60A 3P SOLAR PANELBOARD 'SP' 200A, 480Y/277V, 3ɸ, 4W, NEMA 3R, 14KAIC L = 1 5 F T V. D . = 0 . 0 9 % 'INV1' 55 KVA G N COMM COM M 'INV2' 36 KVA L = 6 5 F T V. D . = 0 . 5 2 % 1"C - 3 #4 THWN-2 AL, #6 AL GND 1"C - BELDEN RS485 CABLE (LOOP THROUGH INVERTERS) 90A 3P COMM COMM COMM FREE-AIR - #10 CU PV-WIRE/USE-2/RHH/RHW-2-1000V, #6 CU GND (SEE STRINGING TABLE FOR EXACT QUANTITIES) SEE STRINGING TABLE WEATHERHEAD @ CARPORT (TYP) 1 1/2"C - 6 #10 CU PV-WIRE/USE-2/RHH/RHW-2-1000V, #6 CU GND GENERAL NOTES: 1.ALL DC CONDUCTORS SHALL BE COPPER. 2.NEUTRAL CONDUCTORS SHALL MATCH MATERIALS OF THE PHASE CONDUCTORS. 3.CPS INVERTERS ARE EQUIPPED WITH STANDARD 20A DC FUSES IN THE FUSE HOLDERS. CONTRACTOR SHALL SWAP OUT 20A FUSES WITH 25A FUSES PRIOR TO CONNECTION OF DC STRINGS IN THE FIELD. CONSULT WITH INVERTER MANUFACTURER FOR MATCHING FUSES. 4.INVERTER COMM KNOCK-OUTS ARE 3/4". CONTRACTOR SHALL PROVIDE 1"C BELOW GRADE AND TRANSITION TO 3/4" AT INVERTER. 5.ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. 6.MODULES SHALL MEET UL FIRE TESTING REQUIREMENTS. 7.THE RACK GROUNDING ELECTRODE CONDUCTOR SHALL BE INSTALLED PER CEC 250.64. CONDUCTOR SPLICES SHALL BE WITH COMPRESSION CONNECTORS OR EXOTHERMIC WELDING. 8.PROVIDE REJECTION TYPE FUSE HOLDERS FOR ALL FUSES. 9.PROVIDE PVC SCHED. 40 CONDUIT BELOW GRADE, RMC/IMC WHERE SUBJECT TO PHYSICAL DAMAGE AND UP TO A HEIGHT OF 8' ABOVE GRADE, EMT CONDUIT ELSEWHERE. 10.CONTRACTOR SHALL TRIM ALL FACTORY LEEDS FOR CT'S, COMMUNICATION & CONTROLS TO LENGTH. 11.PROVIDE FULLY RATED EQUIPMENT. SERIES RATING IS NOT ALLOWED. 12.ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION. 13.SUPPLY SIDE CONNECTION SHALL BE FIELD CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION. 14.CONTRACTOR SHALL NOT USE ADJACENT TERMINALS WITHIN EACH MPPT WHEN UTILIZING FUSES LARGER THAN 20A AS PER THE INVERTER INSTALLATION INSTRUCTIONS. BIFACIAL MODULE GAIN: THE DESIGN ASSUMES A BIFACIAL MODULE GAIN NOT IN EXCESS OF 15%. ADJUSTED ISC = MODULE ISC x 1.15 = 15.97A IMAX = ISC x 1.25 = 19.97A ITERM = 1.25 x IMAX = 24.96A OCPD = 25A DC CONDUCTOR CALCULATION: TERMINATION CHECK: #10 CU PV-WIRE/USE-2/RHH/RHW-2-1000V: 60°C = 30A 30A > 25A OCPD, OKAY. IMAX CHECK: #10 CU PV-WIRE/USE-2/RHH/RHW-2-1000V: 90°C = 40A CHECK WORST CASE SCENARIO: 8 CONDUCTORS IN A RACEWAY & AVERAGE SITE HIGH TEMP= 47°C IMAX = 19.97A (FROM BIFACIAL MODULE GAIN CALCULATION ABOVE) 40A x 0.82 x 0.7 = 22.96A (DERATED CONDUCTOR VALUE) 22.96A > 19.97A [IMAX], OKAY. DAS: ALSOENERGY DAS ENCLOSURE. 277V, 1P. PROVIDE WITH CELLULAR MODEM. ALSOENERGY POA IRRADIANCE SENSOR. ALSOENERGY MODULE TEMPERATURE SENSOR. BRANCH BREAKER FEEDING EV CHARGER SHALL BE LOCKABLE (TYP). EQUIPMENT SCHEDULE: 150A 3P L = 6 0 F T V. D . = 0 . 5 3 % 'T-SP' 112.5KVA 208V - 480Y/277V, NEMA 3R, Z = 3.7% 150°C RISE, DRY-TYPE G N 1 1/2"C - 3 #1 THWN-2 AL, #6 AL GND 2"C - 3 #3/0 THWN-2 AL, #4 AL NEU, #4 AL SSBJ 1 1/4"C - 4 #10 CU PV-WIRE/USE-2/RHH/RHW-2-1000V, #8 CU GND #4 AWG CU GEC TO (2) 5/8"x8' GND RODS 6'-0" APART 1"C - 3 #12 THWN-2 CU, #12 GND, 6 #14 SIS CABLE (FOR RGM VT & CT) 3/4"C - 2 #12 THWN-2 CU, #12 GND (DAS 277VAC PWR) 15A 2P TC 3/4"C - 2 #10 THWN-2 CU, #10 GND 1"C - 2 #10 THWN-2 CU, #10 GND WHERE BELOW GRADE #10-2 THWN-2 CU PVC COATED MC CABLE @ UNDERSIDE OF CARPORT ASTRONOMIC TIMECLOCK TORK CAT #EWZ201C, 2-20A/277V CIRCUIT, NEMA 3R TO LTG CIRCUIT SEE STRINGING TABLE 300A 3P L = 2 8 0 F T V. D . = 2 . 0 6 % PANELBOARD 'EV' 400A, 208Y/120V, 3ɸ, 4W, NEMA 3R, 22KAIC G N 3 1/2"C - 3 #500 THWN-2 AL, #500 AL NEU, #2 AL GND 1 1/2"C - 4 #1 THWN-2 CU, #6 CU GND L = 1 5 F T V. D . = 0 . 1 8 % EV C S 2 EV C S 1 100A 2P 100A 2P L = 3 0 F T V. D . = 0 . 3 7 % EV C S 4 EV C S 3 100A 2P 100A 2P PANEL EV SCHEDULE #2 AWG CU GEC TO (2) 5/8"x8' GND RODS 6'-0" APART CHARGEPOINT DUAL PORT CP6021B-80A-L5.5 80A, 208V, 1ɸ, 2W, NEMA 3R (TYP) (E) 'MSB' DEMAND CALCULATIONS 1-YEAR MAX 15-MIN INTERVAL DATA = 24.36KWH DEMAND KW = 24.36KWH/15MIN x 60MIN/1HR = 97.44KW DEMAND KVA @ 0.8 ASSUMED P.F. = 97.44KW / 0.8 = 121.8KVA DEMAND KVA @ 125% NEC MULTIPLIER = 121.8KVA x 125% = 152.25KVA ADDED EV LOAD 3 x 31.3KVA = 93.9KVA (FROM PNL EV MAX UNBALANCED PHASE) TOTAL NEW & (E) DEMAND KVA = 152.25KVA + 93.9KVA = 246.15KVA AMPS @ 208V = 683.2A < 1,600A, OKAY. D T5.106.5.3.6 CALCULATIONS # OF ALTERED PARKING SPACES: 26 TOTAL KVA REQUIRED (EVSE & EV CAPABLE) = 52.8KVA PROPOSED # OF LEVEL II EVSE = 4 KVA/EVSE = 80A x 208V / 1,000VA/KVA = 16.64KVA 4 x 16.64KVA = 66.56KVA 66.56KVA > 52.8KVA, OKAY. SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 GROUNDING DIAGRAM A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E201 1.COMBINED DC GEC/AC EGC SHALL BE INSTALLED IN ACCORDANCE WITH CEC 250.64(E) IN COMPLIANCE WITH 250.92(B) AND ENSURED BY ONE OF THE METHODS IN 250.92(B)(2) THROUGH (B)(4). FOR FERROUS METAL RACEWAYS & ENCLOSURES, CONTRACTOR SHALL INSTALL BONDING-TYPE LOCKNUTS OR BUSHINGS ON EACH END OF THE RACEWAY OR ENCLOSURE TO THE GROUNDING ELECTRODE OR GROUNDING ELECTRODE CONDUCTOR. 2.EACH MODULE TO BE BONDED TO EQUIPMENT GROUND AS CALLED OUT ON THE LINE DIAGRAM AND THESE NOTES. SEE MODULE MANUFACTURER INSTRUCTIONS OF RECOMMENDED GROUNDING COMPONENTS AND METHODS. 3.CEC ARTICLE 250 - GROUNDING EARTH RESISTANCE SHALL NOT EXCEED 25 OHMS. IF A SINGLE ROD, PIPE OR PLATE HAS EARTH RESISTANCE IN EXCESS OF 25 OHMS, SUPPLEMENTAL GROUNDING ELECTRODES SHALL BE ADDED AT 6' MINIMUM INTERVALS IN ORDER TO ACHIEVE EARTH RESISTANCE OF LESS THAN 25 OHMS. GENERAL NOTES: 3 STRUCTURE BONDING DIAGRAM PURLIN TO BEAM BONDING JUMPER (TYP) PURLIN TO PURLIN (TYP) BEAM WITH COLUMN THAT IS CONNECTED TO AUXILIARY GROUNDING ELECTRODE PER DETAIL 2 THIS SHEET. BEAM TO COLUMN FACTORY WELD (TYP) FOOTING PER STRUCTURAL FINISHED SURFACE COLUMN #4 REBAR CAGE WITH STEEL TIE WIRES PER STRUCTUREL (TYP) EXOTHERMIC WELD OR ILSCO GBL-4DBT LAY-IN ON VERTICAL COLUMN WITH 10-32 X 3/4" MIN SS THREAD CUT SCREW MOUNTED INSPECT BEFORE CONCRETE IS POURED 20FT #4 AWG BARE CU UFER GROUND REBAR TO UFER WITH UL APPROVED BONDING CLAMP RATED FOR DIRECT BURIAL AND CONCRETE SUCH AS RACO CAT #RBC2DBAG1R (OR EQUAL). NOTES: 1.TRIM END AND CURL WIRE BACK ONTO ITSELF 2.ADD ANTI-OXIDANT COMPOUND (NOALOX OR EQUIV) AT GROUND LUG WIRE TERMINATION 3.PHOTOGRAPH ALL CONNECTIONS BEFORE THEY ARE BURIED. 4.GROUND ONLY 1 COLUMN PER STRUCTURE. USE COLUMN WHERE PANEL 'PV1' IS MOUNTED. WHERE NO PANEL 'PV1' IS LOCATED ON STRUCTURE, USE COLUMN WHERE INVERTER IS MOUNTED. 2 STRUCTURE COLUMN GROUNDING #4 REBAR CAGE WITH STEEL TIE WIRES PER STRUCTUREL (TYP) CONCRETE FOOTING SEE 1-LINE '(E) MSB' GNDNEU INVERTER 'INV1' GND NEU SEE 1-LINE #4 CU FREE-AIR GEC TO COLUMN WHERE 'INV1' IS MOUNTED PV MODULES @ STRUCTURE #6 AWG CU FREE-AIR OR A LISTED BRAIDED BONDING STRAP(TYP OF PURLIN TO BEAM & PURLIN TO PURLIN. USE ILSCO GBL-4DBT LAY-IN LUG) LISTED CONNECTION PER MODULE INSTALLATION MANUAL SEE DETAIL 2 THIS SHEET FOR STRUCTURE COLUMN GROUNDING ELECTRODE SYSTEM FACTORY WELD (TYP) 'ULD' GND GEC PER 1-LINE 1 GROUNDING DIAGRAM NEU (E) MAIN BONDING JUMPER PNL 'SP' GND NEU SSBJ PER 1-LINE SEE 1-LINE #4 CU FREE-AIR GEC TO COLUMN WHERE PNL 'SP' IS MOUNTED SSBJ PER 1-LINE MAIN BONDING JUMPER PER 1-LINE 'T-SP' GND NEU SEE 1-LINE FACTORY SYSTEM BONDING JUMPER PER 1-LINE SEE 1-LINETO 'INV2' (TYP 'INV1') (E) GROUNDING SYSTEM #4 AWG GEC TO (2) 5/8"x8' GND RODS 6'-0" APART SEE 1-LINE PNL 'EV' GND NEU GND PER 1-LINE #2 AWG GEC TO (2) 5/8"x8' GND RODS 6'-0" APART EVCS1/2 GND SEE 1-LINE SEE 1-LINETO EVCS3/4 (TYP EVCS1/2) SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 ELECTRICAL DETAILS A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E300 1 TRENCH DETAIL 3 PULL BOX DETAIL 4 PV WIRE SECURING S.S TIE-WRAP @ EACH WIRE CLIP PV WIRE TYP PV WIRE CLIP PURLIN FRAME GENERAL NOTES: 1.PROVIDE CONCRETE ELECTRICAL PULLBOXES W/METAL BOLT DOWN H20 TRAFFIC COVERS. EISEL PRODUCTS NO. 5T PB/DP OR APPROVED EQUAL. CONCRETE BOX W/METAL BOLT DOWN COVER FINISHED GRADE 1' CRUSHED ROCK 24" 18" 30" 18" 2" 12" TOP OF (E) FINISHED GRADE / PAVEMENT (UNDISTURBED) UNDISTURBED (E) SUB-GRADE COMM AND LIGHTING CONDUITS (IF APP.) BORE SIZE PER GC POWER & SPARE CONDUITS SIZES & QTY'S PER DRAWINGS (IF APP.) 24" MIN. DEPTH 2 BORE DETAIL 5 PV PANEL WIRE MANAGEMENT DETAIL 8 CANOPY MOUNTED PANELBOARD 6 CONDUIT GROUNDING DETAIL CONDUIT COMPRESSION FITTING ENCLOSURE LOCK NUT GROUNDING BUSHING WITH LAY-IN LUG CONTINUOUS GROUND STRIP INSULATION AT LUG 7 CANOPY MOUNTED INVERTER BEAM RMC/IMC CONDUIT LUMINAIRE (WHERE OCCURS) COLUMN PURLIN PV PANEL EXISTING GRADE TO PANEL 'SSBx' & INV (IF APPLICABLE) PVC CONDUIT <=6'-7" EMT CONDUIT TO INVERTER 'SPx' MYERS HUB TO HIGHEST BREAKER HANDLE WHEN IT IS IN THE HIGHEST POSITION EMT R.T. COMP. CONN. (TYP) TOP OF (N) FINISHED GRADE TO MATCH (E) GRADE 2 SACK SLURRY UP TO 6" BELOW FINISHED GRADE TOP 6" TO MATCH FINISH MATERIAL. LIGHTING CONDUIT (IF APP.) POWER CONDUITS PER DRAWINGS (IF APP.) 24" MIN. AT TRENCH 24" MIN. DEPTH 3" MIN. COMMUNICATION CONDUIT (IF APP.) NOTES: 1.PAVING SECTION PROFILE TO MATCH EXISTING AT FIRE LANE TO MAINTAIN FIRE LANE STRENGTH. BEAM RMC/IMC CONDUIT LUMINAIRE (WHERE OCCURS) EMT CONDUIT PURLIN PV PANEL PV STRING WIRING WEATHERHEAD (TYP) INTEGRAL DC DISCONNECT EXISTING GRADE TO PANEL 'SPx' & DAS (IF APPLICABLE) FOOTING PER STRUCTURAL PVC CONDUIT EMT TO LFMC TRANSITION LOOP LFMC 180° TO LAND AT KNOCK-OUTS LOCATED AT BOTTOM OF INVERTER WIRING BOX>=6'-7" INTEGRAL AC DISCONNECT TO PANEL 'SPx' & DAS (IF APPLICABLE) INVERTER INTEGRAL DC & AC DISCONNECTS. MAY BE MOUNTED HIGHER THAN 6'-7" ABOVE GRADE AS PERMITTED BY CEC 404.8(A) EXCEPTION 2. IN ORDER TO REDUCE TAMPERING WITH EQUIPMENT BY UNAUTHORIZED PERSONNEL COLUMN >=6'-8" FOR EQUIPMENT MOUNTED IN PARKING AREAS BOTTOM EDGE PROJECTS MORE THAN 4" INTO THE CIRCULATION PATH. PVC TO RMC/IMC CONDUIT TRANSITION IN POLE BASE USE 10MIL DOUBLE WRAPPED TAPE FOOTING PER STRUCTURAL PVC TO RMC/IMC CONDUIT TRANSITION IN POLE BASE USE 10MIL DOUBLE WRAPPED TAPE NOPARKING NOPARKING NOPARKING EV CHA R G I N G ONL Y NO PAR K I N G SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 ELECTRICAL PLACARDS A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E400 POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN CAUTION 1 MOUNTING LOCATION: (E) 'MSB' 4 MOUNTING LOCATION: INVERTER DC DISCONNECT 253 208V PV SYSTEM DISCONNECT MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: 2 MOUNTING LOCATION: UTILITY LOCKABLE AC DISCONNECT 'ULD' ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION 3 MOUNTING LOCATION: PANEL 'SP' & TRANSFORMER 'T-SP' ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.56(C)(3) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION INVX 5 MOUNTING LOCATION: DC J-BOXES & EMT/ CONDUIT RACEWAYS EVERY 10 FEET WARNING: PHOTOVOLTAIC POWER SOURCE 1.MARKING IS REQUIRED ON ALL INTERIOR AND EXTERIOR PV CONDUIT, RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERT THE FIRE SERVICE TO AVOID CUTTING THEM. MARKING SHALL BE PLACED EVERY 10 FEET, AT TURNS AND ABOVE AND/OR BELOW PENETRATIONS, AND AT ALL PV COMBINER AND JUNCTION BOXES. 2.REFLECTIVE WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (DURABLE ADHESIVE MATERIALS MUST MEET THIS REQUIREMENT) 3.MARKING CONTENT AND FORMAT: RED BACKGROUND, WHITE LETTERING, MINIMUM 3/8” LETTER HEIGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON BOLD SIGNAGE REQUIRMENTS: 6 MOUNTING LOCATION: DAS DAS SP DC DISCONNECT MAXIMUM VOLTAGE: MAXIMUM CIRCUIT CURRENT: 982V 40A AC DISCONNECT 'ULD' SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE 'OFF' POSITION TO SHUT DOWN CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS WITHIN THE ARRAY REMAIN ENERGIZED IN SUNLIGHT. SOLAR ELECTRIC PV PANELS PANEL 'SP' WARNING! RACEWAY IS ENERGIZED WHEN DISCONNECT IS IN THE OPEN POSITION. DO NOT RELOCATE OR CUT. 'INV1' EACH INVERTER'INV1' (YOU ARE HERE) MAIN SERVICE BOARD 'MSB' 'INV2' 'T-SP' DC DISCONNECT MAXIMUM VOLTAGE: MAXIMUM CIRCUIT CURRENT: 873V 40A 'INV-2' T-SP NO PARKING NO PARKING NO PARKING EV CH A R G I N G ON L Y NO PA R K I N G PROPOSED FIXTURE TYPE 'PV' MOUNTED TO UNDERSIDE OF CANOPY (TYP) #10-2 THWN-2 CU PVC COATED MC CABLE ROUTED TO STRUCTURE PURLIN (TYP) TIMECLOCK TC STRUCTURE 'A' PANEL 'EV' PROPOSED UNDERGROUND TRENCH OR BORE. REFERENCE DETAILS 1 & 2/E300 (TYP) SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 LIGHTING PLAN A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 LIGHTING FIXTURE SCHEDULE MARK MANUFACTURER & CATALOG # MAXLITE CPL-30-U-CS-B-CR LED MOUNTING SURFACE VOLTS UNV WATTS 30 REMARKS 1'x1' LOW BAY OUTDOOR RATED LED FIXTURE WITH FIELD SELECTABLE COLOR TEMPERATURE, 3860-4178 LUMEN AND INTEGRAL DIMMING BALLAST. SET COLOR TEMPERATURE TO 5000K.PV LAMPS LIGHTING CONTROL NOTES: 1.ALL OUTDOOR LIGHTING SHALL BE CONTROLLED THROUGH NEW ASTRONOMICAL TIMECLOCK AND FIXTURE INTEGRATED PHOTOCELL AND STEP DIMMING SENSOR. E500 SCALE: 1"=20' LIGHTING PLAN1 0'5'10'20' GENERAL NOTES: 1.COORDINATE EXACT STRUCTURE COLUMN LOCATIONS WITH STRUCTURAL. 2.PROVIDE PVC SCHED. 40 CONDUIT BELOW GRADE, RMC/IMC WHERE SUBJECT TO PHYSICAL DAMAGE AND UP TO A HEIGHT OF 8' ABOVE GRADE, EMT CONDUIT WITH RAINTIGHT COMPRESSION FITTINGS ELSEWHERE. 3.UNDERGROUND RACEWAYS SHALL BE INSTALLED A MINIMUM OF 24" BELOW GRADE TO TOP OF RACEWAY. 4.CONTACT DIGALERT PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATIONS. 5.COORDINATE UNDERGROUND INSTALLATIONS WITH AS-BUILTS AND OTHER TRADES. 6.MAINTAIN CODE REQUIRED CLEARANCES BETWEEN NEW UNDERGROUND RACEWAYS AND EXISTING UTILITIES AS REQUIRED. WHERE EXISTING UTILITIES ARE IN CONFLICT, A TRENCH DEEPER THAN 24" SHALL BE REQUIRED. OF SOUTHERN CALIFORNIA UNDERGROUND SERVICE ALERT DIG ALERT NO PARKING NO PARKING NO PARKING EV CH A R G I N G ON L Y NO PA R K I N G STRUCTURE 'A' 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.1 0.1 0.2 0.2 0.3 0.4 0.5 0.5 0.5 0.5 0.5 0.6 0.6 0.5 0.5 0.5 0.5 0.6 0.6 0.5 0.5 0.5 0.6 0.6 0.5 0.5 0.4 0.5 0.5 0.4 0.3 0.2 0.2 0.2 0.1 0.1 0.0 0.0 0.1 0.1 0.2 0.3 0.4 0.5 0.7 0.8 0.7 0.7 0.7 0.9 0.9 0.8 0.6 0.6 0.7 0.9 0.8 0.7 0.6 0.7 0.8 0.9 0.8 0.7 0.7 0.7 0.7 0.5 0.4 0.3 0.2 0.2 0.1 0.0 0.0 0.0 0.1 0.1 0.2 0.3 0.4 0.6 1.1 1.3 1.0 0.8 1.0 1.3 1.3 1.0 0.7 0.8 1.0 1.4 1.1 0.9 0.7 0.9 1.1 1.5 1.1 0.8 0.9 1.1 1.2 0.7 0.5 0.3 0.3 0.2 0.1 0.0 0.0 0.0 0.1 0.2 0.3 0.4 0.6 0.9 1.9 2.3 1.5 1.2 1.4 2.3 2.2 1.4 1.1 1.1 1.5 2.2 1.9 1.2 1.0 1.1 1.8 2.3 1.7 1.1 1.2 1.9 2.0 1.2 0.6 0.4 0.3 0.2 0.1 0.0 0.0 0.0 0.1 0.2 0.4 0.6 0.9 2.0 4.4 5.0 3.3 1.9 2.9 4.9 4.8 2.6 1.6 1.7 3.3 4.9 4.2 2.1 1.5 2.0 4.0 4.9 3.6 1.9 2.2 4.2 4.5 2.6 1.0 0.6 0.4 0.3 0.1 0.0 0.0 0.0 0.1 0.2 0.4 0.8 1.5 2.8 5.9 6.7 4.6 3.2 4.3 6.6 6.5 3.8 2.6 2.7 4.6 6.7 5.8 3.1 2.5 2.9 5.6 7.0 5.2 3.2 3.6 6.1 6.6 4.0 1.7 1.0 0.5 0.3 0.1 0.0 0.0 0.0 0.1 0.2 0.4 0.6 0.8 1.9 4.3 4.8 3.2 1.9 2.9 4.9 4.8 2.7 1.6 1.8 3.5 5.2 4.5 2.3 1.7 2.2 4.5 5.5 4.1 2.2 2.6 4.9 5.2 3.1 1.2 0.7 0.5 0.3 0.1 0.0 0.0 0.0 0.1 0.2 0.3 0.4 0.6 0.9 1.8 2.1 1.4 1.1 1.4 2.2 2.2 1.3 1.1 1.1 1.5 2.3 2.0 1.2 1.1 1.2 2.0 2.5 1.8 1.2 1.3 2.2 2.3 1.3 0.7 0.5 0.4 0.2 0.1 0.0 0.0 0.0 0.1 0.1 0.2 0.3 0.4 0.6 1.1 1.3 0.9 0.8 0.9 1.3 1.3 0.9 0.7 0.8 1.0 1.4 1.1 0.9 0.7 0.9 1.2 1.5 1.1 0.9 0.9 1.2 1.3 0.7 0.5 0.3 0.3 0.2 0.1 0.0 0.0 0.0 0.1 0.1 0.2 0.3 0.3 0.5 0.7 0.8 0.7 0.7 0.7 0.9 0.9 0.7 0.6 0.6 0.7 0.9 0.8 0.7 0.6 0.7 0.9 1.0 0.8 0.7 0.7 0.8 0.8 0.6 0.4 0.3 0.2 0.2 0.1 0.0 0.0 0.0 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.5 0.5 0.5 0.5 0.6 0.6 0.5 0.5 0.5 0.5 0.6 0.6 0.5 0.5 0.5 0.6 0.6 0.6 0.5 0.5 0.5 0.5 0.4 0.3 0.2 0.2 0.2 0.1 0.1 0.0 0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.3 0.3 0.3 0.3 0.4 0.4 0.3 0.3 0.3 0.4 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.1 0.1 0.1 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 PHOTOMETRIC PLAN A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E501 SCALE: 1"=20' PHOTOMETRIC PLAN1 0'5'10'20' SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 TITLE 24 CALCULATIONS A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 E502 SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 DATA SHEETS A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 D100 SHEET NO.: SHEET TITLE DATE: 02.22.24 REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-0837 2 CROMWELL IRVINE CA 92618 949-460-0460 DATA SHEETS A REV A 07.24.24 B REV B 01.08.25 C REV C 04.10.25 D REV C 06.02.25 D101C DESIGN CRITERIA BUILDING CODE: 2022 CALIFORNIA BUILDING CODE, REFERRED TO AS "THE CODE" GOVERNING JURISDICTION: CITY OF ARCADIA, CA OCCUPANCY TYPE: S-2 ROOF LIVE LOADS: DISTRIBUTED = 12 PSF * POINT LOAD = 300 LBS ** * NON-CONCURRENT W/ PV PANEL DEAD LOAD & WIND LOAD ** CONCURRENT W/ PV PANEL DEAD SNOW LOADS: MAXIMUM GROUND SNOW LOAD = 0 PSF WIND ANALYSIS: DIRECTIONAL PROCEDURE PER ASCE 7, CHAPTER 27 BASIC WIND SPEED, V = 95 MPH WIND EXPOSURE = CATEGORY C RISK CATEGORY = II GUST EFFECT FACTOR, G = 0.85 INTERNAL PRESSURE COEFFICIENT, GCpi = ±0 SEISMIC CRITERIA: SITE CLASSIFICATION = D RISK CATEGORY = II SEISMIC DESIGN CATEGORY = D SEISMIC ANALYSIS: ASCE 7-16, CHAPTER 15 SEISMIC FORCE-RESISTING SYSTEM = INVERTED PENDULUM RESPONSE MODIFICATION COEFFICIENT, R = 2.00 SYSTEM OVERSTRENGTH FACTOR, Ωo = 2.00 DEFLECTION AMPLIFICATION FACTOR, Cd = 2.00 SEISMIC IMPORTANCE FACTOR, IE = 1.0 REDUNDANCY FACTOR, ρ = 1.0 longitudinal REDUNDANCY FACTOR, ρ = 1.3 transverse Ss= 1.989g, Sds = 1.326g S1 = 0.701g SEISMIC BASE SHEAR...................................Cs = 0.663W GENERAL STRUCTURAL NOTES GENERAL 1.THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. DO NOT SCALE THE DRAWINGS. THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES. SUBMIT CLARIFICATION REQUEST PRIOR TO PROCEEDING WITH WORK. 2.ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE ISSUED. ANY DEVIATION FROM THE APPROVED SET OF CONTRACT DOCUMENTS SHALL ONLY BE MADE AFTER WRITTEN APPROVAL BY THE ENGINEER OF RECORD. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE. 3.THE STRUCTURES IN THESE CONTRACT DOCUMENTS ARE PROPRIETARY TO TEICHERT ENERGY & UTILITIES GROUP, INC. DBA TEICHERT SOLAR. THESE STRUCTURES MAY NOT GO OUT TO BID AND MUST BE BUILT BY TEICHERT SOLAR. 4.NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK. UNLESS NOTED OTHERWISE, DETAILS IN STRUCTURAL DRAWINGS ARE TYPICAL AS INDICATED BY CUTS, REFERENCES OR TITLES. 5.ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING LOCAL BUILDING CODE, AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK AND THOSE CODES AND STANDARDS LISTED IN THESE NOTES AND SPECIFICATIONS. 6.THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE ITEMS. 7.ALL REFERENCED STANDARDS (i.e. ACI, AISC, ASTM, ETC.) SHOWN IN THESE DOCUMENTS SHALL BE PER THE LATEST ADOPTED EDITION AS LISTED IN CHAPTER 35 OF THE CODE. 8.CONTRACTOR TO PROVIDE A LIST OF ALL PROPOSED SUBSTITUTIONS, WITH APPLICABLE MANUFACTURER'S ICC/IAPMO REPORTS, TO ARCHITECT, ENGINEER OF RECORD AND GOVERNING JURISDICTION FOR REVIEW AND APPROVAL BEFORE FABRICATION. SUBMITTALS 1.THE STRUCTURAL SHOP DRAWING REVIEW IS INTENDED TO HELP THE ENGINEER VERIFY THE DESIGN CONCEPT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CHECK THEIR OWN SHOP DRAWINGS. 2.THE STRUCTURAL SHOP DRAWINGS WILL BE RETURNED FOR RESUBMITTAL IF A CURSORY REVIEW SHOWS MAJOR ERRORS WHICH SHOULD HAVE BEEN FOUND BY THE CONTRACTOR'S CHECKING. 3.THE FOLLOWING SHOP DRAWINGS ARE NOT REQUIRED FOR SUBMITTAL FOR STRUCTURAL REVIEW: a.SHORING AND BRACING. b.UNSPLICED REBAR AT SLAB-ON-GRADE AND SPREAD FOOTINGS. c.FORMWORK. d.STRUCTURAL STEEL MILL REPORTS. 4.THE FOLLOWING SHOP DRAWINGS (AND CALCULATIONS WHEN APPLICABLE) ARE REQUIRED FOR SUBMITTAL FOR STRUCTURAL REVIEW: a.CONCRETE MIX DESIGNS, INCLUDING STRENGTH TEST RESULTS b.REINFORCING STEEL (EXCEPT WHERE NOTED BY NOTE 3 ABOVE) c.STRUCTURAL STEEL d.ANCHOR ROD CUT SHEET WITH DIAMETER, LENGTH, AND MATERIAL STRENGTH e.WELDING PROCEDURE SPECIFICATIONS 5.ANY SUBMITTAL OF A DETAIL SHEET WITH ADDED INFORMATION NOT SHOWN ON PLANS SHALL BE ACCOMPANIED BY LOCATION PLAN IDENTIFYING THE MEMBERS INVOLVED AND CLOUDING AROUND ADDED INFORMATION. 6.THE SHOP DRAWINGS SHALL REFERENCE THE DATA OF THE DESIGN USED TO PRODUCE THE SUBMITTAL. 7.CONTRACTOR/SUBCONTRACTOR TO PROVIDE DIGITAL SET OF SHOP DRAWINGS FOR REVIEW BY THE STRUCTURAL ENGINEER. DIGITAL SET WILL BE RETURNED TO THE CONTRACTOR FOR DISTRIBUTION. FOUNDATIONS 1.FOUNDATION DESIGN BASED ON THE FOLLOWING GEOTECHNICAL REPORT: COMPANY: KRAZAN & ASSOCIATES, INC. DATE: JANUARY 22, 2024 REPORT NUMBER: 112-23151 2.DRILLED PIERS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION: ALLOWABLE SKIN FRICTION (DOWN / UP) = 270 PSF* / 160 PSF* LATERAL BEARING CAPACITY = 137 PSF/FT * 13 ALLOWABLE INCREASE FOR WIND OR SEISMIC LOADS. 3.DE-WATERING OF EXCAVATIONS FROM EITHER SURFACE WATER, GROUND WATER, OR SEEPAGE SHOULD BE PERFORMED, IF REQUIRED. 4.FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON DRAWINGS. SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE APPROVED BY THE INSPECTOR OR SOILS ENGINEER, FOUNDATION ELEVATIONS WILL BE ALTERED. 5.FOOTING BACKFILL AND UTILITY TRENCH BACKFILL SHALL BE MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS REPORT OR BACKFILLED WITH 2-SACK SAND CEMENT SLURRY AND APPROVED BY THE SPECIAL INSPECTOR. SOILS REPORT SHALL TAKE PRECEDENT WHEN RECOMMENDATION GIVEN. 6.CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY SUCH STRUCTURES ARE FOUND, STRUCTURAL ENGINEER SHALL BE NOTIFIED IMMEDIATELY. 7.SOIL REMOVAL AND RECOMPACTION SHALL BE PER THE SOILS REPORT AND APPROVED CONTRACT DOCUMENTS. 8.THE DRILLED PIERS MUST BE INSPECTED BY THE SOILS ENGINEER PRIOR TO PLACING CONCRETE AND REINFORCING STEEL. ADJUST SHAFT LENGTHS UNDER DIRECTION OF THE SOILS ENGINEER AND THE OWNER'S REPRESENTATIVE BASED ON SOIL CONDITIONS AT TIME OF DRILLING. 9.PRECAUTIONS SHOULD BE TAKEN DURING THE INSTALLATION OF PIERS TO MINIMIZE THE POSSIBILITY OF CAVING. PIERS SPACED CLOSER 3 PIER DIAMETERS SHOULD BE DRILLED AND FILLED ALTERNATELY, ALLOWING THE CONCRETE TO SET AT LEAST EIGHT HOURS BEFORE DRILLING AN ADJACENT HOLE. 10.PIER EXCAVATIONS SHOULD BE FILLED WITH CONCRETE WITHIN 72 HOURS OR AS NOTED IN THE SOILS REPORT AFTER DRILLING AND INSPECTION, WHICHEVER IS SOONER. 11.KEEP EXCAVATIONS FREE OF WATER BEFORE PLACING CONCRETE UNLESS OTHERWISE APPROVED BY THE SOILS ENGINEER. IF UNABLE TO SEAL OFF WATER FLOW, PER THE APPROVAL OF THE SOILS ENGINEER, ALLOW WATER LEVEL TO ATTAIN ITS NORMAL LEVEL AND PLACE CONCRETE BY THE TREMIE METHOD OR OTHER APPROVED METHOD. 12.PLACE REINFORCING STEEL IN ONE CONTINUOUS UNIT AND ACCURATELY HOLD SECURELY IN FINAL POSITION USING CHAIRS OR SPACERS DURING CONCRETE PLACEMENT. 13.AN UNREINFORCED HEIGHT OF 18 INCHES AT THE BOTTOM OF THE SHAFT IS ACCEPTABLE. 14.CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF ACI 336.3R, LATEST EDITION. CONCRETE 1.ALL CONCRETE CONSTRUCTION SHALL CONFORM WITH THE CODE AND WITH THE PROVISIONS OF ACI 318 AND ACI 301. 2.CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND APPROVED BY THE STRUCTURAL ENGINEER. a.MIX DESIGN METHODS (TEST HISTORY OR TRIAL BATCH METHOD) PER THE CODE SHALL BE USED TO PROPORTION CONCRETE. SUBMIT MIX DESIGN METHOD DATA b.MIX DESIGNS SHALL SATISFY EITHER THE SHRINKAGE CRITERIA OR THE W/C RATIO AND TOTAL WATER CRITERIA. 3.SCHEDULE OF STRUCTURAL CONCRETE PERFORMANCE REQUIREMENTS: 4.PORTLAND CEMENT SHALL CONFORM TO ASTM C-150 TYPE II 5.AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS OFASTM C33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF THE STRUCTURAL ENGINEER. 6.CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C94. 7.PLACEMENT OF CONCRETE SHALL CONFORM TO ACI 301 AND PROJECT SPECIFICATIONS. CLEAN AND ROUGHEN TO MIN. 14" AMPLITUDE ALL CONCRETE SURFACES AGAINST WHICH NEW CONCRETE IS TO BE PLACED. 8.ALL REINFORCING BARS, ANCHOR BOLTS, AND OTHER CONCRETE INSERTS SHALL BE WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE. 9.PIPES OR CONDUITS LARGER THAN 4" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY PERMITTED OR APPROVED BY STRUCTURAL ENGINEER. PIPES OR CONDUITS SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS. SPACE THE PIPES OR CONDUITS SUCH THAT PROPER CONCRETE PLACEMENT AND CONSOLIDATION IS ACHIEVED. 10.PROVIDE MIN. 14" CHAMFER ON ALL EXPOSED CORNERS. 11.THE STEEL STRUCTURES MAY BE INSTALLED 24 HOURS AFTER THE FOUNDATIONS HAVE BEEN CAST OR AFTER CONCRETE REACHES A MINIMUM COMPRESSIVE STRENGTH OF 1,000-PSI,WHICHEVER COMES FIRST. BREAK TESTS NOT REQUIRED IF WAITING UNTIL 24 HOURS TO ERECT STEEL. MINIMUM CONCRETE PROPERTIES ELEMENT f'c @ 28 DAYS [PSI]MAX W/C MAX DENSITY [PCF] 24" DIAM. PIER FOUNDATIONS 3,000 0.50 150 EQUIPMENT PADS & MISC.3,000 0.50 150 SHEET INDEX S100 GENERAL STRUCTURAL NOTES S200 FRAMING PLAN & SCHEDULE S300 SECTION - 5X S400 FOUNDATION & ANCHORAGE DETAILS S500 STEEL DETAILS REINFORCING STEEL 1.REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 OF THE CODE, ASTM A615 (A706 WHERE NOTED ON PLANS), GRADE 60 U.N.O. 2.BARS SHALL BE CLEAN OF RUST, GREASE, OR OTHER MATERIALS LIKELY TO IMPAIR BOND. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. 3.REINFORCING BAR SPLICES SHALL, IN CONCRETE, CONFORM TO THE PROVISIONS OF ACI 318. LAP ALL HORIZONTAL BARS AT CORNERS AND INTERSECTIONS. 4.BARS IN SLABS SHALL BE SECURELY SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR APPROVED METAL CHAIRS, PRIOR TO PLACING CONCRETE. 5.REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH ACI 315. 6.COMPLETE AND DETAILED REINFORCING PLACEMENT DRAWINGS SHALL BE PREPARED AND SUBMITTED FOR REVIEW BY THE STRUCTURAL ENGINEER PRIOR TO FABRICATION IN ACCORDANCE WITH SPECIFICATIONS AND APPLICABLE CODES. THE APPROVED DRAWINGS SHALL BE AVAILABLE ON THE JOB SITE PRIOR TO PLACING OF CONCRETE. 7.REBAR SPACINGS GIVEN ARE MAXIMUM ON CENTER WHETHER STATED AS "O.C." OR NOT. UNLESS A SPECIFIED LENGTH IS GIVEN, ALL REBAR IS CONTINUOUS WHETHER STATED AS "CONT." OR NOT. 8.MECHANICAL BAR SPLICES (COUPLERS) SHALL BE USED WHERE SPECIFIED ON PLANS. THEY MAY ALSO BE USED AT THE CONTRACTOR'S OPTION IN LIEU OF LAP SPLICES AND WHERE REINFORCING IS SHOWN CONTINUOUS THROUGH CONSTRUCTION JOINTS. UNLESS NOTED OTHERWISE, ALL MECHANICAL BAR SPLICES SHALL BE "TYPE 2" AS DEFINED BY ACI 318. 9.COUPLERS SHALL BE AND BE LENTON A2 SERIES MECHANICAL SPLICES (IAPMO ER-0129), OR EQUIVALENT, AND INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS. 9.CONTINUOUS INSPECTION OF CONCRETE SHALL INCLUDE INSPECTION DURING INSTALLATION OF REINFORCING STEEL. INSPECTION SHALL BE SCHEDULED SO THAT PLACEMENT OF REINFORCING STEEL, CONDUIT, SLEEVES, AND EMBEDDED ITEMS, MAY BE CORRECTED PRIOR TO THE SCHEDULED POUR 10.CONCRETE PROTECTION FOR REINFORCEMENT: a.CAST-IN-PLACE CONCRETE. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT: MINIMUM CONCRETE COVER ELEMENT COVER TOLERANCE (+/-) PERMANENTLY CAST AGAINST OR PERMANENTLY EXPOSED TO EARTH 3"38" EXPOSED TO EARTH OR WEATHER a) #6 THROUGH #18 BAR 2"38" b) #5 BAR OR SMALLER 112"38" NOT EXPOSED TO WEATHER OR CAST AGAINST GROUND 34"14" STRUCTURAL STEEL 1.STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH AISC 360 AND AISC 303. 2.ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED BELOW (U.N.O.): 3.THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STEEL FOR STRUCTURAL ENGINEER'S REVIEW BEFORE FABRICATION. 4.HOLES IN STEEL SHALL BE 1/16" LARGER DIAMETER THAN NOMINAL SIZE OF BOLT USED, EXCEPT AS NOTED. COLUMN BASE PLATE HOLES MAY BE OVERSIZED PER AISC MANUAL OR AS NOTED. 5.ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, MASONRY, OR SPRAY ON FIREPROOFING, OR ARE ENCASED BY BUILDING FINISH, SHALL BE LEFT UNPAINTED. 6.ALL STRUCTURAL STEEL AND MISCELLANEOUS METAL EXPOSED TO THE WEATHER SHALL BE HOT DIP GALVANIZED OR PAINTED AFTER FABRICATION, U.N.O. 7.GALVANIZING AT FIELD WELDS AND DAMAGE SHALL BE REPAIRED WITH A GALVANIZING REPAIR PAINT ACCORDING TO ASTM A780. 8.TIGHTEN HIGH STRENGTH BOLTS TO "SNUG-TIGHT" CONDITION PER AISC SPECIFICATION FOR STRUCTURAL JOINTS, U.N.O. 9.PROVIDE BEVELED WASHERS PER ANSI B18.23.1 AS REQUIRED ON SLOPED SURFACES. 21.GROUT OTHER SHALL BE NON-SHRINK, NON-METALLIC GROUT, MEETING ASTM C-1107, MIXED AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. 22.TIGHTEN ANCHOR BOLTS TO "SNUG TIGHT" CONDITION PER AISC SPECIFICATIONS, U.N.O. 23.WELDING: 24.ALL WELDS SHALL BE IN CONFORMITY WITH THE PROJECT SPECIFICATIONS AND AWS D1.1, SEE SPECIAL INSPECTION SECTION FOR WELDING INSPECTION REQUIREMENTS. a.ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING E70XX ELECTRODES (U.N.O.). b.WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360. c.WELDS TERMINATING AT ENDS OR SIDES, WHERE PRACTICAL, SHALL BE RETURNED CONTINUOUSLY AROUND CORNERS A DISTANCE 2 TIMES THE NOMINAL SIZE OF THE WELD PER AISC 360 SECTION J2.2B, U.N.O. d.ALL FULL-PENETRATION FIELD WELDS SHALL BE ULTRASONICALLY TESTED. e.ALL TWO-SIDED FILLET WELDS SHOWN SHALL BE WELDED WITH THE SAME (GIVEN) WELD SIZE ON BOTH SIDES. f.ALL UNSIZED GROOVE OR BUTT WELDS SHOWN SHALL BE COMPLETE PENETRATION. g.ALL PROVISIONS OF AWS SHALL BE OBSERVED INCLUDING REQUIREMENTS FOR BACK-UP PLATES AND WELD TRANSITIONS WHETHER OR NOT THEY ARE SPECIFICALLY SHOWN. h.A WRITTEN WELDING PROCEDURE SPECIFICATION SHALL BE SUBMITTED TO THE TESTING LABORATORY. IT SHALL INCLUDE ALL WELDING PROCEDURES TO BE USED AS DESCRIBED IN AWS, CHAPTER 4. i.WHERE FIELD WELDING IS INDICATED, THE FIELD DESIGNATION IS GIVEN AS A RECOMMENDATION ONLY. MINIMUM MATERIAL PROPERTIES ELEMENT ASTM BASE PLATES & CAP PLATES A572, GR 50 ALL OTHER PLATES A36, GR 36 OR DUAL GRADE WF MATERIAL A992, GR 50 HSS MATERIAL A500, GR C STRUCTURAL PIPES A53, GR B HIGH STRENGTH BOLTS A325 MACHINE BOLTS A307 ANCHOR BOLTS F1554, GR 105 POST-INSTALLED CONCRETE ANCHORS 1.POST-INSTALLED ANCHORAGE SHALL BE AS DETAILED ON THE PLANS. SUBSTITUTION OF PRODUCTS SPECIFICALLY DETAILED IN THESE DRAWINGS SHALL NOT BE ALLOWED WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD. 2.SPECIAL INSPECTION IS REQUIRED FOR ALL POST-INSTALLED ANCHORS, U.N.O. 3.WHERE ANCHOR TYPE IS NOT NOTED OR AN ALTERNATE BRAND IS PREFERRED, THE FOLLOWING PRODUCTS ARE ACCEPTABLE TO BE SUBMITTED FOR A SUBSTITUTION REQUEST: EXPANSION ANCHORS a.HILTI KWIK BOLT TZ (ICC ESR-1917) b.SIMPSON STRONG-BOLT-2 (ICC ESR-3037) c.POWERS POWER-STUD +SD2 (ICC ESR-2502) d.ALTERNATE APPROVED BY THE SEOR 4. ALL CONCRETE ANCHORS WHICH ARE EXPOSED TO THE WEATHER SHALL BE STAINLESS STEEL OR HOT DIP GALVANIZED. COLD FORMED STEEL 1.ALL COLD-FORMED METAL FRAMING CONSTRUCTION SHALL BE IN ACCORDANCE WITH AISI S100 "SPECIFICATIONS FOR DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS". 2.ALL COLD-FORMED STEEL SHALL CONFORM TO THE FOLLOWING (U.N.O): 3.ALL COLD-FORMED STEEL SHALL HAVE A MINIMUM COATING PROTECTION G90. 4.WELDING IS NOT PERMITTED UNLESS SPECIFICALLY APPROVED BY THE SEOR. 5.ALL APPROVED WELDING SHALL BE PERFORMED BY WELDERS CERTIFIED FOR ALL APPROPRIATE DIRECTIONS COMPLYING WITH AWS D1.3. WELDING RODS SHALL CONFORM TO THE FOLLOWING: 6.WIRE TYING OF FRAMING COMPONENTS SHALL NOT BE PERMITTED. 7.TEMPORARY BRACING REQUIREMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR. 8.ALL SCREWS SHALL BE FULLY DRIVEN AND PROTRUDE THE LARGER OF 3 THREADS OR 1/4" THROUGH THE LAST MATERIAL JOINED. THERE SHALL BE NO SPACE BETWEEN JOINING MEMBERS AT THE SCREW LOCATION. 9.ALL FIELD CUTTING OF MEMBERS SHALL BE BY SAWING OR SHEARING. TORCH OR PLASMA CUTTING OF MEMBERS SHALL NOT BE PERMITTED. 10.ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS OR AS REQUIRED ON AN ANGULAR FIT AGAINST ABUTTING MEMBERS. MEMBERS SHALL BE HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED. 11.SPLICING OF PURLINS OR OTHER LOAD CARRYING MEMBERS SHALL NOT BE PERMITTED UNLESS SPECIFICALLY APPROVED BY THE ENGINEER OF RECORD. 12.WHEN CLIP ANGLES WITH SCREW CONNECTIONS ARE USED TO ATTACH A COMPONENT TO THE PRIMARY STRUCTURE, THE CLIP ANGLE SHALL BE FASTENED TO THE PRIMARY STRUCTURE FIRST; THEN THE COMPONENT SHALL BE BROUGHT TO BEAR ON THE STRUCTURE AND FASTENED TO THE CLIP ANGLE. 13.MEMBERS SHALL BE IDENTIFIED PER SECTION 2203.1 OF 2016 CBC PART 2, VOL. 2. 14.ALL EXTERIOR SCREWS SHALL BE ELCO DRIL-FLEX (ICC ESR-3332) OR ITW BUILDEX TEKS SELECT (ICC ESR-3223) UNLESS APPROVED BY THE SEOR. 43 MIL / 18GA AND LIGHTER ASTM A1003, GR 33 OR ASTM 653, GR 33 54 MIL / 16 GA AND HEAVIER ASTM A1003, GR 55 OR ASTM 653, GR 55 MIN. Fy = 55 ksi, MIN. Fu = 70 ksi 43 MIL / 18GA AND LIGHTER E60XX 54 MIL / 16 GA AND HEVIER E70XX OR E6013 COLD FORMED TO STRUCTURAL STEEL E70XX LOW HYDROGEN STRUCTURAL INSPECTION AND TESTING THE FOLLOWING ELEMENTS OF CONSTRUCTION SHALL REQUIRE SPECIAL INSPECTION PER CHAPTER 17 OF THE CODE. U.N.O. SPECIAL INSPECTIONS AND TESTING SHALL BE PROVIDED BY AN INSPECTION AGENCY, EMPLOYED BY THE OWNER, AND QUALIFIED BY THE BUILDING OFFICIAL TO INSPECT THE PARTICULAR TYPE OF CONSTRUCTION. TESTS AND INSPECTIONS, AS REQUIRED BY SECTIONS 110 & 1705 OF THE 2016 CBC W/ CALIFORNIA AMENDMENTS, SHALL BE PERFORMED DURING CONSTRUCTION ON THE TYPES OF WORK LISTED BELOW: 1.THE SPECIAL INSPECTIONS IDENTIFIED ON PLANS ARE, IN ADDITION TO, AND NOT A SUBSTITUTE FOR, THOSE INSPECTIONS REQUIRED TO BE PERFORMED BY THE GOVERNING JURISDICTION. SPECIALLY INSPECTED WORK WHICH IS INSTALLED OR COVERED WITHOUT THE APPROVAL OF AN INSPECTOR FROM THE GOVERNING JURISDICTION IS SUBJECT TO REMOVAL OR EXPOSURE. 2.FOR CONTINUOUS INSPECTION, WHEN WORK IN MORE THAN ONE CATEGORY OF WORK REQUIRING SPECIAL INSPECTION IS TO BE PERFORMED SIMULTANEOUSLY, OR THE GEOGRAPHIC LOCATION OF THE WORK IS SUCH THAT IT CANNOT BE CONTINUOUSLY OBSERVED IN ACCORDANCE WITH THE PROVISIONS OF THE CODE, IT IS THE AGENT'S RESPONSIBILITY TO EMPLOY A SUFFICIENT NUMBER OF INSPECTORS TO ASSURE THAT ALL WORK IS INSPECTED IN ACCORDANCE WITH THOSE PROVISIONS. 3.THE SPECIAL INSPECTORS MUST BE CERTIFIED BY THE GOVERNING JURISDICTION IN THE CATEGORY OF WORK REQUIRED TO HAVE SPECIAL INSPECTION. EXCEPTIONS: a.SOILS INSPECTIONS BY THE SOILS ENGINEER OF RECORD OR PROJECT INSPECTOR b.WHEN WAIVED BY THE GOVERNING JURISDICTION 5.IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INFORM THE OWNER'S REPRESENTATIVE, SPECIAL INSPECTOR OR INSPECTION AGENCY AT LEAST TWO WORKING DAYS PRIOR TO PERFORMING ANY WORK THAT REQUIRES SPECIAL INSPECTION. ALL WORK PERFORMED WITHOUT REQUIRED SPECIAL INSPECTION IS SUBJECT TO REMOVAL. 6.PROVIDE SPECIAL INSPECTION FOR CONNECTIONS BOLTED WITH A325 AND A490 BOLTS. INSPECTIONS SHALL BE DONE PER APPROVED NATIONALLY RECOGNIZED STANDARDS AND THE REQUIREMENTS OF THE CODE AND THE GOVERNING JURISDICTION. WHILE THE WORK IS IN PROGRESS, THE SPECIAL INSPECTOR SHALL DETERMINE THE BOLTS, NUTS, WASHERS AND PAINT; BOLTED PARTS; AND INSTALLATION AND TIGHTENING MEET THE STANDARDS REQUIREMENTS. 7.THE SPECIAL INSPECTOR FOR HIGH STRENGTH BOLTED CONNECTIONS SHALL: a.OBSERVE THE CALIBRATION PROCEDURES WHEN SUCH PROCEDURES ARE REQUIRED BY THE PLANS OR SPECIFICATIONS. b.MONITOR THE INSTALLATION OF BOLTS TO DETERMINE THAT ALL PLIES OF CONNECTED MATERIALS HAVE BEEN DRAWN TOGETHER. c.MONITOR THAT THE SELECTED PROCEDURE IS PROPERLY USED TO TIGHTEN ALL BOLTS. 8.IF DEEMED NECESSARY, THE SPECIAL INSPECTOR SHALL PROVIDE PROGRESS REPORTS AND A FINAL REPORT TO THE STRUCTURAL ENGINEER. 9.THE SPECIAL INSPECTOR SHALL ENSURE THAT ALL DEFICIENCIES NOTED BY THE STRUCTURAL ENGINEER IN STRUCTURAL OBSERVATION REPORTS ARE CORRECTED. SUCH COMPLIANCE SHALL BE REFERENCED IN SPECIAL INSPECTOR REPORT. 10.THE CONSTRUCTION MATERIALS TESTING LABORATORY MUST BE APPROVED BY THE GOVERNING JURISDICTION, FOR TESTING OF MATERIALS, SYSTEMS, COMPONENTS AND, EQUIPMENTS. 11.PERIODIC INSPECTION SHALL OCCUR FREQUENTLY ENOUGH TO INSPECT ALL OF THE INSTALLED ITEMS AND TO PERIODICALLY WITNESS THE INSTALLATION OF THE ITEMS. TESTING AND INSPECTION INSPECTIONS TESTING STEEL CONSTRUCTION 1706.2 1705.13 CONCRETE CONSTRUCTION 1705.3 1705.3 SOILS 1705.6 CAST IN-PLACE DEEP FOUNDATIONS 1705.8 GENERAL STRUCTURAL NOTES S100 SHEET NO.: SHEET TITLE DATE: REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 1 FRAMING PLAN SCALE: 14" = 1'-0" 2 SCHEDULE NO SCALE ARRAY SIZE # OF COLUMNS COLUMN BEAM PURLIN PANEL LENGTH PANEL WIDTH SPAN LENGTH, Lspan MAX* CANT. LENGTH, Lcant MAX* SPLICE LENGTH, Lsplice MAX. COLUMN LENGTH MIN. CLEARANCE 5X37 4 HSS12x8x12 W14x30 12X4X14GA w/ 1.1" LIP 89.7"44.6"41'-3"14'-11 7/8"7'-6"15'-0"10'-0" A B PU R L I N E N D C A P BE A M P E R S C H E D U L E COLU M N P E R SCH E D U L E BE A M P E R S C H E D U L E COLU M N P E R SCH E D U L E PURLIN SPLICE PER , TYP.7 S500 Lcant PER SCHEDULE Lspan PER SCHEDULE Lspan PER SCHEDULE PV PANELS = 2.5-PSF MAX, DIMS PER SCHEDULE 3 S500 12 S500 TYP. Lsplice PER SCHEDULE 5 S500 TYP. BLOCKING, TYP. EQ.EQ.EQ.EQ.EQ.EQ. PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE C D PU R L I N E N D C A P BE A M P E R S C H E D U L E COLU M N P E R SCH E D U L E BE A M P E R S C H E D U L E COLU M N P E R SCH E D U L E PURLIN SPLICE PER , TYP.7 S500 Lspan PER SCHEDULE Lcant PER SCHEDULE 12 S500 TYP. EQ.EQ.EQ. PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE PURLIN PER SCHEDULE 1 S310 TYP. *REFERENCE SHEET A1.0 FOR COLUMN LAYOUT SHEET NO.: SHEET TITLE DATE: REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 FRAMING PLAN & SCHEDULE S200 1 SECTION SCALE: 12" = 1'-0" BEAM PER SCHEDULE COLUMN PER SCHEDULE 10 ' - 0 " MI N . C L E A R A N C E DRILLED PIER FOUNDATION EQ. EQ. ℄ COLUMN PURLINS PER SCHEDULE PANEL LENGTH PER SC H E D U L E ELECTRICAL EQUIPMENT, WHERE OCCURS 18 S400 14 S500 20 S500 5 S500 8 S500 CO L U M N L E N G T H P E R S C H E D U L E O N S 2 0 0 5.00° SHEET NO.: SHEET TITLE DATE: REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 SECTION - 5X S300 17 WALL MOUNTED EQUIPMENT SCALE: 12" = 1'-0" 6"MAX. Wp = 100# MAX. (E) SOLID GROUTED CMU WALL, 8" MIN. (4) 38" DIAM. HILTI KB3 ANCHORS W/ 212" EMBED (ICC ESR: 1385) 6"MAX. Wp = 100# MAX. (E) CONC. WALL, 6" MIN. (4) 38" DIAM. HILTI KB-TZ ANCHORS W/ 2" EMBED (ICC ESR: 1917) 6"MAX. Wp = 100# MAX. (E) CFS STUD WALL, MIN. 20GA & @ 24" O.C. P1000 STRUT, T&B ALIGNED W/ UNIT MOUNTING HOLES W/ 14" DIAM. A307 BOLTS IN EQUIPMENT HOLES #12 SMS TO MIN. (2) STUDS 6"MAX. Wp = 100# MAX. (E) WOOD STUD WALL @ 24" O.C. P1000 STRUT, T&B ALIGNED W/ UNIT MOUNTING HOLES W/ 14" DIAM. A307 BOLTS IN EQUIPMENT HOLES #12 WOOD SCREWS TO MIN. (2) STUDS W/ 10D PENETRATION 12" DIA. HILTI KWIK BOLT TZ2 w/ 212" EMBED, MIN OF (4) ANCHORS ELECTRICAL EQUIPMENT, MAX WEIGHT = 1000# 7 EQUIPMENT PAD SCALE: 1" = 1'-0" EQ . EQ . 5"MIN.2" MI N . 6" #4 @ 16" O.C., E.W. CONC. PAD, f'c,min = 3,000 PSI PAD SIZE: 46"X46"X6" DEEP Hc g = 4 0 " ( M A X ) HILTI KWIK BOLT TZ2 (ICC ESR 4266) ANCHORS, PER SCHEDULE Wp = 550# (MAX) (N) OR (E) CONC. SLAB PER 15/- D = 24" (MIN) H = 8 0 " ( M A X ) ELECTRICAL EQUIPMENT 9 SLAB MOUNTED EQUIPMENT SCALE: 12" = 1'-0" 3 GENERIC PAD SCALE: 1" = 1'-0" Hc g ( M A X ) Wp (MAX) CONC. SLAB PER SCHEDULE W (MIN) H ( M A X ) ELECTRICAL EQUIPMENT PER SCHDULE PAD MOUNTED EQUIPMENT SCHEDULE TYPE TYP. EQUIPMENT EV CHARGER PEDESTAL NUMBER OF ANCHORS 4 4 ANCHOR DIA.12" DIA.12" DIA. MIN SLAB THICKNESS 6"12" LENGTH, L 27" MAX 7.4" MAX WIDTH, W 28.25" MAX 7.4" MAX HEIGHT, H 36" MAX 20.5" MAX HEIGHT (C.O.G.), Hcg 18" MAX 10.25" MAX WEIGHT, Wp 770-LBS MAX 35-LBS MAX CONCRETE SLAB PER NOTES: 1. INSTALL HILTI KB-TZ2 PER ICC ESR-4266 WITH SPECIAL INSPECTION. 2. FOR 1/2" DIA ANCHORS, PROVIDE MIN 212" EMBED, MIN 6" THICK CONCRETE, MIN 6" EDGE DISTANCE, AND 6" MIN SPACING IN MIN 3,000 PSI NORMAL WT. CONC. PAD TORQUE TO 40. 7 - 1 - NOTE: ONLY ONE LAYER OF REBAR 8 SCALE: 3" = 1'-0" REINF. PLACEMENT SPIRAL REINF. VERT REINF., TYP. CONC. PIER ℄ OF PIER ℄ OF PIER 3" CLR. CONDUIT PER ELECTRICAL, WHERE OCCURS DE P T H P E R 1 8 / - (N)TRENCH AT ALL CONDUIT RUNS, BACKFILL w/ TWO-SACK SLURRY U.O.N. IN GEOTECHNICAL REPORT 19 CONDUIT ROUTING SCALE: 12" = 1'-0" 1' - 6 " M I N . CO L U M N H T . ' H ' P E R S C H E D U L E ME A S U R E D F R O M T O P O F S T R U C T U R E P I E R 12 " M A X (E) NATURAL GRADE OR HARDSCAPE, REPAIR AND REPLACE AS NEEDED T.O.CONDUIT TRENCH 30 " M A X FINISHED GRADE EM B E D M E N T P E R S C H E D U L E COLUMN PER SCHEDULE 2'-0"Ø #4 SPIRAL REINF. @ 112" PITCH (3 TURNS) 2"MA X C O V E R MI N . 3 ' - 6 " EM B E D M E N T #4 S P I R A L R E I N F . @ 4 . 5 " P I T C H EX T E N D E D T O 6 ' - 0 " B E L O W G R A D E #4 S P I R A L R E I N F . @ 9 " PI T C H F O R R E S T VERT REINF. PER SCHEDULE 3" M I N C O V E R 12 " M A X C O V E R 18 PIER FOUNDATION SCALE: 12" = 1'-0" OPTIONAL COLD JOINT 1' - 6 " MI N . CONDUITS PER ELECT. 4" MAX DIAM. 34" DIAM. x 3" WELDED STUDS, EA SIDE, (4) TOTAL 6" 1' - 0 " 8- f'c = 3,000 PSI ARRAY PIER EMBEDMENT VERT REINF. 5X37 16'-0"(10) #6 SHEET NO.: SHEET TITLE DATE: REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 FOUNDATION & ANCHORAGE DETAILS S400 1 EV CHARGER BASE CONNECTION PLAN SCALE: 1" = 1'-0" CHARGING STATION PAD SIZE: 12"x12"x12" DEEP w/ (4) #4 EACH WAY, TOP AND BOTTOM FOOTING (4) 12" DIA. HILTI KWIK BOLT TZ2 ANCHORS EV CHARGER A A SECTION A-A BACK LE F T RI G H T FRONT (4) 0.47"Ø THRU METAL BASE PLATE FOR 20.5"X7.4"X7.4" PEDESTAL PER MANUFACTURER 2" C L R 3" CLR TYP 3" C L R 814" 118" 618" 118" 618" 53 8" 1' - 0 5 8" 5 PURLIN BLOCKING SCALE: 12" = 1'-0" PURLIN PER PLAN 12" MAX. 9"x2"x18GA BLOCKING 4 - 3 END CAP CONN. DETAIL SCALE: 3" = 1'-0" 112"12" MIN. PURLIN PER PLAN #12 SMS, T&B, EA PURLIN PV PANEL CONT. 18GA (MIN.) END CAP STIFF ⅊ 38" GR. 50, ALIGN W/ COLUMN FLANGES 10 STIFFENER PLATE SCALE: 3" = 1'-0" 14 14" MAX. 'K'PER AISC 6" 112" (4) 12" DIAM. A307 BOLTS 112" ℄ OF SPLICE PER PLAN 7" 112"13 4"112"13 4" 9" ⅊ 10GA (55 KSI) PURLIN PER PLAN 7 PURLIN SPLICE SCALE: 3" = 1'-0" 4 BLOCKING TO PURLIN CONN. SCALE: 3" = 1'-0" 3" 8" 1" 1" 3" PURLIN PER PLAN BLOCKING PER PLAN 2x2x16GAx10" LONG BLKG CLIP W/ (2) 12" DIAM. A307 BOLTS IN EACH LEG 12 BEAM TO PURLIN CONN. SCALE: 3" = 1'-0" 314" 6" 112" 3"3" BENT ⅊ 516" GR. 50 (2) 12" DIAM. A307 BOLTS, EA. LEG, W/ WASHERS EA. FACE BEAM PER PLAN PURLIN PER PLAN 14 20 BEAM TO COLUMN CONN. SCALE: 112" = 1'-0" COLUMN PER PLAN BEAM PER PLAN STIFF. ⅊ PER 10 - 19 - 8 BEAM END DETAIL SCALE: 112" = 1'-0" BEAM PER PLAN 6" 3" 2'-6" R 1 4" R1 4" 14 EQUIPMENT MOUNTING SCALE: 112" = 1'-0" Wp = 250# MAX. COLUMN PER PLAN UNISTRUT P1000, (2) PER UNIT ALIGNED W/ MOUNTING HOLES 3 8" DIAM. A307 BOLT (2) #12 SMS ELECT. EQUIPMENT, WHERE OCCURS 2" 19 CAP PLATE SCALE: 112" = 1'-0" ℄ ℄ 1" M I N . 134" M A X . tW 1" M I N . 134" M A X . GA G E PE R A I S C 214"2"MIN. CAP ⅊ 138" (A572) (4) 1" DIAM. A325, PRE-TENSIONED 12" MI N . ARRAY WELD 5X37 tW = 5/16 2" 516" DIAM. F593C SERRATED FLANGE PANEL BOLT AND NUT IN HOLES BY MFR., 12-15 FT-LBS TORQUE PV PANEL PURLIN PER PLAN 17 PV PANEL ATTACHMENT SCALE: 6" = 1'-0" WEEB 12" GAP PURLIN BELOW ALIGNED W/ PANEL MOUNTING HOLES PE R S C H E D U L E PER SCHEDULE 12" GA P PV PANELS SHEET NO.: SHEET TITLE DATE: REVISION DATENO. HOLY ANGELS CATHOLIC CHURCH ARCADIA PROJECT 370 CAMPUS DR, ARCADIA, CA 91007 ARCHITECT / ENGINEER OF RECORD ARCHITECT OF RECORD M M P V d e s i g n MARIANA MONCADA, ARCHITECT 718 WEST ARBOR DRIVE SAN DIEGO, CA 92103 619.632.2883 SYSTEM DEVELOPER SYSTEM HOST ELECTRICAL CONSTRUCTORS AND ENGINEERS STRUCTURAL ENGINEERING AND STEEL CONSTRUCT 370 CAMPUS DR ARCADIA, CA 91007 626-447-1671 10620 TREENA STREET, STE. 140 SAN DIEGO, CA 92131 562-283-2970 2514 JAMACHA ROAD #502-182 EL CAJON, CA 92019 619-333-6703 2 CROMWELL IRVINE CA 92618 949-460-0460 STEEL DETAILS S500 PERMIT CORRECTIONS REPORT (Comm-24-1833) FOR CITY OF ARCADIA, CA PARCEL:5778012001PERMIT ADDRESS:370 CAMPUS DR Arcadia, CA 91007 APPLICATION DATE:09/11/2024 EXPIRATION DATE:09/11/2025 SQUARE FEET: 5,208.00 VALUATION:$559,776.00 DESCRIPTION:NEW COVERED SOLAR CARPORT 37' X138' CONTACTS NAME COMPANY ADDRESS Applicant Dianna Mauricio Mesa Energy Systems 2 Cromwell, Irvine, CA 92618 Irvine, CA 92618 Building Review (Comm Add/Alt) REVIEW ITEM STATUS REVIEWER Building Review v.1 Ali Doudar Ph: (626) 574-5419 email: adoudar@arcadiaca.gov Requires Re-submit [14/14] Building Department Building Review v.2 Ali Doudar Ph: (626) 574-5419 email: adoudar@arcadiaca.gov Requires Re-submit [14/14] Building Department Fire Department Review v.1 Mark Krikorian email: mkrikorian@arcadiaca.gov Approved [14/14] Fire Department (Inherit) Planning/Zoning Review-Building v.1 Edwin Arreola email: earreola@arcadiaca.gov Conditionally Approved [14/14] Planning/Zoning Department (Inherit) Page 1 of 2City of Arcadia, 240 West Huntington Drive, P.O. Box 60021, Arcadia, CA 91066-6021May 12, 2025 PERMIT CORRECTIONS REPORT (Comm-24-1833) eReview Session for Building Review (Comm Add/Alt) v.2 FILES:Emcor_Holy Angels_Tap Design-Stamped_12-1-23 (1).pdf GeotechReport (Holy Angels Church Arcadia).pdf HOLY ANGELS COMBINED DWG V2.pdf Holy Angels Structural Calculations - 2024.07.23.pdf REVIEWER MARKUP DATE/TIME FILE NAME PG # Ali Doudar Provide fully dimensioned EV Plan. Dimensions 4' minimum width for all accessible routes. Specify length and width for all stalls and access aisle. 05/08/2025 11:06 pm HOLY ANGELS COMBINED DWG V2.pdf 3 Ali Doudar Is this a zero curb transition? Provide a curb ramp for access to raised curbs. CBC 11B-406, 11B-705 05/08/2025 11:10 pm HOLY ANGELS COMBINED DWG V2.pdf 2 Ali Doudar Specify width of detectable warnings. 48" minimum.05/08/2025 11:12 pm HOLY ANGELS COMBINED DWG V2.pdf 4 Ali Doudar Provide clear floor space in front of EV charger in accordance with 11B-812.10.3,11B-707.2, 11B-305. Consider placing charger further back. 05/08/2025 11:42 pm HOLY ANGELS COMBINED DWG V2.pdf 3 Ali Doudar Include specification sheet for EV charger on plans.05/09/2025 12:19 am HOLY ANGELS COMBINED DWG V2.pdf 4 Ali Doudar Provide table analysis for number of EV capable spaces and number of required EVCS in accordance with CALGreen table 5.106.5.6.3.1 or using the power allocation method in CALGreen Table 5.106.5.3.6. Indicate level 1, low power level 2, level 2, or DCFC for EVSE (service equipment) and EVCS (capable spaces), CALGreen §5.106.5.3.2 For purpose of determining the number of altered parking spaces resulting from the photo voltaic carport; shall be 26 spaces. 05/09/2025 6:12 pm HOLY ANGELS COMBINED DWG V2.pdf 3 Ali Doudar Existing path of travel shall not exceed a 5% running slope and 2.08% cross slope. Note on plans inspector to verify. 05/09/2025 7:35 pm HOLY ANGELS COMBINED DWG V2.pdf 3 Ali Doudar Include EVCS and EVSE on scope of work.05/09/2025 7:51 pm HOLY ANGELS COMBINED DWG V2.pdf 1 Page 2 of 2City of Arcadia, 240 West Huntington Drive, P.O. Box 60021, Arcadia, CA 91066-6021May 12, 2025 SEE CHARGER SPECS ON SHT. D101 MOVED BACK CLR FLOOR SPACE ADDED DIMS ADDED DIMS ADDED DIMS ADDED ADDED "LEVEL 2" ON KEYNOTES ADDED IN LEGEND AND AS NOTE #3 ADDED AS NOTE #3 TABLE ANALYSIS ADDED ADDED UNDER SCOPE OF WORK DIMS ADDED yes, revised location of truncated domes yes no raised curbs 12/01/2023 San Diego Office 10620 Treena Street, #140 San Diego, CA 92131 916.484.3011 www.teichert.com Structural Calculations for Holy Angels Catholic Church Arcadia 370 Campus Dr Arcadia, CA 91007 Date: 1/14/2025 The calculations provided herein are the property of Teichert Solar and may be used solely for the project located at the address noted. Project: Holy Angels Designer: MR Date: 7/22/2024 Basis of Design Codes 2022 California Building Code ASCE 7-16 Minimum Design Loads and Associated Criteria for Buildings and Other Structures ACI 318-14 AISC 360 AISI S100 Material Properties Cold Rolled Steel Purlins Fy = 55ksi Hot Rolled Steel Fy = 50 ksi Concrete Piers f'c = 3000 psi Reinforcing Steel fy = 60 ksi Seismic Design Data: ASCE 7-16 Risk Category II Importance Factor 1.0 Ss 1.989 S1 0.701 Sds 1.326 Site Class D Seismic Design Cat. D Analysis Procedure Equiv. Lateral Force Wind Design Data: ASCE 7-16 Basic Wind Speed 95 Exposure Category C Enclosure Category Open Scope of Work The project consists of new solar carport canopy structures. The roof framing consists of cold-formed steel C- shaped purlins and hot-rolled wide-flange beams. The lateral resistance is provided by HSS steel cantilevered columns. The foundation consists of cast-in place concrete caissons. A RISA 3D model for the 5x37 array was made to analyze and design the framing. Project: Holy Angels Designer: MR Date: 7/22/2024 Load Information Purlin Trib 3.74 ft Superimposed DL 2.5 psf wdl= 9.34625 wdl= 4.673125 Superimposed DL, plf 9.35 plf Uniform LL 12 psf wll= 44.862 wll= 22.431 Uniform LL, plf 44.86 plf Seismic Sds 1.326 g Ie 1.0 System Inverted Pendulum R 2 Cd 2 Omega 2 Cs 0.663 *W Csmin 0.058 *W Cs 0.663 *W Ex = Cs*DL*Trib = 6.20 plf Ez = Cs*DL*Trib = 6.20 plf FULL TRIB HALF TRIB Project:Holy Angels Designer:MR Date: Wind Loads - MWFRS (Directional Procedure) [ASCE 7-16 Ch. 27] V 95 mph Exp Category C Kd 0.85 wind directionality factor Kzt 1.00 topographic factor Ke 1.00 ground elevation factor Kz 0.86 for exp C velocity pressure coefficient G 0.85 Gust-effect factor L 138.72 ft min array length B 37.55 ft array width hmax 16.00 ft slope 5.00° q 16.90 psf CN Coefficients per Fig. 27.3-4 and Resulting Design Pressures per Eqn. 27.3-2: Clr/Obs γ θ CNW pNW (psf) pNW (plf) CNL pNL (psf) pNL (plf) Clear 0°5°1.2 17.2 -64.4 0.3 4.3 -16.1 Obs 0°5°-0.5 -7.2 26.8 -1.2 -17.2 64.4 Clear 180°5°1.2 17.2 -64.4 0.3 4.3 -16.1 Obs 180°5°-0.5 -7.2 26.8 -1.2 -17.2 64.4 Clear 0°5°-1.1 -15.8 59.1 -0.1 -1.4 5.4 Obs 0°5°-1.1 -15.8 59.1 -0.6 -8.6 32.2 Clear 180°5°-1.1 -15.8 59.1 -0.1 -1.4 5.4 Obs 180°5°-1.1 -15.8 59.1 -0.6 -8.6 32.2 Note: Highlighted cells apply to upper purlins in RISA 3D model CN Coefficients per Fig. 27.3-7 and Resulting Design Pressures per Eqn. 27.3-2: For 90 deg and 270 degree wind loading: Flow CN(h) p(h), psf p(h), plf CN (mid) p(mid), psf p(mid), plf CN(2h) p(2h), psf p(2h), plf Clear -0.8 -11.49 42.96 -0.6 -8.62 32.22 -0.3 -4.31 16.11 Obs -1.2 -17.24 64.44 -0.9 -12.93 48.33 -0.6 -8.62 32.22 Clear 0.8 11.49 -42.96 0.5 7.18 -26.85 0.3 4.31 -16.11 Obs 0.5 7.18 -26.85 0.5 7.18 -26.85 0.3 4.31 -16.11 Note: Case B Clear wind flow governs for positive pressure Case A Obstructed wind flow governs for negative pressure Highlighted cells are applied to purlins in RISA 3D model for Ca s e B Case A Case B < h h < x < 2h 2h < Ca s e A 7/22/2024 x Project:Holy Angels Designer:MR Date:7/22/2024 CN Coefficients for C&C, Ch. 30, Fig 30.7-1 Effective Wind Area 518.60 sf a 3.76 ft a2 14.10 sf 4a2 56.41 sf (+)(-)(+)(-)(+)(-)(+)(-)(+)(-)(+)(-) EWA < a2 2.93 -4.60 -157.5 247.0 2.20 -2.33 -118.1 125.3 1.47 -1.53 -78.8 82.3 a2 < EWA < 4a2 2.20 -2.33 -118.1 125.3 2.20 -2.33 -118.1 125.3 1.47 -1.53 -78.8 82.3 4a2 < EWA 1.47 -1.53 -78.8 82.3 1.47 -1.53 -78.8 82.3 1.47 -1.53 -78.8 82.3 Zone 1 (plf)Zone 3 (CN) Zone 2 (CN) Zone 1 (CN)Zone 3 (plf) Zone 2 (plf) RISA 3D MODEL GRAPHICS Teichert Solar MR Holy Angels 5x37 SK-21 Jul 22, 2024 at 10:52 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-22 Jul 22, 2024 at 10:53 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-24 Jul 22, 2024 at 10:54 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-25 Jul 22, 2024 at 10:54 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-26 Jul 22, 2024 at 10:54 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-27 Jul 22, 2024 at 10:55 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-28 Jul 22, 2024 at 10:55 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-29 Jul 22, 2024 at 10:55 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-30 Jul 22, 2024 at 10:55 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-31 Jul 22, 2024 at 10:56 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-32 Jul 22, 2024 at 10:56 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-33 Jul 22, 2024 at 10:56 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-34 Jul 22, 2024 at 10:56 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-35 Jul 22, 2024 at 10:56 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-36 Jul 22, 2024 at 10:57 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-37 Jul 22, 2024 at 10:57 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-38 Jul 22, 2024 at 10:57 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-39 Jul 22, 2024 at 10:57 AM 5x30.r3d Teichert Solar MR Holy Angels 5x37 SK-20 Jul 22, 2024 at 10:49 AM 5x30.r3d Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:50:49 AM RISA-3D Version 22 [ 5x30.r3d ]Page 1 Hot Rolled Steel Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Density [k/ft³]Yield [ksi]Ry Fu [ksi]Rt 1 A992 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1 2 A36 Gr.36 29000 11154 0.3 0.65 0.49 36 1.5 58 1.2 3 A572 Gr.50 29000 11154 0.3 0.65 0.49 50 1.1 65 1.1 4 A500 Gr.B RND 29000 11154 0.3 0.65 0.527 42 1.4 58 1.3 5 A500 Gr.B RECT 29000 11154 0.3 0.65 0.527 46 1.4 58 1.3 6 A500 Gr.C RND 29000 11154 0.3 0.65 0.527 46 1.4 62 1.3 7 A500 Gr.C RECT 29000 11154 0.3 0.65 0.527 50 1.4 62 1.3 8 A53 Gr.B 29000 11154 0.3 0.65 0.49 35 1.6 60 1.2 9 A1085 29000 11154 0.3 0.65 0.49 50 1.4 65 1.3 10 A913 Gr.65 29000 11154 0.3 0.65 0.49 65 1.1 80 1.1 Cold Formed Steel Properties Label E [ksi]G [ksi]Nu Therm. Coeff. [1e⁵°F⁻¹]Density [k/ft³]Yield [ksi]Fu [ksi] 1 A653 SS Gr33 29500 11346 0.3 0.65 0.49 33 45 2 A653 SS Gr55/1 29500 11346 0.3 0.65 0.49 55 70 Hot Rolled Steel Section Sets Label Shape Type Design List Material Design Rule Area [in²]Iyy [in⁴]Izz [in⁴]J [in⁴] 1 Column-1 HSS12X8X8 Column Tube A500 Gr.C RECT Typical 17.2 178 333 377 2 Beam-1 W14X30 Beam Wide Flange A992 Typical 8.85 19.6 291 0.38 Cold Formed Steel Section Sets Label Shape Type Design List Material Design RuleArea [in²]Iyy [in⁴]Izz [in⁴]J [in⁴] 1 Purlin-L 12CS04X075_1.1 Beam CS A653 SS Gr55/1 Typical 1.613 3.409 35.209 0.003 2 Blocking-1 9CS2X059 Beam CS A653 SS Gr33 Typical 0.825 0.415 9.169 0.000958 Load Combinations Description Solve BLC Factor BLC Factor BLC Factor 1 DL Yes DL 1 2 Yes 3 SW+Unif LL Yes 1 1 5 1 4 DL+Point LL Yes DL 1 RLL 1 5 Yes 6 D+0.6WL0A_Clr Yes DL 1 7 0.6 7 D+0.6WL0A_Obs Yes DL 1 8 0.6 8 D+0.6WL180A_Clr Yes DL 1 9 0.6 9 D+0.6WL180A_Obs Yes DL 1 10 0.6 10 D+0.6WL0B_Clr Yes DL 1 11 0.6 11 D+0.6WL0B_Obs Yes DL 1 12 0.6 12 D+0.6WL180B_Clr Yes DL 1 13 0.6 13 D+0.6WL180B_Obs Yes DL 1 14 0.6 14 D+0.6WL_CC+Yes DL 1 15 0.6 15 D+0.6WL_CC-Yes DL 1 16 0.6 16 D+0.6WL_90 Yes DL 1 17 0.6 17 D+0.6WL_270 Yes DL 1 18 0.6 18 Yes 19 0.6D+0.6WL0A_Clr Yes DL 0.6 7 0.6 20 0.6D+0.6WL0A_Obs Yes DL 0.6 8 0.6 21 0.6D+0.6WL180A_Clr Yes DL 0.6 9 0.6 22 0.6D+0.6WL180A_Obs Yes DL 0.6 10 0.6 23 0.6D+0.6WL0B_Clr Yes DL 0.6 11 0.6 24 0.6D+0.6WL0B_Obs Yes DL 0.6 12 0.6 25 0.6D+0.6WL180B_Clr Yes DL 0.6 13 0.6 26 0.6D+0.6WL180B_Obs Yes DL 0.6 14 0.6 27 0.6D+0.6WL_CC+Yes DL 0.6 15 0.6 Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:50:49 AM RISA-3D Version 22 [ 5x30.r3d ]Page 2 Load Combinations (Continued) Description Solve BLC Factor BLC Factor BLC Factor 28 0.6D+0.6WL_CC-Yes DL 0.6 16 0.6 29 0.6D+0.6WL_90 Yes DL 0.6 17 0.6 30 0.6D+0.6WL_270 Yes DL 0.6 18 0.6 31 Yes 32 D+0.75PtLL+0.45WL0A_Clr Yes DL 1 RLL 0.75 7 0.45 33 D+0.75PtLL+0.45WL0A_Obs Yes DL 1 RLL 0.75 8 0.45 34 D+0.75PtLL+0.45WL180A_Clr Yes DL 1 RLL 0.75 9 0.45 35 D+0.75PtLL+0.45WL180A_Obs Yes DL 1 RLL 0.75 10 0.45 36 D+0.75PtLL+0.45WL0B_Clr Yes DL 1 RLL 0.75 11 0.45 37 D+0.75PtLL+0.45WL0B_Obs Yes DL 1 RLL 0.75 12 0.45 38 D+0.75PtLL+0.45WL180B_Clr Yes DL 1 RLL 0.75 13 0.45 39 D+0.75PtLL+0.45WL180B_Obs Yes DL 1 RLL 0.75 14 0.45 40 D+0.75PtLL+0.45WL_CC+Yes DL 1 RLL 0.75 15 0.45 41 D+0.75PtLL+0.45WL_CC-Yes DL 1 RLL 0.75 16 0.45 42 D+0.75PtLL+0.45WL_90 Yes DL 1 RLL 0.75 17 0.45 43 D+0.75PtLL+0.45WL_270 Yes DL 1 RLL 0.75 18 0.45 44 Yes 45 D+0.7Ex Yes DL 1 Sds*DL 0.14 ELX 0.7 46 D-0.7Ex Yes DL 1 Sds*DL 0.14 ELX -0.7 47 D+0.7Ez Yes DL 1 Sds*DL 0.14 ELZ 0.7 48 D-0.7Ez Yes DL 1 Sds*DL 0.14 ELZ -0.7 49 Yes 50 0.6D+0.7Ex Yes DL 0.6 Sds*DL -0.14 ELX 0.7 51 0.6D-0.7Ex Yes DL 0.6 Sds*DL -0.14 ELX -0.7 52 0.6D+0.7Ez Yes DL 0.6 Sds*DL -0.14 ELZ 0.7 53 0.6D-0.7Ez Yes DL 0.6 Sds*DL -0.14 ELZ -0.7 54 Yes 55 D+0.7OmegaEx Yes DL 1 Sds*DL 0.14 Om*ELX 0.7 56 D-0.7OmegaEx Yes DL 1 Sds*DL 0.14 Om*ELX -0.7 57 D+0.7OmegaEz Yes DL 1 Sds*DL 0.14 Om*ELZ 0.7 58 D-0.7OmegaEz Yes DL 1 Sds*DL 0.14 Om*ELZ -0.7 59 Yes 60 0.6D+0.7OmegaEx Yes DL 0.6 Sds*DL -0.14 Om*ELX 0.7 61 0.6D-0.7OmegaEx Yes DL 0.6 Sds*DL -0.14 Om*ELX -0.7 62 0.6D+0.7OmegaEz Yes DL 0.6 Sds*DL -0.14 Om*ELZ 0.7 63 0.6D-0.7OmegaEz Yes DL 0.6 Sds*DL -0.14 Om*ELZ -0.7 64 Yes 65 D+0.7RhoEx Yes DL 1 Sds*DL 0.14 Rho*ELX 0.7 66 D-0.7RhoEx Yes DL 1 Sds*DL 0.14 Rho*ELX -0.7 67 D+0.7RhoEz Yes DL 1 Sds*DL 0.14 Rho*ELZ 0.7 68 D-0.7RhoEz Yes DL 1 Sds*DL 0.14 Rho*ELZ -0.7 69 Yes 70 0.6D+0.7RhoEx Yes DL 0.6 Sds*DL 0.14 Rho*ELX 0.7 71 0.6D-0.7RhoEx Yes DL 0.6 Sds*DL 0.14 Rho*ELX -0.7 72 0.6D+0.7RhoEz Yes DL 0.6 Sds*DL 0.14 Rho*ELZ 0.7 73 0.6D-0.7RhoEz Yes DL 0.6 Sds*DL 0.14 Rho*ELZ -0.7 74 75 DL+Ez-Drift DL 1 21 1 76 DL+Ex-Drift DL 1 20 1 77 DL 1 20 1 78 1.4DL DL 1.4 79 80 1.2SW+0.5Unif LL 1 1.2 5 0.5 81 1.2DL+0.5Point LL DL 1.2 RLL 0.5 82 83 0.9D+WL0A_Clr DL 0.9 7 1 84 0.9D+WL0A_Obs DL 0.9 8 1 85 0.9D+WL180A_Clr DL 0.9 9 1 86 0.9D+WL180A_Obs DL 0.9 10 1 87 0.9D+WL0B_Clr DL 0.9 11 1 88 0.9D+WL0B_Obs DL 0.9 12 1 Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:50:49 AM RISA-3D Version 22 [ 5x30.r3d ]Page 3 Load Combinations (Continued) Description Solve BLC Factor BLC Factor BLC Factor 89 0.9D+WL180B_Clr DL 0.9 13 1 90 0.9D+WL180B_Obs DL 0.9 14 1 91 0.9D+WL_90 DL 0.9 17 1 92 0.9D+WL_270 DL 0.9 18 1 93 94 1.2D+1.6PtLL+0.5WL0A_Clr DL 1.2 RLL 1.6 7 0.5 95 1.2D+1.6PtLL+0.5WL0A_Obs DL 1.2 RLL 1.6 8 0.5 96 1.2D+1.6PtLL+0.5WL180A_Clr DL 1.2 RLL 1.6 9 0.5 97 1.2D+1.6PtLL+0.5WL180A_Obs DL 1.2 RLL 1.6 10 0.5 98 1.2D+1.6PtLL+0.5WL0B_Clr DL 1.2 RLL 1.6 11 0.5 99 1.2D+1.6PtLL+0.5WL0B_Obs DL 1.2 RLL 1.6 12 0.5 100 1.2D+1.6PtLL+0.5WL180B_Clr DL 1.2 RLL 1.6 13 0.5 101 1.2D+1.6PtLL+0.5WL180B_Obs DL 1.2 RLL 1.6 14 0.5 102 1.2D+0.75PtLL+0.5WL_90 DL 1.2 RLL 1.6 17 0.5 103 1.2D+0.75PtLL+0.5WL_270 DL 1.2 RLL 1.6 18 0.5 104 105 1.2D+0.5PtLL+1.0WL0A_Clr DL 1.2 RLL 0.5 7 1 106 1.2D+0.5PtLL+1.0WL0A_Obs DL 1.2 RLL 0.5 8 1 107 1.2D+0.5PtLL+1.0WL180A_Clr DL 1.2 RLL 0.5 9 1 108 1.2D+0.5PtLL+1.0WL180A_Obs DL 1.2 RLL 0.5 10 1 109 1.2D+0.5PtLL+1.0WL0B_Clr DL 1.2 RLL 0.5 11 1 110 1.2D+0.5PtLL+1.0WL0B_Obs DL 1.2 RLL 0.5 12 1 111 1.2D+0.5PtLL+1.0WL180B_Clr DL 1.2 RLL 0.5 13 1 112 1.2D+0.5PtLL+1.0WL180B_Obs DL 1.2 RLL 0.5 14 1 113 1.2D+0.5PtLL+1.0WL_90 DL 1.2 RLL 0.5 17 1 114 1.2D+0.5PtLL+1.0WL_270 DL 1.2 RLL 0.5 18 1 115 116 0.9D+Ex DL 0.9 Sds*DL 0.14 ELX 1 117 0.9D-Ex DL 0.9 Sds*DL 0.14 ELX -1 118 0.9D+Ez DL 0.9 Sds*DL 0.14 ELZ 1 119 0.9D-Ez DL 0.9 Sds*DL 0.14 ELZ -1 120 121 0.9D+OmegaEx DL 0.9 Sds*DL 0.14 Om*ELX 1 122 0.9D-OmegaEx DL 0.9 Sds*DL 0.14 Om*ELX -1 123 0.9D+OmegaEz DL 0.9 Sds*DL 0.14 Om*ELZ 1 124 0.9D-OmegaEz DL 0.9 Sds*DL 0.14 Om*ELZ -1 125 126 0.9D+RhoEx DL 0.9 Sds*DL 0.14 Rho*ELX -1 127 0.9D-RhoEx DL 0.9 Sds*DL 0.14 Rho*ELX -1 128 0.9D+RhoEz DL 0.9 Sds*DL 0.14 Rho*ELZ -1 129 0.9D-RhoEz DL 0.9 Sds*DL 0.14 Rho*ELZ -1 Envelope AISC 15TH (360-16): ASD Member Steel Code Checks Member Shape Code Check Loc[ft]LC Shear CheckLoc[ft]Dir LC Pnc/om [k]Pnt/om [k]Mnyy/om [k-ft]Mnzz/om [k-ft]Cb Eqn 1 M275 W14X30 0.843 0 68 0.632 0 z 73 139.096 264.97 22.43 118.014 2.198 H1-1b 2 M269 W14X30 0.843 0 68 0.632 0 z 73 139.225 264.97 22.43 118.014 2.187 H1-1b 3 M273 W14X30 0.941 0 68 0.632 0 z 73 139.096 264.97 22.43 118.014 2.19 H1-1b 4 M270 W14X30 0.941 0 68 0.632 0 z 73 139.225 264.97 22.43 118.014 2.178 H1-1b 5 M12 HSS12X8X8 0.796 0 58*0.063 0 z 63*409.607 514.97 128.493 169.91 1 H1-1b 6 M1 HSS12X8X8 0.792 0 58*0.063 0 z 63*409.607 514.97 128.493 169.91 1 H1-1b 7 M184 W14X30 0.852 0 68 0.632 0 z 73 139.096 264.97 22.43 118.014 2.197 H1-1b 8 M185 W14X30 0.852 0 68 0.632 0 z 73 139.225 264.97 22.43 118.014 2.186 H1-1b 9 M186 HSS12X8X8 0.793 0 58*0.063 0 z 63*409.607 514.97 128.493 169.91 1 H1-1b 10 M122 W14X30 0.942 0 68 0.632 0 z 73 139.096 264.97 22.43 118.014 2.189 H1-1b 11 M123 W14X30 0.942 0 68 0.632 0 z 73 139.225 264.97 22.43 118.014 2.178 H1-1b 12 M124 HSS12X8X8 0.796 0 58*0.063 0 z 63*409.607 514.97 128.493 169.91 1 H1-1b Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:50:49 AM RISA-3D Version 22 [ 5x30.r3d ]Page 4 Envelope AISI S100-16: ASD Member Cold Formed Steel Code Checks Member Shape Code CheckLoc[ft]LCShear Check Loc[ft]DirLCPn/Om[k]Tn/Om[k]Mnyy/Om[k-ft]Mnzz/Om[k-ft]Vny/Om[k]Vnz/Om[k]Cb Eqn 1 M116 9CS2X059 0.01 2.04868 0.005 4.097 y 6 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 2 M119 9CS2X059 0.01 2.04868 0.005 4.097 y 6 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 3 M87 9CS2X059 0.01 2.04868 0.005 4.097 y 34 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 4 M86 9CS2X059 0.01 2.04868 0.005 4.097 y 34 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 5 M49 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 6 M47 12CS04X075_1.1 0.973 18.77114 0.403 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 7 M135 12CS04X075_1.1 0.972 18.77114 0.404 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 8 M46 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 9 M50 12CS04X075_1.1 0.974 18.77114 0.403 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 10 M130 12CS04X075_1.1 0.976 18.77114 0.404 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 11 M139 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 12 M138 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 13 M168 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 14 M161 12CS04X075_1.1 0.978 18.77114 0.403 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 15 M179 12CS04X075_1.1 0.774 15 14 0.404 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 16 M266 12CS04X075_1.1 0.778 14.58314 0.403 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 17 M267 12CS04X075_1.1 0.77 15 14 0.403 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 18 M268 12CS04X075_1.1 0.771 15 14 0.403 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 19 M271 12CS04X075_1.1 0.766 15 14 0.403 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 20 M150 9CS2X059 0.01 2.04868 0.005 4.097 y 34 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 21 M153 9CS2X059 0.01 2.04868 0.006 4.097 y 34 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 22 M170 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 23 M173 12CS04X075_1.1 0.972 18.77114 0.403 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 24 M174 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 25 M192 12CS04X075_1.1 0.976 18.77114 0.403 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 26 M213 12CS04X075_1.1 0.766 15 14 0.403 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 27 M214 12CS04X075_1.1 0.774 15 14 0.402 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 28 M247 9CS2X059 0.01 2.04968 0.006 4.097 y 6 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 29 M248 9CS2X059 0.01 2.04968 0.006 4.097 y 6 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 30 M249 12CS04X075_1.1 0.974 18.77114 0.404 39.888 y 14 8.696 53.138 2.725 9.581 3.272 10.748 1.664H1.2-1 31 M250 12CS04X075_1.1 0.974 18.77114 0.404 39.888 y 14 8.696 53.138 2.725 9.581 3.272 10.748 1.664H1.2-1 32 M251 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 33 M252 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 34 M257 12CS04X075_1.1 0.771 15 14 0.404 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 35 M261 12CS04X075_1.1 0.77 15 14 0.404 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 36 M162 12CS04X075_1.1 0.256 8.73 14 0.166 8.73 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 37 M163 12CS04X075_1.1 0.97 18.77114 0.402 39.888 y 14 8.697 53.138 2.725 9.582 3.272 10.748 1.664H1.2-1 38 M167 12CS04X075_1.1 0.762 15 14 0.402 35 y 14 9.57 53.138 2.725 9.613 3.272 10.748 1.732H1.2-1 39 M180 9CS2X059 0.013 4.09712 0.013 4.097 y 12 6.837 16.311 0.451 3.119 2.149 2.199 1.136F3.1-1 40 M181 9CS2X059 0.015 4.09710 0.015 4.097 y 10 6.837 16.311 0.451 3.119 2.149 2.199 1.136F3.1-1 41 M99 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 42 M100 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 43 M101 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 44 M102 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 45 M103 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 46 M104 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 47 M105 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 48 M106 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 49 M107 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 50 M108 12CS04X075_1.1 0.317 0 14 0.189 0 y 14 14.999 53.138 3.142 12.092 3.272 10.748 2.326F3.1-1 51 M109 9CS2X059 0.01 2.04868 0.003 4.097 y 65 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 52 M110 9CS2X059 0.01 2.04868 0.003 4.097 y 65 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 53 M111 9CS2X059 0.01 2.04868 0.003 4.097 y 65 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 54 M113 9CS2X059 0.01 2.04868 0.003 4.097 y 65 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 55 M114 9CS2X059 0.01 2.04868 0.004 4.097 y 4 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 56 M115 9CS2X059 0.01 2.04868 0.006 4.097 y 4 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 57 M117 9CS2X059 0.01 2.04968 0.003 4.097 y 65 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 58 M118 9CS2X059 0.01 2.04968 0.003 4.097 y 65 6.837 16.311 0.389 2.367 2.149 2.199 1.136H1.1-2 59 M120 9CS2X059 0.01 2.04968 0.008 4.097 y 10 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 60 M121 9CS2X059 0.015 4.09712 0.015 4.097 y 12 6.837 16.311 0.451 3.119 2.149 2.199 1.136F3.1-1 61 M147 9CS2X059 0.01 2.04868 0.005 4.097 y 6 6.837 16.311 0.389 2.369 2.149 2.199 1.136H1.1-2 Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:50:49 AM RISA-3D Version 22 [ 5x30.r3d ]Page 5 Envelope AISI S100-16: ASD Member Cold Formed Steel Code Checks (Continued) Member Shape Code CheckLoc[ft]LCShear Check Loc[ft]DirLCPn/Om[k]Tn/Om[k]Mnyy/Om[k-ft]Mnzz/Om[k-ft]Vny/Om[k]Vnz/Om[k]Cb Eqn 62 M149 9CS2X059 0.01 2.04868 0.005 4.097 y 6 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 63 M151 9CS2X059 0.01 2.04868 0.006 4.097 y 34 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 64 M152 9CS2X059 0.01 2.04868 0.006 4.097 y 34 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 65 M154 9CS2X059 0.01 2.04868 0.006 4.097 y 34 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 66 M155 9CS2X059 0.01 2.04868 0.006 4.097 y 34 6.837 16.311 0.389 2.369 2.149 2.199 1.136H1.1-2 67 M157 9CS2X059 0.01 2.04968 0.006 4.097 y 6 6.837 16.311 0.389 2.368 2.149 2.199 1.136H1.1-2 68 M159 9CS2X059 0.01 2.04968 0.006 4.097 y 6 7.644 16.311 0.389 2.367 2.149 2.199 1.136H1.2-1 69 M160 9CS2X059 0.011 4.09710 0.011 4.097 y 10 6.837 16.311 0.451 3.119 2.149 2.199 1.136F3.1-1 70 M169 9CS2X059 0.015 4.09712 0.015 4.097 y 12 6.837 16.311 0.451 3.119 2.149 2.199 1.136F3.1-1 71 M171 12CS04X075_1.1 0.903 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 72 M172 12CS04X075_1.1 0.903 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 73 M175 12CS04X075_1.1 0.906 16.03114 0.361 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 74 M176 12CS04X075_1.1 0.903 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 75 M177 12CS04X075_1.1 0.9 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 76 M178 12CS04X075_1.1 0.909 16.03114 0.361 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 77 M182 12CS04X075_1.1 0.906 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 78 M183 12CS04X075_1.1 0.9 16.03114 0.361 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 79 M187 12CS04X075_1.1 0.903 16.03114 0.362 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 80 M189 12CS04X075_1.1 0.897 16.03114 0.36 34.977 y 14 10.375 53.138 2.725 9.617 3.272 10.748 1.805H1.2-1 BEAM TO COLUMN CONNECTION Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:51:27 AM RISA-3D Version 22 [ 5x30.r3d ]Page 1 Member End Reactions LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 1 1 M12 I 8.208 0 0 0 0 0.295 2 J 7.263 0 0 0 0 0.295 3 3 M12 I 22.798 0 0 0 0 1.014 4 J 21.853 0 0 0 0 1.014 5 4 M12 I 8.566 0 0 0 0 5.98 6 J 7.622 0 0 0 0 5.98 7 6 M12 I 18.099 -0.865 0 0 0 -71.997 8 J 17.154 -0.865 0 0 0 -59.016 9 7 M12 I -3.002 0.981 0 0 0 -29.981 10 J -3.946 0.981 0 0 0 -44.691 11 8 M12 I 18.099 -0.865 0 0 0 45.443 12 J 17.155 -0.865 0 0 0 58.423 13 9 M12 I -3.001 0.981 0 0 0 61.332 14 J -3.946 0.981 0 0 0 46.622 15 10 M12 I 0.285 0.693 0 0 0 76.498 16 J -0.659 0.693 0 0 0 66.101 17 11 M12 I -3.004 0.981 0 0 0 48.409 18 J -3.948 0.981 0 0 0 33.695 19 12 M12 I 0.285 0.693 0 0 0 -54.166 20 J -0.659 0.693 0 0 0 -64.563 21 13 M12 I -3.004 0.981 0 0 0 -17.05 22 J -3.949 0.981 0 0 0 -31.763 23 16 M12 I -0.924 0.799 0 0 0 12.825 24 J -1.868 0.799 0 0 0 0.841 25 17 M12 I 12.991 -0.419 0 0 0 -6.269 26 J 12.047 -0.419 0 0 0 0.009 27 19 M12 I 14.816 -0.865 0 0 0 -72.115 28 J 14.249 -0.865 0 0 0 -59.134 29 20 M12 I -6.285 0.981 0 0 0 -30.099 30 J -6.851 0.981 0 0 0 -44.809 31 21 M12 I 14.816 -0.865 0 0 0 45.325 32 J 14.249 -0.865 0 0 0 58.305 33 22 M12 I -6.284 0.981 0 0 0 61.214 34 J -6.851 0.981 0 0 0 46.504 35 23 M12 I -2.998 0.693 0 0 0 76.38 36 J -3.564 0.693 0 0 0 65.983 37 24 M12 I -6.287 0.981 0 0 0 48.291 38 J -6.854 0.981 0 0 0 33.577 39 25 M12 I -2.998 0.693 0 0 0 -54.284 40 J -3.565 0.693 0 0 0 -64.681 41 26 M12 I -6.288 0.981 0 0 0 -17.168 42 J -6.854 0.981 0 0 0 -31.882 43 29 M12 I -4.207 0.799 0 0 0 12.707 44 J -4.774 0.799 0 0 0 0.723 45 30 M12 I 9.708 -0.419 0 0 0 -6.387 46 J 9.142 -0.419 0 0 0 -0.109 47 32 M12 I 15.894 -0.649 0 0 0 -49.66 48 J 14.95 -0.649 0 0 0 -39.924 49 33 M12 I 0.069 0.735 0 0 0 -18.148 50 J -0.875 0.735 0 0 0 -29.181 51 34 M12 I 15.895 -0.649 0 0 0 38.42 52 J 14.95 -0.649 0 0 0 48.155 53 35 M12 I 0.069 0.735 0 0 0 50.337 54 J -0.875 0.735 0 0 0 39.304 55 36 M12 I 2.534 0.52 0 0 0 61.711 56 J 1.59 0.52 0 0 0 53.913 57 37 M12 I 0.067 0.736 0 0 0 40.644 58 J -0.877 0.736 0 0 0 29.609 59 38 M12 I 2.534 0.52 0 0 0 -36.287 60 J 1.59 0.52 0 0 0 -44.084 61 39 M12 I 0.067 0.736 0 0 0 -8.45 5X37 ASD Reactions I = BASE END J = TOP END MAX REACTION AT TOP OF COLUMN FOR BEAM-COLUMN CONNECTION Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 10:51:27 AM RISA-3D Version 22 [ 5x30.r3d ]Page 2 Member End Reactions (Continued) LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 62 J -0.877 0.736 0 0 0 -19.485 63 42 M12 I 1.627 0.599 0 0 0 13.956 64 J 0.683 0.599 0 0 0 4.969 65 43 M12 I 12.064 -0.314 0 0 0 -0.364 66 J 11.12 -0.314 0 0 0 4.344 67 45 M12 I 9.731 -3.809 0 0 0 -57.346 68 J 8.612 -3.371 0 0 0 -3.492 69 46 M12 I 9.731 3.809 0 0 0 58.046 70 J 8.612 3.371 0 0 0 4.191 71 47 M12 I 9.731 0 3.352 -0.114 -50.267 0.35 72 J 8.612 0 2.914 -0.114 -3.27 0.35 73 48 M12 I 9.731 0 -3.352 0.114 50.267 0.35 74 J 8.612 0 -2.914 0.114 3.27 0.35 75 50 M12 I 3.401 -3.809 0 0 0 -57.574 76 J 3.01 -3.371 0 0 0 -3.719 77 51 M12 I 3.401 3.809 0 0 0 57.818 78 J 3.01 3.371 0 0 0 3.964 79 52 M12 I 3.401 0 3.352 -0.114 -50.267 0.122 80 J 3.01 0 2.914 -0.114 -3.27 0.122 81 53 M12 I 3.401 0 -3.352 0.114 50.267 0.122 82 J 3.01 0 -2.914 0.114 3.27 0.122 83 55*M12 I 9.731 -7.619 0 0 0 -115.042 84 J 8.612 -6.742 0 0 0 -7.333 85 56*M12 I 9.731 7.619 0 0 0 115.742 86 J 8.612 6.742 0 0 0 8.033 87 57*M12 I 9.731 0 6.705 -0.229 -100.534 0.35 88 J 8.612 0 5.828 -0.229 -6.54 0.35 89 58*M12 I 9.731 0 -6.705 0.229 100.534 0.35 90 J 8.612 0 -5.828 0.229 6.54 0.35 91 60*M12 I 3.401 -7.619 0 0 0 -115.27 92 J 3.01 -6.742 0 0 0 -7.561 93 61*M12 I 3.401 7.619 0 0 0 115.515 94 J 3.01 6.742 0 0 0 7.805 95 62*M12 I 3.401 0 6.705 -0.229 -100.534 0.122 96 J 3.01 0 5.828 -0.229 -6.54 0.122 97 63*M12 I 3.401 0 -6.705 0.229 100.534 0.122 98 J 3.01 0 -5.828 0.229 6.54 0.122 99 65 M12 I 9.731 -4.952 0 0 0 -74.655 100 J 8.612 -4.383 0 0 0 -4.644 101 66 M12 I 9.731 4.952 0 0 0 75.355 102 J 8.612 4.383 0 0 0 5.344 103 67 M12 I 9.731 0 3.352 -0.114 -50.267 0.35 104 J 8.612 0 2.914 -0.114 -3.27 0.35 105 68 M12 I 9.731 0 -3.352 0.114 50.267 0.35 106 J 8.612 0 -2.914 0.114 3.27 0.35 107 70 M12 I 6.448 -4.952 0 0 0 -74.773 108 J 5.706 -4.383 0 0 0 -4.762 109 71 M12 I 6.448 4.952 0 0 0 75.237 110 J 5.707 4.383 0 0 0 5.226 111 72 M12 I 6.448 0 3.352 -0.114 -50.267 0.232 112 J 5.706 0 2.914 -0.114 -3.27 0.232 113 73 M12 I 6.448 0 -3.352 0.114 50.267 0.232 114 J 5.706 0 -2.914 0.114 3.27 0.232 Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 11:17:27 AM RISA-3D Version 22 [ 5x30.r3d ]Page 1 Member End Reactions LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 1 1 M124 I 8.232 0 0 0 0 0.296 2 J 7.287 0 0 0 0 0.296 3 3 M124 I 22.87 0 0 0 0 1.018 4 J 21.926 0 0 0 0 1.018 5 4 M124 I 8.78 0 0 0 0 7.093 6 J 7.836 0 0 0 0 7.093 7 6 M124 I 18.156 -0.868 0 0 0 -72.235 8 J 17.211 -0.868 0 0 0 -59.212 9 7 M124 I -3.015 0.984 0 0 0 -30.08 10 J -3.959 0.984 0 0 0 -44.839 11 8 M124 I 18.156 -0.868 0 0 0 45.594 12 J 17.212 -0.868 0 0 0 58.617 13 9 M124 I -3.015 0.984 0 0 0 61.536 14 J -3.959 0.984 0 0 0 46.777 15 10 M124 I 0.283 0.695 0 0 0 76.752 16 J -0.662 0.695 0 0 0 66.32 17 11 M124 I -3.018 0.984 0 0 0 48.57 18 J -3.962 0.984 0 0 0 33.807 19 12 M124 I 0.282 0.695 0 0 0 -54.345 20 J -0.662 0.695 0 0 0 -64.777 21 13 M124 I -3.018 0.984 0 0 0 -17.106 22 J -3.962 0.984 0 0 0 -31.869 23 16 M124 I 0.293 0.695 0 0 0 11.19 24 J -0.652 0.695 0 0 0 0.771 25 17 M124 I 12.202 -0.347 0 0 0 -5.151 26 J 11.258 -0.347 0 0 0 0.059 27 19 M124 I 14.863 -0.868 0 0 0 -72.354 28 J 14.296 -0.868 0 0 0 -59.33 29 20 M124 I -6.308 0.984 0 0 0 -30.199 30 J -6.874 0.984 0 0 0 -44.958 31 21 M124 I 14.863 -0.868 0 0 0 45.475 32 J 14.297 -0.868 0 0 0 58.499 33 22 M124 I -6.307 0.984 0 0 0 61.418 34 J -6.874 0.984 0 0 0 46.659 35 23 M124 I -3.01 0.695 0 0 0 76.634 36 J -3.576 0.695 0 0 0 66.202 37 24 M124 I -6.31 0.984 0 0 0 48.451 38 J -6.877 0.984 0 0 0 33.689 39 25 M124 I -3.01 0.695 0 0 0 -54.464 40 J -3.577 0.695 0 0 0 -64.896 41 26 M124 I -6.311 0.984 0 0 0 -17.224 42 J -6.877 0.984 0 0 0 -31.987 43 29 M124 I -3 0.695 0 0 0 11.071 44 J -3.567 0.695 0 0 0 0.653 45 30 M124 I 8.909 -0.347 0 0 0 -5.27 46 J 8.343 -0.347 0 0 0 -0.06 47 32 M124 I 16.086 -0.651 0 0 0 -49.005 48 J 15.142 -0.651 0 0 0 -39.237 49 33 M124 I 0.208 0.738 0 0 0 -17.389 50 J -0.736 0.738 0 0 0 -28.458 51 34 M124 I 16.086 -0.651 0 0 0 39.367 52 J 15.142 -0.651 0 0 0 49.134 53 35 M124 I 0.208 0.738 0 0 0 51.324 54 J -0.736 0.738 0 0 0 40.254 55 36 M124 I 2.681 0.522 0 0 0 62.735 56 J 1.737 0.522 0 0 0 54.912 57 37 M124 I 0.206 0.738 0 0 0 41.599 58 J -0.738 0.738 0 0 0 30.527 59 38 M124 I 2.681 0.522 0 0 0 -35.587 60 J 1.737 0.522 0 0 0 -43.411 61 39 M124 I 0.206 0.738 0 0 0 -7.658 Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 11:17:27 AM RISA-3D Version 22 [ 5x30.r3d ]Page 2 Member End Reactions (Continued) LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 62 J -0.739 0.738 0 0 0 -18.73 63 42 M124 I 2.689 0.521 0 0 0 13.564 64 J 1.744 0.521 0 0 0 5.75 65 43 M124 I 11.621 -0.261 0 0 0 1.308 66 J 10.676 -0.261 0 0 0 5.216 67 45 M124 I 9.76 -3.821 0 0 0 -57.525 68 J 8.64 -3.382 0 0 0 -3.503 69 46 M124 I 9.76 3.821 0 0 0 58.227 70 J 8.64 3.382 0 0 0 4.206 71 47 M124 I 9.76 0 3.352 -0.114 -50.268 0.351 72 J 8.64 0 2.914 -0.114 -3.27 0.351 73 48 M124 I 9.76 0 -3.352 0.114 50.268 0.351 74 J 8.64 0 -2.914 0.114 3.27 0.351 75 50 M124 I 3.411 -3.821 0 0 0 -57.753 76 J 3.019 -3.382 0 0 0 -3.732 77 51 M124 I 3.411 3.821 0 0 0 57.999 78 J 3.02 3.382 0 0 0 3.977 79 52 M124 I 3.411 0 3.352 -0.114 -50.268 0.123 80 J 3.02 0 2.914 -0.114 -3.27 0.123 81 53 M124 I 3.411 0 -3.352 0.114 50.268 0.123 82 J 3.02 0 -2.914 0.114 3.27 0.123 83 55*M124 I 9.759 -7.641 0 0 0 -115.4 84 J 8.64 -6.765 0 0 0 -7.358 85 56*M124 I 9.76 7.641 0 0 0 116.103 86 J 8.64 6.765 0 0 0 8.061 87 57*M124 I 9.76 0 6.705 -0.229 -100.536 0.351 88 J 8.64 0 5.828 -0.229 -6.54 0.351 89 58*M124 I 9.76 0 -6.705 0.229 100.536 0.351 90 J 8.64 0 -5.828 0.229 6.54 0.351 91 60*M124 I 3.411 -7.641 0 0 0 -115.629 92 J 3.019 -6.765 0 0 0 -7.587 93 61*M124 I 3.411 7.641 0 0 0 115.874 94 J 3.02 6.765 0 0 0 7.832 95 62*M124 I 3.411 0 6.705 -0.229 -100.536 0.123 96 J 3.02 0 5.828 -0.229 -6.54 0.123 97 63*M124 I 3.411 0 -6.705 0.229 100.536 0.123 98 J 3.02 0 -5.828 0.229 6.54 0.123 99 65 M124 I 9.76 -4.967 0 0 0 -74.887 100 J 8.64 -4.397 0 0 0 -4.66 101 66 M124 I 9.76 4.967 0 0 0 75.59 102 J 8.64 4.397 0 0 0 5.362 103 67 M124 I 9.76 0 3.352 -0.114 -50.268 0.351 104 J 8.64 0 2.914 -0.114 -3.27 0.351 105 68 M124 I 9.76 0 -3.352 0.114 50.268 0.351 106 J 8.64 0 -2.914 0.114 3.27 0.351 107 70 M124 I 6.467 -4.967 0 0 0 -75.006 108 J 5.725 -4.397 0 0 0 -4.778 109 71 M124 I 6.467 4.967 0 0 0 75.471 110 J 5.725 4.397 0 0 0 5.244 111 72 M124 I 6.467 0 3.352 -0.114 -50.268 0.233 112 J 5.725 0 2.914 -0.114 -3.27 0.233 113 73 M124 I 6.467 0 -3.352 0.114 50.268 0.233 114 J 5.725 0 -2.914 0.114 3.27 0.233 MAX REACTION AT BOTTOM OF COLUMN FOR PIER DESIGN Project: Holy Angels Designer: MR Date: 7/24/2024 Beam: Column: bf bcol dbeam dcol tw tcol tf Sc k Syy Szz Bolt Dia Bolt Desc A325N Abolt Fnt 90 ksi Fnt/Ω 45 ksi Min Edge Dist Fnv 54 ksi Fnv/Ω 27 ksi N Loads from RISA ASD LC: Mzz Myy Vy Vz P Bolt Design Tbolt ft OK Vbolt fv OK Check if fv is less than or equal to 30% of available stress: YES then combined stress effects need not be considered Cap Plate Design Fy T xT B treq 0.22 ksi 0.79 in 4.23 in 66.10 k-ft 0.00 k-ft 0.69 k 24.20 k 16.50 in 1 Ø 0.785 in^2 1.25 4 bolts 50 ksi 48.40 k 2.25 in 8.50 in 1.31 in -0.66 k 0.00 k 30.81 ksi 0.17 k 13.80 in 12.00 in 0.270 in 0.47 in 0.385 in 2.25 in Beam to Column Connection 5x37 W14x30 HSS12x8x1/2 6.73 in 8.00 in Project: Holy Angels Designer: MR Date: 7/24/2024 Beam to Column Connection 5x37 Stiffener Plate Check Confirm if stiffener plates are required: Req'd Comp., C Fy,beam Ebeam Check Web Compression Buckling: Rn/Ω=compression capacity of the beam per AISC J10-8 Is C > Rn/Ω?Y, Stiffeners required Design Stiffener Plates: Req'd Capacity:difference between C and Web Compression strength Fystiff ts As Check Tension Rn/Ω (Tens) Check Compression Fcr Fe Lc r E Rn/Ω (Comp) Check Weld WS L Rn/Ω (Weld) Governing Rn/Ω Check Rn/Ω > C 53.33 k 75% 0.38 in 50 ksi 39.960 k 170.16 k 66.10 k 1.161 in^2 69.50 k 38.37 ksi 79.02 ksi 6.52 in 0.11 in 29000 ksi 53.33 k 4 /16 11.46 in 50 ksi 29000 ksi 26.141 k Project: Holy Angels Designer: MR Date: 7/24/2024 Beam to Column Connection 5x37 Column to Cap Plate Weld Check HSS or WF Col? HSS Nw 2 WSw 5 /16 Max weld size is t-1/16 WSf 5 /16 Max weld size is t-1/16 Izz 4320 in4 Iyy 2346.666667 in4 Aw 2000 in2 rf,perp 5.52 k/in rf,par 0.00 k/in Θ 90.00 rn,f/Ω 6.96 k/in D/C 79% rw,perp 5.52 k/in rw,par 0.03 k/in Θ 89.70 rn,w/Ω 6.96 k/in D/C 79% PIER FOUNDATION DESIGN Flagpole Foong Design Based on Chapter 18 both IBC & UBC INPUT DATA & DESIGN SUMMARY IS FOOTING RESTRAINED @ GRADE LEVEL ? (1=YES,0=NO)0 no LATERAL FORCE @ TOP OF POLE P =7.641 k HEIGHT OF POLE ABOVE GRADE H =15.195 DIAMETER OF POLE FOOTING B =2 LATERAL SOIL BEARING CAPACITY S =0.137 ksf / ISOLATED POLE FACTOR (IBC 1804.3.1 or UBC note 3 on Tab 18-I-A) F =2 FIRST TRIAL DEPTH D =8 Use 2 dia x 14.54 deep foong unrestrained @ ground level Units ? ( English = 1, Metric = 2 )1 English ANALYSIS NONCONSTRAINED CONSTRAINED LATERAL FORCE @ TOP OF POLE P =>7.64 k 7.64 k HEIGHT OF POLE ABOVE GRADE H =>15.2 15.2 DIAMETER OF POLE FOOTING B =>2.00 2.00 LATERAL SOIL BEARING CAPACITY FS =>0.27 ksf / 0.27 ksf / 1ST TRIAL TRY D =>8.00 8.00 LAT SOIL BEARING @ 1/3 D S =>0.72 ksf 0.72 ksf LAT SOIL BEARING @ 1.0 D S =>2.19 ksf 2.19 ksf CONSTANT 2.34P/(BS ) A =>12.36 - - REQD FOOTING DEPTH RQRD D =>21.76 10.61 2ND TRIAL : TRY D2=>14.88 9.30 LAT SOIL BEARING @ 1/3 D S =>1.35 ksf 0.84 ksf LAT SOIL BEARING @ 1.0 D S =>4.08 ksf 2.55 ksf CONSTANT 2.34P/(BS ) A =>6.64 - - REQD FOOTING DEPTH RQRD D =>14.33 9.84 3RD TRIAL : TRY D3=>14.60 9.57 LAT SOIL BEARING @ 1/3 D S =>1.32 ksf 0.87 ksf LAT SOIL BEARING @ 1.0 D S =>4.00 ksf 2.62 ksf CONSTANT 2.34P/(BS ) A =>6.77 - - REQD FOOTING DEPTH RQRD D =>14.50 9.70 4TH TRIAL : TRY D4=>14.55 9.64 LAT SOIL BEARING @ 1/3 D S =>1.32 ksf 0.87 ksf LAT SOIL BEARING @ 1.0 D S =>3.99 ksf 2.64 ksf CONSTANT 2.34P/(BS ) A =>6.79 - - REQD FOOTING DEPTH RQRD D =>14.54 9.67 5TH TRIAL : TRY D5=>14.54 9.65 LAT SOIL BEARING @ 1/3 D S =>1.32 ksf 0.87 ksf LAT SOIL BEARING @ 1.0 D S =>3.99 ksf 2.64 ksf CONSTANT 2.34P/(BS ) A =>6.80 - - REQD FOOTING DEPTH RQRD D =>14.54 9.66 1 1 3 1 1 3 1 1 3 1 1 3 1 1 3 1 Project:Holy Angels Designer:MR Date:7/22/2024 Array Pier Diameter (ft) Allowable Skin Friction Down (psf) Allowable Skin Friction Up (ft) Depth to Formational Soil, DF (ft) Max Downward Reaction, C (lbs) Max Uplift Reaction, Pup (lbs) Required Embedment for Downward Reaction, Ddown (ft) Required Embedment for Uplift, Dup (ft) Required Embedment for Lateral Bearing, Dlat (ft) Design Embedment including DF (ft) 5x37 2 360.0 160.0 1 22870 6311 10.11 4.90 14.54 15.54 Required Embedment Design 1/3 increase applied for governing seismic short term load case Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 12:00:13 PM RISA-3D Version 22 [ 5x37.r3d ]Page 1 Member End Reactions LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 1 78 M124 I 11.524 0 0 0 0 0.415 2 J 10.202 0 0 0 0 0.415 3 80 M124 I 14.499 0 0 0 0 0.583 4 J 13.366 0 0 0 0 0.583 5 81 M124 I 10.152 0 0 0 0 3.754 6 J 9.019 0 0 0 0 3.754 7 83 M124 I 23.948 -1.447 0 0 0 -120.619 8 J 23.099 -1.447 0 0 0 -98.914 9 84 M124 I -11.336 1.64 0 0 0 -50.361 10 J -12.186 1.64 0 0 0 -74.96 11 85 M124 I 23.949 -1.447 0 0 0 75.762 12 J 23.099 -1.447 0 0 0 97.468 13 86 M124 I -11.336 1.64 0 0 0 102.333 14 J -12.185 1.64 0 0 0 77.735 15 87 M124 I -5.84 1.159 0 0 0 127.693 16 J -6.69 1.159 0 0 0 110.307 17 88 M124 I -11.341 1.64 0 0 0 80.723 18 J -12.19 1.64 0 0 0 56.118 19 89 M124 I -5.841 1.159 0 0 0 -90.802 20 J -6.69 1.159 0 0 0 -108.189 21 90 M124 I -11.341 1.64 0 0 0 -28.737 22 J -12.191 1.64 0 0 0 -53.342 23 91 M124 I -5.823 1.158 0 0 0 18.422 24 J -6.673 1.158 0 0 0 1.058 25 92 M124 I 14.025 -0.579 0 0 0 -8.813 26 J 13.176 -0.579 0 0 0 -0.129 27 94 M124 I 19.025 -0.724 0 0 0 -49.213 28 J 17.892 -0.724 0 0 0 -38.36 29 95 M124 I 1.383 0.82 0 0 0 -14.084 30 J 0.25 0.82 0 0 0 -26.383 31 96 M124 I 19.026 -0.724 0 0 0 48.978 32 J 17.893 -0.724 0 0 0 59.831 33 97 M124 I 1.383 0.82 0 0 0 62.263 34 J 0.25 0.82 0 0 0 49.964 35 98 M124 I 4.131 0.58 0 0 0 74.943 36 J 2.998 0.58 0 0 0 66.25 37 99 M124 I 1.381 0.82 0 0 0 51.458 38 J 0.248 0.82 0 0 0 39.156 39 100 M124 I 4.131 0.58 0 0 0 -34.305 40 J 2.998 0.58 0 0 0 -42.998 41 101 M124 I 1.381 0.82 0 0 0 -3.272 42 J 0.248 0.82 0 0 0 -15.574 43 102 M124 I 4.14 0.579 0 0 0 20.308 44 J 3.006 0.579 0 0 0 11.626 45 103 M124 I 14.064 -0.289 0 0 0 6.69 46 J 12.931 -0.289 0 0 0 11.032 47 105 M124 I 26.692 -1.447 0 0 0 -117.132 48 J 25.559 -1.447 0 0 0 -95.426 49 106 M124 I -8.592 1.64 0 0 0 -46.874 50 J -9.726 1.64 0 0 0 -71.472 51 107 M124 I 26.693 -1.447 0 0 0 79.249 52 J 25.56 -1.447 0 0 0 100.956 53 108 M124 I -8.592 1.64 0 0 0 105.82 54 J -9.725 1.64 0 0 0 81.222 55 109 M124 I -3.096 1.159 0 0 0 131.18 56 J -4.229 1.159 0 0 0 113.794 57 110 M124 I -8.597 1.64 0 0 0 84.21 58 J -9.73 1.64 0 0 0 59.605 59 111 M124 I -3.097 1.159 0 0 0 -87.315 60 J -4.23 1.159 0 0 0 -104.702 61 112 M124 I -8.597 1.64 0 0 0 -25.25 5x37 LRFD Reactions I = BASE END J = TOP END Company Designer Job Number Model Name : : : : Teichert Solar MR Holy Angels 5x37 Checked By : __________ 7/22/2024 12:00:13 PM RISA-3D Version 22 [ 5x37.r3d ]Page 2 Member End Reactions (Continued) LC Member Label Member End Axial[k]y Shear[k]z Shear[k]Torque[k-ft]y-y Moment[k-ft]z-z Moment[k-ft] 62 J -9.73 1.64 0 0 0 -49.855 63 113 M124 I -3.08 1.158 0 0 0 21.909 64 J -4.213 1.158 0 0 0 4.545 65 114 M124 I 16.769 -0.579 0 0 0 -5.326 66 J 15.636 -0.579 0 0 0 3.358 67 116 M124 I 8.936 -5.458 0 0 0 -82.358 68 J 7.911 -4.832 0 0 0 -5.185 69 117 M124 I 8.937 5.458 0 0 0 83.001 70 J 7.912 4.832 0 0 0 5.828 71 118 M124 I 8.937 0 4.789 -0.163 -71.811 0.322 72 J 7.911 0 4.163 -0.163 -4.672 0.322 73 119 M124 I 8.937 0 -4.789 0.163 71.811 0.322 74 J 7.911 0 -4.163 0.163 4.672 0.322 75 121*M124 I 8.936 -10.916 0 0 0 -165.038 76 J 7.911 -9.664 0 0 0 -10.692 77 122*M124 I 8.937 10.916 0 0 0 165.681 78 J 7.912 9.664 0 0 0 11.335 79 123*M124 I 8.937 0 9.578 -0.327 -143.622 0.322 80 J 7.911 0 8.326 -0.327 -9.344 0.322 81 124*M124 I 8.937 0 -9.578 0.327 143.622 0.322 82 J 7.911 0 -8.326 0.327 9.344 0.322 83 126 M124 I 8.937 7.095 0 0 0 107.805 84 J 7.912 6.281 0 0 0 7.48 85 127 M124 I 8.937 7.095 0 0 0 107.805 86 J 7.912 6.281 0 0 0 7.48 87 128 M124 I 8.937 0 -4.789 0.163 71.811 0.322 88 J 7.911 0 -4.163 0.163 4.672 0.322 89 129 M124 I 8.937 0 -4.789 0.163 71.811 0.322 90 J 7.911 0 -4.163 0.163 4.672 0.322 MAX REACTION AT BOTTOM OF COLUMN FOR CONCRETE REINFORCEMENT Licensee stated below acknowledges that STRUCTUREPOINT (SP) is not and cannot be responsible for either the accuracy or adequacy of the material supplied as input for processing by the spColumn computer program. Furthermore, STRUCTUREPOINT neither makes any warranty expressed nor implied with respect to the correctness of the output prepared by the spColumn program. Although STRUCTUREPOINT has endeavored to produce spColumn error free the program is not and cannot be certified infallible. The final and only responsibility for analysis, design and engineering documents is the licensee's. Accordingly, STRUCTUREPOINT disclaims all responsibility in contract,negligence or other tort for any analysis, design or engineering documents prepared in connection with the use of the spColumn program. Licensed to: Teichert Energy & Utilities Group. License ID: 77756-1088284-4-26FD1-26FD1 spColumn v10.10 (TM) Computer program for the Strength Design of Reinforced Concrete Sections Copyright - 1988-2023, STRUCTUREPOINT, LLC. All rights reserved y x STRUCTUREPOINT - spColumn v10.10 (TM)Page |2 Licensed to: Teichert Energy & Utilities Group. License ID:77756-1088284-4-26FD1-26FD1 7/22/2024 C:\Users\mgrygar\Teichert\Teichert Job Folders - 30726.00 (Holy Angels Arca...\5x37 Foundation.colx 3:50 PM Contents 1. General Information............................................................................................................................................... 3 2. Material Properties................................................................................................................................................. 3 2.1. Concrete......................................................................................................................................................... 3 2.2. Steel ............................................................................................................................................................... 3 3. Section................................................................................................................................................................... 3 3.1. Shape and Properties..................................................................................................................................... 3 3.2. Section Figure ................................................................................................................................................ 4 4. Reinforcement ....................................................................................................................................................... 4 4.1. Confinement and Factors............................................................................................................................... 4 4.2. Arrangement................................................................................................................................................... 4 5. Diagrams ............................................................................................................................................................... 5 5.1. PM at θ=0 [deg].............................................................................................................................................. 5 List of Figures Figure 1: Column section........................................................................................................................................... 4 STRUCTUREPOINT - spColumn v10.10 (TM)Page |3 Licensed to: Teichert Energy & Utilities Group. License ID:77756-1088284-4-26FD1-26FD1 7/22/2024 C:\Users\mgrygar\Teichert\Teichert Job Folders - 30726.00 (Holy Angels Arca...\5x37 Foundation.colx 3:50 PM 1. General Information File Name C:\Users\mgrygar\Teichert...\5x37 Foundation.colx Project Holy Angels Column 5x37 Engineer MG Code ACI 318-19 Bar Set ASTM A615 Units English Run Option Investigation Run Axis Biaxial Slenderness Not Considered Column Type Architectural Capacity Method Critical capacity 2. Material Properties 2.1. Concrete Type Standard f'c 3 ksi Ec 3122.02 ksi fc 2.55 ksi εu 0.003 in/in β1 0.85 2.2. Steel Type Standard fy 60 ksi Es 29000 ksi εty 0.00206897 in/in 3. Section 3.1. Shape and Properties Type Circular Diameter 24 in Ag 452.389 in2 Ix 16286 in4 Iy 16286 in4 rx 6 in ry 6 in Xo 0 in Yo 0 in STRUCTUREPOINT - spColumn v10.10 (TM)Page |4 Licensed to: Teichert Energy & Utilities Group. License ID:77756-1088284-4-26FD1-26FD1 7/22/2024 C:\Users\mgrygar\Teichert\Teichert Job Folders - 30726.00 (Holy Angels Arca...\5x37 Foundation.colx 3:50 PM 3.2. Section Figure Circular 24 x 24 in 0.97% reinf. Figure 1: Column section 4. Reinforcement 4.1. Confinement and Factors Confinement type Spiral For #10 bars or less #4 ties For larger bars #4 ties Capacity Reduction Factors Axial compression, (a)0.85 Tension controlled ɸ, (b)0.9 Compression controlled ɸ, (c)0.75 4.2. Arrangement Pattern All sides equal Bar layout Circular Cover to Transverse bars Clear cover 2.5 in Bars 10 #6 Total steel area, As 4.40 in2 Rho 0.97 % Minimum clear spacing 4.58 in (Note: Rho < 1.0%) y x STRUCTUREPOINT - spColumn v10.10 (TM)Page |5 Licensed to: Teichert Energy & Utilities Group. License ID:77756-1088284-4-26FD1-26FD1 7/22/2024 C:\Users\mgrygar\Teichert\Teichert Job Folders - 30726.00 (Holy Angels Arca...\5x37 Foundation.colx 3:50 PM 5. Diagrams 5.1. PM at θ=0 [deg] PURLIN CLIP CONNECTION DESIGN Project: Holy Angels Designer: MR Date: 7/22/2024 Bolt Dia Bolt Desc A307 Abolt Fnt 45 ksi Fnt/Ω 23 ksi S in Fnv 27 ksi Fnv/Ω 14 ksi L in Ω 2.00 tp in Plate, Fy ksi Plate, Fu ksi Purlin, Fu ksi t in WS in E ksi Max Strong-Way Reaction from RISA ASD LC Max Weak-Way Reaction from RISA ASD LC Mzz Mzz Myy Myy Vy Vy Vz Vz P P Bolt Design Vb,perp F'nt Vb,par Tbolt Vb D/C Tb Vbolt fv C mf Vbrg Va D/C Plate Design Weak axis bending check Strong axis bending check Ap Lb*d/t2 Zz 0.08E/Fy Sz 1.9E/Fy Myy Zy Mn Sy Ma Mzz D/C Mp when Lb*d/t2 <0.08E/Fy My Mn when 0.08E/Fy < Lb*d/t2 < 1.9E/Fy Ma/Ω D/C 93.75 k-in 126.17 k-in 75.55 k-in 3.97 k-in 5% 1102.00 2.813 in^3 1.875 in^3 140.63 k-in 1 3.15 k 2.65 k 13% 368.64 46.40 4 /16 0.35 k 0.88 k 2 ksi 0.03 k-ft 0.18 k-ft 0.04 k 0.24 k 0.49 k 20% 2.65 k 3 29000 0.35 k 0.00 k 45.00 ksi Purlin to Clip Connection 50 65 70 0.075 6 0.3125 6 0.196 in^2 1/2 Ø 4.42 k 0.33 k-ft 0.00 k-ft 0.44 k 0.00 k 0.70 k 50% 0.098 in^3 7.32 k-in 1.875 in^2 4.39 k-in 2.18 k-in 0.146 in^3 EQUIPMENT ANCHORAGE DESIGN Project:Holy Angels Arcadia Designer:MR Date:10/29/2024 Cutsheet Info Weight, W 770 lbs Length, L 27 in Width, B 28.25 in Height, h 36 in C.O.G. 18 in Wind Calculation Kz 0.85 Kzt 1.00 Kd 0.85 Ke 1.00 V 95 mph q 16.69 psf Fh 214 lbs Fv 177 lbs Fp Calculation ap 1 Sds 1.326 Wp 770 lbs Rp 2.5 Ip 1 z 1 h 1 Omega 2 Fp 490 lbs Ev 204 lbs LRFD Load Combinations with Omega 1. 0.9D-Omega*Ev+Omega*Fp Rxe = 980 lbs <- Controls shear Rye = -767 lbs Tension Anchorage Design Reactions Shear per Anchor Comp/Tension per anchor 2 lbs 4 lbs Overturning Moment Check MOVT, Fh = (Fh)*(h/2) = (214 lbs)*(36/2)/12/1000 = 0.321 kip-ft MOVT, Fp = (Fp)*(h/2) = (490 lbs)*(36/2)/12/1000 = 0.735 kip-ft MRESISTANCE = (Wconc + Wequip)*(1/2)*(W) Wconc = (length)(width)(thickness)(unit wieght) = (3.79')(3.79')(0.5')(150) = 1077.307 lbs Wequip = 770 lbs MRES = (1077.307 lbs + 770 lbs)*(3.79'/2)/1000 = 3.5 k-ft MRES/MOVT = 4.76 > 1.5 OKAY Equipment Anchorage Battery Anchors ea. side -383 Total anchors 245 See HILTI sheets following for anchor design. Project:Holy Angels Arcadia Designer:MR Date:1/14/2025 Cutsheet Info Weight, W 35 lbs Length, L 7.4 in Width, B 7.4 in Height, h 20.5 in C.O.G. 10.25 in Wind Calculation Kz 0.85 Kzt 1.00 Kd 0.85 Ke 1.00 V 95 mph q 16.69 psf Fh 33 lbs Fv 26 lbs Fp Calculation ap 1 Sds 1.326 Wp 35 lbs Rp 2.5 Ip 1 z 1 h 1 Omega 2 Fp 22 lbs Ev 9 lbs LRFD Load Combinations with Omega 1. 0.9D-Omega*Ev+Omega*Fp Rxe = 45 lbs <- Controls shear Rye = -68 lbs Tension Anchorage Design Reactions Shear per Anchor Comp/Tension per anchor 2 lbs 4 lbs Overturning Moment Check Equipment Anchorage EV Charging Station Anchors ea. side -34 Total anchors 11 MOVT, Fh = (Fh)*(h/2) = (33 lbs)*(20.5/2)/12/1000 = 0.028 kip-ft MOVT, Fp = (Fp)*(h/2) = (22 lbs)*(20.5/2)/12/1000 = 0.018 kip-ft MRESISTANCE = (Wconc + Wequip)*(1/2)*(W) Wconc = (length)(width)(thickness)(unit wieght) = (1')(1')(1')(150) = 150 lbs Wequip = 35 lbs MRES = (150 lbs + 35 lbs)*(1'/2)/1000 = 0.0925 k-ft MRES/MOVT = 3.3 > 1.5 OKAY